Honeywell W7752F, W7752G, W7752E, W7752J, W7752D SPECIFICATION DATA

0 (0)

([FHO

W7752D,E,F,G,J FAN COIL UNIT CONTROLLERS

63(&,),&$7,21 '$7$

)($785(6

/210$5.Š +9$& SURILOH

6WDQG DORQH RSHUDWLRQ RU RQ KLJK VSHHG NLORELW (FKHORQŠ /21:25.6QHWZRUN

8VHV (FKHORQ /RQ7DONŠ SURWRFRO

)77 $ 7UDQVFHLYHU

'LUHFW FRQQHFWLRQ RI WKHUPDO DFWXDWRUV

'LUHFW FRQQHFWLRQ WR IDQ VZLWFK

'LUHFW FRQQHFWLRQ WR HOHFWULF KHDW

)DFWRU\ FRQILJXUHG GHIDXOW SDUDPHWHUV

:LGH UDQJH RI VXSSRUWHG YDOYHV DQG DFWXDWRUV

,QWHUORFNV DQG WLPH GHOD\V WR SURWHFW HTXLSPHQW

6OLP GHVLJQ ILWV LQWR QDUURZ IDQ FRLO XQLWV

7HUPLQDWLRQV DOO RQ RQH VLGH DOORZ FRQWUROOHU WR EH SRVLWLRQHG DW EDFN RI IDQ FRLO XQLW

3RZHU VXSSOLHG E\ SRZHU PDLQV

*(1(5$/

The W7752D,E,F,G and J Controllers are communicating mains-powered Fan Coil Unit Controllers in the Excel 10 product line. They cover a wide range of fan coil control applications. The controllers can operate as stand-alone units or networked using the standard Echelon LONWORKS® bus. Interfaces are provided for a wide range of actuator types. Heating systems can be water or electric, and cooling systems can be chilled water supply or compressors. Extensive timing and interlock features make the W7752 especially suitable for systems using electric heat and compressors.

7DEOH )&8 &RQWUROOHU PRGHOV

26 QXPEHU

 

3RZHU LQSXW

 

5HKHDW UHOD\

W7752D2007

 

230 Vac

 

X

W7752E2004

 

230 Vac

 

 

W7752F2002

 

115 Vac

 

X

W7752G2000

 

115 Vac

 

 

W7752J2003

 

100 Vac

 

 

® U.S. Registered Trademark

Copyright © 1999 Honeywell Inc.

All Rights Reserved

'(6&5,37,21

The W7752D,E,F,G and J are LONMARK compliant Fan Coil Unit Controllers in the Excel 10 family product line. These controllers provide room temperature control for two and four pipe fan coil units with optional electric heating coils (W7752D,F) and can control single, two or three speed fans. The controller is provided with default configuration settings from the factory and is fully operable on installation. Using standard Echelon configuration tools, the controller can be configured with job-specific settings. A variety of optional wall modules interface with the FCU Controllers and provide any or all of the following: setpoint adjustment, fan speed adjustment, and an occupancy bypass button. All wall modules include a space temperature sensor, however, a remote C7068A return air sensor can also be used.

7DEOH 6XSSRUWHG RXWSXW W\SHV

 

 

 

 

 

 

2XWSXW

 

2SWLRQV

Heating

 

Floating, thermal, PWM, on/off, multi-

 

 

stage electric.

Cooling

 

Floating, thermal, PWM, on/off, multi-

 

 

stage compressor.

Fan

 

On/off, 2-speed, 3-speed

Electric reheat

 

On/off

74-2959-3

Honeywell W7752F, W7752G, W7752E, W7752J, W7752D SPECIFICATION DATA

: ' ( ) * - )$1 &2,/ 81,7 &21752//(56

6HTXHQFHV

Heat and cool sequences can be selected to be active or not active, giving a total of eight different sequence options (each can be with or without fan control):

-Heat only

-Cool only

-Heat/cool changeover

-Heat and cool sequence

-All of the above with electric reheat.

)LJ 2SHUDWLRQDO VHTXHQFH

0RGHV RI 2SHUDWLRQ

The controller has the following modes of operation.

2FFXSLHG PRGH

This is the normal operating condition for a room or zone when it is occupied. The controller can be switched into this mode by a network command, by the room occupancy sensor, or by a bypass button on the wall module. In the occupied mode the fan is controlled by the setting of the fan speed switch on the wall module or by the control algorithm when the switch is set to “auto.” The fan can be configured to remain on or turn off during the zero energy band.

6WDQGE\ PRGH

The standby mode saves energy by reducing heating or cooling demand during periods where the room is temporarily unoccupied. In this mode the fan is switched off during the zero energy band.

8QRFFXSLHG PRGH

This mode is used for longer unoccupied periods, such as at night or during weekends and holidays.

:LQGRZ RSHQ

If the controller is configured for window open detection, the controller automatically disables heat and cool control until the window is closed again. Frost protection remains active.

)URVW SURWHFWLRQ

If the temperature drops below 46°F (8°C), the controller enables the heating circuit as frost protection.

6PRNH FRQWURO

The fan can be turned on or off by network command for smoke control.

)DQ IDLO

When configured with an air flow detector, the controller protects equipment by disabling the system when the fan fails.

&KDQJHRYHU

The controller operates two-pipe FCUs configured with a changeover input.

)LJ 7\SLFDO DSSOLFDWLRQ

63(&,),&$7,216

0RGHOV

The W7752D and W7752E are 230 Vac versions and are identical except for one additional relay in the W7752D for switching electric heat coils. The W7752F and W7752G are 115 Vac versions of the W7752D and W7752E, respectively. The W7752J is a 100 Vac version of the W7752E.

,QSXW 2XWSXW

7DEOH ,QSXW RXWSXW VSHFLILFDWLRQV

,QSXWV

 

)XQFWLRQ

 

&KDUDFWHULVWLFV

Digital

 

Window/occupancy/

 

closed £400 W (1.5 mA),

 

 

changeover/air flow

 

open ³ 10 kW (4.8 V)

Analog/

 

Fan speed/override

 

resistor network

Digital1

 

 

 

 

Analog

 

Temperature

 

20k ohm NTC

 

 

sensor

 

 

Analog1

 

Setpoint adjustment

 

10k ohm

 

 

 

 

 

2XWSXWV

 

 

 

 

Digital1

 

Override LED

 

0/5 Vdc

Triac

 

Heat and cool

 

24 Vac, 250 mA max.

(2 pairs)2

 

 

 

continuous, 650 mA

 

 

 

 

max. surge (£30 sec)

Relay (3)

 

Fan switching

 

20 to 253 Vac, 3 A max.

High

 

Electric heat

 

20 to 300 Vac,

power

 

(resistive load)

 

10 A max.

relay3

 

 

 

6 A max. (UL916)

1Wall Module connection only.

2See Table 2 for output type options.

3W7752D,F only.

74-2959-3

2

Loading...
+ 2 hidden pages