Only qualified personnel should install and service the equipment. The installation, starting up, and servicing
of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and
training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or
serious injury. When working on the equipment, observe all precautions in the literature and on the tags,
stickers, and labels that are attached to the equipment.
This document and the information in it are the property of Trane and may not be used
or reproduced in whole or in part, without the written permission of Trane. Tranereserves
the right to revise this publication at any time and to make changes to its content without
obligation to notify any person of such revision or change.
Trademarks
Trane and its logo are trademarks of Trane in the United States and other countries. All
trademarks referenced in this document are the trademarks of their respective owners.
Warnings, Cautions, and Notices
Warnings, cautions, and notices are provided in appropriate places throughout this
document:
WARNING: Indicates a potentially hazardous situation which, if not avoided,
could result in death or serious injury.
CAUTION: Indicates a potentially hazardous situation which, if not avoided,
may result in minor or moderate injury. It may also be used to alert against
unsafe practices.
NOTICE: Indicates a situation that may result in equipment or property-damage-
only accidents.
This section provides a description of the sensors, as well as part numbers and dimensions.
Product Description
The Trane®programmable zone sensor (p/n X1379088401) can be used with UCP, Reliatel, and
IntelliPak control units. It has the following features:
•A liquid crystal display (LCD) with symbols for zone temperature, temperature setpoints,
system operating modes, day of the week, time of day, and occupancy settings
•Configurable to operate with constant-volume (CV) units, heat pump (HP) units, and variableair-volume (VAV) units
•System modes:
– CV: Heat, Cool, Auto, Off
– HP: Emergency Heat, Heat, Cool, Auto, Off
– VAV: Auto, Off
•A cooling setpoint range (occupied) of 45ºF to 98ºF (7.2ºC to 36.7ºC)
•A heating setpoint range (occupied) of 43ºF to 96ºF (6.1ºC to 35.6ºC)
•Two fan modes (CV and HP only): On, Auto
•A table of configurable functional options (see Tab l e 3 , p . 1 4 and Ta bl e 4 , p . 16 )
•Scheduling function: 7 days per week and up to 4 periods per day, occupied/unoccupied mode
•Temporary override function
•During occupied periods, an auxiliary relay rated for 1.25 A @ 30 Vac with one set of single-pole
double-throw contacts is activated.
4BAS-SVX17B-EN
Page 5
Dimensions
2.9 in (73.5 cm)
1.08 in (27.5 mm)
4.68 in (118.9 mm)
1.34 in (34.14 mm)
0.58 in (14.76 mm)
0.31 in (8 mm)
0.12 in (3 mm)
TYP R.07 in
(R1.80 mm)
3.39 in (86 mm)
0.24 in (6.00 mm)
2.62 in (66.5 mm)
General Information
The following illustration provides specific dimension details. The dimensions are the same for all
models.
BAS-SVX17B-EN5
Page 6
Pre-Installation
This section provides the following pre-installation information:
•Location considerations
•Height requirements
•Mounting surfaces
•Recommended wire lengths
Location Considerations
Placement of the sensor is critical to proper operation. When selecting a location, avoid the
following:
•Areas of direct sunlight
•Areas in the direct airstream of air diffusers
•Exterior walls and other walls that have a temperature differential between the two sides
•Areas that are close to heat sources such as sunlight, appliances, concealed pipes, chimneys,
or other heat-generating equipment
•Drafty areas
•Dead spots behind doors, projection screens, or corners
•Walls that are subject to high vibration
•Areas with high humidity
•High traffic areas (to reduce accidental damage or tampering)
Height Requirements
It is recommended that you mount the back plate a maximum distance of 54 inches above the floor.
If a parallel approach by a person in a wheelchair is required, reduce the maximum height to 48
inches.
Note: Consult section 4.27.3 of the 2002 ADA (Americans with Disability Act) guideline, and local
building codes, for further details regarding wheelchair requirements.
Mounting Surfaces
Using the hardware provided, mount the back plate to a flat surface such as sheetrock or plaster,
or an electrical junction box. The sensor must be mounted plumb for accurate temperature control
and to ensure proper air movement through the sensor.
•If mounting onto sheetrock or plaster, use the plastic threaded anchors (pre-drilling holes is not
usually necessary) and the two M3.5 x 20 mm mounting screws.
•For mounting onto an electrical junction box, use the two 6-32 x 3/4 in. screws.
•If you are replacing a horizontally mounted sensor and need to cover an opening in the wall,
use the adapter kit (p/n BAYMTPL103A).
6BAS-SVX17B-EN
Page 7
Wire Length
Pre-Installation
Maximum recommended wire lengths for the sensor are given in Ta b l e 1:
Table 1.Recommended wire lengths
Wire size
AWGmm
220.330–460–150
200.5047–73151–240
180.7574–117241–385
161.30118–185386–610
142.00186–296611–970
Note: The total resistance of these low voltage wires must not exceed 2.5 Ω/conductor. Any resistance greater than 2.5 Ω
may cause the control to malfunction due to an excessive voltage drop.
2
Maximum recommended wire length from unit
controller to sensor
MetersFeet
BAS-SVX17B-EN7
Page 8
Security screw
Installation
This section provides step-by-step installation instructions. Read through the pre-installation
information before proceeding with the installation.
Note: Before installing the sensor, ensure that:
•A wire access hole is available at the sensor location
•The wires are accessible through the hole
•The wires are attached to the appropriate unit controller
•There is continuity between the sensor location and the unit controller
•The wires are accurately labeled or identified by color
Mounting the Back Plate
WARNI NG
Hazardous voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper
lockout/tagout procedures to ensure the power cannot be inadvertently energized. Failure to
disconnect power before servicing could result in death or serious injury.
NOTICE
Equipment damage!
Applying excessive voltage to the sensor will permanently damage it.
Note: Refer to the illustration below when installing the sensor.
1. Shut off power to the unit controller.
2. Remove the cover by firmly pressing the thumb tab at the bottom of the cover and pulling the
cover away from the back plate.
Note: If present, remove the security screw before removing the cover.
3. Determine the number of wires required by referring to Tab le 2 , p . 1 0 .
4. Feed the wires through the opening in the back plate.
5. Hold the back plate against the mounting surface and mark the screw locations.
6. Secure the back plate to the mounting surface using the included hardware.
8BAS-SVX17B-EN
Page 9
Wiring the Sensor
WARNI NG
Hazardous voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper
lockout/tagout procedures to ensure the power cannot be inadvertently energized. Failure to
disconnect power before servicing could result in death or serious injury.
NOTICE
Equipment damage!
Applying excessive voltage to the sensor will permanently damage it.
To wire the sensor to the unit controller (see guidelines for wire sizes and lengths in Table 1, p. 7.):
1. Ensure that the wires are connected to the appropriate
2. Connect the wires to the terminal block (included in the hardware package with the sensor). See
Ta b le 2, p. 10 to determine where to terminate wires in the terminal block.
Note: The numbers on the terminal block correspond to the numbers on the terminals of the
3. Attach the terminal block to the pins on the circuit board inside the sensor cover (Figure 1).
Installation
terminals at the unit controller.
unit controllers most frequently used with the sensor.
Figure 1. Attaching the terminal block to the pins on the circuit board
4. Push the excess wire into the wall cavity and plug it with nonflammable insulation to prevent
drafts from affecting the sensor.
Important: Do not coil excess wire inside the back plate.
BAS-SVX17B-EN9
Page 10
10BAS-SVX17B-EN
Table 2. Programmable zone sensor wiring diagram
3–25 ton
packaged rooftops
split
system
units
27.5–50 ton
packaged rooftops
*CD/*CH/*SC/
3–20
*HC
UCP
control
Sensor
(5)
(2)
(2)
S2Optional remote sensor
S1Optional remote sensor
14 -------14
12 -------1212121212121212121TB8-12
11 -------11111111116711111TB8-11
8-------8888889881TB8-8
7-------7777778771TB8-7
A3
A1
REMOTE SENSOR INPUT
REMOTE SENSOR INPUT
24 VAC INPUT
COMMUNICATIONS
COMMON
SERVICE STATUS (UCM INPUT)10 -------1010101010101110101TB8-10
SYSTEM STATUS (ON/OFF INPUT)9-------99999910991TB8-9
COOL STATUS
(UCM INPUT)
HEAT S TATU S
(UCM INPUT)
AUX RELAY (CLOSED—
UNOCCUPIED)
AUX RELAY (CLOSED—
OCCUPIED)
(1)LTB and LTB1 refer to low-voltage terminal boards with numbers 1–20 and two test terminals.
(2)Connect an optional remote sensor (p/n BAYSENS017) to terminals S1 and S2. Connect the shield wire (drain wire) from the shielded cable to terminal 11.
(3)Connect the 24 Vac power supply from the unit controller to terminals 11 and 14. (IntelliPak power supply voltage is 12–15 Vac.)
(4)Use terminal 15 on older 3–25 ton Voyager units with low-voltage terminal boards numbered 1–18 with two test terminals.
(5)Data communication between the unit controller and the sensor is accomplished by a serial link connected at terminal 12.
(3)
(3)
LTB
(1)
(4)
ReliaTel
Control
The auxiliary relay on the sensor is form C, rated for 1.25 A at 30 Vac. It is energized during occupied periods.AUX RELAY (COMMON)A2
TTA/TWA
ReliaTel
Control
J6
1414141414114141TB11-4
J6
YC*/TC*/TE*
UCP
control
LTB1
ReliaTel
Control J6IntelliPak
(1)
ton
packaged
rooftops
S*HF/
W*HB
1TB4
90–162
ton
packaged
rooftops
S*HJ
IntelliPak
1TB4
20–130
TC
330–600
model
number
10th digit
= A+ L
LTB1
UCP
control
LTB1
YC* TE*
(1)
YC* TE*
TC
330–600
model
number
10th digit
= M+
RTRM J6
ReliaTel
Control
J6IntelliPak
Commercial
self-
contained
(CSC)
S**F, S**G
Installation
Page 11
Replacing the Cover
Security screw
To replace the cover:
1. Hook the cover over the top of the back plate. Apply light pressure to the bottom of the cover
until it snaps in place.
2. Secure the cover by installing the security screw into the bottom of the cover.
Installation
BAS-SVX17B-EN11
Page 12
AM
PM
DAYS
HOURS
Mo Tu
We Th Fr SatSu
.
Service indicator, filter timer,
keypad lockout, occupancy
indicator, temporary override
Zone temperature and
setpoint temperature
System settings
Fan sett ings
Scheduling area/day and clock
A. Home screen
B. Configuration screen
Option value
Option number
Installation
Applying Power to the Sensor
Restore power to the unit controller. The following sequence appears on the display:
•The display lights up and all of the symbols appear for 2 seconds (see Figure 2).
Figure 2. Display with all the symbols appearing
Figure 3. Display at power-up
12BAS-SVX17B-EN
•The software version appears for 2 seconds.
•If the sensor has been in service for any length of time, the home screen appears (see Figure 3A
example). If the sensor is new, the configuration screen appears (see Figure 3B). If no buttons
are pressed for 90 seconds, the display returns to the home screen in constant-volume (CV)
configuration.
•The light dims.
Mo
.
AM
.
Page 13
Configuration
Test/Configuration button
Keypad
The programmable zone sensor is configured by selecting options to determine system and
functional operations.
The sensor can be configured to operate with one of the following units:
•A constant-volume (CV) unit
•A heat pump (HP) unit
•A variable-air-volume (VAV) unit
The functional options that are available depend on whether the sensor is configured for a CV, an
HP, or a VAV unit.
To configure the sensor:
1. Press and hold the Test/Configuration button for 2 seconds (Figure 4). The configuration screen
appears (see Figure 3, p. 12).
Figure 4. Pressing the Test/Configuration button
2. Use the keypad on the sensor cover to select the system and functional options. See Ta b le 3 ,
p. 14 for sensors used with CV or HP units; see Table 4, p. 16, for sensors used with VAV units.
•Press , , or to change the option number.
•Press or to change the option value.
3. To confirm the selection and return the display to the home screen, either:
•Press the Test/Configuration button, or
•Press and hold for 2 seconds
Note: The sensor will revert to the home screen if no buttons are pressed for 90 seconds.
BAS-SVX17B-EN13
Page 14
Configuration
Table 3.Configuration options for sensors used with constant-volume (CV) or heat pump (HP) units
Option
number
0
(See Note)
1Morning warm-up
2
3Temperature scale
4Supply air tempering
5Time clock
6Smart fan
7Computed recovery
8
9
10
11Remote sensor installed
12Check filter interval
Function Option valueDefault Description
Operation mode
Economizer minimum
position override during
unoccupied period
0 = 7 days (M, T, W, Th, F, S, S)
1 = 5 +1 days (M–F, S, S)
2 = 5 + 2 days (M–F, S–S)
3 = 1 day
2 = Day and Night
3 = Morning, Day, Night
4 = Morning, Day, Evening,
Night
0 = Disabled
1 = Enabled
0 = No
1 = Yes
0 = Disabled
1–199 = Number of 1-day
increments
Configures the operation mode of the sensor.
Note: To access option number 0, with the configuration
0
0
1
0Displays the temperature in the selected format.
0
0
1
0
0
4
0
0
30
screen showing, press the up and down arrows
simultaneously for 2 seconds. Option number 0 will
appear on the display.
If enabled, the heat turns on when the program switches
from unoccupied to occupied and the zone temperature is
2ºF (1.1ºC) below the heating setpoint temperature. The
heat terminates after 60 minutes regardless of whether
the setpoint has been reached.
If enabled, the minimum position of the economizer
damper is overridden during the unoccupied period.
If enabled, this setting sends the tempering signal to the
UCP.
• 0 sets clock to 12-hour format with AM and PM.
• 1 sets clock to 24-hour military time.
If enabled, the supply fan operates in the Auto mode
during unoccupied periods, regardless of the fan setting.
If enabled, this option offsets the setpoint temperature
and starts the system before the scheduled occupied
period to efficiently reach the occupied temperature
setpoint. The time is calculated based on a recovery rate
of 6ºF (3.3ºC) per hour. If configured for an HP unit, option
7 is disabled for emergency heat operation.
• If 0 is selected, all 7 days to be programmed differently.
• If 1 is selected, week days, Sat, and Sun can be
programmed differently from one another.
• If 2 is selected, week days can be programmed one way
and Sat-Sun can be programmed another way.
• If 3 is selected, all seven days are limited to being
programmed the same way.
• If 2 is selected, only Day and Night periods can be
programmed.
• If 3 is selected, only Morning, Day, and Night periods can
be programmed.
• If 4 is selected, Morning, Day, Evening, and Night
periods can be programmed.
If enabled, the supply fan operation can be programmed
for On or Auto operation for each programmed period.
If Yes is selected, the space temperature of the remote
sensor will appear on the display and will be communicated
to the unit controller.
Adjustable in 1-day increments. The check filter symbol
flashes when the accumulated run time is greater than the
programmed setting.
14BAS-SVX17B-EN
Page 15
Configuration
Table 3.Configuration options for sensors used with constant-volume (CV) or heat pump (HP) units (continued)
Option
number
13
14Keypad lockout
15
16
17Baud rate
18Default cooling setpoint45–98ºF (7.2–36.7ºC)74
19Default heating setpoint 43–96ºF (6.1–35.6ºC)68
20
21
22
Function Option valueDefault Description
Display zone
temperature
Default temporary
override timer setting
Zone temperature
calibration
Minimum cooling
setpoint
Maximum heating
setpoint
Minimum setpoint
deadband
0 = No
1 = Yes
0 = Disabled
1 = Enabled
1, 2, 3, 4, 5 (hours)3Sets the default temporary override time in hours.
Displays current temperature
reading with any offsets:
Allows for field calibration in 0.1ºF (0.6ºC) increments of
either the internal sensor on the sensor, or the remote
sensor if used.
(0
Important: Apply power to the sensor for 60 minutes before
If no setpoint has been programmed or the program is
lost, the value that is set becomes the operation setpoint.
If no setpoint has been programmed or the program is
lost, the value that is set becomes the operation setpoint.
If no setpoint has been programmed or the program is
lost, the value that is set becomes the operation setpoint.
If no setpoint has been programmed or the program is
lost, the value that is set becomes the operation setpoint.
If no setpoint has been programmed or the program is
lost, the value that is set becomes the operation setpoint.
Sets the minimum programmable cooling temperature
setpoint.
Sets the maximum programmable heating temperature
setpoint.
Sets the minimum programmable cooling temperature
setpoint.
Sets the maximum programmable heating temperature
setpoint.
Sets the maximum programmable heating temperature
setpoint.
Sets the minimum difference between the heating and
0
cooling setpoints.
calibrating.
Configuration
BAS-SVX17B-EN17
Page 18
.
.
Mo
AM
Keypad
Occupancy indicator
Tem p e rat u re
System setting
Fan sett ing
Day and clock
Operation
This section describes sensor operations, explains sensor symbols, and provides the default
settings.
Set-up Procedures
The following procedures show how to set up the programmable zone sensor for operation using
the keypad and display. Procedures begin at the home screen (see Figure 5).
Figure 5.Programmable zone sensor showing an example of the home screen on the display
Changing the System Setting
System in cooling mode
System in heating mode
Emergency heat (HP only). Used by facility
operators or service technicians only.
System Auto. The system automatically switches
18BAS-SVX17B-EN
between heating and cooling as needed.
System Off.
1. From the home screen, select the system setting by
pressing twice.
2. Press or to select the desired system setting.
3. To confirm your setting, press or wait 10 seconds.
The home screen will apprear.
Page 19
Changing the Fan Setting (CV/HP Configuration only)
.
.
Mo
AM
Operation
Fan Auto: The fan automatically
powers On and Off as needed to reach
the selected temperature.
Fan On: Fa n is powered On.
Setting the Time Clock and the Day
Day of week and time clock
1. From the home screen, select the fan setting by pressing
twice and then .
2. Press or to select the desired fan setting.
Note: The sensor can be configured for programmable fan
operation (see Table 3, p. 14). If this feature is enabled,
fan operation is controlled by the schedule. If you
attempt to change the fan setting, the sensor display will
change to temporary override set-up. Follow the
procedure in “Temporary Override Set-up (CV/HP only),”
p. 22 to override the fan setting.
3. To confirm your setting, press or wait 10 seconds. The
home screen will appear.
1. From the home screen, select the time clock and day
setting by pressing twice and then three times.
2. Press or to select the hour. The hour flashes.
3. Press or to change the hour.
4. Press to select the minutes. The minutes flash.
5. Press or to change the minutes.
6. Press to select the days of the week. All days of the
week appear, and the currently selected day flashes.
7. Press or to change the day.
8. To confirm your settings, press for 2 seconds, or wait
10 seconds. The home screen will appear.
BAS-SVX17B-EN19
Page 20
Mo Tu
We Th Fr SatSu
Mo Tu
We Th Fr SatSu
Operation
Scheduling
Morning, Day, Evening, Night
1
The programmable zone sensor has a feature that “copies” the schedule for one of the five
weekdays to the other four weekdays, and one of the two weekend days to the other weekend day.
To use this feature, the sensor must be configured for 7 programmable days per week and
scheduling must be completely blank. If you set a complete schedule for any one weekday, that
schedule will be copied to the other four weekdays. If you set a complete schedule either Saturday
or Sunday, the schedule will be copied to the other weekend day. You can modify each day
individually, as necessary.
Notes:
•To erase all scheduling, select scheduling and press the Test/Configuration button for 2 seconds.
Scheduling
setting selected
Days of week
selected
1. From the home screen, select the scheduling setting by pressing
twice and then two times.
2. Press or to select the days of the week. All days of the week
appear and Monday flashes.
3. Press or to select the day you want to schedule.
Period of day
selected
4. Press to select the period of the day. All periods appear, and
the first period (morning) flashes.
5. Press or to select the period of the day you want to schedule.
Period start time
selected
6. Press or to select the period start time. The selected period
start time flashes (or dashes flash if nothing has been set).
7. Press or to change the period start time.
Occupancy
setting selected
8. Press to select occupancy. Both occupancy symbols appear
and the selected symbol flashes.
9. Press or to select the occupancy setting you want for the
period you are scheduling.
Heating setpoint
selected
10.Press to select the heating setpoint. The bottom arrow of the
setpoint symbol and the heating symbol flash. The current
heating setpoint appears (or dashes if nothing has been set).
11. Press or to change the heating setpoint for the period
you are scheduling.
1
For VAV occupied periods, refer to “Scheduling for VAV Occupied Periods,” p. 21
20BAS-SVX17B-EN
Page 21
Operation
Cooling setpoint
selected
12.Press to select the cooling setpoint. The top arrow of the
setpoint symbol and the cooling symbol flash. The current
cooling setpoint appears (or dashes if nothing has been set).
13.Press or to change the cooling setpoint for the period
you are scheduling.
Fan Auto
14.Press to select the fan setting. The fan setting appears and
the currently selected fan setting flashes.
Note: CV/HP only, and only if the programmable fan option is enabled.
Fan On
15.Press or to select the fan setting for the period you are
scheduling.
16. To confirm your schedule settings, press and hold for 2
seconds, or wait 30 seconds. The home screen will appear.
Scheduling for VAV Occupied Periods
Occupancy setting
selected
Warm-up setpoint
selected
1. Follow steps 1—8 of the procedure described in “Scheduling,”
2. Press or to select the occupied setting.
3. Press to select the warm-up setpoint. The bottom current
4. Press or to change the setpoint.
p. 20.
period will flash.
Note: Only if the heat installed option is enabled.
Supply air heating
setpoint selected
5. Press to select the supply air heating setpoint. The bottom
arrow of the setpoint symbol, the heating symbol, and the fan
and arrow outlines all flash.
Note: Only if the modulated heat option is enabled.
6. Press or to change the setpoint.
Supply air cooling
setpoint selected
7. Press to select the supply air cooling setpoint.The top
arrow of the setpoint symbol, the cooling symbol, and the fan
and arrow outlines all flash.
8. Press or to change the setpoint.
9. To confirm your schedule settings, press and hold for 2
seconds, or wait 30 seconds. The home screen will appear.
BAS-SVX17B-EN21
Page 22
DAYS
HOURS
Operation
Temporary Override Set-up (CV/HP only)
To override a setting for a specified period of time, start at the home screen and proceed
as follows:
The heating setpoint symbol
flashes when selected.
The cooling setpoint symbol
flashes when selected.
The override symbol flashes
throughout the temporary
override set-up operation.
1. Press or . The current temperature setpoint
appears.
2. Within 5 seconds of Step 1, press to raise the
setpoint or to lower the setpoint. The thermostat
enters timed override mode, giving you the
opportunity to specify the other parameters of the
override.
•The override symbol flashes, and continues
flashing throughout the procedure.
•Either the heating or cooling setpoint symbol
flashes.
Note: The current zone temperature determines whether
the heating or cooling setpoint symbol appears first.
3. Press or to toggle between the heating and
cooling setpoints.
4. Press or to increase or decrease the heating
or cooling setpoint.
The fan setting flashes when
selected.
The time setting for override
set-up.
The occupancy setting flashes
when selected.
The temporary override
symbol appears on the display
and stays on while an override
is present.
5. To override the fan setting, press (if starting from
the heating setpoint, press twice). Press or to
change between Auto and On.
Note: Only if the programmable fan option is enabled.
6. Press to specify the amount of time the override
las ts. Pres s o r t o se lec t th e nu mbe r of hou rs .
If your override time is over 23 hours, press or to
select days. Press or to select the number of
days.
7. To override occupancy, press (if starting from
days, press twice). The occupancy symbol flashes.
Press or to change between occupied and
unoccupied.
8. To confirm your override settings, press and hold
2 seconds, or wait 15 seconds. The home screen
appears with the override symbol on it.
Note: To delete override settings, select temporary override
set-up and press the Test/Configuration button. The
home screen appears without the override symbol.
22BAS-SVX17B-EN
Page 23
Locking or Unlocking the Keypad
.
.
AM
You can lock or unlock the keypad to prevent changes as follows:
Operation
Locked symbol
Status Inputs
If the service symbol appears, the system requires service.
If the colon on the time clock is flashing, the system is powered up.
If the cooling symbol is flashing, the system is in cooling mode.
If the heating symbol is flashing, the system is in heating mode.
Default Operation
1. Begin at the home screen.
2. Press and simultaneously for 4 seconds.
The locked symbol appears on the display if the keypad is locked.
If you press a keypad button, the locked symbol flashes three
times.
If the sensor has not been scheduled, it operates with the following default settings:
•For sensors configured to operate with CV or HP units:
– Occupied
– Heating setpoint: 68ºF (20ºC)
– Cooling setpoint: 74ºF (23.3ºC)
•For sensors configured to operate with VAV units:
– Occupied
– Warm-up setpoint: 68ºF (20ºC)
– Supply-air heating setpoint: 100ºF (37.8ºC)
– Supply-air cooling setpoint: 55ºF (12.8ºC)
BAS-SVX17B-EN23
Page 24
Indicates that setpoints
are on display and not
space temperature
Operation
Setpoint Only Display
You can configure the zone sensor to present setpoints instead of the space temperature on the
main display. To display setpoints instead of space temperatures, follow these steps:
1. Begin at the home screen
2. Press the and simultaneously for four seconds. The active setpoint now appears
instead of the space temperature. Setpoint presentation is indicated by an arrow in the upper
left corner of the display (see Figure 6).
3. Press
4. To return to showing space temperature on the display, press the and
Figure 6. Setpoint only display
or to toggle between the heating and cooling setpoints.
simultaneously for four seconds.
Weekly Operating Schedule Forms
Figure 7. Sequential completion of a weely operating schedule.
24BAS-SVX17B-EN
The easiest scheduling procedure is sequential. You should complete the schedule setup for each
period of the day, in order, before you move on to the next day. For instance (refer to Figure 7
below), once the schedule is opened, you will start with Monday and the Morning period (1). Set
the start time, occupancy, heating and cooling setpoints, and fan operation if applicable. Once you
finish with the morning period, you will complete the Day period (2)(same settings as for
Morning...start time, occupancy, etc.). You should complete all available periods for Monday before
moving on to Tuesday (5). The same rules apply for Tuesday. Each period should be set in order
before moving on to Wednesday. This applies to all days in the schedule.
You can use Table 5, p. 25 to create a weekly operating schedule for sensors configured for CV or
HP units. For sensors configured as VAV, see Tab l e 6 , p. 26 .
Page 25
Table 5.Weekly operating schedule for sensors configured for CV or HP units
Operation
DayPeriodStart timeOccupancy
Morning :°°Auto On
Monday
Tuesday
Wedn esday
Thursday
Friday
Saturday
Sunday
(1)Applies to CV/HP only and only if the programmable fan is enabled.
Day :°°Auto On
Evening :°°Auto On
Night :°°Auto On
Morning :°°Auto On
Day :°°Auto On
Evening :°°Auto On
Night :°°Auto On
Morning :°°Auto On
Day :°°Auto On
Evening :°°Auto On
Night :°°Auto On
Morning :°°Auto On
Day :°°Auto On
Evening :°°Auto On
Night :°°Auto On
Morning :°°Auto On
Day :°°Auto On
Evening :°°Auto On
Night :°°Auto On
Morning :°°Auto On
Day :°°Auto On
Evening :°°Auto On
Night :°°Auto On
Morning :°°Auto On
Day :°°Auto On
Evening :°°Auto On
Night :°°Auto On
Heating
setpoint
Cooling
setpointFan
(1)
BAS-SVX17B-EN25
Page 26
Operation
Ta bl e 6 can be used to create a weekly operating schedule for sensors configured for VAV units.
Table 6.Weekly operating schedule for sensors configured for VAV units
DayPeriodStart timeOccupancy
Morning :°°°
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Day :°°°
Evening :°°°
Night :°°°
Morning :°°°
Day :°°°
Evening :°°°
Night :°°°
Morning :°°°
Day :°°°
Evening :°°°
Night :°°°
Morning :°°°
Day :°°°
Evening :°°°
Night :°°°
Morning :°°°
Day :°°°
Evening :°°°
Night :°°°
Morning :°°°
Day :°°°
Evening :°°°
Night :°°°
Morning :°°°
Day :°°°
Evening :°°°
Night :°°°
Warm-up
or unoccupied
heating
setpoint
Supply air or
unoccupied
cooling
setpoint
Supply air heat
setpoint
(modulating
heat only)
26BAS-SVX17B-EN
Page 27
Maintenance and Troubleshooting
This section describes maintenance and troubleshooting for the programmable zone sensor.
Error Codes
An error code indicates that technical assistance may be required.
Note: On the display, error codes toggle with the clock.
Heat failure
Cool failure
Tes t m od e
Fan fail ure
Conducting a Self-Test
Starting from the home screen, press the Test/Configuration button. The following sequence
appears on the display:
•The display lights up.
•All of the symbols appear for 2 seconds.
•The software version appears for 2 seconds.
•The number of years in service appears for 2 seconds.
•The home screen appears and the light dims.
Check Filter Timer
Check filter interval is a configuration option that allows you to set a timer that is adjustable in 1day increments. After the number of selected days passes, the check filter time symbol will flash
on the display: . The symbol is a reminder to check the condition of the filter.
To reset the timer, press both and for 2 seconds. The check filter symbol will disappear.
Indicates that there is an error in the heating system.
Indicates that there is an error in the cooling system.
Indicates that the system is operating in test mode.
Indicates that a fan failure has occurred and service is required.
BAS-SVX17B-EN27
Page 28
Maintenance and Troubleshooting
Troubleshooting Table
ProblemSolution
Display does not come on.
No communication to the unit controller.
SH appears in the temperature location on the display and
“Off” flashes.
OP appears in the temperature location on the display and
“Off” flashes.
Zone temperature does not appear.
Keypad does not respond.
The fan is set to the On position, but the fan is not running
(CV/HP configurations only).
The system is operating before the scheduled period begins
(CV/HP configurations only).
The check filter symbol flashes.
The number “99” flashes.Space temperature is above the measurable range.
The number “32” flashes.Space temperature is below the measurable range.
Check the 24 Vac power supply at terminals 11 and 14 at the sensor. Verify that
the terminal block is properly positioned on its pins.
Check for 22–32 Vdc between terminals 11 and 12 at the sensor. Check wiring if
no voltage is present.
Verify that Option 11 is set correctly for CV/HP configurations (option 10 for VAV
configurations):
• If set to 1, check the wiring from the remote sensor at terminals S1 and S2 for
a shorted condition.
• If set to 0, the on-board thermistor has shorted and the sensor must be
replaced.
Verify that option 11 is set correctly for CV/HP configurations (option 10 for VAV
configurations):
• If set to 1, check the wiring from the remote sensor at terminals S1 and S2 for
an open circuit condition.
• If set to 0, the on-board thermistor is open and the sensor must be replaced.
Verify that option value 1 has been selected for option 13 (CV/HP configurations).
Verify that option value 1 has been selected for option 12 (VAV configurations).
Check to see if the lock symbol is on. To unlock the keypad, press and hold the
left and right arrow keys for 4 seconds.
Verify that the value for option 10 is set correctly (CV/HP configurations only).
• If set to 1, check that the fan is set to On for the current period of day.
• If set to 0, check the value for Option 6. If it is set to 1, the fan will always
operate in Auto mode for unoccupied periods.
If option 7 is set to 1, the computed recovery option is enabled. This allows system
operation to begin before the scheduled occupied period, so that the occupied
temperature setpoint is reached efficiently.
To reset the timer, press the up and down arrows for 2 seconds. The check filter
symbol will disappear. If this function is not desired, or a different interval is
desired, set option 11 (VAV configurations) or option 12 (CV/HP configurations)
to a different value.
28BAS-SVX17B-EN
Page 29
Specifications
Sensor operating temperature32 to 122ºF (0 to 50ºC)
Storage temperature–67 to 176ºF (–55 to 80°C)
Storage and operating humidity range5% to 95%, non-condensing
Accuracy±2.0°F (±1.1°C) over a range of 50 to 90°F (10 to 32°C)
Resolution0.225ºF (0.2°C) over a range of 50 to 90ºF (10 to 32°C)
Setpoint functional range43 to 98ºF (6.1 to 36.6ºC)
Input voltage (from unit controller)Nominal 24 Vac (18–32 Vac)
Power consumption<3 VA
HousingPolycarbonate/ABS blend, UV protected, UL 94-5VA
Mounting3.24 in (8.26 cm) for 2 mounting screws (supplied)
±4.0°F (±2.2°C) when outside this range
0.40ºF (0.125°C) when outside this range
flammability rating, suitable for application in a plenum
BAS-SVX17B-EN29
Page 30
Declaration of CE Conformity
Manufacturer name:
Manufacturer address:
The manufacturer hereby declares that the product:
Product name:
Model numbers:
Conforms to the following standards or other normative documents:
Electromagnetic Emission:
(by Council Directive 89/336/EEC)Radiated EN55011:20062006 Class B limit
Electromagnetic Immunity for Industrial:
(by Council Directive 89/336/EEC)EN61000-4-2:2006±4.0 kV by contact
Societ
1, rue des Ameriques, B.P. 6
F-88191 Golbey Cedex, France
Phone: (33) 329.31.73.00
Fax: (33) 329.81.24.98
Where and When Issued:
Mark of Compliance:
EN61000-4-4:2006
EN61000-4-5:2006
EN61000-4-6:20063 V
EN61000-4-11:2006
Elecromagentic Emmission07/18/2008
Elecromagentic Immunity07/18/2008
This document valides CE conformity of the Programmable Zone Sensor module.
30BAS-SVX17B-EN
Page 31
Notes:
Declaration of CE Conformity
BAS-SVX17B-EN31
Page 32
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the
leader in creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad
portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more
information, visit www.Trane.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.