TML
Flux Vector Drive
0.25 kW... 2.2 kW |
Operating Instructions |
EN |
|
|
|
|
|
|
|
Betriebsanleitung |
DE |
|
|
|
|
Instructions de mise en service |
FR |
|
|
|
|
Istruzioni operative |
IT |
|
|
|
|
Instrucciones para el servicio |
ES |
|
|
|
(13466187)
Contents
About these instructions................................................................................. |
2 |
|
|||
1 |
Safety information.................................................................................... |
3 |
|
||
|
1.1 |
Pictographs used in these instructions.......................................... |
4 |
|
|
2 |
Technical data.......................................................................................... |
6 |
|
||
|
2.1 |
Standards and application conditions............................................ |
6 |
|
|
|
2.2 |
Ratings........................................................................................... |
7 |
|
|
3 |
................................................................................................Installation |
|
8 |
|
|
|
3.1 |
...................................................................Mechanical installation |
8 |
|
|
|
|
3.1.1 Dimensions and mounting.................................................... |
8 |
|
|
|
3.2 |
Electrical installation...................................................................... |
9 |
|
|
|
|
3.2.1 |
Installation according to EMC requirements......................... |
9 |
|
|
|
3.2.2 |
Fuses/cable cross-sections ................................................. |
9 |
|
|
|
3.2.3 |
Connection diagram........................................................... |
10 |
|
|
|
3.2.4 |
Control terminals................................................................ |
11 |
|
4 |
Commissioning...................................................................................... |
12 |
|
||
|
4.1 |
Parameter setting......................................................................... |
12 |
|
|
|
4.2 |
Electronic programming module (EPM)....................................... |
12 |
|
|
|
4.3 |
Parameter menu.......................................................................... |
13 |
|
|
|
4.4 |
Vector mode................................................................................. |
20 |
|
|
|
|
4.4.1 Vector speed and torque modes........................................ |
20 |
|
|
|
|
4.4.2 Enhanced V/Hz mode....................................................... |
20 |
|
|
5 |
Troubleshooting and fault elimination.................................................... |
21 |
|
Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES |
1 |
About these instructions
This documentation applies to the Tml vector frequency inverter, and contains important technical data and describes installation, operation, and commissioning.
Please read the instructions before commissioning.
|
|
|
|
A |
|
B |
|
|
C |
|
D |
E F |
|||||
|
|
|
|
Type: |
|
|
|
|
|
|
|
|
|
+ |
|
||
|
|
|
|
|
|
Input: 1/N/PE (2PE) |
Output: 3/PE |
For detailed information |
|
||||||||
|
|
|
|
ETML751X2SFA |
|
|
|
230 V |
|
0-230 V |
refer to instruction |
|
|
|
|||
|
|
|
|
|
|||||||||||||
|
|
|
|
Id-No: 13xxxxx |
|
|
|
9.2 A |
|
4.2 A |
Manual TL03 |
|
|
|
|||
|
|
|
|
|
|||||||||||||
|
|
Made in USA |
|
|
|
|
|
|
50-60 Hz |
|
0.75 kW |
SN: 13xxxxxx012345678 |
|
|
|
||
|
|
Inverter |
|
|
|
|
|
|
|
|
|
0 - 240 Hz |
ETML751X2SFA000XX |
XX |
|
XX |
|
|
|
|
|
LISTED |
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
||||||
|
|
|
|
5D81 |
|
|
|
1341308801234567 |
|
|
|
|
|||||
|
|
Tml - basic I/O |
|
|
IND. CONT. EQ. |
|
N10104 |
|
|
|
|
|
|||||
|
|
|
|
|
|
Z519 |
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
V0006 |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
A Certifications |
|
|
C Input Ratings |
|
|
E Hardware Version |
|
|
|
||||||
|
|
B Type |
|
|
D Output Ratings |
|
|
F Software Version |
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
Scope of delivery |
|
|
|
|
Important |
|
|
|
|
|
|
|
|||
|
|
|
|
|
|||||||||||||
|
|
• 1 Tml vector inverter (ETML...) |
|
After receipt of the delivery, check immediately whether the items |
|||||||||||||
|
|
with EPM installed (see Section 4.2) delivered match the accompanying papers. Lenze does not accept |
|||||||||||||||
|
|
• 1 Operating Instructions |
|
|
any liability for deficiencies claimed subsequently. |
|
|
|
|||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
Claim
•visible transport damage immediately to the forwarder.
•visible deficiencies/incompleteness immediately to your Lenze representative.
© 2013 - 2004 Lenze AC Tech Corporation
No part of this documentation may be copied or made available to third parties without the explicit written approval of Lenze AC Tech Corporation.
All information given in this documentation has been carefully selected and tested for compliance with the hardware and software described. Nevertheless, discrepancies cannot be ruled out. We do not accept any responsibility nor liability for damages that may occur. Any necessary corrections will be implemented in subsequent editions.
2 |
Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES |
Safety information
1 Safety information
General
Some parts of Lenze controllers (frequency inverters, servo inverters, DC controllers) can be live, moving and rotating. Some surfaces can be hot.
Non-authorized removal of the required cover, inappropriate use, and incorrect installation or operation creates the risk of severe injury to personnel or damage to equipment.
All operations concerning transport, installation, and commissioning as well as maintenance must be carried out by qualified, skilled personnel (IEC 364 and CENELEC HD 384 or DIN
VDE 0100 and IEC report 664 or DIN VDE0110 and national regulations for the prevention of accidents must be observed).
According to this basic safety information, qualified skilled personnel are persons who are familiar with the installation, assembly, commissioning, and operation of the product and who have the qualifications necessary for their occupation.
Application as directed
Drive controllers are components which are designed for installation in electrical systems or machinery. They are not to be used as appliances. They are intended exclusively for professional and commercial purposes according to EN 61000-3-2. The documentation includes information on compliance with the EN 61000-3-2.
When installing the drive controllers in machines, commissioning (i.e. the starting of operation as directed) is prohibited until it is proven that the machine complies with the regulations of the EC Directive 2006/42/EC (Machinery Directive); EN 60204 must be observed.
Commissioning (i.e. starting of operation as directed) is only allowed when there is compliance with the EMC Directive (2004/108/EEC).
The drive controllers meet the requirements of the Low Voltage Directive 2006/95/EC. The harmonised standards of the series EN 50178/DIN VDE 0160 apply to the controllers.
Note: The availability of controllers is restricted according to EN 61800-3.These products can cause radio interference in residential areas. In this case, special measures can be necessary.
Installation
Ensure proper handling and avoid excessive mechanical stress. Do not bend any components and do not change any insulation distances during transport or handling. Do not touch any electronic components and contacts.
Controllers contain electrostatically sensitive components, which can easily be damaged by inappropriate handling. Do not damage or destroy any electrical components since this might endanger your health!
Electrical connection
When working on live drive controllers, applicable national regulations for the prevention of accidents (e.g. VBG 4) must be observed.
The electrical installation must be carried out according to the appropriate regulations (e.g. cable cross-sections, fuses, PE connection). Additional information can be obtained from the documentation.
The documentation contains informa3tion about installation in compliance with EMC (shielding, grounding, filters and cables). These notes must also be observed for CE-marked controllers.
The manufacturer of the system or machine is responsible for compliance with the required limit values demanded by EMC legislation.
Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES |
3 |
Safety information
Operation
Systems including controllers must be equipped with additional monitoring and protection devices according to the corresponding standards (e.g. technical equipment, regulations for prevention of accidents, etc.). You are allowed to adapt the controller to your application as described in the documentation.
WARNING!
• After the controller has been disconnected from the supply voltage, live components and power connection must not be touched immediately, since capacitors could be charged. Please observe the corresponding notes on the controller.
•Do not continuously cycle input power to the controller more than once every three minutes.
•Please close all protective covers and doors during operation.
1.1Pictographs used in these instructions
Pictograph |
Signal word |
Meaning |
Consequences if ignored |
||
|
|
|
|
|
|
|
|
|
WARNING! |
Impending or possible danger |
Death or injury. |
|
|
|
|
for persons. |
Damage to drive system or its |
|
|
|
|
Possible damage to equipment |
surroundings |
|
|
|
|
|
|
|
|
|
Note |
Useful tip: If observed, it will |
|
|
|
|
|
||
|
|
|
|
make using the drive easier |
|
|
|
|
|
|
|
|
|
|
|
|
|
4 |
Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES |
Safety information
Note for UL approved system with integrated controllers
UL warnings are notes which apply to UL systems. The documentation contains special information about UL.
• Integral solid state protection does not provide branch circuit protection. Branch circuit protection must be provided in accordance with the National Electrical Code and any additional local codes. The use of fuses or circuit breakers is
Warnings! |
the only approved means for branch circuit protection. |
|
|
• When protected by CC and T Class Fuses, suitable for use on a circuit capable |
|
||
|
|
||
|
of delivering not more than 200,000 rms symmetrical amperes, at the maximum |
|
|
|
|
||
|
voltage rating marked on the drive. |
|
|
|
|
||
|
• Additionally suitable when protected by a circuit breaker having an interrupting |
|
|
|
rating not less than 200,000 rms symmetrical amperes, at the maximum voltage |
|
|
|
rating marked on the drive. |
|
|
|
• Use minimum 75°C copper wire only, except for control circuits. |
|
|
|
• For control circuits, use wiring suitable for NEC Class 1 circuits only. |
|
|
|
• Torque Requirements are listed in section 3.2.3, Connection diagram. |
|
|
|
• Shall be installed in a pollution degree 2 macro-environment. |
|
|
|
|
|
|
WARNING!
Risk of Electric Shock! Capacitors retain charge for approximately 180 seconds after power is removed. Disconnect incoming power and wait at least 3 minutes before touching the drive.
WARNING!
The opening of branch-circuit protective device may be an indication that a fault has been interrupted. To reduce the risk of fire or electric shock, current carrying parts and other components of the controller should be examined and replaced if damaged.
Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES |
5 |
Technical data
2 Technical data
2.1Standards and application conditions
|
|
Conformity |
CE |
Low Voltage Directive (2006/95/EC) |
|
|
|
Approvals |
UL 508C |
Underwriters Laboratories - Power Conversion Equipment |
|
|
|
|
|
|
|
|
|
Max. permissible motor cable |
shielded: |
50 m (low-capacitance) |
|
|
|
length (1) |
unshielded: |
100 m |
|
|
|
Input voltage phase imbalance |
< 2% |
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
Humidity |
< 95% non-condensing |
||
|
|||||
|
|
Output frequency |
0...240 Hz |
|
|
|
|
|
|
|
|
|
|
Environmental conditions |
Class 3K3 to EN 50178 |
||
|
|
|
|
|
|
|
|
|
Transport |
|
-25 … +70 °C |
|
|
Temperature range |
Storage |
|
-20 … +70 °C |
|
|
|
|
|
|
|
|
|
Operation |
|
0 … +55 °C (with 2.5 %/°C current derating above +40 °C) |
|
|
Installation height |
0 … 4000 m a.m.s.l. (with 5 %/1000 m current derating above 1000 m |
||
|
|
a.m.s.l.) |
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
Vibration resistance |
acceleration resistant up to 0.7 g |
||
|
|
|
|
|
|
|
|
Earth leakage current (EN 50178) |
> 3.5 mA to PE |
|
|
|
|
Enclosure (EN 60529) |
IP 20 |
|
|
|
|
|
|
||
|
|
Protection measures against |
short circuit, earth fault, overvoltage, motor stalling, motor overload |
||
|
|
|
Total power |
|
Compliance with the requirements (2) |
|
|
|
connected to |
|
|
|
|
Operation in public supply networks |
the mains |
|
|
|
|
(Limitation of harmonic currents |
< 0.5 kW |
|
With mains choke |
|
|
according to EN 61000-3-2) |
|
|
|
|
|
0.5 … 1 kW |
|
With active filter (in preparation) |
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
> 1 kW |
|
Without additional measures |
|
|
|
|
|
|
(1)For compliance with EMC regulations, the permissible cable lengths may change.
(2)The additional measures described only ensure that the controllers meet the requirements of the EN 61000-3-2. The machine/system manufacturer is responsible for the compliance with the regulations of the machine!
6 |
Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES |
Technical data
2.2Ratings
|
|
Mains |
|
|
|
Output Current |
|
|
|
|
Type |
Power |
|
|
|
|
|
|
|
|
|
[kW] |
|
Current |
IN |
|
Imax for 60 s |
|
|
|||
|
Voltage, frequency |
|
|
|
||||||
|
|
[A] |
|
|
|
|
|
|
|
|
|
|
|
[A] (1) |
|
[A] (2) |
[A] (1) |
[A] (2) |
|
|
|
ETML251X2SFA |
0.25 |
|
3.4 |
1.7 |
|
1.6 |
2.6 |
2.4 |
|
|
|
|
|
|
|
|
|
|
|
|
|
ETML371X2SFA |
0.37 |
|
5.0 |
2.4 |
|
2.2 |
3.6 |
3.3 |
|
|
|
|
|
|
|
|
|
|
|
|
|
ETML551X2SFA |
0.55 |
1/N/PE 230 V |
6.0 |
3.2 |
|
2.9 |
4.8 |
4.4 |
|
|
|
||||||||||
|
|
(180 V -0%…264 V +0%) |
|
|
|
|
|
|
|
|
ETML751X2SFA |
0.75 |
9.2 |
4.2 |
|
3.9 |
6.3 |
5.8 |
|
|
|
50/60 Hz |
|
|
|
|||||||
|
|
|
|
|
|
|
|
|
|
|
ETML112X2SFA |
1.1 |
(48 Hz -0%…62 Hz +0%) |
12.0 |
6.0 |
|
5.5 |
9.0 |
8.3 |
|
|
|
|
|
|
|
|
|
|
|
|
|
ETML152X2SFA |
1.5 |
|
16.0 |
7.0 |
|
6.4 |
10.5 |
9.6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
ETML222X2SFA |
2.2 |
|
21 |
9.6 |
|
8.8 |
14.4 |
13.2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
(1)For rated mains voltage and carrier frequencies 4, 6, and 8 kHz
(2)For rated mains voltage and carrier frequency 10 kHz
Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES |
7 |
Installation
3 Installation
3.1Mechanical installation
3.1.1Dimensions and mounting
|
|
|
|
|
|
|
|
|
|
|
|
Tml002 |
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Type |
a |
a1 |
b |
b1 |
b2 |
c |
s1 |
s2 |
m |
||
|
|
[mm] |
[mm] |
[mm] |
[mm] |
[mm] |
[mm] |
[mm] |
[mm] |
[kg] |
|||
|
|
|
|
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ETML251X2SFA |
93 |
84 |
146 |
128 |
17 |
83 |
15 |
50 |
0.5 |
|
|
|
|
ETML371X2SFA |
|
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ETML551X2SFA |
93 |
84 |
146 |
128 |
17 |
92 |
15 |
50 |
0.6 |
|
|
|
|
ETML751X2SFA |
|
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ETML112X2SFA |
114 |
105 |
146 |
128 |
17 |
124 |
15 |
50 |
1.2 |
|
|
|
|
ETML152X2SFA |
|
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ETML222X2SFA |
114 |
105 |
146 |
128 |
17 |
140 |
15 |
50 |
1.4 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
WARNING!
Drives must not be installed where subjected to adverse environmental conditions such as: combustible, oily, or hazardous vapors or dust; excessive moisture; excessive vibration or excessive temperatures. Contact Lenze for more information.
8 |
Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES |
Installation
3.2Electrical installation
3.2.1Installation according to EMC requirements
EMC
Compliance with EN 61800-3/A11
Noise emission
Drive models ending in the suffix “SFA” are in compliance with limit value class A
according to EN 55011 if installed in a control cabinet and with a motor cable not B longer than 10m.
A Screen clamps |
|
|
|
|
|
|
|
C |
|||
B Control cable |
|
|
|
|
|
|
|
|
|
D |
|
A |
|
|
|||
|
|
|
CLow-capacitance motor cable
(core/core < 75 pF/m, core/screen < 150 pF/m)
DElectrically conductive mounting plate
Tml005
3.2.2Fuses/cable cross-sections(1)
|
Installation to EN 60204-1 |
Installation to UL |
|
|||
Type |
Fuse |
Miniature |
L1, L2, L3, |
Fuse (3) |
L1, L2, L3, |
E.l.c.b.(2) |
|
circuit |
PE [mm²] |
PE [AWG] |
|
||
|
|
breaker |
|
|
||
|
|
|
|
|
|
|
ETML251X2SFA |
|
|
|
|
|
|
ETML371X2SFA |
M10 A |
C10 A |
1.5 |
10 A |
14 |
|
ETML551X2SFA |
|
|
|
|
|
|
ETML751X2SFA |
M16 A |
C16 A |
2.5 |
15 A |
14 |
> 30 mA |
ETML112X2SFA |
M20 A |
C20 A |
2.5 |
20 A |
12 |
|
ETML152X2SFA |
M25 A |
C25 A |
2.5 |
25 A |
12 |
|
ETML222X2SFA |
M30 A |
C30 A |
4.0 |
30 A |
10 |
|
(1)Observe the applicable local regulations
(2)Pulse-current or universal-current sensitive earth leakage circuit breaker
(3)UL Class CC or T fast-acting current-limiting type fuses, 200,000 AIC, required. Bussman KTK-R, JJN, JJS, or equivalent
Observe the following when using E.l.c.b:
•Installation of E.l.c.b only between supplying mains and controller.
•The E.l.c.b can be activated by:
-apacitive leakage currents between the cable screens during operation (especially with long, screened motor cables)
-connecting several controllers to the mains at the same time
-RFI filters
Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES |
9 |
Installation
3.2.3Connection diagram
Tml003
WARNING!
• Hazard of electrical shock! Circuit potentials are up to 230 VAC above earth ground. Capacitors retain charge after power is removed. Disconnect power and wait until the voltage between B+ and B- is 0 VDC before servicing the drive.
•Do not connect mains power to the output terminals (U,V,W)! Severe damage to the drive will result.
•Do not cycle mains power more than once every three minutes. Damage to the drive will result.
10 |
Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES |
Installation
3.2.4Control terminals
Terminal |
Data for control connections (printed in bold = Lenze setting) |
|
|
|
||
|
|
|
|
|
|
|
7 |
Reference common |
|
|
|
|
|
|
|
|
|
|
|
|
8 |
Analog input |
input resistance: >50 kΩ |
|
|
|
|
0 … 10 V (changeable under C34) |
(with current signal: 250 Ω) |
|
|
|
||
|
|
|
|
|||
|
|
|
|
|
|
|
9 |
Internal DC supply for setpoint potentiometer |
+10 V, max. 10 mA |
|
|
|
|
|
|
|
|
|
|
|
20 |
Internal DC supply for digital inputs |
+12 V, max. 20 mA |
|
|
|
|
|
|
|
|
|
|
|
28 |
Digital input Start/Stop |
LOW = Stop; HIGH = Run Enable |
|
|
|
|
|
|
|
||||
input resistance = 3.3 kΩ |
|
|
|
|||
|
|
|
|
|
||
|
|
|
|
|
|
|
E1 |
Digital input configurable with CE1 |
HIGH = JOG1 active |
|
|
|
|
Activate fixed setpoint 1 (JOG1) |
|
|
|
|
||
|
|
Both HIGH = JOG3 active |
kΩ |
|
|
|
|
|
|
|
|
||
|
|
|
|
|
||
E2 |
Digital input configurable with CE2 |
HIGH = JOG2 active |
|
3.3 |
|
|
|
Activate fixed setpoint 2 (JOG2) |
|
|
= |
|
|
|
|
|
|
i |
|
|
E3 |
Digital input configurable with CE3 |
HIGH = DCB active |
R |
|
|
|
|
|
|
||||
Activate DC injection brake (DCB) |
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
K14 |
Relay output (N.O. contact) |
AC 250V / 3A |
|
|
|
|
|
configurable with C08 |
|
|
|
||
|
DC 24V / 2A ... 240V / 0.22A |
|
|
|
||
K12 |
Fault (TRIP) |
|
|
|
||
|
|
|
|
|
||
|
|
|
|
|
|
|
LOW = 0 … +3 V, HIGH = +12 … +30 V
Protection against contact
•All terminals have a basic isolation (single insulating distance)
•Protection against contact can only be ensured by additional measures (i.e. double insulation)
Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES |
11 |
Commissioning
4 Commissioning
4.1Parameter setting
|
Status/fault messages |
Change parameters |
|
|
|
|
|
|
Tml004
Note
If the password function is enabled, the password must be entered into C00 to access the parameters. C00 will not appear unless the password function is enabled. See C94.
4.2Electronic programming module (EPM)
Tmd007
The EPM contains the controller’s memory. Whenever parameter settings are changed, the values are stored in the EPM. It can be removed, but must be installed for the controller to operate (a missing EPM will trigger an F1 fault). The controller ships with protective tape over the EPM that can be removed after installation.
An optional EPM Programmer (model EEPM1RA) is available that allows: the controller to be programmed without power; OEM settings to be default settings; fast copying of EPMs when multiple controllers require identical settings. It can also store up to 60 custom parameter files for even faster controller programming.
12 |
Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES |
Commissioning
4.3Parameter menu
Code |
|
Possible Settings |
IMPORTANT |
||
No. |
Name |
Lenze |
Selection |
||
|
|||||
C00 |
Password entry |
0 |
0 |
999 Visible only when password is active |
|
|
|
|
|
(see C94) |
|
C01 |
Setpoint and control |
0 |
Setpoint source: |
Control configuration: |
|
|
source |
|
|
|
0Analog input (terminal 8; see C34)
1Code c40 / Code C47
|
|
|
Control = terminals |
|
|
|
|
|
|
||
|
2 |
Analog input (terminal 8; see C34) |
Programming = keypad |
|
|
|
|
|
|
|
|
|
3 |
Code c40 / Code C47 |
|
|
|
|
|
|
|
|
|
|
4 |
Analog input (terminal 8; see C34) |
Control = terminals |
|
|
|
|
|
Programming = remote keypad |
|
|
|
5 |
Code c40 / Code C47 |
|
||
|
Monitoring = remote keypad |
|
|||
|
|
|
|
|
|
|
6 |
Analog input (terminal 8; see C34) |
Control = remote keypad |
|
|
|
|
|
Programming = remote keypad |
|
|
|
7 |
Code c40 / Code C47 |
|
||
|
Monitoring = remote keypad |
|
|||
|
|
|
|
|
|
Note
•When C01 = 1, 3, 5, or 7 and C14 = 0...4, 6, 7, use c40 for speed setpoint
•When C01 = 1, 3, 5, or 7 and C14 = 5, use C47 for torque setpoint
•When C01 = 4...7, terminals E2 and E3 must be used for the remote keypad, selections made for CE2 and CE3 will be ignored.
C02 Load Lenze setting |
0 |
No action/loading complete |
• C02 = 1, 2, 3 only possible with |
|
1 |
Load 50 Hz Lenze settings |
OFF or 1NH |
|
• C02 = 2 : C11, C15 and C89 = 60 |
||
|
2 |
Load 60 Hz Lenze settings |
Hz and C87 = 1750RPM |
|
|
||
|
3 |
Load OEM settings (if present) |
|
|
WARNING! |
|
|
|
C02 = 1...3 overwrites all settings! TRIP circuitry may be disabled! Check codes CE1... |
||
|
CE3. |
|
Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES |
13 |
Commissioning
Code |
|
Possible Settings |
IMPORTANT |
||
No. |
Name |
Lenze |
Selection |
||
|
|||||
CE1 |
Configuration - |
1 |
1 Activate fixed setpoint 1 (JOG1) |
Activate JOG3: Both terminals = HIGH |
|
|
Digital input E1 |
|
|
|
2Activate fixed setpoint 2 (JOG2)
|
|
|
3 |
DC braking (DCB) |
see also C36 |
|
|
|
|
4 |
Direction of rotation |
LOW = CW rotation |
|
|
|
|
|
|
HIGH = CCW rotation |
|
|
|
|
5 |
Quick stop |
Controlled deceleration to standstill, |
|
|
|
|
|
|
active LOW; Set decel rate in C13 |
|
|
|
|
|
|
or c03 |
|
|
|
|
6 |
CW rotation |
CW rotation = LOW and CCW rotation |
|
CE2 |
Configuration - |
2 |
7 |
CCW rotation |
= LOW: Quick stop; Open-circuit |
|
protected |
||||||
|
Digital input E2 |
|
|
|
||
|
|
8 |
UP (setpoint ramp-up) |
UP = LOW and DOWN = LOW: Quick |
||
|
|
|
||||
|
|
|
9 |
DOWN (setpoint ramp-down) |
stop; Use momentary NC contacts |
|
|
|
|
10 |
TRIP set |
Active LOW, triggers EER (motor |
|
|
|
|
|
|
coasts to standstill) |
|
|
|
|
|
|
NOTE: NC thermal contact from the |
|
|
|
|
|
|
motor can be used to trigger this input |
|
|
|
|
11 |
TRIP reset |
see also c70 |
|
|
|
|
12 |
Accel/decel 2 |
see c01 and c03 |
|
CE3 |
Configuration - |
3 |
1…12 (same as above) |
• 1…12 configures terminal E3 as |
||
|
Digital input/output E3 |
|
13...19 (reserved) |
an input. |
||
|
|
|
• 20…29 configures terminal E3 as a |
|||
|
|
|
20 |
Ready |
current-sourcing (PNP) output rated |
|
|
|
|
12 VDC / 50 mA |
|||
|
|
|
21 |
Fault |
||
|
|
|
|
|||
|
|
|
22 |
Motor is running |
|
|
|
|
|
23 |
Motor is running - CW rotation |
|
|
|
|
|
24 |
Motor is running - CCW rotation |
|
|
|
|
|
25 |
Output frequency = 0Hz |
|
|
|
|
|
26 |
Frequency setpoint reached |
|
|
|
|
|
27 |
Frequency threshold (C17) exceeded |
|
|
|
|
|
28 |
Current limit (motor or generator mode) |
|
|
|
|
|
|
reached |
|
|
|
|
|
29 |
Dynamic braking |
|
|
|
|
|
Note |
|
||
|
|
|
A CFG fault will occur under the following conditions: |
|||
|
|
|
• E1...E3 settings are duplicated (each setting can only be used once) |
|||
|
|
|
• One input is set to UP and another is not set to DOWN, or vice-versa |
|||
|
|
|
• When C01 = 4...7, terminals E2 and E3 must be used for the remote keypad, selections |
|||
|
|
|
|
made for CE2 and CE3 will be ignored. |
|
|
C08 |
Configuration - Relay |
1 |
Relay is energized if |
|
||
|
output (terminals K14 |
|
0 |
Ready |
|
|
|
and K12 |
|
1 |
Fault |
|
|
|
|
|
2 |
Motor is running |
|
|
|
|
|
3 |
Motor is running - CW rotation |
|
|
|
|
|
4 |
Motor is running - CCW rotation |
|
|
|
|
|
5 |
Output frequency = 0Hz |
|
|
|
|
|
6 |
Frequency setpoint reached |
|
|
|
|
|
7 |
Frequency threshold (C17) exceeded |
|
|
|
|
|
8 |
Current limit (motor or generator mode) |
|
|
|
|
|
|
reached |
|
14 |
Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES |
|
|
|
|
Commissioning |
||
Code |
|
Possible Settings |
|
IMPORTANT |
||
No. |
Name |
Lenze |
Selection |
|
||
|
|
|||||
C10 |
Minimum output |
0.0 |
0.0 |
{Hz} |
240 |
• Output frequency at 0% analog |
|
frequency |
|
|
|
|
setpoint |
|
|
|
|
|
|
• C10 not active for fixed setpoints or |
|
|
|
|
|
|
setpoint selection via c40 |
C11 |
Maximum output |
50.0 |
7.5 |
{Hz} |
240 |
• Output frequency at 100% analog |
|
frequency |
|
|
|
|
setpoint |
|
|
|
|
|
|
• C11 is never exceeded |
|
|
|
WARNING! |
|
|
|
|
|
|
Consult motor/machine manufacturer before operating above rated frequency. |
|||
|
|
|
Overspeeding the motor/machine may cause damage to equipment and injury to |
|||
|
|
|
personnel! |
|
|
|
C12 |
Acceleration time 1 |
5.0 |
0.0 |
{s} |
999 |
• C12 = frequency change |
|
|
|
|
|
|
0 Hz...C11 |
C13 |
Deceleration time 1 |
5.0 |
0.0 |
{s} |
999 |
• C13 = frequency change |
C11...0 Hz |
||||||
|
|
|
|
|
|
• For S-ramp accel/decel, adjust c82 |
C14 |
Operating Mode |
2 |
0 |
Linear characteristic with |
|
• Linear characteristic: for standard |
|
|
|
|
Auto-Boost |
|
applications |
|
|
|
1 Square-law characteristic with |
|
• Square-law characteristic: for fans |
|
|
|
|
|
and pumps with square-law load |
||
|
|
|
|
Auto-Boost |
|
|
|
|
|
|
|
characteristic |
|
|
|
|
|
|
|
|
|
|
|
2 Linear characteristic with constant |
|
• Auto boost: load-dependent output |
|
|
|
|
|
Vmin boost |
|
voltage for low-loss operation |
3Square-law characteristic with constant Vmin boost
|
4 |
Vector speed control |
• Vector speed control: for single- |
|
|
|
motor applications requiring higher |
|
|
|
starting torque and better speed |
|
|
|
regulation |
|
5 |
Vector torque control |
• Vector torque control: for single- |
|
|
|
motor applications requiring torque |
|
|
|
control independent of speed |
|
6 |
Enhanced linear characteristic |
• Enhanced: for single or multiple |
|
|
with Auto-Boost |
motor applications that require better |
|
|
|
performance than settings 0...3, but |
|
7 |
Enhanced linear characteristic with |
|
|
cannot operate in vector mode |
||
|
|
constant Vmin boost |
|
Note
•Settings 4...7 require Motor Calibration using c48
•Settings 4 and 5 require proper setting of C86...C91 prior to calibration
•Settings 6 and 7 require proper setting of C88...C90 prior to calibration
C15 |
V/f reference point |
50.0 |
25.0 |
{Hz} |
999 |
|
|
|
Set the rated motor frequency (nameplate) |
||
|
|
|
for standard applications |
|
|
C16 |
Vmin boost |
|
0.0 |
{%} |
40.0 |
|
(optimization of torque |
|
C16 not active in Vector mode (see C14) |
|
|
|
behavior) |
|
|
||
|
|
|
|
|
|
|
|
|
Set after commissioning: The unloaded motor |
||
|
|
|
should run at slip frequency (approx. 5 Hz), |
||
|
|
|
increase C16 until motor current (C54) = 0.8 x |
||
|
|
|
rated motor current |
|
smd006 |
|
|
|
|
|
C17 Frequency threshold |
0.0 0.0 |
{Hz} |
240 See C08 selection 7, and CE3 |
(Qmin) |
|
|
selection 27 |
Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES |
15 |
Commissioning
Code |
|
Possible Settings |
|
IMPORTANT |
||
No. |
Name |
Lenze |
Selection |
|
||
|
|
|||||
C18 |
Chopper frequency |
2 |
0 |
4 kHz |
|
• As chopper frequency is increased, |
|
|
|
1 |
6 kHz |
|
motor noise is decreased |
|
|
|
|
• Observe derating in Section 2.2 |
||
|
|
|
2 |
8 kHz |
|
|
|
|
|
|
• C18 = 1, 2, 3: Automatic derating to |
||
|
|
|
3 |
10 kHz |
|
4 kHz at 1.2 x IN |
C21 |
Slip compensation |
0.0 |
0.0 |
{%} |
40.0 |
Change C21 until the motor speed no |
|
|
|
|
|
|
longer changes between no load and |
|
|
|
C21 not active in Vector mode (see C14) |
|
maximum load |
|
C22 |
Current limit |
200 |
30 |
{%} |
200 |
• When the limit value is reached, |
|
|
|
Reference: Tml rated output current |
|
either the acceleration time |
|
|
|
|
|
increases or the output frequency |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
decreases |
|
|
|
|
|
|
• When c73 = 0, max setting is 167% |
C24 |
Accel boost |
0.0 |
0.0 |
{%} |
20.0 |
Accel boost is only active during |
|
|
|
|
|
|
acceleration |
C34 |
Configuration - |
0 |
0 |
0...10 V |
|
|
|
analog input |
|
1 |
0...5 V |
|
|
|
|
|
|
|
||
|
|
|
2 |
Reserved |
|
|
|
|
|
3 |
0...20 mA |
|
• With 250 W resistance between |
|
|
|
4 |
4...20 mA |
|
terminals 7 and 8 |
|
|
|
|
• C34 = 5 will trigger 5D5 fault if |
||
|
|
|
|
|
|
|
|
|
|
5 |
4...20 mA monitored |
|
signal falls below 2 mA |
C36 |
Voltage - DC injection |
4.0 |
0.0 |
{%} |
50.0 |
• See CE1...CE3 and c06 |
|
brake (DCB) |
|
|
|
|
• Confirm motor suitability for use |
|
|
|
|
|
|
with DC braking |
C37 |
Fixed setpoint 1 |
20.0 |
0.0 |
{Hz} |
240 |
Lenze setting: active at E1 = HIGH |
|
(JOG 1) |
|
|
|
|
|
C38 |
Fixed setpoint 2 |
30.0 |
0.0 |
{Hz} |
240 |
Lenze setting: active at E2 = HIGH |
|
(JOG 2) |
|
|
|
|
|
C39 |
Fixed setpoint 3 |
40.0 |
0.0 |
{Hz} |
240 |
Lenze setting: active at E1 = HIGH |
|
(JOG 3) |
|
|
|
|
and E2 = HIGH |
C46 |
Frequency setpoint |
|
0.0 |
{Hz} |
240 |
Display: Setpoint via analog input, |
|
|
|
|
|
|
function UP/DOWN |
C47 |
Torque setpoint/range |
100 |
0 |
{%} |
400 |
• When C14 = 5 and C01 = 1, 3, 5, 7 |
|
|
|
|
|
|
sets the torque setpoint |
|
|
|
|
|
|
• When C14 = 5 and C01 = 0, 2, 4, 6 |
|
|
|
|
|
|
sets the torque range for C34 |
C50 |
Output frequency |
|
0.0 |
{Hz} |
240 |
Display |
C52 |
Motor voltage |
|
0 |
{V} |
999 |
Display |
C53 |
DC bus voltage |
|
0 |
{V} |
999 |
Display |
C54 |
Motor current |
|
0.0 |
{A} |
400 |
Display |
C56 |
Controller load |
|
0 |
{%} |
255 |
Display |
C57 |
Motor torque |
|
0 |
{%} |
400 |
Display: vector mode only |
|
|
|
|
|
|
(C14 = 4, 5) |
C65 |
Vector speed control |
30.0 |
0.0 |
|
100 |
Optimizes dynamic performance in |
|
loop gain |
|
|
|
|
vector mode |
C66 |
Vector speed stability |
30.0 |
0.0 |
|
100 |
Optimizes steady-state speed stability |
|
|
|
|
|
|
in vector mode |
16 |
|
|
|
Lenze 13466187 |
EDBTL03 v8 EN, DE, FR, IT, ES |
|
|
|
|
|
Commissioning |
||
Code |
|
Possible Settings |
|
|
|
IMPORTANT |
|
No. |
Name |
Lenze |
Selection |
|
|
|
|
|
|
|
|
||||
C77 |
Imax gain |
0.25 |
0.00 |
|
16.0 |
For most applications, there is no need |
|
|
|
|
|
|
|
to change the Lenze settings (1) |
|
C78 |
Integral action time |
65 |
12 |
{ms} |
9990 |
|
|
C84 |
Motor stator |
0.00 |
0.00 |
{W} |
64.0 |
Will be automatically programmed |
|
|
resistance |
|
|
|
|
by c48 (1) |
|
C86 |
Motor rated power |
|
0.00 |
{kW} |
99.9 |
• Set to motor nameplate kW |
|
|
|
|
|
|
|
• |
Lenze setting = Tml rated kW |
C87 |
Motor rated speed |
1390 |
300 |
{RPM} |
65000 |
Set to motor nameplate speed |
|
C88 |
Motor rated current |
0.0 |
0.0 |
{A} |
480 |
Set to motor nameplate current |
|
C89 |
Motor rated |
50 |
10 |
{Hz} |
999 |
Set to motor nameplate frequency |
|
|
frequency |
|
|
|
|
|
|
C90 |
Motor rated voltage |
0 |
0 |
{V} |
600 |
Set to motor nameplate voltage |
|
C91 |
Motor cosine phi |
0.80 |
0.40 |
|
1.00 |
Set to motor power factor |
|
|
|
|
Note |
|
|
|
|
|
|
|
If motor power factor is not known, use the following formulas: |
||||
|
|
|
cos phi = motor Watts / (motor efficiency X |
C90 X C88 X 1.732) |
|||
|
|
|
cos phi = cos [ sin-1 (magnetizing current / motor current) ] |
||||
C92 |
Motor stator |
0.0 |
0.0 |
{mH} |
2000 |
Will be automatically programmed |
|
|
inductance |
|
|
|
|
by c48 (1) |
|
C93 |
Drive identification |
|
|
|
|
• |
Indicates controller rating, |
|
|
|
|
|
|
|
format: x.yz, or x.y.z |
|
|
|
|
|
|
• x. = voltage (2. = 200/240V, 1~) |
|
|
|
|
|
|
|
• yz or y.z = kW rating |
|
|
|
|
|
|
|
• |
Example: |
|
|
|
|
|
|
• 2.0.3 = 200/240 V, 1~, 0.37 kW |
|
C94 |
User password |
0 |
0 |
|
999 |
When set to a value other than |
|
|
|
|
Changing from “0” (no password), value will |
0, must enter password at C00 to |
|||
|
|
|
access parameters |
||||
|
|
|
start at 763 |
|
|
||
|
|
|
|
|
|
|
|
C99 |
Software version |
|
|
|
|
Display, format: x.yz |
|
C01 |
Acceleration time 2 |
5.0 |
0.0 |
{s} |
999 |
• |
Activated using CE1...CE3 |
|
|
|
|
|
|
• c01 = frequency change |
|
|
|
|
|
|
|
|
0 Hz...C11 |
C03 |
Deceleration time 2 |
5.0 |
0.0 |
{s} |
999 |
• c03 = frequency change |
|
|
|
|
|
|
|
|
C11...0 Hz |
|
|
|
|
|
|
• For S-ramp accel/decel, adjust c82 |
|
C06 |
Holding time - |
0.0 |
0.0 |
{s} |
999 |
• Automatic motor braking after STP |
|
|
automatic DC injection |
|
|
|
|
|
by means of motor DC current for |
|
brake (Auto-DCB) |
|
0.0 = not active |
|
|
|
|
|
|
|
|
|
the entire holding time (afterwards: |
||
|
|
|
999 = continuous brake |
|
|
U, V, W inhibited) |
|
|
|
|
|
|
|
• Confirm motor suitability for use with |
|
|
|
|
|
|
|
|
DC braking |
(1)Changing these settings can adversely affect performance. Contact Lenze technical support prior to changing.
Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES |
17 |
Commissioning
Code |
|
Possible Settings |
|
|
IMPORTANT |
|
||
No. |
Name |
Lenze |
Selection |
|
|
|
||
|
|
|
|
|||||
C20 |
I2t switch-off (thermal |
100 |
30 |
{%} |
100 |
• |
Triggers 0C6 fault when motor |
|
|
motor monitoring) |
|
100% = Tml rated output current |
|
|
current exceeds c20 for too long |
||
|
|
|
|
|
||||
|
|
|
|
• Correct setting = (motor |
||||
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
nameplate current) / (Tml |
|
|
|
|
|
|
|
|
output current rating) X 100% |
|
|
|
|
|
|
|
• Example: motor = 6.4 amps |
||
|
|
|
|
|
|
|
and Tml = 7.0 amps; |
|
|
|
|
|
|
|
|
correct setting = 91% |
|
|
|
|
|
|
|
|
(6.4 / 7.0 = 0.91 x 100% = 91%) |
|
|
|
|
WARNING! |
|
|
|
|
|
|
|
|
Maximum setting is rated motor current (see nameplate). Does not provide full motor |
|||||
|
|
|
protection! |
|
|
|
|
|
C21 |
Motor Overload Type |
00 |
00 |
Speed Compensation |
|
Ir |
1 |
|
|
|
|
|
Reduces the allowable continuous current |
100% |
|
||
|
|
|
|
when operating below 30Hz. |
|
|
0 |
|
|
|
|
01 |
No Speed Compensation |
|
60% |
|
|
|
|
|
|
Example: Motor is cooled by forced |
|
|
|
|
|
|
|
|
ventilation as apposed to shaft mounted, |
|
|
|
|
|
|
|
|
self cooling fans. |
|
|
30 |
f |
|
|
|
|
|
|
Ir: rated current (%), f: motor frequency |
||
|
|
|
|
|
|
(Hz) |
|
|
C40 |
Frequency setpoint via |
0.0 |
0.0 |
{Hz} |
240 |
Only active if C01 is set properly |
||
|
keys |
|
|
|
|
(C01 = 1, 3, 5,7) |
|
|
C42 |
Start condition |
1 |
0 Start after LOW-HIGH change at |
|
See also c43 and c70 |
|
||
|
(with mains on) |
|
|
terminal 28 |
|
|
|
|
1Auto start if terminal 28 = HIGH
2Flying restart (auto start disabled)
3Auto start if terminal 28 = HIGH, with flying restart
|
|
|
WARNING! |
|
|
|
|
|
|
Automatic starting/restarting may cause damage to equipment and/or injury to |
|||
|
|
|
personnel! Automatic starting/restarting should only be used on equipment that is |
|||
|
|
|
inaccessible to personnel. |
|
|
|
C43 |
Flying restart selection |
0 |
0 |
Search range: C11...0 Hz |
If c42 = 2 or 3, the controller will start |
|
|
|
|
|
|
the motor speed search at C11, or at |
|
|
|
|
1 |
Search range: last frequency...0 Hz |
the last output frequency before the |
|
|
|
|
fault, depending on the setting of c43 |
|||
C48 |
Motor auto- |
0 |
0 |
Calibration not done |
• If C14 = 4...7, motor calibration |
|
|
calibration |
|
|
|
must be performed, |
but C86... |
|
|
|
1 |
Calibration enabled |
C91 must be programmed first |
|
|
|
|
|
|
(see C14) |
|
|
|
|
2 |
Calibration complete |
• If motor calibration is attempted |
|
|
|
|
before programming C86...C91, |
|||
|
|
|
|
|
||
|
|
|
|
|
triggers N1D fault |
|
C60 Mode selection for c61 |
0 |
0 |
Monitoring only |
c60 = 1 allows the keys |
to |
|
|
|
|
1 |
Monitoring and editing |
adjust speed setpoint (c40) while |
|
|
|
|
monitoring c61 |
|
||
|
|
|
|
|
|
18 |
Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES |
|
|
|
|
Commissioning |
|||
Code |
|
Possible Settings |
|
|
IMPORTANT |
||
No. |
Name |
Lenze |
Selection |
|
|
||
|
|
|
|||||
C61 |
Present status/error |
|
status/error message |
|
• |
Display |
|
C62 |
Last error |
|
error message |
|
• Refer to Section 5 for explanation |
||
|
|
|
of status and error messages |
||||
|
|
|
|
|
|
|
|
C63 |
Last error but one |
|
|
|
|
|
|
C64 |
Last error but two |
|
|
|
|
|
|
C70 |
Configuration TRIP |
0 |
0 TRIP reset after LOW-HIGH change at |
|
|
||
|
reset (error reset) |
|
|
terminal 28, mains switching, or after |
|
|
|
|
|
|
|
LOW-HIGH change at digital input “TRIP |
|
|
|
|
|
|
|
reset” |
|
|
|
|
|
|
1 |
Auto-TRIP reset |
|
• Auto-TRIP reset after the time |
|
|
|
|
|
|
|
|
set in c71 |
|
|
|
|
|
|
• More than 8 errors in 10 minutes |
|
|
|
|
|
|
|
|
will trigger RST fault |
|
|
|
WARNING! |
|
|
|
|
|
|
|
Automatic starting/restarting may cause damage to equipment and/or injury to |
||||
|
|
|
personnel! Automatic starting/restarting should only be used on equipment that |
||||
|
|
|
is inaccessible to personnel. |
|
|
|
|
C71 |
Auto-TRIP reset |
0.0 |
0.0 |
{s} |
60.0 |
See c70 |
|
|
delay |
|
|
|
|
|
|
C73 |
Input voltage |
|
0 Low (for 200 V input) |
|
• Lenze setting depends on C93 |
||
|
selection |
|
|
|
|
• |
During commissioning, confirm |
|
|
|
1 High (for 230 V input) |
|
|
correct setting based on mains |
|
|
|
|
|
|
|
|
voltage |
C78 |
Operating time |
|
Display |
|
0...999 h: format xxx |
||
|
counter |
|
Total time in status “Start” |
|
1000...9999 h: format x.xx (x1000) |
||
C79 |
Mains connection |
|
Display |
|
10000...99999 h: format xx.x (x1000) |
||
|
|
|
|
||||
|
time counter |
|
Total time of mains = on |
|
|
|
|
C82 |
S-ramp integration |
0.0 |
0.0 |
{s} |
50.0 |
• |
c82 = 0.0: Linear accel/decel ramp |
|
time |
|
|
|
|
• |
c82 > 0.0: Adjusts S-ramp curve |
|
|
|
|
|
|
|
for smoother ramp |
L25 |
Skip frequency 1 |
0.0 |
0.0 |
{Hz} |
240 |
• |
L25 and L26 define the start of the |
|
|
|
|
|
|
|
skip range |
L26 |
Skip frequency 2 |
0.0 |
0.0 |
{Hz} |
240 |
• |
L28 defines the bandwidth of the |
|
|
|
|
|
|
|
skip range |
L28 |
Skip frequency |
0.0 |
0.0 |
{Hz} |
10.0 |
|
|
|
bandwidth |
|
Note |
|
|
|
|
|
|
|
|
|
|
||
|
|
|
Bandwidth (Hz) = fs (Hz) + L28 (Hz) |
fs = L25 or L26 |
|||
|
|
|
Example: L25 = 18 Hz and L28 = 4 Hz; the bandwidth = 18...22 Hz |
Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES |
19 |
Commissioning
4.4Vector mode
Use the following procedures to select either Vector mode or Enhanced V/Hz mode. Enhanced V/Hz mode should be used in the following cases:
1.Multiple motor applications
2.Where required motor data is not available (especially C91)
3.Where running in Vector mode causes unstable motor operation
4.4.1 |
Vector speed and torque modes |
1. |
Connect the controller to the motor according to the diagram in Section 3.2.3. |
2. |
Apply power to the controller. |
3. |
Set C14 to 4 for Vector speed mode, or 5 for Vector torque mode. |
4. |
Set C86...C91 according to the motor’s nameplate data. |
5. |
Set c48 to 1 to enable the motor calibration function. |
6. |
Make sure the motor is cold (rotor and windings are at room temperature of 20º to 25º C), and |
|
apply a HIGH signal at terminal 28. The display will show CAL for about 40 seconds. Once the |
|
calibration is complete, the display will show OFF or 1NH. Apply another HIGH signal to terminal |
|
28 to actually start the motor. |
4.4.2 |
Enhanced V/Hz mode |
Follow the procedure in 4.4.1 above, replacing steps 3 and 4 with those below:
3.Set C14 to 6 for Enhanced with Auto-Boost, or 7 for Enhanced with constant boost.
4.Set C88...C90 according to the motor’s nameplate data.
Note
•If the motor is hot when the motor calibration is performed, the controller will not be able to achieve maximum performance.
•In Vector speed and Vector torque modes, if an attempt is made to start the controller before performing the motor calibration, the controller will display N1D and the motor will not operate.
20 |
Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES |
Troubleshooting and fault elimination
5 Troubleshooting and fault elimination
|
Status |
|
Cause |
Remedy |
e.g. |
Present output frequency |
Trouble free operation |
|
|
50.0 |
|
|
|
|
OFF |
Stop (outputs U, V, W inhibited) |
LOW signal at terminal 28 |
Set terminal 28 to HIGH |
|
1NH |
Inhibit (outputs U, V, W inhibited) |
Controller is set up for remote |
Start the controller via the remote |
|
|
|
keypad (see C01) |
keypad |
|
STP |
Output frequency = 0 Hz |
Quick stop activated through digital |
Deactivate Quick stop |
|
|
(outputs U, V, W inhibited) |
input |
|
|
FST |
Flying restart attempt |
c42 = 2, 3 |
|
|
BR |
DC-injection brake active |
DC-injection brake activated |
Deactivate DC-injection brake |
|
|
|
• |
via digital input |
• digital input = LOW |
|
|
• |
automatically |
• automatically after holding time c06 |
|
|
|
|
has expired |
CAL |
Motor calibration is in process |
c48 = 1 and terminal 28 = HIGH |
Only perform the motor calibration |
|
|
|
|
|
when C14 = 4...7 |
CL,FCL |
Current limit reached |
Controllable overload |
Automatically (see C22) |
|
LU |
Undervoltage on DC bus |
Mains voltage too low |
Check mains voltage |
|
DEC |
Overvoltage on DC bus during |
Excessively short deceleration time |
Automatically if overvoltage |
|
|
deceleration (warning) |
(C13, c03) |
< 1 s, OU, if overvoltage > 1 s |
|
NED |
No access to code |
Can only be changed when the control- |
Set terminal 28 to LOW |
|
|
|
ler is in OFF or 1NH |
|
|
RC |
Remote keypad is active |
Attempt to use buttons on front of |
Buttons on front of controller are dis- |
|
|
|
controller |
abled when remote keypad is active |
|
|
Error |
|
Cause |
Remedy (1) |
AD |
A/D converter error |
|
|
Please contact Lenze |
BF |
Identification fault |
C93 value stored on EPM does not |
|
|
|
|
match controller model |
|
|
CF |
|
Data not valid for controller |
• Use EPM providing valid data |
|
CF |
Data on EPM not valid |
Data error |
• Load Lenze setting |
|
|
||||
GF |
|
OEM data not valid |
|
|
LC |
Automatic start inhibited |
c42 = 0, 2 |
LOW-HIGH signal change at terminal 28 |
|
F1 |
EPM error |
EPM missing or defective |
Power down and replace EPM |
|
CFG |
Digital inputs not |
E1...E3 assigned with the same digital |
Each digital signal can only be used |
|
|
uniquely assigned |
signals |
once |
|
|
|
Either just “UP” or “DOWN” used |
Assign the missing digital signal to a |
|
|
|
|
|
second terminal |
DF |
Dynamic braking fault |
Dynamic braking resistors are |
Increase deceleration time |
|
|
|
overheating |
|
|
EER |
External error |
Digital input “TRIP set” is active |
Remove external error |
|
FC5, |
Internal fault |
|
|
Please contact Lenze |
F2...F0 |
|
|
|
|
(1) The drive can only be restarted if the error message has been reset; see c70 |
|
|||
Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES |
21 |
Troubleshooting and fault elimination
|
Error |
Cause |
|
Remedy (1) |
JF |
Remote keypad fault |
Remote keypad disconnected |
Check remote keypad connections |
|
N1D |
Drive identification fault |
Attempt was made to perform motor |
Must set C86...C91 before performing |
|
|
|
calibration before setting C86...C91 |
motor calibration (see c48) |
|
0C1 |
Short-circuit or overload |
Short-circuit |
Find reason for short-circuit; check |
|
|
|
|
motor cable |
|
|
|
Excessive capacitive charging |
Use shorter motor cables with lower |
|
|
|
current of the motor cable |
charging current |
|
|
|
Acceleration time (C12, c01) too short |
• |
Increase acceleration time |
|
|
|
• |
Check controller selection |
|
|
Defective motor cable |
Check wiring |
|
|
|
Internal fault in motor |
Check motor |
|
|
|
Frequent and long overload |
Check controller selection |
|
0C2 |
Earth fault |
Grounded motor phase |
Check motor/motor cable |
|
|
|
Excessive capacitive charging |
Use shorter motor cables with lower |
|
|
|
current of the motor cable |
charging current |
|
0C6 |
Motor overload (I2t overload) |
Motor is thermally overloaded, due to: |
• |
Check controller selection |
|
|
• impermissable continuous current |
||
|
|
• frequent or too long acceleration |
• Check setting of c20 |
|
|
|
processes |
|
|
0H |
Controller overtemperature |
Controller too hot inside |
• |
Reduce controller load |
|
|
|
• |
Improve cooling |
OU |
Overvoltage on DC bus |
Mains voltage too high |
Check mains voltage |
|
|
|
Excessively short deceleration time or |
Increase deceleration time or use |
|
|
|
motor in generator mode |
dynamic braking option |
|
|
|
Earth leakage on the motor side |
Check motor/motor cable |
|
|
|
|
(separate motor from controller) |
|
RF |
Flying restart fault |
Controller was unable to synchronize |
Check motor/load |
|
|
|
with motor during restart attempt |
|
|
RST |
Faulty auto-TRIP reset |
More than 8 errors in 10 minutes |
Depends on the error |
|
SD5 |
Loss of 4-20 mA reference |
4-20 mA signal (terminal 8I) is below 2 |
Check signal/signal wire |
|
|
|
mA (C34 = 5) |
|
|
SF |
Single phase fault |
A mains phase has been lost |
Check mains voltage |
(1) The drive can only be restarted if the error message has been reset; see c70
NOTE
In the event of an “OC6” (Motor Overload) failure there is a 3-minute delay before resetting is possible.
This is a requirement of UL508C. This delay is intended to allow time for the motor to cool.
If power is removed when the drive is in an “OC6” fault state, when the power is restored the “OC6” fault will still be present and the delay will still be active even if power was removed for longer than 3 minutes.
22 |
Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES |
Notes
Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES |
23 |
|
|
Notes
|
|
Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES |
24 |
Inhalt
Info zu diesen Anweisungen.................................................................................. |
2 |
|
|||
1 |
Sicherheitsinformationen............................................................................... |
3 |
|
||
|
1.1 |
In diesen Anweisungen verwendete Piktogramme............................. |
4 |
|
|
2 |
Technische Daten.......................................................................................... |
6 |
|
||
|
2.1 |
Normen und Anwendungsbedingungen.............................................. |
6 |
|
|
|
2.2 |
Bemessungsdaten.............................................................................. |
7 |
|
|
3 |
Installation...................................................................................................... |
|
8 |
|
|
|
3.1 |
.....................................................................Mechanische Installation |
8 |
|
|
|
|
.....................................................3.1.1 Abmessungen und Montage |
9 |
|
|
3.2 |
Elektroinstallation........................................................................................... |
9 |
|
||
|
3.2.1 |
Installation gemäß EMV-Richtlinien.................................................... |
9 |
|
|
|
3.2.2 |
Sicherungen/Leitungsquerschnitte ..................................................... |
9 |
|
|
|
3.2.3 |
Schaltplan......................................................................................... |
10 |
|
|
|
3.2.4 |
Steuerungsklemmen......................................................................... |
11 |
|
|
4 |
Inbetriebnahme............................................................................................ |
12 |
|
||
|
4.1 |
Parametrierung................................................................................. |
12 |
|
|
|
4.2 |
Elektronisches Programmiermodul (EPM)........................................ |
12 |
|
|
|
4.3 |
Parametermenü................................................................................ |
13 |
|
|
|
4.4 |
Vektorbetrieb..................................................................................... |
20 |
|
|
|
|
4.4.1 |
Drehzahlund Drehmomentregelung im Vektorbetrieb........... |
20 |
|
|
|
4.4.2 |
Erweiterter U/f-Betrieb............................................................. |
20 |
|
5 |
Fehlersuche und -behebung........................................................................ |
21 |
|
Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES |
1 |
Info zu diesen Anweisungen
Diese Dokumentation gilt für den vektorgeregelten Frequenzumrichter Tml. Sie beinhaltet wichtige technische Daten und beschreibt die Installation, die Inbetriebnahme sowie den Betrieb.
Bitte lesen Sie vor der Inbetriebnahme die Anweisungen.
|
|
|
|
A |
|
B |
|
C |
|
D |
E F |
|||||
|
|
|
|
Type: |
|
|
|
|
|
|
|
|
+ |
|
||
|
|
|
|
|
Input: 1/N/PE (2PE) |
Output: 3/PE |
For detailed information |
|
||||||||
|
|
|
|
ETML751X2SFA |
|
|
230 V |
|
0-230 V |
refer to instruction |
|
|
|
|||
|
|
|
|
Id-No: 13xxxxx |
|
|
9.2 A |
|
4.2 A |
Manual TL03 |
|
|
|
|||
|
|
Made in USA |
|
|
|
|
|
50-60 Hz |
|
0.75 kW |
SN: 13xxxxxx012345678 |
|
|
|
||
|
|
Inverter |
|
|
LISTED |
|
|
|
|
0 - 240 Hz |
ETML751X2SFA000XX |
XX |
|
XX |
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||
|
|
|
|
5D81 |
|
|
|
1341308801234567 |
|
|
|
|
||||
|
|
Tml - basic I/O |
|
|
IND. CONT. EQ. |
N10104 |
|
|
|
|
|
|||||
|
|
|
|
|
Z519 |
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
V0006 |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
A Approbationen |
|
C Eingangsbemessungsdaten |
E Hardwarestand |
|
|
|
||||||||
|
|
B Typ |
|
D Ausgangsbemessugsdaten |
F Softwarestand |
|
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
Lieferumfang |
|
|
|
Wichtig |
|
|
|
|
|
|
|
|||
|
|
|
|
|
||||||||||||
|
|
• 1 Frequenzumrichter Tml Vector |
|
Prüfen Sie unmittelbar nach Erhalt der Lieferung, ob alle gelief- |
||||||||||||
|
|
control (ETML...) mit installiertem |
|
erten Objekte den Angaben auf den beiliegenden Unterlagen |
|
|
|
|||||||||
|
|
EPM (siehe Abschnitt 4.2) |
|
entsprechen. Lenze haftet nicht für im Nachhinein gemeldete |
||||||||||||
|
|
• 1 Betriebsanleitung |
|
|
|
Mängel. |
|
|
|
|
|
|
|
|||
|
|
|
|
|
Melden Sie |
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
•erkennbare Transportschäden umgehend dem Transportunternehmen.
•erkennbare Mängel/unvollständige Lieferungen umgehend Ihrem Lenze-Vertreter.
© 2013 - 2004 Lenze AC Tech Corporation
Diese Dokumentation darf ohne ausdrückliche schriftliche Genehmigung der Lenze AC Tech Corporation weder ganz noch auszugsweise kopiert oder Dritten zur Verfügung gestellt werden.
Alle in dieser Dokumentation enthaltenen Informationen wurden sorgfältig ausgewählt und auf Übereinstimmung mit der beschriebenen Hardware und Software hin getestet. Fehler können jedoch nicht vollkommen ausgeschlossen werden. Wir übernehmen keinerlei Verantwortung für eventuell auftretende Schäden. Erforderliche Korrekturen werden in folgende Ausgaben dieser Dokumentation aufgenommen.
2 |
Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES |
Sicherheitsinformationen
1Sicherheitsinformationen
Allgemeine Informationen
Einige Bauteile in Lenze-Reglern (Frequenzumrichter, Servoumrichter, DC-Steuerungen) können stromführend sein, sich bewegen oder rotieren. Einige Oberflächen können heiß werden.
Unbefugtes Entfernen der erforderlichen Abdeckung, unsachgemäße Verwendung und nicht vorschriftsmäßige Installation oder Bedienung können schwere Personenoder Sachschäden verursachen.
Sämtliche Tätigkeiten bei Transport, Installation und Inbetriebnahme sowie Wartungsarbeiten müssen von qualifiziertem und geschultem Fachpersonal durchgeführt werden (IEC 364 und CENELEC HD 384 oder DIN VDE 0100 und IEC-Report 664 oder DIN VDE 0110 sowie nationale Unfallverhütungsvorschriften müssen beachtet werden).
Gemäß diesen grundlegenden Sicherheitsinformationen handelt es sich bei qualifiziertem und geschultem Fachpersonal um Personen, die mit der Installation, der Montage, der Inbetriebnahme und dem Betrieb des Produkts vertraut sind und die über die für ihre Tätigkeit erforderlichen Qualifikationen verfügen.
Anwendung wie vorgeschrieben
Antriebsregler sind Bauteile, die für die Installation in elektrischen Systemen oder Maschinen vorgesehen sind. Sie dürfen nicht als separate Geräte verwendet werden. Sie sind ausschließlich für professionelle und kommerzielle Zwecke gemäß EN 61000-3-2 gedacht. Die Dokumentation enthält Informationen zur Einhaltung der Norm EN 61000-3-2.
Bei der Installation der Antriebsregler in Maschinen ist die Inbetriebnahme (d. h. der Start des Betriebs wie vorgeschrieben) untersagt, bis nachgewiesen wurde, dass die Maschine den Bestimmungen der EG-Richtlinie 2006/42/EG (Maschinenrichtlinie) entspricht und die harmonisierte Norm EN 60204 eingehalten wird.
Die Inbetriebnahme (d. h. der Start des Betriebs wie vorgeschrieben) ist nur dann zulässig, wenn die EMV-Richtlinie 2004/108/EG eingehalten wird.
Die Antriebsregler genügen den Anforderungen der Niederspannungsrichtlinie 2006/95/EG. Für die
Regler gelten die harmonisierten Normen der Serie EN 50178/DIN VDE 0160.
Hinweis: Die Verfügbarkeit von Reglern ist gemäß Norm EN 61800-3 eingeschränkt. Diese Produkte können in Wohngebieten Funkstörungen verursachen. In diesem Fall sind eventuell besondere Vorkehrungen zu treffen.
Installation
Sorgen Sie für sachgemäßen Umgang und vermeiden Sie übermäßige mechanische Beanspruchung. Vermeiden Sie ein Verbiegen von Bauteilen und das Ändern von Isolationsabständen beim Transport oder dem Umgang mit der Einheit. Berühren Sie keine elektronischen Bauteile und Kontakte.
Regler enthalten elektrostatisch empfindliche Bauteile, die bei unsachgemäßem Umgang leicht beschädigt werden können. Beschädigen oder zerstören Sie keine elektrischen Bauteile, da dadurch Ihre Gesundheit gefährdet werden könnte!
Elektrische Anschlüsse
WennArbeiten an stromführendenAntriebsreglern durchgeführt werden, müssen die geltenden nationalen Unfallverhütungsvorschriften (z. B. VBG 4) eingehalten werden.
Die Elektroinstallation muss im Sinne der geltenden Bestimmungen (z. B. Leitungsquerschnitte, Sicherungen, PE-Anschlüsse) durchgeführt werden. Zusätzliche Informationen können der Dokumentation entnommen werden.
Die Dokumentation enthält Informationen über die Installation gemäß den EMV-Richtlinien (Abschirmung, Erdung, Filter und Leitungen). Diese Hinweise gelten auch für mit dem CE-Zeichen gekennzeichnete Regler.
Der Hersteller des Systems oder der Maschine ist für die Einhaltung der erforderlichen Grenzwerte gemäß den EMV-Richtlinien verantwortlich.
Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES |
3 |
Sicherheitsinformationen
Betrieb
Systeme mit Reglern müssen mit zusätzlichen Überwachungsund Schutzvorrichtungen ausgerüstet werden, die den geltenden Normen (z. B. Normen für technische Einrichtungen, Unfallverhütungsvorschriften usw.) entsprechen. Der Regler darf wie in der Dokumentation beschrieben für Ihre Anwendung angepasst werden.
WARNUNG!
• Nachdem die Stromversorgung des Reglers unterbrochen wurde, dürfen stromführende Bauteile und Netzverbindungen nicht sofort berührt werden, da Kondensatoren noch geladen sein können. Beachten Sie hierzu die entsprechenden Hinweise auf dem Regler.
•Schalten Sie den Regler nicht öfter als einmal alle drei Minuten ein und wieder aus.
•Schließen Sie beim Betrieb alle Schutzabdeckungen und -türen.
1.1In diesen Anweisungen verwendete Piktogramme
Piktogramm |
Signalwort |
Bedeutung |
Folgen bei Missachtung |
||
|
|
|
|
|
|
|
|
|
WARNUNG! |
Mögliche drohende |
Tod oder Verletzungen. |
|
|
|
|
Personenschäden. |
Schäden am Antriebssystem |
|
|
|
|
Mögliche Sachschäden |
oder seiner Umgebung |
|
|
|
|
|
|
|
|
|
Hinweis |
Nützlicher Tipp: Das Befolgen |
|
|
|
|
|
||
|
|
|
|
dieser Tipps vereinfacht den |
|
|
|
|
|
Umgang mit dem Antrieb. |
|
|
|
|
|
|
|
|
|
|
|
|
|
4 |
Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES |