Lenze TML Flux Vector User Manual [en, de, es, fr, it]

4.5 (2)

TML

Flux Vector Drive

0.25 kW... 2.2 kW

Operating Instructions

EN

 

 

 

 

 

 

Betriebsanleitung

DE

 

 

 

 

Instructions de mise en service

FR

 

 

 

 

Istruzioni operative

IT

 

 

 

 

Instrucciones para el servicio

ES

 

 

 

(13466187)

Contents

About these instructions.................................................................................

2

 

1

Safety information....................................................................................

3

 

 

1.1

Pictographs used in these instructions..........................................

4

 

2

Technical data..........................................................................................

6

 

 

2.1

Standards and application conditions............................................

6

 

 

2.2

Ratings...........................................................................................

7

 

3

................................................................................................Installation

 

8

 

 

3.1

...................................................................Mechanical installation

8

 

 

 

3.1.1 Dimensions and mounting....................................................

8

 

 

3.2

Electrical installation......................................................................

9

 

 

 

3.2.1

Installation according to EMC requirements.........................

9

 

 

 

3.2.2

Fuses/cable cross-sections .................................................

9

 

 

 

3.2.3

Connection diagram...........................................................

10

 

 

 

3.2.4

Control terminals................................................................

11

 

4

Commissioning......................................................................................

12

 

 

4.1

Parameter setting.........................................................................

12

 

 

4.2

Electronic programming module (EPM).......................................

12

 

 

4.3

Parameter menu..........................................................................

13

 

 

4.4

Vector mode.................................................................................

20

 

 

 

4.4.1 Vector speed and torque modes........................................

20

 

 

 

4.4.2 Enhanced V/Hz mode.......................................................

20

 

5

Troubleshooting and fault elimination....................................................

21

 

Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES

1

About these instructions

This documentation applies to the Tml vector frequency inverter, and contains important technical data and describes installation, operation, and commissioning.

Please read the instructions before commissioning.

 

 

 

 

A

 

B

 

 

C

 

D

E F

 

 

 

 

Type:

 

 

 

 

 

 

 

 

 

+

 

 

 

 

 

 

 

Input: 1/N/PE (2PE)

Output: 3/PE

For detailed information

 

 

 

 

 

ETML751X2SFA

 

 

 

230 V

 

0-230 V

refer to instruction

 

 

 

 

 

 

 

 

 

 

 

 

Id-No: 13xxxxx

 

 

 

9.2 A

 

4.2 A

Manual TL03

 

 

 

 

 

 

 

 

 

 

Made in USA

 

 

 

 

 

 

50-60 Hz

 

0.75 kW

SN: 13xxxxxx012345678

 

 

 

 

 

Inverter

 

 

 

 

 

 

 

 

 

0 - 240 Hz

ETML751X2SFA000XX

XX

 

XX

 

 

 

 

 

LISTED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5D81

 

 

 

1341308801234567

 

 

 

 

 

 

Tml - basic I/O

 

 

IND. CONT. EQ.

 

N10104

 

 

 

 

 

 

 

 

 

 

 

Z519

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

V0006

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A Certifications

 

 

C Input Ratings

 

 

E Hardware Version

 

 

 

 

 

B Type

 

 

D Output Ratings

 

 

F Software Version

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Scope of delivery

 

 

 

 

Important

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• 1 Tml vector inverter (ETML...)

 

After receipt of the delivery, check immediately whether the items

 

 

with EPM installed (see Section 4.2) delivered match the accompanying papers. Lenze does not accept

 

 

• 1 Operating Instructions

 

 

any liability for deficiencies claimed subsequently.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Claim

visible transport damage immediately to the forwarder.

visible deficiencies/incompleteness immediately to your Lenze representative.

© 2013 - 2004 Lenze AC Tech Corporation

No part of this documentation may be copied or made available to third parties without the explicit written approval of Lenze AC Tech Corporation.

All information given in this documentation has been carefully selected and tested for compliance with the hardware and software described. Nevertheless, discrepancies cannot be ruled out. We do not accept any responsibility nor liability for damages that may occur. Any necessary corrections will be implemented in subsequent editions.

2

Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES

Safety information

1 Safety information

General

Some parts of Lenze controllers (frequency inverters, servo inverters, DC controllers) can be live, moving and rotating. Some surfaces can be hot.

Non-authorized removal of the required cover, inappropriate use, and incorrect installation or operation creates the risk of severe injury to personnel or damage to equipment.

All operations concerning transport, installation, and commissioning as well as maintenance must be carried out by qualified, skilled personnel (IEC 364 and CENELEC HD 384 or DIN

VDE 0100 and IEC report 664 or DIN VDE0110 and national regulations for the prevention of accidents must be observed).

According to this basic safety information, qualified skilled personnel are persons who are familiar with the installation, assembly, commissioning, and operation of the product and who have the qualifications necessary for their occupation.

Application as directed

Drive controllers are components which are designed for installation in electrical systems or machinery. They are not to be used as appliances. They are intended exclusively for professional and commercial purposes according to EN 61000-3-2. The documentation includes information on compliance with the EN 61000-3-2.

When installing the drive controllers in machines, commissioning (i.e. the starting of operation as directed) is prohibited until it is proven that the machine complies with the regulations of the EC Directive 2006/42/EC (Machinery Directive); EN 60204 must be observed.

Commissioning (i.e. starting of operation as directed) is only allowed when there is compliance with the EMC Directive (2004/108/EEC).

The drive controllers meet the requirements of the Low Voltage Directive 2006/95/EC. The harmonised standards of the series EN 50178/DIN VDE 0160 apply to the controllers.

Note: The availability of controllers is restricted according to EN 61800-3.These products can cause radio interference in residential areas. In this case, special measures can be necessary.

Installation

Ensure proper handling and avoid excessive mechanical stress. Do not bend any components and do not change any insulation distances during transport or handling. Do not touch any electronic components and contacts.

Controllers contain electrostatically sensitive components, which can easily be damaged by inappropriate handling. Do not damage or destroy any electrical components since this might endanger your health!

Electrical connection

When working on live drive controllers, applicable national regulations for the prevention of accidents (e.g. VBG 4) must be observed.

The electrical installation must be carried out according to the appropriate regulations (e.g. cable cross-sections, fuses, PE connection). Additional information can be obtained from the documentation.

The documentation contains informa3tion about installation in compliance with EMC (shielding, grounding, filters and cables). These notes must also be observed for CE-marked controllers.

The manufacturer of the system or machine is responsible for compliance with the required limit values demanded by EMC legislation.

Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES

3

Safety information

Operation

Systems including controllers must be equipped with additional monitoring and protection devices according to the corresponding standards (e.g. technical equipment, regulations for prevention of accidents, etc.). You are allowed to adapt the controller to your application as described in the documentation.

WARNING!

• After the controller has been disconnected from the supply voltage, live components and power connection must not be touched immediately, since capacitors could be charged. Please observe the corresponding notes on the controller.

Do not continuously cycle input power to the controller more than once every three minutes.

Please close all protective covers and doors during operation.

1.1Pictographs used in these instructions

Pictograph

Signal word

Meaning

Consequences if ignored

 

 

 

 

 

 

 

 

 

WARNING!

Impending or possible danger

Death or injury.

 

 

 

 

for persons.

Damage to drive system or its

 

 

 

 

Possible damage to equipment

surroundings

 

 

 

 

 

 

 

 

 

Note

Useful tip: If observed, it will

 

 

 

 

 

 

 

 

 

make using the drive easier

 

 

 

 

 

 

 

 

 

 

 

 

 

4

Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES

Safety information

Note for UL approved system with integrated controllers

UL warnings are notes which apply to UL systems. The documentation contains special information about UL.

• Integral solid state protection does not provide branch circuit protection. Branch circuit protection must be provided in accordance with the National Electrical Code and any additional local codes. The use of fuses or circuit breakers is

Warnings!

the only approved means for branch circuit protection.

 

• When protected by CC and T Class Fuses, suitable for use on a circuit capable

 

 

 

 

of delivering not more than 200,000 rms symmetrical amperes, at the maximum

 

 

 

 

voltage rating marked on the drive.

 

 

 

 

• Additionally suitable when protected by a circuit breaker having an interrupting

 

 

rating not less than 200,000 rms symmetrical amperes, at the maximum voltage

 

 

rating marked on the drive.

 

 

• Use minimum 75°C copper wire only, except for control circuits.

 

 

• For control circuits, use wiring suitable for NEC Class 1 circuits only.

 

 

• Torque Requirements are listed in section 3.2.3, Connection diagram.

 

 

• Shall be installed in a pollution degree 2 macro-environment.

 

 

 

 

 

WARNING!

Risk of Electric Shock! Capacitors retain charge for approximately 180 seconds after power is removed. Disconnect incoming power and wait at least 3 minutes before touching the drive.

WARNING!

The opening of branch-circuit protective device may be an indication that a fault has been interrupted. To reduce the risk of fire or electric shock, current carrying parts and other components of the controller should be examined and replaced if damaged.

Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES

5

Technical data

2 Technical data

2.1Standards and application conditions

 

 

Conformity

CE

Low Voltage Directive (2006/95/EC)

 

 

Approvals

UL 508C

Underwriters Laboratories - Power Conversion Equipment

 

 

 

 

 

 

 

 

Max. permissible motor cable

shielded:

50 m (low-capacitance)

 

 

length (1)

unshielded:

100 m

 

 

Input voltage phase imbalance

< 2%

 

 

 

 

 

 

 

 

 

 

 

 

Humidity

< 95% non-condensing

 

 

 

Output frequency

0...240 Hz

 

 

 

 

 

 

 

 

 

Environmental conditions

Class 3K3 to EN 50178

 

 

 

 

 

 

 

 

 

Transport

 

-25 … +70 °C

 

 

Temperature range

Storage

 

-20 … +70 °C

 

 

 

 

 

 

 

 

 

Operation

 

0 … +55 °C (with 2.5 %/°C current derating above +40 °C)

 

 

Installation height

0 … 4000 m a.m.s.l. (with 5 %/1000 m current derating above 1000 m

 

 

a.m.s.l.)

 

 

 

 

 

 

 

 

 

 

 

 

 

Vibration resistance

acceleration resistant up to 0.7 g

 

 

 

 

 

 

 

 

Earth leakage current (EN 50178)

> 3.5 mA to PE

 

 

 

 

Enclosure (EN 60529)

IP 20

 

 

 

 

 

 

 

 

Protection measures against

short circuit, earth fault, overvoltage, motor stalling, motor overload

 

 

 

Total power

 

Compliance with the requirements (2)

 

 

 

connected to

 

 

 

Operation in public supply networks

the mains

 

 

 

 

(Limitation of harmonic currents

< 0.5 kW

 

With mains choke

 

 

according to EN 61000-3-2)

 

 

 

 

 

0.5 … 1 kW

 

With active filter (in preparation)

 

 

 

 

 

 

 

 

 

 

 

 

 

> 1 kW

 

Without additional measures

 

 

 

 

 

 

(1)For compliance with EMC regulations, the permissible cable lengths may change.

(2)The additional measures described only ensure that the controllers meet the requirements of the EN 61000-3-2. The machine/system manufacturer is responsible for the compliance with the regulations of the machine!

6

Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES

Technical data

2.2Ratings

 

 

Mains

 

 

 

Output Current

 

 

 

Type

Power

 

 

 

 

 

 

 

 

 

[kW]

 

Current

IN

 

Imax for 60 s

 

 

 

Voltage, frequency

 

 

 

 

 

[A]

 

 

 

 

 

 

 

 

 

 

[A] (1)

 

[A] (2)

[A] (1)

[A] (2)

 

 

ETML251X2SFA

0.25

 

3.4

1.7

 

1.6

2.6

2.4

 

 

 

 

 

 

 

 

 

 

 

 

 

ETML371X2SFA

0.37

 

5.0

2.4

 

2.2

3.6

3.3

 

 

 

 

 

 

 

 

 

 

 

 

 

ETML551X2SFA

0.55

1/N/PE 230 V

6.0

3.2

 

2.9

4.8

4.4

 

 

 

 

 

(180 V -0%…264 V +0%)

 

 

 

 

 

 

 

 

ETML751X2SFA

0.75

9.2

4.2

 

3.9

6.3

5.8

 

 

50/60 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

ETML112X2SFA

1.1

(48 Hz -0%…62 Hz +0%)

12.0

6.0

 

5.5

9.0

8.3

 

 

 

 

 

 

 

 

 

 

 

 

 

ETML152X2SFA

1.5

 

16.0

7.0

 

6.4

10.5

9.6

 

 

 

 

 

 

 

 

 

 

 

 

 

ETML222X2SFA

2.2

 

21

9.6

 

8.8

14.4

13.2

 

 

 

 

 

 

 

 

 

 

 

 

 

(1)For rated mains voltage and carrier frequencies 4, 6, and 8 kHz

(2)For rated mains voltage and carrier frequency 10 kHz

Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES

7

Installation

3 Installation

3.1Mechanical installation

3.1.1Dimensions and mounting

 

 

 

 

 

 

 

 

 

 

 

 

Tml002

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Type

a

a1

b

b1

b2

c

s1

s2

m

 

 

[mm]

[mm]

[mm]

[mm]

[mm]

[mm]

[mm]

[mm]

[kg]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ETML251X2SFA

93

84

146

128

17

83

15

50

0.5

 

 

 

ETML371X2SFA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ETML551X2SFA

93

84

146

128

17

92

15

50

0.6

 

 

 

ETML751X2SFA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ETML112X2SFA

114

105

146

128

17

124

15

50

1.2

 

 

 

ETML152X2SFA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ETML222X2SFA

114

105

146

128

17

140

15

50

1.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WARNING!

Drives must not be installed where subjected to adverse environmental conditions such as: combustible, oily, or hazardous vapors or dust; excessive moisture; excessive vibration or excessive temperatures. Contact Lenze for more information.

8

Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES

Installation

3.2Electrical installation

3.2.1Installation according to EMC requirements

EMC

Compliance with EN 61800-3/A11

Noise emission

Drive models ending in the suffix “SFA” are in compliance with limit value class A

according to EN 55011 if installed in a control cabinet and with a motor cable not B longer than 10m.

A Screen clamps

 

 

 

 

 

 

 

C

B Control cable

 

 

 

 

 

 

 

 

 

D

A

 

 

 

 

 

CLow-capacitance motor cable

(core/core < 75 pF/m, core/screen < 150 pF/m)

DElectrically conductive mounting plate

Tml005

3.2.2Fuses/cable cross-sections(1)

 

Installation to EN 60204-1

Installation to UL

 

Type

Fuse

Miniature

L1, L2, L3,

Fuse (3)

L1, L2, L3,

E.l.c.b.(2)

 

circuit

PE [mm²]

PE [AWG]

 

 

 

breaker

 

 

 

 

 

 

 

 

ETML251X2SFA

 

 

 

 

 

 

ETML371X2SFA

M10 A

C10 A

1.5

10 A

14

 

ETML551X2SFA

 

 

 

 

 

 

ETML751X2SFA

M16 A

C16 A

2.5

15 A

14

> 30 mA

ETML112X2SFA

M20 A

C20 A

2.5

20 A

12

 

ETML152X2SFA

M25 A

C25 A

2.5

25 A

12

 

ETML222X2SFA

M30 A

C30 A

4.0

30 A

10

 

(1)Observe the applicable local regulations

(2)Pulse-current or universal-current sensitive earth leakage circuit breaker

(3)UL Class CC or T fast-acting current-limiting type fuses, 200,000 AIC, required. Bussman KTK-R, JJN, JJS, or equivalent

Observe the following when using E.l.c.b:

Installation of E.l.c.b only between supplying mains and controller.

The E.l.c.b can be activated by:

-apacitive leakage currents between the cable screens during operation (especially with long, screened motor cables)

-connecting several controllers to the mains at the same time

-RFI filters

Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES

9

Installation

3.2.3Connection diagram

Tml003

WARNING!

• Hazard of electrical shock! Circuit potentials are up to 230 VAC above earth ground. Capacitors retain charge after power is removed. Disconnect power and wait until the voltage between B+ and B- is 0 VDC before servicing the drive.

Do not connect mains power to the output terminals (U,V,W)! Severe damage to the drive will result.

Do not cycle mains power more than once every three minutes. Damage to the drive will result.

10

Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES

Installation

3.2.4Control terminals

Terminal

Data for control connections (printed in bold = Lenze setting)

 

 

 

 

 

 

 

 

 

 

7

Reference common

 

 

 

 

 

 

 

 

 

 

 

 

8

Analog input

input resistance: >50 kΩ

 

 

 

0 … 10 V (changeable under C34)

(with current signal: 250 Ω)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

Internal DC supply for setpoint potentiometer

+10 V, max. 10 mA

 

 

 

 

 

 

 

 

 

 

20

Internal DC supply for digital inputs

+12 V, max. 20 mA

 

 

 

 

 

 

 

 

 

 

28

Digital input Start/Stop

LOW = Stop; HIGH = Run Enable

 

 

 

 

 

 

input resistance = 3.3 kΩ

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E1

Digital input configurable with CE1

HIGH = JOG1 active

 

 

 

 

Activate fixed setpoint 1 (JOG1)

 

 

 

 

 

 

Both HIGH = JOG3 active

kΩ

 

 

 

 

 

 

 

 

 

 

 

 

E2

Digital input configurable with CE2

HIGH = JOG2 active

 

3.3

 

 

 

Activate fixed setpoint 2 (JOG2)

 

 

=

 

 

 

 

 

 

i

 

 

E3

Digital input configurable with CE3

HIGH = DCB active

R

 

 

 

 

 

Activate DC injection brake (DCB)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

K14

Relay output (N.O. contact)

AC 250V / 3A

 

 

 

 

configurable with C08

 

 

 

 

DC 24V / 2A ... 240V / 0.22A

 

 

 

K12

Fault (TRIP)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW = 0 … +3 V, HIGH = +12 … +30 V

Protection against contact

All terminals have a basic isolation (single insulating distance)

Protection against contact can only be ensured by additional measures (i.e. double insulation)

Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES

11

Commissioning

4 Commissioning

4.1Parameter setting

 

Status/fault messages

Change parameters

 

 

 

 

 

 

Tml004

Note

If the password function is enabled, the password must be entered into C00 to access the parameters. C00 will not appear unless the password function is enabled. See C94.

4.2Electronic programming module (EPM)

Tmd007

The EPM contains the controller’s memory. Whenever parameter settings are changed, the values are stored in the EPM. It can be removed, but must be installed for the controller to operate (a missing EPM will trigger an F1 fault). The controller ships with protective tape over the EPM that can be removed after installation.

An optional EPM Programmer (model EEPM1RA) is available that allows: the controller to be programmed without power; OEM settings to be default settings; fast copying of EPMs when multiple controllers require identical settings. It can also store up to 60 custom parameter files for even faster controller programming.

12

Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES

Commissioning

4.3Parameter menu

Code

 

Possible Settings

IMPORTANT

No.

Name

Lenze

Selection

 

C00

Password entry

0

0

999 Visible only when password is active

 

 

 

 

(see C94)

C01

Setpoint and control

0

Setpoint source:

Control configuration:

 

source

 

 

 

0Analog input (terminal 8; see C34)

1Code c40 / Code C47

 

 

 

Control = terminals

 

 

 

 

 

 

2

Analog input (terminal 8; see C34)

Programming = keypad

 

 

 

 

 

 

 

 

3

Code c40 / Code C47

 

 

 

 

 

 

 

 

 

 

4

Analog input (terminal 8; see C34)

Control = terminals

 

 

 

 

Programming = remote keypad

 

 

5

Code c40 / Code C47

 

 

Monitoring = remote keypad

 

 

 

 

 

 

 

 

6

Analog input (terminal 8; see C34)

Control = remote keypad

 

 

 

 

Programming = remote keypad

 

 

7

Code c40 / Code C47

 

 

Monitoring = remote keypad

 

 

 

 

 

 

 

Note

When C01 = 1, 3, 5, or 7 and C14 = 0...4, 6, 7, use c40 for speed setpoint

When C01 = 1, 3, 5, or 7 and C14 = 5, use C47 for torque setpoint

When C01 = 4...7, terminals E2 and E3 must be used for the remote keypad, selections made for CE2 and CE3 will be ignored.

C02 Load Lenze setting

0

No action/loading complete

• C02 = 1, 2, 3 only possible with

 

1

Load 50 Hz Lenze settings

OFF or 1NH

 

• C02 = 2 : C11, C15 and C89 = 60

 

2

Load 60 Hz Lenze settings

Hz and C87 = 1750RPM

 

 

 

3

Load OEM settings (if present)

 

 

WARNING!

 

 

C02 = 1...3 overwrites all settings! TRIP circuitry may be disabled! Check codes CE1...

 

CE3.

 

Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES

13

Commissioning

Code

 

Possible Settings

IMPORTANT

No.

Name

Lenze

Selection

 

CE1

Configuration -

1

1 Activate fixed setpoint 1 (JOG1)

Activate JOG3: Both terminals = HIGH

 

Digital input E1

 

 

 

2Activate fixed setpoint 2 (JOG2)

 

 

 

3

DC braking (DCB)

see also C36

 

 

 

4

Direction of rotation

LOW = CW rotation

 

 

 

 

 

HIGH = CCW rotation

 

 

 

5

Quick stop

Controlled deceleration to standstill,

 

 

 

 

 

active LOW; Set decel rate in C13

 

 

 

 

 

or c03

 

 

 

6

CW rotation

CW rotation = LOW and CCW rotation

CE2

Configuration -

2

7

CCW rotation

= LOW: Quick stop; Open-circuit

protected

 

Digital input E2

 

 

 

 

 

8

UP (setpoint ramp-up)

UP = LOW and DOWN = LOW: Quick

 

 

 

 

 

 

9

DOWN (setpoint ramp-down)

stop; Use momentary NC contacts

 

 

 

10

TRIP set

Active LOW, triggers EER (motor

 

 

 

 

 

coasts to standstill)

 

 

 

 

 

NOTE: NC thermal contact from the

 

 

 

 

 

motor can be used to trigger this input

 

 

 

11

TRIP reset

see also c70

 

 

 

12

Accel/decel 2

see c01 and c03

CE3

Configuration -

3

1…12 (same as above)

• 1…12 configures terminal E3 as

 

Digital input/output E3

 

13...19 (reserved)

an input.

 

 

 

• 20…29 configures terminal E3 as a

 

 

 

20

Ready

current-sourcing (PNP) output rated

 

 

 

12 VDC / 50 mA

 

 

 

21

Fault

 

 

 

 

 

 

 

22

Motor is running

 

 

 

 

23

Motor is running - CW rotation

 

 

 

 

24

Motor is running - CCW rotation

 

 

 

 

25

Output frequency = 0Hz

 

 

 

 

26

Frequency setpoint reached

 

 

 

 

27

Frequency threshold (C17) exceeded

 

 

 

 

28

Current limit (motor or generator mode)

 

 

 

 

 

reached

 

 

 

 

29

Dynamic braking

 

 

 

 

Note

 

 

 

 

A CFG fault will occur under the following conditions:

 

 

 

• E1...E3 settings are duplicated (each setting can only be used once)

 

 

 

• One input is set to UP and another is not set to DOWN, or vice-versa

 

 

 

• When C01 = 4...7, terminals E2 and E3 must be used for the remote keypad, selections

 

 

 

 

made for CE2 and CE3 will be ignored.

 

C08

Configuration - Relay

1

Relay is energized if

 

 

output (terminals K14

 

0

Ready

 

 

and K12

 

1

Fault

 

 

 

 

2

Motor is running

 

 

 

 

3

Motor is running - CW rotation

 

 

 

 

4

Motor is running - CCW rotation

 

 

 

 

5

Output frequency = 0Hz

 

 

 

 

6

Frequency setpoint reached

 

 

 

 

7

Frequency threshold (C17) exceeded

 

 

 

 

8

Current limit (motor or generator mode)

 

 

 

 

 

reached

 

14

Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES

 

 

 

 

Commissioning

Code

 

Possible Settings

 

IMPORTANT

No.

Name

Lenze

Selection

 

 

 

C10

Minimum output

0.0

0.0

{Hz}

240

• Output frequency at 0% analog

 

frequency

 

 

 

 

setpoint

 

 

 

 

 

 

• C10 not active for fixed setpoints or

 

 

 

 

 

 

setpoint selection via c40

C11

Maximum output

50.0

7.5

{Hz}

240

• Output frequency at 100% analog

 

frequency

 

 

 

 

setpoint

 

 

 

 

 

 

• C11 is never exceeded

 

 

 

WARNING!

 

 

 

 

 

Consult motor/machine manufacturer before operating above rated frequency.

 

 

 

Overspeeding the motor/machine may cause damage to equipment and injury to

 

 

 

personnel!

 

 

C12

Acceleration time 1

5.0

0.0

{s}

999

• C12 = frequency change

 

 

 

 

 

 

0 Hz...C11

C13

Deceleration time 1

5.0

0.0

{s}

999

• C13 = frequency change

C11...0 Hz

 

 

 

 

 

 

• For S-ramp accel/decel, adjust c82

C14

Operating Mode

2

0

Linear characteristic with

 

• Linear characteristic: for standard

 

 

 

 

Auto-Boost

 

applications

 

 

 

1 Square-law characteristic with

 

• Square-law characteristic: for fans

 

 

 

 

and pumps with square-law load

 

 

 

 

Auto-Boost

 

 

 

 

 

 

characteristic

 

 

 

 

 

 

 

 

 

2 Linear characteristic with constant

 

• Auto boost: load-dependent output

 

 

 

 

Vmin boost

 

voltage for low-loss operation

3Square-law characteristic with constant Vmin boost

 

4

Vector speed control

• Vector speed control: for single-

 

 

 

motor applications requiring higher

 

 

 

starting torque and better speed

 

 

 

regulation

 

5

Vector torque control

• Vector torque control: for single-

 

 

 

motor applications requiring torque

 

 

 

control independent of speed

 

6

Enhanced linear characteristic

• Enhanced: for single or multiple

 

 

with Auto-Boost

motor applications that require better

 

 

 

performance than settings 0...3, but

 

7

Enhanced linear characteristic with

 

cannot operate in vector mode

 

 

constant Vmin boost

 

Note

Settings 4...7 require Motor Calibration using c48

Settings 4 and 5 require proper setting of C86...C91 prior to calibration

Settings 6 and 7 require proper setting of C88...C90 prior to calibration

C15

V/f reference point

50.0

25.0

{Hz}

999

 

 

 

Set the rated motor frequency (nameplate)

 

 

 

for standard applications

 

C16

Vmin boost

 

0.0

{%}

40.0

 

(optimization of torque

 

C16 not active in Vector mode (see C14)

 

 

behavior)

 

 

 

 

 

 

 

 

 

 

Set after commissioning: The unloaded motor

 

 

 

should run at slip frequency (approx. 5 Hz),

 

 

 

increase C16 until motor current (C54) = 0.8 x

 

 

 

rated motor current

 

smd006

 

 

 

 

 

C17 Frequency threshold

0.0 0.0

{Hz}

240 See C08 selection 7, and CE3

(Qmin)

 

 

selection 27

Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES

15

Commissioning

Code

 

Possible Settings

 

IMPORTANT

No.

Name

Lenze

Selection

 

 

 

C18

Chopper frequency

2

0

4 kHz

 

• As chopper frequency is increased,

 

 

 

1

6 kHz

 

motor noise is decreased

 

 

 

 

• Observe derating in Section 2.2

 

 

 

2

8 kHz

 

 

 

 

 

• C18 = 1, 2, 3: Automatic derating to

 

 

 

3

10 kHz

 

4 kHz at 1.2 x IN

C21

Slip compensation

0.0

0.0

{%}

40.0

Change C21 until the motor speed no

 

 

 

 

 

 

longer changes between no load and

 

 

 

C21 not active in Vector mode (see C14)

 

maximum load

C22

Current limit

200

30

{%}

200

• When the limit value is reached,

 

 

 

Reference: Tml rated output current

 

either the acceleration time

 

 

 

 

increases or the output frequency

 

 

 

 

 

 

 

 

 

 

 

 

decreases

 

 

 

 

 

 

• When c73 = 0, max setting is 167%

C24

Accel boost

0.0

0.0

{%}

20.0

Accel boost is only active during

 

 

 

 

 

 

acceleration

C34

Configuration -

0

0

0...10 V

 

 

 

analog input

 

1

0...5 V

 

 

 

 

 

 

 

 

 

 

2

Reserved

 

 

 

 

 

3

0...20 mA

 

• With 250 W resistance between

 

 

 

4

4...20 mA

 

terminals 7 and 8

 

 

 

 

• C34 = 5 will trigger 5D5 fault if

 

 

 

 

 

 

 

 

 

5

4...20 mA monitored

 

signal falls below 2 mA

C36

Voltage - DC injection

4.0

0.0

{%}

50.0

• See CE1...CE3 and c06

 

brake (DCB)

 

 

 

 

• Confirm motor suitability for use

 

 

 

 

 

 

with DC braking

C37

Fixed setpoint 1

20.0

0.0

{Hz}

240

Lenze setting: active at E1 = HIGH

 

(JOG 1)

 

 

 

 

 

C38

Fixed setpoint 2

30.0

0.0

{Hz}

240

Lenze setting: active at E2 = HIGH

 

(JOG 2)

 

 

 

 

 

C39

Fixed setpoint 3

40.0

0.0

{Hz}

240

Lenze setting: active at E1 = HIGH

 

(JOG 3)

 

 

 

 

and E2 = HIGH

C46

Frequency setpoint

 

0.0

{Hz}

240

Display: Setpoint via analog input,

 

 

 

 

 

 

function UP/DOWN

C47

Torque setpoint/range

100

0

{%}

400

• When C14 = 5 and C01 = 1, 3, 5, 7

 

 

 

 

 

 

sets the torque setpoint

 

 

 

 

 

 

• When C14 = 5 and C01 = 0, 2, 4, 6

 

 

 

 

 

 

sets the torque range for C34

C50

Output frequency

 

0.0

{Hz}

240

Display

C52

Motor voltage

 

0

{V}

999

Display

C53

DC bus voltage

 

0

{V}

999

Display

C54

Motor current

 

0.0

{A}

400

Display

C56

Controller load

 

0

{%}

255

Display

C57

Motor torque

 

0

{%}

400

Display: vector mode only

 

 

 

 

 

 

(C14 = 4, 5)

C65

Vector speed control

30.0

0.0

 

100

Optimizes dynamic performance in

 

loop gain

 

 

 

 

vector mode

C66

Vector speed stability

30.0

0.0

 

100

Optimizes steady-state speed stability

 

 

 

 

 

 

in vector mode

16

 

 

 

Lenze 13466187

EDBTL03 v8 EN, DE, FR, IT, ES

 

 

 

 

 

Commissioning

Code

 

Possible Settings

 

 

 

IMPORTANT

No.

Name

Lenze

Selection

 

 

 

 

 

 

 

C77

Imax gain

0.25

0.00

 

16.0

For most applications, there is no need

 

 

 

 

 

 

to change the Lenze settings (1)

C78

Integral action time

65

12

{ms}

9990

 

 

C84

Motor stator

0.00

0.00

{W}

64.0

Will be automatically programmed

 

resistance

 

 

 

 

by c48 (1)

C86

Motor rated power

 

0.00

{kW}

99.9

• Set to motor nameplate kW

 

 

 

 

 

 

Lenze setting = Tml rated kW

C87

Motor rated speed

1390

300

{RPM}

65000

Set to motor nameplate speed

C88

Motor rated current

0.0

0.0

{A}

480

Set to motor nameplate current

C89

Motor rated

50

10

{Hz}

999

Set to motor nameplate frequency

 

frequency

 

 

 

 

 

 

C90

Motor rated voltage

0

0

{V}

600

Set to motor nameplate voltage

C91

Motor cosine phi

0.80

0.40

 

1.00

Set to motor power factor

 

 

 

Note

 

 

 

 

 

 

 

If motor power factor is not known, use the following formulas:

 

 

 

cos phi = motor Watts / (motor efficiency X

C90 X C88 X 1.732)

 

 

 

cos phi = cos [ sin-1 (magnetizing current / motor current) ]

C92

Motor stator

0.0

0.0

{mH}

2000

Will be automatically programmed

 

inductance

 

 

 

 

by c48 (1)

C93

Drive identification

 

 

 

 

Indicates controller rating,

 

 

 

 

 

 

 

format: x.yz, or x.y.z

 

 

 

 

 

 

• x. = voltage (2. = 200/240V, 1~)

 

 

 

 

 

 

• yz or y.z = kW rating

 

 

 

 

 

 

Example:

 

 

 

 

 

 

• 2.0.3 = 200/240 V, 1~, 0.37 kW

C94

User password

0

0

 

999

When set to a value other than

 

 

 

Changing from “0” (no password), value will

0, must enter password at C00 to

 

 

 

access parameters

 

 

 

start at 763

 

 

 

 

 

 

 

 

 

C99

Software version

 

 

 

 

Display, format: x.yz

C01

Acceleration time 2

5.0

0.0

{s}

999

Activated using CE1...CE3

 

 

 

 

 

 

• c01 = frequency change

 

 

 

 

 

 

 

0 Hz...C11

C03

Deceleration time 2

5.0

0.0

{s}

999

• c03 = frequency change

 

 

 

 

 

 

 

C11...0 Hz

 

 

 

 

 

 

• For S-ramp accel/decel, adjust c82

C06

Holding time -

0.0

0.0

{s}

999

• Automatic motor braking after STP

 

automatic DC injection

 

 

 

 

 

by means of motor DC current for

 

brake (Auto-DCB)

 

0.0 = not active

 

 

 

 

 

 

 

 

the entire holding time (afterwards:

 

 

 

999 = continuous brake

 

 

U, V, W inhibited)

 

 

 

 

 

 

• Confirm motor suitability for use with

 

 

 

 

 

 

 

DC braking

(1)Changing these settings can adversely affect performance. Contact Lenze technical support prior to changing.

Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES

17

Commissioning

Code

 

Possible Settings

 

 

IMPORTANT

 

No.

Name

Lenze

Selection

 

 

 

 

 

 

 

C20

I2t switch-off (thermal

100

30

{%}

100

Triggers 0C6 fault when motor

 

motor monitoring)

 

100% = Tml rated output current

 

 

current exceeds c20 for too long

 

 

 

 

 

 

 

 

 

• Correct setting = (motor

 

 

 

 

 

 

 

 

 

 

 

 

 

nameplate current) / (Tml

 

 

 

 

 

 

 

output current rating) X 100%

 

 

 

 

 

 

• Example: motor = 6.4 amps

 

 

 

 

 

 

 

and Tml = 7.0 amps;

 

 

 

 

 

 

 

 

correct setting = 91%

 

 

 

 

 

 

 

(6.4 / 7.0 = 0.91 x 100% = 91%)

 

 

 

WARNING!

 

 

 

 

 

 

 

Maximum setting is rated motor current (see nameplate). Does not provide full motor

 

 

 

protection!

 

 

 

 

C21

Motor Overload Type

00

00

Speed Compensation

 

Ir

1

 

 

 

 

 

Reduces the allowable continuous current

100%

 

 

 

 

 

when operating below 30Hz.

 

 

0

 

 

 

 

01

No Speed Compensation

 

60%

 

 

 

 

 

Example: Motor is cooled by forced

 

 

 

 

 

 

 

 

ventilation as apposed to shaft mounted,

 

 

 

 

 

 

 

self cooling fans.

 

 

30

f

 

 

 

 

 

 

Ir: rated current (%), f: motor frequency

 

 

 

 

 

 

(Hz)

 

C40

Frequency setpoint via

0.0

0.0

{Hz}

240

Only active if C01 is set properly

 

keys

 

 

 

 

(C01 = 1, 3, 5,7)

 

C42

Start condition

1

0 Start after LOW-HIGH change at

 

See also c43 and c70

 

 

(with mains on)

 

 

terminal 28

 

 

 

 

1Auto start if terminal 28 = HIGH

2Flying restart (auto start disabled)

3Auto start if terminal 28 = HIGH, with flying restart

 

 

 

WARNING!

 

 

 

 

 

Automatic starting/restarting may cause damage to equipment and/or injury to

 

 

 

personnel! Automatic starting/restarting should only be used on equipment that is

 

 

 

inaccessible to personnel.

 

 

C43

Flying restart selection

0

0

Search range: C11...0 Hz

If c42 = 2 or 3, the controller will start

 

 

 

 

 

the motor speed search at C11, or at

 

 

 

1

Search range: last frequency...0 Hz

the last output frequency before the

 

 

 

fault, depending on the setting of c43

C48

Motor auto-

0

0

Calibration not done

• If C14 = 4...7, motor calibration

 

calibration

 

 

 

must be performed,

but C86...

 

 

 

1

Calibration enabled

C91 must be programmed first

 

 

 

 

 

(see C14)

 

 

 

 

2

Calibration complete

• If motor calibration is attempted

 

 

 

before programming C86...C91,

 

 

 

 

 

 

 

 

 

 

triggers N1D fault

 

C60 Mode selection for c61

0

0

Monitoring only

c60 = 1 allows the keys

to

 

 

 

1

Monitoring and editing

adjust speed setpoint (c40) while

 

 

 

monitoring c61

 

 

 

 

 

 

 

18

Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES

 

 

 

 

Commissioning

Code

 

Possible Settings

 

 

IMPORTANT

No.

Name

Lenze

Selection

 

 

 

 

 

C61

Present status/error

 

status/error message

 

Display

C62

Last error

 

error message

 

• Refer to Section 5 for explanation

 

 

 

of status and error messages

 

 

 

 

 

 

 

C63

Last error but one

 

 

 

 

 

 

C64

Last error but two

 

 

 

 

 

 

C70

Configuration TRIP

0

0 TRIP reset after LOW-HIGH change at

 

 

 

reset (error reset)

 

 

terminal 28, mains switching, or after

 

 

 

 

 

 

 

LOW-HIGH change at digital input “TRIP

 

 

 

 

 

 

reset”

 

 

 

 

 

 

1

Auto-TRIP reset

 

• Auto-TRIP reset after the time

 

 

 

 

 

 

 

set in c71

 

 

 

 

 

 

• More than 8 errors in 10 minutes

 

 

 

 

 

 

 

will trigger RST fault

 

 

 

WARNING!

 

 

 

 

 

 

Automatic starting/restarting may cause damage to equipment and/or injury to

 

 

 

personnel! Automatic starting/restarting should only be used on equipment that

 

 

 

is inaccessible to personnel.

 

 

 

C71

Auto-TRIP reset

0.0

0.0

{s}

60.0

See c70

 

delay

 

 

 

 

 

 

C73

Input voltage

 

0 Low (for 200 V input)

 

• Lenze setting depends on C93

 

selection

 

 

 

 

During commissioning, confirm

 

 

 

1 High (for 230 V input)

 

 

correct setting based on mains

 

 

 

 

 

 

 

voltage

C78

Operating time

 

Display

 

0...999 h: format xxx

 

counter

 

Total time in status “Start”

 

1000...9999 h: format x.xx (x1000)

C79

Mains connection

 

Display

 

10000...99999 h: format xx.x (x1000)

 

 

 

 

 

time counter

 

Total time of mains = on

 

 

 

C82

S-ramp integration

0.0

0.0

{s}

50.0

c82 = 0.0: Linear accel/decel ramp

 

time

 

 

 

 

c82 > 0.0: Adjusts S-ramp curve

 

 

 

 

 

 

 

for smoother ramp

L25

Skip frequency 1

0.0

0.0

{Hz}

240

L25 and L26 define the start of the

 

 

 

 

 

 

 

skip range

L26

Skip frequency 2

0.0

0.0

{Hz}

240

L28 defines the bandwidth of the

 

 

 

 

 

 

 

skip range

L28

Skip frequency

0.0

0.0

{Hz}

10.0

 

 

 

bandwidth

 

Note

 

 

 

 

 

 

 

 

 

 

 

 

Bandwidth (Hz) = fs (Hz) + L28 (Hz)

fs = L25 or L26

 

 

 

Example: L25 = 18 Hz and L28 = 4 Hz; the bandwidth = 18...22 Hz

Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES

19

Commissioning

4.4Vector mode

Use the following procedures to select either Vector mode or Enhanced V/Hz mode. Enhanced V/Hz mode should be used in the following cases:

1.Multiple motor applications

2.Where required motor data is not available (especially C91)

3.Where running in Vector mode causes unstable motor operation

4.4.1

Vector speed and torque modes

1.

Connect the controller to the motor according to the diagram in Section 3.2.3.

2.

Apply power to the controller.

3.

Set C14 to 4 for Vector speed mode, or 5 for Vector torque mode.

4.

Set C86...C91 according to the motor’s nameplate data.

5.

Set c48 to 1 to enable the motor calibration function.

6.

Make sure the motor is cold (rotor and windings are at room temperature of 20º to 25º C), and

 

apply a HIGH signal at terminal 28. The display will show CAL for about 40 seconds. Once the

 

calibration is complete, the display will show OFF or 1NH. Apply another HIGH signal to terminal

 

28 to actually start the motor.

4.4.2

Enhanced V/Hz mode

Follow the procedure in 4.4.1 above, replacing steps 3 and 4 with those below:

3.Set C14 to 6 for Enhanced with Auto-Boost, or 7 for Enhanced with constant boost.

4.Set C88...C90 according to the motor’s nameplate data.

Note

If the motor is hot when the motor calibration is performed, the controller will not be able to achieve maximum performance.

In Vector speed and Vector torque modes, if an attempt is made to start the controller before performing the motor calibration, the controller will display N1D and the motor will not operate.

20

Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES

Lenze TML Flux Vector User Manual

Troubleshooting and fault elimination

5 Troubleshooting and fault elimination

 

Status

 

Cause

Remedy

e.g.

Present output frequency

Trouble free operation

 

50.0

 

 

 

 

OFF

Stop (outputs U, V, W inhibited)

LOW signal at terminal 28

Set terminal 28 to HIGH

1NH

Inhibit (outputs U, V, W inhibited)

Controller is set up for remote

Start the controller via the remote

 

 

keypad (see C01)

keypad

STP

Output frequency = 0 Hz

Quick stop activated through digital

Deactivate Quick stop

 

(outputs U, V, W inhibited)

input

 

FST

Flying restart attempt

c42 = 2, 3

 

BR

DC-injection brake active

DC-injection brake activated

Deactivate DC-injection brake

 

 

via digital input

• digital input = LOW

 

 

automatically

• automatically after holding time c06

 

 

 

 

has expired

CAL

Motor calibration is in process

c48 = 1 and terminal 28 = HIGH

Only perform the motor calibration

 

 

 

 

when C14 = 4...7

CL,FCL

Current limit reached

Controllable overload

Automatically (see C22)

LU

Undervoltage on DC bus

Mains voltage too low

Check mains voltage

DEC

Overvoltage on DC bus during

Excessively short deceleration time

Automatically if overvoltage

 

deceleration (warning)

(C13, c03)

< 1 s, OU, if overvoltage > 1 s

NED

No access to code

Can only be changed when the control-

Set terminal 28 to LOW

 

 

ler is in OFF or 1NH

 

RC

Remote keypad is active

Attempt to use buttons on front of

Buttons on front of controller are dis-

 

 

controller

abled when remote keypad is active

 

Error

 

Cause

Remedy (1)

AD

A/D converter error

 

 

Please contact Lenze

BF

Identification fault

C93 value stored on EPM does not

 

 

 

match controller model

 

CF

 

Data not valid for controller

• Use EPM providing valid data

CF

Data on EPM not valid

Data error

• Load Lenze setting

 

GF

 

OEM data not valid

 

LC

Automatic start inhibited

c42 = 0, 2

LOW-HIGH signal change at terminal 28

F1

EPM error

EPM missing or defective

Power down and replace EPM

CFG

Digital inputs not

E1...E3 assigned with the same digital

Each digital signal can only be used

 

uniquely assigned

signals

once

 

 

Either just “UP” or “DOWN” used

Assign the missing digital signal to a

 

 

 

 

second terminal

DF

Dynamic braking fault

Dynamic braking resistors are

Increase deceleration time

 

 

overheating

 

EER

External error

Digital input “TRIP set” is active

Remove external error

FC5,

Internal fault

 

 

Please contact Lenze

F2...F0

 

 

 

 

(1) The drive can only be restarted if the error message has been reset; see c70

 

Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES

21

Troubleshooting and fault elimination

 

Error

Cause

 

Remedy (1)

JF

Remote keypad fault

Remote keypad disconnected

Check remote keypad connections

N1D

Drive identification fault

Attempt was made to perform motor

Must set C86...C91 before performing

 

 

calibration before setting C86...C91

motor calibration (see c48)

0C1

Short-circuit or overload

Short-circuit

Find reason for short-circuit; check

 

 

 

motor cable

 

 

Excessive capacitive charging

Use shorter motor cables with lower

 

 

current of the motor cable

charging current

 

 

Acceleration time (C12, c01) too short

Increase acceleration time

 

 

 

Check controller selection

 

 

Defective motor cable

Check wiring

 

 

Internal fault in motor

Check motor

 

 

Frequent and long overload

Check controller selection

0C2

Earth fault

Grounded motor phase

Check motor/motor cable

 

 

Excessive capacitive charging

Use shorter motor cables with lower

 

 

current of the motor cable

charging current

0C6

Motor overload (I2t overload)

Motor is thermally overloaded, due to:

Check controller selection

 

 

• impermissable continuous current

 

 

• frequent or too long acceleration

• Check setting of c20

 

 

processes

 

 

0H

Controller overtemperature

Controller too hot inside

Reduce controller load

 

 

 

Improve cooling

OU

Overvoltage on DC bus

Mains voltage too high

Check mains voltage

 

 

Excessively short deceleration time or

Increase deceleration time or use

 

 

motor in generator mode

dynamic braking option

 

 

Earth leakage on the motor side

Check motor/motor cable

 

 

 

(separate motor from controller)

RF

Flying restart fault

Controller was unable to synchronize

Check motor/load

 

 

with motor during restart attempt

 

 

RST

Faulty auto-TRIP reset

More than 8 errors in 10 minutes

Depends on the error

SD5

Loss of 4-20 mA reference

4-20 mA signal (terminal 8I) is below 2

Check signal/signal wire

 

 

mA (C34 = 5)

 

 

SF

Single phase fault

A mains phase has been lost

Check mains voltage

(1) The drive can only be restarted if the error message has been reset; see c70

NOTE

In the event of an “OC6” (Motor Overload) failure there is a 3-minute delay before resetting is possible.

This is a requirement of UL508C. This delay is intended to allow time for the motor to cool.

If power is removed when the drive is in an “OC6” fault state, when the power is restored the “OC6” fault will still be present and the delay will still be active even if power was removed for longer than 3 minutes.

22

Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES

Notes

Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES

23

 

 

Notes

 

 

Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES

24

Inhalt

Info zu diesen Anweisungen..................................................................................

2

 

1

Sicherheitsinformationen...............................................................................

3

 

 

1.1

In diesen Anweisungen verwendete Piktogramme.............................

4

 

2

Technische Daten..........................................................................................

6

 

 

2.1

Normen und Anwendungsbedingungen..............................................

6

 

 

2.2

Bemessungsdaten..............................................................................

7

 

3

Installation......................................................................................................

 

8

 

 

3.1

.....................................................................Mechanische Installation

8

 

 

 

.....................................................3.1.1 Abmessungen und Montage

9

 

3.2

Elektroinstallation...........................................................................................

9

 

 

3.2.1

Installation gemäß EMV-Richtlinien....................................................

9

 

 

3.2.2

Sicherungen/Leitungsquerschnitte .....................................................

9

 

 

3.2.3

Schaltplan.........................................................................................

10

 

 

3.2.4

Steuerungsklemmen.........................................................................

11

 

4

Inbetriebnahme............................................................................................

12

 

 

4.1

Parametrierung.................................................................................

12

 

 

4.2

Elektronisches Programmiermodul (EPM)........................................

12

 

 

4.3

Parametermenü................................................................................

13

 

 

4.4

Vektorbetrieb.....................................................................................

20

 

 

 

4.4.1

Drehzahlund Drehmomentregelung im Vektorbetrieb...........

20

 

 

 

4.4.2

Erweiterter U/f-Betrieb.............................................................

20

 

5

Fehlersuche und -behebung........................................................................

21

 

Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES

1

Info zu diesen Anweisungen

Diese Dokumentation gilt für den vektorgeregelten Frequenzumrichter Tml. Sie beinhaltet wichtige technische Daten und beschreibt die Installation, die Inbetriebnahme sowie den Betrieb.

Bitte lesen Sie vor der Inbetriebnahme die Anweisungen.

 

 

 

 

A

 

B

 

C

 

D

E F

 

 

 

 

Type:

 

 

 

 

 

 

 

 

+

 

 

 

 

 

 

Input: 1/N/PE (2PE)

Output: 3/PE

For detailed information

 

 

 

 

 

ETML751X2SFA

 

 

230 V

 

0-230 V

refer to instruction

 

 

 

 

 

 

 

Id-No: 13xxxxx

 

 

9.2 A

 

4.2 A

Manual TL03

 

 

 

 

 

Made in USA

 

 

 

 

 

50-60 Hz

 

0.75 kW

SN: 13xxxxxx012345678

 

 

 

 

 

Inverter

 

 

LISTED

 

 

 

 

0 - 240 Hz

ETML751X2SFA000XX

XX

 

XX

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5D81

 

 

 

1341308801234567

 

 

 

 

 

 

Tml - basic I/O

 

 

IND. CONT. EQ.

N10104

 

 

 

 

 

 

 

 

 

 

Z519

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

V0006

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A Approbationen

 

C Eingangsbemessungsdaten

E Hardwarestand

 

 

 

 

 

B Typ

 

D Ausgangsbemessugsdaten

F Softwarestand

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Lieferumfang

 

 

 

Wichtig

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• 1 Frequenzumrichter Tml Vector

 

Prüfen Sie unmittelbar nach Erhalt der Lieferung, ob alle gelief-

 

 

control (ETML...) mit installiertem

 

erten Objekte den Angaben auf den beiliegenden Unterlagen

 

 

 

 

 

EPM (siehe Abschnitt 4.2)

 

entsprechen. Lenze haftet nicht für im Nachhinein gemeldete

 

 

• 1 Betriebsanleitung

 

 

 

Mängel.

 

 

 

 

 

 

 

 

 

 

 

 

Melden Sie

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

erkennbare Transportschäden umgehend dem Transportunternehmen.

erkennbare Mängel/unvollständige Lieferungen umgehend Ihrem Lenze-Vertreter.

© 2013 - 2004 Lenze AC Tech Corporation

Diese Dokumentation darf ohne ausdrückliche schriftliche Genehmigung der Lenze AC Tech Corporation weder ganz noch auszugsweise kopiert oder Dritten zur Verfügung gestellt werden.

Alle in dieser Dokumentation enthaltenen Informationen wurden sorgfältig ausgewählt und auf Übereinstimmung mit der beschriebenen Hardware und Software hin getestet. Fehler können jedoch nicht vollkommen ausgeschlossen werden. Wir übernehmen keinerlei Verantwortung für eventuell auftretende Schäden. Erforderliche Korrekturen werden in folgende Ausgaben dieser Dokumentation aufgenommen.

2

Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES

Sicherheitsinformationen

1Sicherheitsinformationen

Allgemeine Informationen

Einige Bauteile in Lenze-Reglern (Frequenzumrichter, Servoumrichter, DC-Steuerungen) können stromführend sein, sich bewegen oder rotieren. Einige Oberflächen können heiß werden.

Unbefugtes Entfernen der erforderlichen Abdeckung, unsachgemäße Verwendung und nicht vorschriftsmäßige Installation oder Bedienung können schwere Personenoder Sachschäden verursachen.

Sämtliche Tätigkeiten bei Transport, Installation und Inbetriebnahme sowie Wartungsarbeiten müssen von qualifiziertem und geschultem Fachpersonal durchgeführt werden (IEC 364 und CENELEC HD 384 oder DIN VDE 0100 und IEC-Report 664 oder DIN VDE 0110 sowie nationale Unfallverhütungsvorschriften müssen beachtet werden).

Gemäß diesen grundlegenden Sicherheitsinformationen handelt es sich bei qualifiziertem und geschultem Fachpersonal um Personen, die mit der Installation, der Montage, der Inbetriebnahme und dem Betrieb des Produkts vertraut sind und die über die für ihre Tätigkeit erforderlichen Qualifikationen verfügen.

Anwendung wie vorgeschrieben

Antriebsregler sind Bauteile, die für die Installation in elektrischen Systemen oder Maschinen vorgesehen sind. Sie dürfen nicht als separate Geräte verwendet werden. Sie sind ausschließlich für professionelle und kommerzielle Zwecke gemäß EN 61000-3-2 gedacht. Die Dokumentation enthält Informationen zur Einhaltung der Norm EN 61000-3-2.

Bei der Installation der Antriebsregler in Maschinen ist die Inbetriebnahme (d. h. der Start des Betriebs wie vorgeschrieben) untersagt, bis nachgewiesen wurde, dass die Maschine den Bestimmungen der EG-Richtlinie 2006/42/EG (Maschinenrichtlinie) entspricht und die harmonisierte Norm EN 60204 eingehalten wird.

Die Inbetriebnahme (d. h. der Start des Betriebs wie vorgeschrieben) ist nur dann zulässig, wenn die EMV-Richtlinie 2004/108/EG eingehalten wird.

Die Antriebsregler genügen den Anforderungen der Niederspannungsrichtlinie 2006/95/EG. Für die

Regler gelten die harmonisierten Normen der Serie EN 50178/DIN VDE 0160.

Hinweis: Die Verfügbarkeit von Reglern ist gemäß Norm EN 61800-3 eingeschränkt. Diese Produkte können in Wohngebieten Funkstörungen verursachen. In diesem Fall sind eventuell besondere Vorkehrungen zu treffen.

Installation

Sorgen Sie für sachgemäßen Umgang und vermeiden Sie übermäßige mechanische Beanspruchung. Vermeiden Sie ein Verbiegen von Bauteilen und das Ändern von Isolationsabständen beim Transport oder dem Umgang mit der Einheit. Berühren Sie keine elektronischen Bauteile und Kontakte.

Regler enthalten elektrostatisch empfindliche Bauteile, die bei unsachgemäßem Umgang leicht beschädigt werden können. Beschädigen oder zerstören Sie keine elektrischen Bauteile, da dadurch Ihre Gesundheit gefährdet werden könnte!

Elektrische Anschlüsse

WennArbeiten an stromführendenAntriebsreglern durchgeführt werden, müssen die geltenden nationalen Unfallverhütungsvorschriften (z. B. VBG 4) eingehalten werden.

Die Elektroinstallation muss im Sinne der geltenden Bestimmungen (z. B. Leitungsquerschnitte, Sicherungen, PE-Anschlüsse) durchgeführt werden. Zusätzliche Informationen können der Dokumentation entnommen werden.

Die Dokumentation enthält Informationen über die Installation gemäß den EMV-Richtlinien (Abschirmung, Erdung, Filter und Leitungen). Diese Hinweise gelten auch für mit dem CE-Zeichen gekennzeichnete Regler.

Der Hersteller des Systems oder der Maschine ist für die Einhaltung der erforderlichen Grenzwerte gemäß den EMV-Richtlinien verantwortlich.

Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES

3

Sicherheitsinformationen

Betrieb

Systeme mit Reglern müssen mit zusätzlichen Überwachungsund Schutzvorrichtungen ausgerüstet werden, die den geltenden Normen (z. B. Normen für technische Einrichtungen, Unfallverhütungsvorschriften usw.) entsprechen. Der Regler darf wie in der Dokumentation beschrieben für Ihre Anwendung angepasst werden.

WARNUNG!

• Nachdem die Stromversorgung des Reglers unterbrochen wurde, dürfen stromführende Bauteile und Netzverbindungen nicht sofort berührt werden, da Kondensatoren noch geladen sein können. Beachten Sie hierzu die entsprechenden Hinweise auf dem Regler.

Schalten Sie den Regler nicht öfter als einmal alle drei Minuten ein und wieder aus.

Schließen Sie beim Betrieb alle Schutzabdeckungen und -türen.

1.1In diesen Anweisungen verwendete Piktogramme

Piktogramm

Signalwort

Bedeutung

Folgen bei Missachtung

 

 

 

 

 

 

 

 

 

WARNUNG!

Mögliche drohende

Tod oder Verletzungen.

 

 

 

 

Personenschäden.

Schäden am Antriebssystem

 

 

 

 

Mögliche Sachschäden

oder seiner Umgebung

 

 

 

 

 

 

 

 

 

Hinweis

Nützlicher Tipp: Das Befolgen

 

 

 

 

 

 

 

 

 

dieser Tipps vereinfacht den

 

 

 

 

 

Umgang mit dem Antrieb.

 

 

 

 

 

 

 

 

 

 

 

 

 

4

Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES

Loading...
+ 94 hidden pages