Split-type Air-Conditioner
MXZ-3C24NA2
MXZ-3C30NA2
MXZ-4C36NA2
Installation Manual |
For INSTALLER |
•This manual only describes the installation of outdoor unit.
When installing the indoor unit, refer to the installation manual of indoor unit. Any structural alterations necessary for installation must comply with local building code requirements.
Notice d’installation |
Destinée à l’INSTALLATEUR |
•Cette notice ne décrit que l’installation de l’appareil extérieur.
Lors de l’installation de l’appareil intérieur, consultez la notice d’installation de cet appareil.
Toute altération structurelle requise pour l’installation doit être conforme aux exigences du code du bâtiment local.
English
Français
Manual de instalación |
Para el INSTALADOR |
|
Español |
• En este manual sólo se describe la instalación de la unidad exterior. |
|||
Para instalar la unidad interior, consulte el manual de instalación de dicha uni- |
|
||
dad. |
|
|
|
Cualquier modificación estructural necesaria para llevar a cabo la instalación de- |
|
||
berá cumplir las normas de edificación locales. |
|
|
|
ENGLISH
CONTENTS |
|
|
1. |
BEFORE INSTALLATION............................................................. |
1 |
2. |
OUTDOOR UNIT INSTALLATION................................................ |
4 |
3. |
FLARING WORK AND PIPE CONNECTION............................... |
5 |
4. |
PURGING PROCEDURES, LEAK TEST, AND TEST RUN......... |
5 |
5. |
PUMPING DOWN......................................................................... |
7 |
Required Tools for Installation
Phillips screwdriver |
5/32 in. (4 mm) hexagonal |
Level |
wrench |
Scale |
Flare tool for R410A |
Utility knife or scissors |
Gauge manifold for R410A |
Torque wrench |
Vacuum pump for R410A |
Wrench (or spanner) |
Charge hose for R410A |
|
Pipe cutter with reamer |
1. BEFORE INSTALLATION
1-1. THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY
•Be sure to read “THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY” before installing the air conditioner.
•Be sure to observe the warnings and cautions specified here as they include important items related to safety.
•After reading this manual, be sure to keep it together with the OPERATING INSTRUCTIONS for future reference.
WARNING |
(Could lead to death, serious injury, etc.) |
nDo not install the unit by yourself (user).
Incomplete installation could cause fire or electric shock, injury due to the unit falling, or leakage of water. Consult the dealer from whom you purchased the unit or a qualified installer.
nPerform the installation securely referring to the installation manual.
Incomplete installation could cause fire or electric shock, injury due to the unit falling, or leakage of water.
nWhen installing the unit, use appropriate protective equipment and tools for safety.
Failure to do so could cause injury.
nInstall the unit securely in a place which can bear the weight of the unit.
If the installation location cannot bear the weight of the unit, the unit could fall causing injury.
nPerform electrical work according to the installation manual and be sure to use an exclusive circuit. Do not connect other electrical appliances to the circuit.
If the capacity of the power circuit is insufficient or there is incomplete electrical work, it could result in a fire or an electric shock.
nDo not damage the wires by applying excessive pressure with parts or screws.
Damaged wires could cause fire.
nBe sure to cut off the main power in case of setting up the indoor P.C. board or wiring works.
Failure to do so could cause electric shock.
nUse the specified wires to connect the indoor and outdoor units securely and attach the wires firmly to the terminal block connecting sections so the stress of the wires is not applied to the sections.
Incomplete connecting and securing could cause fire.
nDo not install the unit in a place where inflammable gas may leak.
If gas leaks and accumulates in the area around the unit, it could cause an explosion.
nDo not use intermediate connection of the power cord or the extension cord and do not connect many devices to one AC outlet.
It could cause a fire or an electric shock due to defective contact, defective insulation, exceeding the permissible current, etc.
nBe sure to use the parts provided or specified parts for the installation work.
The use of defective parts could cause an injury or leakage of water due to a fire, an electric shock, the unit falling, etc.
nWhen plugging the power supply plug into the outlet, make sure that there is no dust, clogging, or loose parts in both the outlet and the plug. Make sure that the power supply plug is pushed completely into the outlet.
If there is dust, clogging, or loose parts on the power supply plug or the outlet, it could cause electric shock or fire. If loose parts are found on the power supply plug, replace it.
nAttach the electrical cover to the indoor unit and the service panel to the outdoor unit securely.
If the electrical cover of the indoor unit and/or the service panel of the outdoor unit are not attached securely, it could result in a fire or an electric shock due to dust, water, etc.
nWhen installing, relocating, or servicing the unit, make sure that no substance other than the specified refrigerant (R410A) enters the refrigerant circuit.
Any presence of foreign substance such as air can cause abnormal pressure rise and may result in explosion or injury. The use of any refrigerant other than that specified for the system will cause mechanical failure, system malfunction, or unit breakdown. In the worst case, this could lead to a serious impediment to securing product safety.
nDo not discharge the refrigerant into the atmosphere. If refrigerant leaks during installation, ventilate the room.
Ifrefrigerantcomesincontactwithafire,harmfulgascouldbegenerated.Refrigerant leakage may cause suffocation. Ventilate the room.
nCheck that the refrigerant gas does not leak after installation has been completed.
If refrigerant gas leaks indoors, and comes into contact with the flame of a fan heater, space heater, stove, etc., harmful substances will be generated.
nUse appropriate tools and piping materials for installation.
The pressure of R410A is 1.6 times more than R22. Not using appropriate tools or materials and incomplete installation could cause the pipes to burst or injury.
nWhen pumping down the refrigerant, stop the compressor before disconnecting the refrigerant pipes.
If the refrigerant pipes are disconnected while the compressor is running and the stop valve is open, air could be drawn in and the pressure in the refrigeration cycle could become abnormally high. This could cause the pipes to burst or injury.
nWhen installing the unit, securely connect the refrigerant pipes before starting the compressor.
If the compressor is started before the refrigerant pipes are connected and when the stop valve is open, air could be drawn in and the pressure in the refrigeration cycle could become abnormally high. This could cause the pipes to burst or injury.
nFasten a flare nut with a torque wrench as specified in this manual.
If fastened too tight, a flare nut may break after a long period and cause refrigerant leakage.
nThe unit shall be installed in accordance with national wiring regulations.
nGround the unit correctly.
Do not connect the ground to a gas pipe, water pipe, lightning rod or telephone ground. Defective grounding could cause electric shock.
nBe sure to install a Ground Fault Interrupt (GFI) circuit breaker.
Failure to install a Ground Fault Interrupt (GFI) circuit breaker may result in electric shock or fire.
CAUTION |
(Could lead to serious injury in particular environments when operated incorrectly.) |
nPerform the drainage/piping work securely according to the installation manual.
If there is defect in the drainage/piping work, water could drop from the unit, soaking and damaging household goods.
nDo not touch the air inlet or the aluminum fins of the outdoor unit.
This could cause injury.
nDo not install the outdoor unit where small animals may live.
If small animals enter and touch the electric parts inside the unit, it could cause a malfunction, smoke emission, or fire. Also, advise user to keep the area around the unit clean.
1-2. SPECIFICATIONS
Model |
Power supply |
|
Pipe length and height difference *1, *2, *3, *4, *5, *6 |
|
||
Rated Voltage |
Frequency |
Max. pipe length per indoor |
Max. height difference |
Max. no. of bends per in- |
Refrigerant adjustment A *7 |
|
|
unit / for multi-system |
door unit / for multi system |
||||
MXZ-3C24NA2 |
|
|
|
|
|
|
MXZ-3C30NA2 |
208 / 230 V |
60 Hz |
82 ft. (25 m) / 230 ft. (70 m) |
49 ft. (15 m) |
25 / 70 |
1.08 oz each 5 ft. (20 g/m) |
MXZ-4C36NA2 |
|
|
|
|
|
|
*1 Never use pipes with thickness less than specified. The pressure resistance will be insufficient.
*2 Use a copper pipe or a copper-alloy seamless pipe.
*3 Be careful not to crush or bend the pipe during pipe bending.
*4 Refrigerant pipe bending radius must be 4 in. (100 mm) or more.
*5 Insulation material : Heat resisting foam plastic 0.045 specific gravity
*6 Be sure to use the insulation of specified thickness. Excessive thickness may cause incorrect installation of the indoor unit and insufficient thickness may cause dew drippage.
*7 If pipe length exceeds 98 ft. (30 m), additional refrigerant (R410A) charge is required. (No additional charge is required for pipe length less than 98 ft.
(30 m).)
Additional refrigerant (ft.) = A × |
(pipe length (ft.) – 98) |
|
5 |
||
|
Additional refrigerant (m) = A × (pipe length (m) – 30)
En-1
1-3. SELECTING OPTIONAL DIFFERENT-DIAMETER JOINTS
If the diameter of connection pipe does not match the port size of outdoor unit, use optional different-diameter joints according to the following table.
|
|
|
|
(Unit: inch (mm)) |
|
|
Port size of outdoor unit |
|
Optional different-diameter joints (port size of outdoor unit → diameter of connection pipe) |
||
MXZ-3C |
MXZ-4C |
Liquid / Gas |
1/4 (6.35) → 3/8 (9.52) : PAC-493PI |
||
3/8 (9.52) → 1/2 (12.7) : MAC-454JP-E |
|||||
|
|
|
|
||
A UNIT |
1/4 (6.35) |
/ 1/2 (12.7) |
3/8 (9.52) → 5/8 (15.88) : PAC-SG76RJ-E |
||
1/2 (12.7) → 3/8 (9.52) : MAC-A455JP-E |
|||||
|
|
|
|
||
B - C UNIT |
B - D UNIT |
1/4 (6.35) |
/ 3/8 (9.52) |
1/2 (12.7) → 5/8 (15.88) : MAC-A456JP-E |
|
Refer to the installation manual of indoor unit for the diameter of connection pipe of indoor unit. |
|||||
|
|
|
|
19-11/16 (500) or more |
3.Obstacles in front (blowing) only
When there is an obstacle in front of the unit as shown in the figure, open space above, behind, and on the sides of the unit is required.
19-11/16 (500) or more
5.Obstacles in front, behind and on side(s)
•When installing the unit in an area that is enclosed with walls such as a verandah, be sure to have enough space as shown below.
In this case, the air conditioning capacity and power consumption might deteriorate.
•When installing two or more units, do not install the units in front or behind each other.
7-7/8 (200) or more |
|
|
3-15/16 (100) |
13-25/32 (350) |
|
or more |
||
or more |
||
|
||
19-11/16 (500) |
19-11/16 (500) |
|
or more |
or more |
|
Height of the obstacle is 47-1/4 (1200) or less |
|
Note:
When operating the air conditioner in low outside temperature, be sure to follow the instructions described below.
•Never install the outdoor unit in a place where its air inlet/outlet side may be exposed directly to wind.
•To prevent exposure to wind, install the outdoor unit with its air inlet side facing the wall.
•To prevent exposure to wind, it is recommended to install a baffle board on
the air outlet side of the outdoor unit.
Avoid the following places for installation where air conditioner trouble is liable to occur.
•Where flammable gas could leak.
•Where there is much machine oil.
•Salty places such as the seaside.
•Where sulfide gas is generated such as a hot spring.
•Where there is high-frequency or wireless equipment.
•Where there is emission of high levels of VOCs, including phthalate compounds, formaldehyde, etc., which may cause chemical cracking.
2.Front (blowing) side open
As long as space indicated in the figure is provided, it is allowed to install the unit where obstacles are behind and on the sides of the unit. (No obstacle above the unit)
7-7/8 (200) or more
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
3-15/16 (100) or more |
|
|
|
|
|
|
|
13-25/32 (350) or more |
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
4.Obstacles in front and behind
The unit can be used by attaching an optional outdoor blowing guide
(PAC-SH96SG-E) (but both sides and top are open).
3-15/16 (100) or more
19-11/16 (500) or more
Blowing guide (PAC-SH96SG-E)
6.Service space
Provide space for service and maintenance as shown in the figure.
Service space
3-15/16 (100) or more
13-25/32 (350) or more
3-15/16 (100) or more |
19-11/16 (500) |
or more |
13-25/32 (350) or more |
(Unit: inch (mm))
En-2
1-5. INSTALLATION DIAGRAM
Open as a rule
More than 19-11/16 in.
(500 mm) if the front and both sides are open
More than
3-15/16 in.
(100 mm)
Open as a rule
More than 19-11/16 in. (500 mm) if the back, both sides and top
are open
After the leak test, apply insulating material tightly so that there is no gap.
When the piping is to be attached to a wall containing metals (tin plated) or metal netting, use a chemically treated wooden piece 25/32 in. (20 mm) or thicker between the wall and the piping or wrap 7 to 8 turns of insulation vinyl tape around the piping.
To use existing piping, perform
COOL operation for 30 minutes and pump down before removing the old air conditioner. Remake flare according to the dimension for new refrigerant.
More than 3-15/16 in. (100 mm) More than 7-7/8 in. (200 mm) if there are obstacles to both sides
More than 13-25/32 in. (350 mm)
PARTS TO BE PROVIDED AT YOUR SITE
(A) |
Power supply cord* |
1 |
|
(B) |
Indoor/outdoor unit connecting wire* |
1 |
|
(C) |
Extension pipe |
1 |
|
(D) |
Wall hole cover |
1 |
|
(E) |
Piping tape |
1 |
|
|
Extension drain hose (or soft PVC |
|
|
(F) |
hose, 19/32 in. (15 mm) inner |
1 |
|
|
diameter or hard PVC pipe VP16) |
|
|
(G) |
Refrigeration oil |
Little |
|
amount |
|||
|
|
||
(H) |
Putty |
1 |
|
(I) |
Pipe fixing band |
2 to 7 |
|
(J) |
Fixing screw for (I) |
2 to 7 |
|
(K) |
Wall hole sleeve |
1 |
|
|
Soft PVC hose, 19/32 in. (15 mm) |
|
|
(L) |
inner diameter or hard PVC pipe |
1 |
|
|
VP16 for drain socket (1) |
|
* Note:
Place indoor/outdoor unit connecting wire (B) and power supply cord (A) at least 3 ft. (1 m) away from the TV antenna wire.
The “Q’ty” for (B) to (K) in the above table is quantity to be used per indoor unit.
Units should be installed by licensed contractor according to local code requirements.
Outdoor unit installation |
Outdoor unit installation |
37-2/5
6-6/7 23-5/8
Air inlet
Air inlet
2 - (15/32 × 6/7) |
Air outlet |
|
|
oval holes (Base bolt M10) |
|
2-U-shape notched holes
(Base bolt M10)
|
|
13 |
|
14-9/16 |
16-13/32 |
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
Unit : inch
950
174 600
Air inlet
Air inlet
2 - 12 × 22 |
Air outlet |
|
|
oval holes (Base bolt M10) |
|
2-U-shape notched holes
(Base bolt M10)
330 |
370 |
417 |
Unit : mm
En-3
2. OUTDOOR UNIT INSTALLATION
2-1. INSTALLING THE UNIT
•Be sure to fix the unit’s legs with bolts when installing it.
•Be sure to install the unit firmly to ensure that it does not fall by an earthquake or a gust.
•Refer to the figure in the right for concrete foundation.
•Do not use the drain socket and the drain caps in the cold region. Drain may freeze and it makes the fan stop.
Fix here with
M10 bolts.
Make the setting depth deeper.
Make with wider.
1-1/6 (30) or less
Anchor leg
Anchor bolt length
23-5/8
(600)
14-9/16 (370)
Anchor bolt pitch
(Unit: inch (mm))
2-2. CONNECTING WIRES FOR OUTDOOR UNIT
•Be sure to use special circuits for room air conditioner.
•Wiring work should be based on applicable technical standards.
•Wiring connections should be made following the diagram.
•Screws should be tightened so they won’t loosen.
1)Remove the service panel.
2)Remove the conduit plate.
3)Attach the conduit connector to conduit plate with lock nut then secure it to the unit with screws.
4)Connect ground wires to the TB support.
5)Loosen terminal screw, and connect indoor/outdoor unit connecting wire (B) from the indoor unit correctly on the terminal block. Be careful not to make mis-wiring. Fix the wire to the terminal block securely so that no part of its core is appeared, and no external force is conveyed to the connecting section of the terminal block.
6)Firmly tighten the terminal screws to prevent them from loosening. After tightening, pull the wires lightly to confirm that they do not move.
7)Perform 5) and 6) for each indoor unit.
8)Connect power supply cord (A).
9)Close the service panel securely. Make sure that 3-2. PIPE CONNECTION is completed.
Connecting order |
Power supply |
||
• Connect the terminal block in |
|
|
|
following order. |
|
|
|
A→B→C→D→P |
|
|
|
D unit is for 4C36NA2 only |
|
|
|
|
|
|
|
|
Terminal block for |
||
|
indoor/outdoor unit |
ELECTRICAL SPECIFICATIONS
OUTDOOR UNIT |
MXZ-3C24NA2 |
MXZ-3C30NA2 |
MXZ-4C36NA2 |
|
Power supply (V, PHASE, Hz) |
|
208/230, 1, 60 |
|
|
Max. Fuse size (time delay) (A) |
|
25 |
|
|
Min. Circuit Ampacity (A) |
|
22.1 |
23.1 |
|
Fan motor (F.L.A) |
|
|
2.43 |
2.43 |
Compressor |
(R.L.A) |
|
12 |
12 |
(L.R.A) |
|
13.7 |
13.7 |
|
|
|
|||
Control voltage |
|
Indoor unit-Remote controller : (Wireless) |
|
|
|
Indoor unit-Outdoor unit : DC12-24V |
|
||
|
|
|
||
|
|
|
|
Conduit plate |
|
|
|
|
Conduit connector |
Lock nut |
Conduit plate |
|
Service panel |
Screws |
|
Remark: |
|
|
|
|
|
|
* |
A disconnect switch should be required. Check the local code. |
|
|
|
||
** |
Use a ring tongue terminal in order to connect a ground wire to terminal. |
|
|
|||
|
INDOOR UNIT A – C D |
1-3/8 in. |
5/8 in. |
|
||
|
(15 mm) |
|
||||
|
|
|
|
|
||
|
Terminal block |
|
Terminal block |
(35 mm) |
|
|
|
|
|
|
|
||
|
|
Grounding |
|
|
|
|
|
|
terminal ** |
|
|
|
|
|
208/230 VAC |
|
|
Power supply |
Lead wire |
|
|
|
|
|
|
||
|
1 phase 60 Hz |
Disconnect |
|
208/230 VAC |
|
|
|
|
switch * |
|
1 phase 2 wires 60 Hz Grounding |
||
|
|
Grounding |
|
|
terminal ** |
|
|
|
|
|
|
|
|
|
|
terminal ** |
|
|
|
|
|
Terminal block |
A – C D |
Terminal block |
Terminal block 1 |
Ground |
|
|
|
OUTDOOR UNIT
D unit is for 4C36NA2 only
•Connect wires to the matching numbers of terminals.
•Be sure to attach each screw to its correspondent terminal when securing the cord and/or the wire to the terminal block.
CONNECTING WIRES AND CONNECTING GROUND WIRE
•Use solid conductor Min. AWG14 or stranded conductor Min. AWG14.
•Use double insulated copper wire with 600 V insulation.
•Use copper conductors only.
* Follow local electrical code.
POWER SUPPLY CABLE AND GROUND WIRE
•Use solid or stranded conductor Min. AWG12.
•Use copper conductors only.
* Follow local electrical code.
WARNING:
Use the indoor/outdoor unit connecting wire that meets the Standards to connect the indoor and outdoor units and fix the wire to the terminal block securely so that no external force is conveyed to the connecting section of the terminal block. An incomplete connection or fixing of the wire could result in a fire.
For future servicing, give extra length to the connecting wires.
En-4
3. FLARING WORK AND PIPE CONNECTION
3-1. FLARING WORK
1)Cut the copper pipe correctly with pipe cutter. (Fig. 1, 2)
2)Completely remove all burrs from the cut cross section of pipe. (Fig. 3)
•Aim the copper pipe downward while removing burrs to prevent burrs from dropping in the pipe.
3)Remove flare nuts attached to indoor and outdoor units, then put them on pipe having completed burr removal. (Not possible to put them on after flaring work.)
4)Flaring work (Fig. 4, 5). Firmly hold copper pipe in the dimension shown in the table. Select A inch (mm) from the table according to the tool selected.
5)Check
•Compare the flared work with Fig. 6.
•If flare is noted to be defective, cut off the flared section and do flaring work again.
Good |
No good |
|
Copper |
|
|
pipe |
Burr |
Copper pipe |
|
||
|
|
Spare reamer |
|
Tilted Uneven Burred |
Pipe cutter |
|
|
|
Fig. 1 |
Fig. 2 |
Fig. 3 |
Flaring tool |
|
|
Inside is shin- |
||
|
|
|
Smooth all |
ing without any |
|
|
|
Copper pipe |
around |
scratches. |
|
|
|
|
|
|
|
|
|
Die |
|
|
|
|
|
Flare nut |
|
Even length |
|
Clutch type |
Wing nut type |
|
|
|
|
B |
|
all around |
|
||
|
Fig. 4 |
Fig. 5 |
Fig. 6 |
||
|
|
||||
|
|
|
|
|
Pipe diameter |
B |
|
A [inch (mm)] |
|
|
Tightening torque |
|
||
|
|
[inch (mm)] |
[inch (mm)] |
Clutch type tool for R410A |
Clutch type tool for R22 |
Wing nut type tool for R22 |
ft-Ib |
|
N•m |
|
kgf•cm |
|
|||||||||||
|
|
1/4 (ø6.35) |
21/32 (17) |
|
|
0.06 to 0.08 |
10 to 13 |
|
13.7 to 17.7 |
|
140 to 180 |
|
|
3/8 (ø9.52) |
7/8 (22) |
0 to 0.02 |
0.04 to 0.06 |
(1.5 to 2.0) |
25 to 30 |
|
34.3 to 41.2 |
|
350 to 420 |
|
|
1/2 (ø12.7) |
1-1/32 (26) |
(0 to 0.5) |
(1.0 to 1.5) |
0.08 to 1.0 |
36 to 42 |
|
49.0 to 56.4 |
|
500 to 575 |
|
|||||||||||
|
|
5/8 (ø15.88) |
1-5/32 (29) |
|
|
(2.0 to 2.5) |
54 to 58 |
|
73.5 to 78.4 |
|
750 to 800 |
3-2. PIPE CONNECTION
1)Apply a thin coat of refrigeration oil (G) to the flared ends of the pipes and the pipe connections of the outdoor unit.
2)Align the center of the pipe with that of the pipe connections of the outdoor unit, then hand tighten the flare nut 3 to 4 turns.
3)Tighten the flare nut with a torque wrench as specified in the table.
•Over-tightening may cause damage to the flare nut, resulting in refrigerant leakage.
•Be sure to wrap insulation around the piping. Direct contact with the bare piping may result in burns or frostbite.
3-3. INSULATION AND TAPING
1)Cover piping joints with pipe cover.
2)For outdoor unit side, surely insulate every piping including valves.
3)Using piping tape (E), apply taping starting from the entry of outdoor unit.
•Stop the end of piping tape (E) with tape (with adhesive agent attached).
•When piping have to be arranged through above ceiling, closet or where the temperature and humidity are high, wind additional commercially sold insulation to prevent condensation.
WARNING
When installing the unit, securely connect the refrigerant pipes before starting the compressor.
CAUTION
When there are the ports which are not used, make sure their nuts are tightened securely.
4. PURGING PROCEDURES, LEAK TEST, AND TEST RUN
4-1. PURGING PROCEDURES AND LEAK TEST
1)Remove service port cap of stop valve on the side of the outdoor unit gas pipe. (The stop valves are fully closed and covered in caps in their initial state.)
2)Connect gauge manifold valve and vacuum pump to service port of stop valve on the gas pipe side of the outdoor unit.
3)Run the vacuum pump. (Vacuumize for more than 15 minutes.)
4)Check the vacuum with gauge manifold valve, then close gauge manifold valve, and stop the vacuum pump.
5)Leave as it is for one or two minutes. Make sure the pointer of gauge manifold valve remains in the same position. Confirm that pressure gauge shows –14.7 psi [Gauge] (–0.101 MPa).
6)Remove gauge manifold valve quickly from service port of stop valve.
7)Fully open all stop valves on the gas pipe and the liquid pipe. Operating without fully opening lowers the performance and this causes trouble.
8)Refer to 1-2., and charge the prescribed amount of refrigerant if needed. Be sure to charge slowly with liquid refrigerant. Otherwise, composition of the refrigerant in the system may be changed and affect performance of the air conditioner.
9)Tighten cap of service port to obtain the initial status.
10)Leak test
*4 to 5 turns
*Close
*Open
Hexagonal wrench
|
Compound pressure |
||
|
gauge (for R410A) |
||
Service port cap |
–14.7 psi |
Pressure gauge |
|
(–0.101MPa) |
|||
(Torque 10 to 13 ft-lb, |
(for R410A) |
||
|
|||
13.7 to 17.7 N•m, 140 |
|
Gauge mani- |
|
to 180 kgf•cm) |
|
||
|
|
fold valve (for |
|
|
|
R410A) |
|
|
Handle |
Handle High |
|
|
Low |
Charge hose |
|
|
|
(for R410A) |
|
|
Stop valve cap |
|
|
Stop valve |
(Torque 15 to |
|
|
for LIQUID |
22 ft-lb, 19.6 to |
Vacuum pump |
|
Stop valve |
29.4 N•m, 200 |
(for R410A) |
|
for GAS |
to 300 kgf•cm) |
|
Precautions when using the control valve
Body |
Close Open |
Control valve
A
Charge hose
(for R410A) Service port
When attaching the control valve to the service port, valve core may deform or loosen if excess pressure is applied. This may cause gas leak.
When attaching the control valve to the service port, make sure that the valve core is in closed position, and then tighten part A. Do not tighten part A or turn the body when valve core is in open position.
En-5
4-2. GAS CHARGE
Perform gas charge to unit.
1)Connect gas cylinder to the service port of stop valve.
2)Perform air purge of the pipe (or hose) coming from refrigerant gas cylinder.
3)Replenish specified amount of the refrigerant, while operating the air conditioner for cooling.
Note:
In case of adding refrigerant, comply with the quantity specified for the refrigerating cycle.
CAUTION:
When charging the refrigerant system with additional refrigerant, be sure to use liquid refrigerant. Adding gas refrigerant may change the composition of the refrigerant in the system and affect normal operation of the air conditioner. Also, charge the liquid refrigerant slowly, otherwise the compressor will be locked.
To maintain the high pressure of the gas cylinder, warm the gas cylinder with warm water (under
104°F (40°C)) during cold season. But never use naked fire or steam.
|
Stop valve |
|
|
Union |
|
Liquid |
|
|
pipe |
||
|
|
||
Union |
|
|
|
|
Indoor |
Outdoor |
|
|
unit |
unit |
|
Union |
Stop valve with |
Gas |
|
Union |
service port |
pipe |
|
|
|
||
Refrigerant gas |
|
* D unit is for |
|
cylinder |
|
||
|
4C36NA2 only. |
||
operating valve |
Gauge manifold |
||
|
|||
(for R410A) |
valve (for R410A) |
||
|
|
Charge hose |
|
|
|
(for R410A) |
|
|
Refrigerant gas cylinder for R410A with siphon |
Refrigerant (liquid)
Electronic scale for refrigerant charging
4-3. LOCKING THE OPERATION MODE OF THE AIR CONDITIONER (COOL, DRY, HEAT)
•Description of the function:
With this function, once the operation mode is locked to either COOL/DRY mode or HEAT mode, the air conditioner operates in that mode only.
* Changing the setting is required to activate this function. Please explain about this function to your customers and ask them whether they want to use it.
[How to lock the operation mode]
1)Be sure to turn off the main power for the air conditioner before making the setting.
2)Set the “3” of SW1 on the outdoor controller board to ON to enable this function.
3)To lock the operation mode in COOL/DRY mode, set the “4” of SW1 on the outdoor controller board to OFF. To lock the operation in HEAT mode, set the same switch to ON.
4)Turn on the main power for the air conditioner.
LED
SW1
SW871
SW2
SW1 |
|
|
|
|
|
|
|
|
SW1 |
|
|
|
|
|
|
|
|
|||||||||
|
ON |
|
|
|
|
|
|
|
|
|
|
ON |
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1 |
2 |
3 |
|
4 |
|
5 |
|
6 |
|
|
|
1 |
|
2 |
|
3 |
|
4 |
|
5 |
|
6 |
|
COOL/DRY HEAT
4-4. LOWERING THE OPERATION NOISE OF THE OUTDOOR UNIT
• Description of the function:
With this function, the operating noise of the outdoor unit can be lowered by reducing the operation load, for example, during nighttime in COOL mode. However, please note that the cooling and heating capacity may lower if this function is activated.
* Changing the setting is required to activate this function. Please explain about this function to your customers and ask them whether they want to use it.
[How to lower the operating noise]
1)Be sure to turn off the main power for the air conditioner before making the setting.
2)Set the “5” of SW1 on the outdoor controller board to ON to enable this function.
3)Turn on the main power for the air conditioner.
SW1
ON |
|
|
|
|
|
1 |
2 |
3 |
4 |
5 |
6 |
Lower the operating noise
En-6
4-5. TEST RUN
•Test runs of the indoor units should be performed individually. See the installation manual coming with the indoor unit, and make sure all the units operate properly.
•If the test run with all the units is performed at once, possible erroneous connections of the refrigerant pipes and the indoor/outdoor unit connecting wires cannot be detected. Thus, be sure to perform the test run one by one.
About the restart protective mechanism
Once the compressor stops, the restart preventive device operates so the compressor will not operate for 3 minutes to protect the air conditioner.
Wiring/piping correction function
This unit has a wiring/piping correction function which corrects wiring and piping combination. When there is possibility of incorrect wiring and piping combination, and confirming the combination is difficult, use this function to detect and correct the combination by following the procedures below.
Make sure that the following is done.
•Power is supplied to the unit.
•Stop valves are open.
Note:
During detection, the operation of the indoor unit is controlled by the outdoor unit. During detection, the indoor unit automatically stops operation. This is not a malfunction.
Procedure
Press the piping/wiring correction switch (SW871) 1 minute or more after turning on the power supply.
•Correction completes in 10 to 20 minutes. When the correction is completed, its result is shown by LED indication. Details are described in the following table.
•To cancel this function during its operation, press the piping/wiring correction switch
(SW871) again.
•When the correction completed without error, do not press the piping/wiring correction switch (SW871) again.
LED indication during detection:
LED1 |
LED2 |
LED3 |
(Red) |
(Yellow) |
(Green) |
Lighted |
Lighted |
Once |
When the result is “Not completed”, press the piping/wiring correction switch (SW871) again to cancel this function. Then, confirm the wiring and piping combination in a conventional manner by operating the indoor units one by one.
•The operation is done while the power is supplied. Make sure not to contact parts other than the switch, including the P.C. board. This may cause electric shock or burn by hot parts and live parts around the switch. Contacting the live parts may cause P.C. board damage.
•To prevent electronic control P.C. board damage, make sure to perform static elimination before operating this function.
•This function does not operate when the outside temperature is 32°F (0°C) or below.
Result of piping/wiring correction function
LED1 |
LED2 |
LED3 |
Result |
|
(Red) |
(Yellow) |
(Green) |
||
|
||||
|
|
|
Completed |
|
Lighted |
Not lighted |
Lighted |
(Problem corrected or |
|
|
|
|
normal) |
|
Once |
Once |
Once |
Not completed |
|
(Detection failed) |
||||
|
|
|
||
|
|
|
Refer to “SAFETY PRE- |
|
Other indications |
CAUTIONS WHEN LED |
|||
BLINKS” located behind |
||||
|
|
|
||
|
|
|
the service panel. |
4-6. EXPLANATION TO THE USER
•Using the OPERATING INSTRUCTIONS, explain to the user how to use the air conditioner (how to use the remote controller, how to remove the air filters, how to remove or put the remote controller in the remote controller holder, how to clean, precautions for operation, etc.).
•Recommend the user to read the OPERATING INSTRUCTIONS carefully.
5. PUMPING DOWN
When relocating or disposing of the air conditioner, pump down the system following the procedure below so that no refrigerant is released into the atmosphere.
1)Turn off the breaker.
2)Connect the gauge manifold valve to the service port of the stop valve on the gas pipe side of the outdoor unit.
3)Fully close the stop valve on the liquid pipe side of the outdoor unit.
4)Turn on the breaker.
5)Start the emergency COOL operation on all the indoor units.
6)When the pressure gauge shows 0.1 to 0 psi [Gauge] (0.05 to 0 MPa), fully close the stop valve on the gas pipe side of the outdoor unit and stop the operation. (Refer to the indoor unit installation manual about the method for stopping the operation.)
*If too much refrigerant has been added to the air conditioner system, the pressure may not drop to 0.1 to 0 psi [Gauge] (0.05 to 0 MPa), or the protection function may operate due to the pressure increase in the high-pressure refrigerant circuit. If this occurs, use a refrigerant collecting device to collect all of the refrigerant in the system, and then recharge the system with the correct amount of refrigerant after the indoor and outdoor units have been relocated.
7)Turn off the breaker. Remove the pressure gauge and the refrigerant piping.
WARNING
When pumping down the refrigerant, stop the compressor before disconnecting the refrigerant pipes.
The compressor may burst and cause injury if any foreign substance, such as air, enters the pipes.
En-7