Honeywell VISTA-10PSIA, VISTA-10P User Manual

0 (0)

ADEMCO VISTA-10P

ADEMCO VISTA-10PSIA

Security Systems

Installation and Setup Guide

K0735V3 10/04 Rev. B

RECOMMENDATIONS FOR PROPER PROTECTION

The Following Recommendations for the Location of Fire and Burglary Detection Devices Help Provide Proper Coverage for the Protected Premises.

Recommendations For Smoke And Heat Detectors

With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations contained in the National Fire Protection Association's (NFPA) Standard #72 noted below.

Early warning fire detection is best achieved by the installation of fire detection equipment in all rooms and areas of the household as follows: For minimum protection a smoke detector should be installed outside of each separate sleeping area, and on each additional floor of a multi-floor family living unit, including basements. The installation of smoke detectors in kitchens, attics (finished or unfinished), or in garages is not normally recommended.

For additional protection the NFPA recommends that you install heat or smoke detectors in the living room, dining room, bedroom(s), kitchen, hallway(s), attic, furnace room, utility and storage rooms, basements and attached garages.

In addition, we recommend the following:

Install a smoke detector inside every bedroom where a smoker sleeps.

Install a smoke detector inside every bedroom where someone sleeps with the door partly or completely closed. Smoke could be blocked by the closed door. Also, an alarm in the hallway outside may not wake up the sleeper if the door is closed.

Install a smoke detector inside bedrooms where electrical appliances (such as

 

KITCHEN

TV ROOM

KITCHEN

DINING

BDRM

DINING

BEDROOM BEDROOM

 

 

 

 

 

 

 

 

LIVING ROOM

BDRM

 

 

 

 

LIVING ROOM

 

 

 

BEDROOM

BEDROOM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Smoke Detectors for Minimum Protection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Smoke Detectors for Additional Protection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BEDROOM

 

 

Heat-Activated Detectors

BEDROOM

TO

BEDROOM

 

 

BR

 

 

 

 

 

 

 

 

KTCHN

 

GARAGE

LVNG RM

 

.

CLOSED

 

 

 

 

 

DOOR

 

BASEMENT

 

 

 

 

 

 

 

 

floor_plan-001-V0

portable heaters, air conditioners or humidifiers) are used.

Install a smoke detector at both ends of a hallway if the hallway is more than 40 feet (12 meters) long.

Install smoke detectors in any room where an alarm control is located, or in any room where alarm control connections to an AC source or phone lines are made. If detectors are not so located, a fire within the room could prevent the control from reporting a fire or an intrusion.

THIS CONTROL COMPLIES WITH NFPA

REQUIREMENTS FOR TEMPORAL PULSE

SOUNDING OF FIRE NOTIFICATION

APPLIANCES.

Recommendations For Proper Intrusion Protection

For proper intrusion coverage, sensors should be located at every possible point of entry to a home or commercial premises. This would include any skylights that may be present, and the upper windows in a multi-level building.

In addition, we recommend that radio backup be used in a security system so that alarm signals can still be sent to the alarm monitoring station in the event that the telephone lines are out of order (alarm signals are normally sent over the phone lines, if connected to an alarm monitoring station).

ii

Table Of Contents

• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •

Features and Installation Highlights ...............................................................................................

1-1

Capabilities.............................................................................................................................................

1-1

Functions..............................................................................................................................................

1-1

Compatible Devices..............................................................................................................................

1-1

Important Installation Highlights (Installer Please Read)...............................................................

1-2

Mounting and Wiring the Control.....................................................................................................

2-1

Cabinet and Lock .................................................................................................................................

2-1

Mounting the PC Board Alone (no RF Receiver)................................................................................

2-1

Mounting Board with RF Receiver .....................................................................................................

2-2

Wiring to Keypads ...............................................................................................................................

2-3

Sounder (Bell) Connections.................................................................................................................

2-4

Wiring the AC Transformer ................................................................................................................

2-4

Backup Battery ....................................................................................................................................

2-4

Earth Ground.......................................................................................................................................

2-5

Hardwire Zones....................................................................................................................................

2-6

Smoke Detectors ..................................................................................................................................

2-6

Installing the RF Receiver ..................................................................................................................

2-7

Installing a 5800TM Module...............................................................................................................

2-7

Installing the Transmitters.................................................................................................................

2-8

Installing a Keyswitch.........................................................................................................................

2-8

Connecting Relay Modules..................................................................................................................

2-9

On-Board Triggers.............................................................................................................................

2-10

Phone Line/Phone Module Connections ...........................................................................................

2-10

Long Range Radio Connections ........................................................................................................

2-11

AAV Connections ...............................................................................................................................

2-12

Programming Overview ......................................................................................................................

3-1

About Programming ............................................................................................................................

3-1

Keypads ................................................................................................................................................

3-1

Wireless Receiver, Transmitters, and Wireless Keys (keyfobs) ........................................................

3-2

Pager Programming.............................................................................................................................

3-2

Function Keys ......................................................................................................................................

3-2

Output Devices.....................................................................................................................................

3-2

Zone Type Definitions..........................................................................................................................

3-3

Mechanics of Programming.................................................................................................................

3-5

Data Field Programming.....................................................................................................................

4-1

About Data Field Programming..........................................................................................................

4-1

Programming Data Fields...................................................................................................................

4-1

System Setup Fields ............................................................................................................................

4-1

Zone Sounds & Timing ........................................................................................................................

4-2

Dialer Programming............................................................................................................................

4-3

System Status Report Codes ...............................................................................................................

4-4

Miscellaneous System Fields ..............................................................................................................

4-6

Pager Programming Fields .................................................................................................................

4-8

Miscellaneous System Fields ..............................................................................................................

4-8

Configurable Zone Type Programming Fields ...................................................................................

4-9

Keypad Programming Fields ............................................................................................................

4-11

iii

Table Of Contents

• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •

Menu Mode Programming...................................................................................................................

5-1

Zone Programming Overview ( 56 and 58 Menu Modes)................................................................

5-1

56 Zone Programming Procedure......................................................................................................

5-1

58 Expert Programming Mode Procedures ......................................................................................

5-3

Wireless Key Programming Templates ..............................................................................................

5-4

Output Device Programming Overview (*79/*80 Menu Mode).........................................................

5-6

*79 Menu Mode: Output Device Mapping..........................................................................................

5-6

*80 Menu Mode: Defining Output Functions.....................................................................................

5-7

Zone List Overview ( 81 Menu Mode) ................................................................................................

5-9

Zone List Programming.......................................................................................................................

5-9

Function Key Programming Overview ( 57 Menu Mode) ...............................................................

5-10

Programming Function Keys ............................................................................................................

5-10

About Descriptor Programming Overview ( 82 Menu Mode) .........................................................

5-11

Programming Zone Descriptors (Menu mode 82) ..........................................................................

5-11

Adding Custom Words.......................................................................................................................

5-12

Programming Installer and User Schedules....................................................................................

5-14

System Communication and Operation...........................................................................................

6-1

System Communication Overview......................................................................................................

6-1

Report Code Formats...........................................................................................................................

6-1

Ademco Contact ID® ...........................................................................................................................

6-3

User Security Codes.............................................................................................................................

6-4

Keypad Functions ................................................................................................................................

6-5

Various System Trouble Displays.......................................................................................................

6-6

Testing the System................................................................................................................................

7-1

About Test Procedures.........................................................................................................................

7-1

System Test..........................................................................................................................................

7-1

Checking Transmitter Enrollment (Sniffer Mode) ............................................................................

7-1

Go/No Go Test Mode ............................................................................................................................

7-2

Dialer Communication Test ................................................................................................................

7-2

Automatic Standby Battery Tests.......................................................................................................

7-2

Specifications & Accessories ..............................................................................................................

8-1

Security Control...................................................................................................................................

8-1

Compatible Devices..............................................................................................................................

8-1

5800 Series Transmitter Input Loop Identification...........................................................................

8-2

Regulatory Agency Statements..........................................................................................................

9-1

Limitations and Warranty.................................................................................................................

10-1

iv

S E C T I O N 1

Features and Installation Highlights

• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •

SIA Installations: The VISTA-10PSIA is a certified SIA-compliant control that meets SIA specifications for False Alarm Reduction. The VISTA-10P is not certified as SIA compliant, but can be programmed for False Alarm Reduction. To program for False Alarm Reduction, follow the SIA Guidelines noted in the applicable programming fields.

Capabilities

Up to 22 zones plus eight keyfob zones (zones 49-56) for total of 30 zones:

--Six basic hardwired zones (zone 1-6)

--Supports up to 16 wireless transmitter zones (5800 series; zones 9-24)

--Supports one configurable zone type

Up to 16 security codes, each with separate authority levels

Supports Downloading: Via an IBM compatible computer, Compass downloading software, and a compatible HAYES or CIA modem specified by Ademco.

Functions

Single-button arming feature: Can use dedicated keys to arm the system AWAY or STAY

Up to two schedules (1 installer, 1 end-user), to control devices and/or auto-arm/disarm the system

One keypad macro, which can simplify a long command string (e.g., bypassing zones before arming)

Paging feature allows certain system conditions to be reported to one pager phone number; can use a dedicated key on keypads to send a signal to the pager

Event Logging records up to 32 selected events in a history log; control and readout from the log is done via Ademco Compass Downloader software or installer/master code at Keypad

Zone descriptors for all zones (useful only when using Alpha keypads and/or the 4285/4286 Phone Module).

Optional bell supervision detects external sounder wiring short or open; causes a trouble condition, keypad display, and sends a report to the central monitoring station, if enabled.

Optional RF jam detection for wireless systems detects a condition that may impede proper RF reception (i.e., jamming or other RF interference); causes keypad display, and sends a report to the central monitoring station (if trouble reporting is enabled).

Compatible Devices

Up to eight Addressable Keypads: 6150 Fixed-Word Keypad, 6160 Alpha Keypad, 6150V FixedWord Display Voice Keypad, 6160V Alpha Display Voice Keypad, 6150RF Keypad/Transceiver

Supports 5881 series receiver and 5800 series transmitters

Up to four output relays (4204) plus two on-board triggers (does not support Powerline Carrier Devices) -- Up to 12 output functions.

Ademco 4285/4286 Phone Module; provides access to the system via on premises or off-premises phones for arming, disarming, etc., plus control of relay outputs.

Audio Alarm Verification (using AAV module, such as ADEMCO UVS); can be used in conjunction with an output trigger to permit voice dialog between an operator at the central station and a person at the premises.

Alarm output provides a 12VDC, 2 AMP output that can drive the compatible sounders; steady output for burglary/panic, or temporal pulse (3 pulses – pause – 3 pulses – pause – 3 pulses. . .) for fire. Uses current limiting circuitry for protection.

Auxiliary Power Output: 12VDC, 600 mA maximum (uses fuse for protection).

Backup Battery: Rechargeable (sealed lead-acid type) 12VDC, 4AH minimum.

Long Range Radio: Primary telephone number messages can be reported via ECP connection to various Long Range Radios (check compatibility and availability of specific models)

AC Power Supply: Plug-in 120VAC transformer, ADEMCO 1321 (1321CN in Canada)

1-1

Installation and Setup Guide

NOTE: All devices and accessories used in a Canadian installation must be Listed for use in Canada.

Important Installation Highlights (Installer Please Read)

This system uses addressable keypads and Relay Modules (see table of addresses in Programming Overview section).

Keypads must be set for addresses 16-23 (first keypad is address 16, which is different from previous controls) and programmed in data fields *190-*196.

4204 Relay Modules must be set for specific address 12 (see Connecting Relay Modules section).

Relays have two programming menu modes: Use *79 Menu mode to map module addresses and device (output) numbers. Use *80 Menu mode to define the output functions (see Output Device Programming section).

This system supports programmable function keys. Use *57 Menu mode to define the function keys (see Function Key Programming section).

This system provides various paging features. Refer to the Programming Overview section for a summary on pager programming.

1-2

S E C T I O N 2

Mounting and Wiring the Control

• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •

Cabinet and Lock

1.Mount the control cabinet to a sturdy wall in a clean, dry area, which is not readily accessible to the general public, using fasteners or anchors (not supplied) with the four cabinet mounting holes.

2.Remove cabinet door, then remove the lock knockout from the door. Insert the key into the lock.

3.Position the lock in the hole, making certain that the latch will make contact with the latch bracket when the door is closed. When correctly positioned, push the lock until it is held securely by its snap tabs.

NOTES

The cabinet can be closed and secured without a lock by using 2 screws in the cover's edge.

CHECK

SNAP

POSITION

TAB

LOCKED

PUSH

 

 

ADEMCO

 

SNAP

UNLOCKED

TAB

CABINET DOOR

STEP 1

BOTTOM

 

PUSH

 

ON LOCK

 

UNTIL IT

IS SEATED

SECURELY

ADEMCO

 

STEP 2

lock snap-001-V0

 

cab

Figure 1. Installing the Cabinet Lock

Mounting the PC Board Alone (no RF Receiver)

1.Hang two short mounting clips (provided) on the raised cabinet tabs (see Detail B in Fig. 2).

2.a. Insert the top of the circuit board into the slots at the top of the cabinet. Make sure that the board rests on the correct row (see Detail A).

b.Swing the base of the board into the mounting clips and secure the board to the cabinet with the accompanying screws (see Detail B).

NOTES

Before installing the cabinet's contents, remove the metal cabinet knockouts required for wiring entry. Do not remove the knockouts after the circuit board has been installed.

CIRCUIT

CABINET

BOARD

 

CIRCUIT

 

BOARD

 

+

+

CABINET

DETAIL B

 

SIDE VIEW

DETAIL A

OF MOUNTING

SIDE VIEW

CLIPS

OF BOARD

 

SUPPORTING

 

SLOTS

 

MOUNTING-001-V0

Figure 2. Mounting the PC Board

2-1

Installation Instructions

Mounting Board with RF Receiver

1.a.Remove the receiver board from its case, then insert the top of the board into the slots at the top of the cabinet, as shown in Detail A in Figure 3. Make sure that the board rests on the correct row of tabs.

b.Swing the base of the board into the mounting clips and secure it to the cabinet with the accompanying screws.

c.Insert the top of the control's board into the slot in the clips and position two clips at the lower edge of the board.

d.Swing this board into place and secure it with two additional screws.

2.Insert grounding lugs (supplied with the receiver) through the top of the cabinet into the lefthand terminals of the antenna blocks (at the upper edge of the receiver board) and secure them to the cabinet top with the screws provided, as shown in Detail B.

3.Insert the receiver's antennas through the top of the cabinet, into the blocks' right-hand terminals, and tighten the screws.

NOTES

Do not mount the cabinet on or near metal objects. This will decrease RF range and/or block RF transmissions from wireless transmitters.

Do not locate the cabinet in an area of high RF interference (revealed by frequent or prolonged lighting of the LED in the receiver after it is operational (random flicker is OK)

CABINET

A

B

 

CABINET

BOARD

RECEIVER CIRCUIT BOARD SUPPORTING

SLOTS

+

+

 

CIRCUIT

 

BOARD

 

MOUNTING

 

CLIP

CONTROL

CIRCUIT

BOARD

 

DETAIL A

MOUNTING

SIDE VIEW

CLIP

OF BOARD -

SUPPORTING SLOTS

INSTALLATION WITH RECEIVER CIRCUIT BOARD

WHITE

BLACK

RED

MOUNTING

MOUNTING

MOUNTING

CLIP

CLIP

CLIP

NOTE

A COMBINATION OF THESE MOUNTING CLIPS HAS BEEN INCLUDED IN YOUR INSTALLATION KIT.

USE THE APPROPRIATE CLIPS FOR MOUNTING.

IF NO RF RECEIVER IS USED, MOUNT THE PC BOARD USING EITHER THE WHITE OR BLACK CLIPS, WHICHEVER ARE INCLUDED IN THE CONTROL PANEL'S HARDWARE KIT.

ANTENNA

(2)

SCREW

(2)

GROUNDING LUG

(2)

ANTENNA

MOUNT

(2 PLACES)

DETAIL B

ANTENNA AND GROUNDING

LUG INSTALLATION

pc_mount-001-V1

Figure 3. Mounting the PC Board and RF Receiver

2-2

Mounting and Wiring the Control

Wiring to Keypads

1.Connect keypads to the keypad terminals as shown on the Summary of Connections diagram. Determine wire size using the Wire Run Chart below.

2.Set keypad addresses. Refer to the address setting instructions included with the keypads and set each keypad device address according to the chart at right.

3.Program the keypad addresses and sound options in data fields *190-*196. IMPORTANT: Each keypad must be assigned a unique address, starting at address 16. Keypads programmed with the same address will give unpredictable results.

Supplementary Power (optional)

1.Connect as shown. Be sure to connect the negative (–) terminal on the power supply unit to terminal 4 (AUX –) on the control.

NOTES

Typical Fixed-Word Display: 6150

Typical Alpha Display: 6160

Voice Keypads: 6150V, 6160V

The system supports up to 8 keypads (see program fields *190-*196).

For single 4-wire runs, determine the current drawn by all units, then refer to the Wiring Run chart to determine the maximum length that can be safely used for each wire size.

Use supplementary power if the control’s aux. power load for all devices exceeds 600mA. Suggested power supply: AD12612

SUPPLEMENTARY

CONTROL TERMINAL STRIP

POWER SUPPLY

 

 

 

 

+

AUX. AUX. DATA DATA

 

 

 

 

+

IN

OUT

 

 

4

5

6

7

WIRERED

 

WIREGRN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WIREBLK

WIREYEL

 

 

 

 

 

WIRERED

 

WIREGRN

 

 

DIRECTLY TO

WIREBLK

 

 

WIREYEL

 

 

 

 

 

IMPORTANT:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MAKE THESE

 

 

 

 

 

 

 

 

 

 

KEYPADTO

KEYPADTO

KEYPADTO

KEYPADTO

CONNECTIONS

KEYPADTO

 

KEYPADTO

 

KEYPADTO

KEYPADTO

V0-supplypwrsupp

SCREW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TERMINALS AS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHOWN.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Keypad Addresses

 

 

 

Keypad

Address

Keypad

Address

Figure 4. Using a Supplementary Power Supply

no. 1

16**

no. 5

20

 

no. 2

17

no. 6

21

 

no. 3

18

no. 7

22

 

no. 4

19

no. 8

23

 

** The first keypad is address 16, which is always enabled and set with all sounds on.

UL Use a UL Listed, battery-backed supply for UL installations. The battery supplies power to these keypads in case of AC power loss.

The battery-backed power supply should have enough power to supply the keypads with the UL required minimum standby power time.

Keypads powered from supplies that do not have a backup battery will not function if AC power is lost. Make sure to power at least one keypad from the control’s auxiliary power output.

Wire Run Chart For Devices* Drawing Aux Power From The Control (12V+ & 12V–)

Wire

TOTAL CURRENT DRAWN BY ALL DEVICES CONNECTED TO A SINGLE WIRE RUN

Size

50 mA or less

100 mA

300 mA

500 mA

600 mA

#22

900 ft (274m)

450 ft (137m)

150 ft (46m)

90 ft (27m)

75 ft (23m)

#20

1400 ft (427m)

700 ft (213m)

240 ft (73m)

140 ft (43m)

120 ft (37m)

#18

1500 ft (457m)

1100 ft (335m)

350 ft (107m)

220 ft (67m)

170 ft (52m)

#16

1500 ft (457m)

1500 ft (457m)

550 ft (168m)

350 ft (107m)

270 ft (82m)

* Includes Keypads, RF Receivers, Zone Expander/Relay Units, 4285/4286 Phone Module, and LRR.

Maximum wire lengths for any device that is homerun to the control can also be determined from the Wiring Run Chart, based on the current draw of that device alone.

The length of all wire runs combined must not exceed 1500 feet (457m) when unshielded quad conductor cable is used (750 feet if shielded cable is used). This restriction is due to the capacitive effect on the data lines when quad cable is used.

2-3

Installation Instructions

Sounder (Bell) Connections

1.Make sounder connections to alarm output terminals 3 (+) and 4 (–).

For supervised output, continue with steps 2 and 3.

2.Cut the red Bell Supervision Jumper located above terminals 2 and 3 on the control board.

3.Connect a 2k ohm resistor across the terminals of the last sounder.

This control complies with NFPA requirements for temporal pulse sounding of fire notification appliances. Temporal pulse sounding for a fire alarm consists of:

3 pulses – pause – 3 pulses – pause – 3 pulses–etc..

NOTES

TERMINALS ON

EXTERNAL ALARM

 

 

CONTROL BOARD

SOUNDER

 

 

4

 

 

 

ALARM

 

2000

 

OBSERVE

OHM

 

OUTPUT

 

POLARITY

EOL

 

TERMINALS

 

+

RESISTOR

+

 

 

 

 

3

 

 

 

2

IF BELL SUPERVISION IS ENABLED

 

 

 

 

 

 

(RED JUMPER ON CONTROL BOARD IS CUT)

 

 

CONNECT A 2000 OHM RESISTOR ACROSS

-V0

 

THE EXTERNAL SOUNDER AS SHOWN BY

CUT RED JUMPER ON CONTROL

THE DOTTED LINE.

 

001-

 

 

 

 

sounder

BOARD TO ENABLE BELL

DO NOT CONNECT THE RESISTOR AT THE

(SOUNDER) SUPERVISION.

ALARM OUTPUT TERMINALS THEMSELVES!

Figure 5. Sounder Wiring (Supervised)

The 12VDC sounder output activates when an alarm occurs.

Total current drawn from this output cannot exceed 2 amps (going beyond 2 amps will overload the power supply, or may cause the electronic circuit protecting the sounder output to trip).

You must install a battery, since the battery supplies this current.

UL

Use only UL Listed sounding devices for UL installations.

Bell supervision is required for fire alarm installations.

The total current drawn from the alarm output and the auxiliary power output, combined, cannot exceed 600 mA. In addition, the sounding device must be a UL Listed audible signal appliance rated to operate in a 10.2- 13.8 VDC voltage range, and must be mounted indoors.

Wiring the AC Transformer

Connect the 1321 Transformer to terminals 1 and

Wire Run Chart

 

2 on the control board. See Wire Run Chart for

Distance from control

Wire Size

wire size to use. (Use 1321CN in Canada.)

Up to 50 feet

# 20

NOTES

50–100 feet

# 18

100-250 feet

# 16

 

 

 

Use caution when wiring the transformer to the control to guard against blowing the transformer fuse (the fuse is non-replaceable).

Wiring to the AC transformer must not exceed 250 feet using 16 gauge wire. The voltage reading between terminals 1 and 2 of the control must not fall below 16.5VAC or an “AC LOSS” message will be displayed.

Do not plug the transformer into the AC outlet while making any wiring connections to the control. As a safety precaution, always power down the control when making such connections.

Backup Battery

1.Place the 12-volt backup battery in the cabinet.

2.After all connections to the control are completed and AC power has been applied, connect the red and black flying leads on the control board to the battery. Do not attach these leads to the battery terminals until all connections are completed.

IMPORTANT: The panel will not power up initially on battery power only. You must plug the transformer in first, and then connect the battery.

UL For UL installations and Residential fire installations, refer to the chart below for the correct battery size required to meet the mandatory standby time.

2-4

Mounting and Wiring the Control

CALIFORNIA STATE FIRE MARSHALL (CSFM) AND UL RESIDENTIAL FIRE

24-HOUR BATTERY BACKUP REQUIREMENTS

The California State Fire Marshal and UL have regulations which require that all residential fire alarm control panels must be provided with a backup battery which has sufficient capacity to operate the panel and its attached peripheral devices for 24 hours in the intended standby condition, followed by at least 4 minutes in the intended fire alarm signaling condition. This control panel can meet these requirements without using a supplementary power supply, provided that the panel’s auxiliary power and bell output currents are limited as indicated below.

OUTPUT LIMITATIONS TO MEET CSFM 24 HOUR BATTERY BACKUP REQUIREMENTS

AND UL RESIDENTIAL FIRE INSTALLATIONS

OUTPUT CURRENT LIMITATIONS

BATTERY INFORMATION

Output Current Total

Maximum Auxiliary Current

Battery Capacity

Recommended Battery

 

 

To Use (Amp/Hrs)

(Yuasa Model No.)

600mA maximum total of

45mA

4AH

NP4-12 (or ADEMCO 467)

auxiliary power plus bell

160mA

7AH

NP7-12

output currents

200mA

8AH

NP4-12 (two) ‡

 

425mA

14AH

NP7-12 (two) ‡

 

500mA

17.2AH

NPG18-12

NOTE: Use two batteries, connected in parallel. Obtain an Ademco Battery Harness Kit SA5140-1. (Both batteries will fit inside the panel’s cabinet.)

Earth Ground

Metal Cold Water Pipe:

Use a non-corrosive metal strap (copper is recommended) firmly secured to the pipe to which the ground lead is electrically connected and secured.

AC Power Outlet Ground:

Available from 3-prong, 120VAC power outlets only. To test the integrity of the ground terminal, use a 3-wire circuit tester with neon lamp indicators, such as the UL Listed Ideal Model 61-035, or equivalent, available at most electrical supply stores.

This product has been designed and laboratory-tested to ensure its resistance to damage from generally expected levels of lightning and electrical discharge, and does not normally require an earth ground.

If an earth ground is desired for additional protection in areas of severe electrical activity, terminal 25 on the control board, or the cabinet, may be used as the ground connection point. The examples of good earth grounds listed at the left are available at most installations.

AUXILIARY DEVICE CURRENT DRAW WORKSHEET

* If using hardwire

 

DEVICE

CURRENT

UNITS

TOTAL CURRENT

devices such as PIRs,

6150

Fixed-Word Keypad

30mA

 

 

refer to the

6160

Alpha Keypad

100mA

 

 

specifications for that

 

 

 

 

 

6150V Fixed-Word Display Voice Keypad

60mA

 

 

particular unit's current

 

 

6160V Alpha Display Voice Keypad

60mA

 

 

draw.

 

 

5881/5882 RF Receiver

35mA

 

 

 

 

 

‡ Figures are for relays

5883

Transceiver

80mA

 

 

4204

Relay Unit

15/180mA

 

 

OFF/relays ON.

 

 

 

4285 Phone Module

160mA

 

 

 

4286 Phone Module

300mA

 

 

 

*

 

 

 

 

 

*

 

 

 

 

 

*

 

 

 

 

(Current available from Aux. terminals = 600 mA max.)

TOTAL =

 

In UL installations, maximum current draw from the Auxiliary Output and the Alarm Output combined must not exceed 600 mA (500 mA max from Auxiliary Output).

2-5

Installation Instructions

Hardwire Zones

Normally Open Zones/ Normally Open EOLR Zones

1.Connect open circuit devices in parallel across the loop; for EOLR zones, connect the EOLR across the loop wires at the last device.

2.Enable normally open/EOLR zones using Zone Programming mode, “Hardwire Type” prompt.

Normally Closed Zones/Normally Closed EOLR Zones

1.Connect closed circuit devices in series in the high (+) side of the loop; for EOLR zones, connect the EOLR in series following the last device.

2.Enable normally closed/EOLR zones using Zone Programming mode, “Hardwire Type” prompt.

NOTES

EOLR: If the EOLR is not at the end of the loop, the zone is not properly supervised and the system may not respond to an “open” on the zone.

UL For UL commercial burglar alarm installations, use EOLR zones.

Smoke Detectors

4-Wire Smoke Detectors

Connect 4-wire smoke detectors (up to 16, depending on detector current draw) to any zone as shown below. This control does not automatically reset power to 4-wire smoke detector zones, so you must use a relay (e.g., 4204), or on-board trigger to reset power (also required for fire verification). Do this by programming the designated relay/trigger as zone type 54 (fire zone reset); see On-Board Trigger section for other information.

Figure 7. 4-Wire Smoke Detector Connections

+

5

 

 

 

 

 

 

RELAY

 

 

 

AUX PWR

PROGRAM

 

BLK

+

RED

RELAY

 

 

 

 

OUTPUT

AS ZONE

 

 

 

EOL

TERMINALS

TYPE 54

 

 

 

 

 

 

POWER

 

(FIRE ZONE

 

 

N.O.

SUPERVISION

 

RESET)

 

 

 

 

 

 

RELAY MODULE

 

4

 

 

 

 

N.C.

 

 

A77-716B.

 

 

 

 

CONTACT OPENS

 

 

 

USE N.O.

 

 

 

CONTACT,

MOMENTARILY UPON

+

 

 

 

VIOLET

WHICH CLOSES

FIRE ALARM RESET

 

 

 

 

 

4-WIRE SMOKE

 

 

WHEN POWER

 

 

 

 

IS APPLIED.

 

 

OR COMBUSTION

 

 

 

 

DETECTOR

2000

 

 

 

 

 

 

 

 

 

 

OHMS

 

 

 

 

 

EOLR

 

 

TO ZONE TERM. (+)

 

 

 

-V0

 

 

 

-007

 

 

HEAT

 

 

TO ZONE TERM. ( )

 

 

wiresmk

 

 

 

 

DETECTOR

 

 

 

 

 

 

 

 

4

4-Wire Smoke Detector Using Relay for Power Reset

AUX PWR (+)

5

 

 

 

 

TO OUTPUT 17 ( )

 

BLK

+

RED

 

 

 

 

 

 

PROGRAM OUTPUT 17

 

 

 

EOL

 

FOR "OUT NORM

 

 

 

POWER

 

LOW" = YES IN 79 MENU

+

 

N.O.

SUPERVISION

 

MODE AND AS ZONE

 

RELAY MODULE

 

 

 

VIOLET

 

TYPE 54 IN

4-WIRE SMOKE

 

A77-716B.

 

80 MENU MODE

OR COMBUSTION

 

 

USE N.O.

 

 

DETECTOR

2000

 

CONTACT,

 

 

 

 

 

 

 

OHMS

 

WHICH CLOSES

 

 

 

EOLR

 

WHEN POWER

 

TO ZONE TERM. (+)

 

 

 

IS APPLIED.

V0

 

 

 

 

-

 

HEAT

 

 

 

-008

TO ZONE TERM. ( )

 

 

 

wiresmk

DETECTOR

 

 

 

 

 

 

 

 

 

 

 

 

 

4

4-Wire Smoke Detector Using Output 17 for Power Reset

NOTES

Fire Verification (zone type 16): The control panel will “verify” a fire alarm by resetting the smoke detectors after the first alarm trigger, and then waiting 90 seconds for a second alarm trigger. If the smoke detector or thermostat does not trigger again, the control will disregard the first trigger, and no alarm signal will occur. This feature eliminates false alarms due to electrical or physical transients.

SIA Installations: If using fire verification on zones other than zone 1, UL Fire Alarm Listed relay accessories must be used to reset power as described above.

Power Reset: Maximum current on trigger 17 is 100mA.

2-6

Mounting and Wiring the Control

Installing the RF Receiver

You can any ADEMCO 5800 Series Wireless Receivers, including:

RF Receiver

No. of Zones

5881L/5882L

up to 8

5881M/5882M

up to 16 (transmitter zone numbers = 9-24; button zone numbers = 49-56)

5883, 6150RF

up to 16 (transmitter zone numbers = 9-24; button zone numbers = 49-56)

 

 

1.Set Device Address to “00” as described in its instructions (set all switches to the right, “off” position).

2.Mount the receiver, noting that the RF receiver can detect signals from transmitters within a nominal range of 200 feet.

3.Connect the receiver's wire harness to the control's keypad terminals. Plug the connector at the other end of the harness into the receiver. Refer to the installation instructions provided with the receiver for further installation procedures regarding antenna mounting, etc.

NOTES

The receiver is supervised and a trouble report is sent (“CHECK 100” displayed) if communication between the panel and receiver is interrupted, or if no valid RF signals from at least one supervised

transmitter are received within 12 hours. If the receiver is mounted remotely:

Place the RF receiver in a high, centrally located area for best reception.

Do not locate the receiver or transmitters on or near metal objects. This will decrease range and/or block transmissions.

Do not locate the RF receiver in an area of high RF interference (indicated by frequent or prolonged lighting of the LED in the receiver; random flicker is OK).

Do not locate RF receiver closer than 10 feet from any keypads to avoid interference from the

microprocessors in those units.

NOTE

CIRCUIT BOARD IS MOUNTED IN CONTROL'S CABINET. GROUNDING LUGS (2) PROVIDED MUST BE INSERTED IN LEFT-HAND TERMINALS OF ANTENNA BLOCKS AND SECURED TO CABINET. (SEE RECEIVER'S AND CONTROL'S INSTRUCTIONS)

MOUNTING

HOLES

 

ANTENNAS

 

 

 

(INSERT IN

 

 

 

RIGHT-HAND

 

 

 

TERMINALS)

 

 

 

INSERT IN

 

 

 

RIGHTHAND

 

 

 

TERMINALS

 

 

 

 

YELLOW

 

 

RED

TO CONTROL'S

 

 

REMOTE KEYPAD

MODEL NO. IS INDICATED ON CIRCUIT BOARD

BLACK

 

 

CONNECTION

 

 

GREEN

5882

DIP

POINTS.

 

LOCATION

 

 

SWITCH

 

 

INTERFERENCE

 

WIRING OPENING

INDICATOR

 

 

 

LED

 

KNOCKOUT AREA

 

 

 

CIRCUIT BOARD

 

FOR SURFACE WIRING

 

 

SOCKET

PLUG

TO RELEASE CIRCUIT BOARD,

 

REMOVE SCREWS AND

 

BEND BACK TABS

5881-003-V0

Figure 9. 5881/5882 RF Receiver (cover removed)

Installing a 5800TM Module

1.Mount the 5800TM next to the RF receiver (between one and two feet from the receiver’s antennas) using its accompanying mounting bracket. Do not install within the control cabinet.

2.Connect the 5800TM to the control panel’s keypad connection terminals as shown on the Summary of Connections diagram and set to address 28.

NOTES

Use this module only if you are using one or more wireless bi-directional keypads or keyfobs with a wireless Receiver; 5800TM is not necessary if using a Transceiver (e.g., 5883).

The 5800TM must be set to address 28 (cut red-W1 jumper).

For additional information regarding the 5800TM, refer to the 5800TM’s instructions.

2-7

Installation Instructions

Installing the Transmitters

1.To be sure reception of the transmitter's signal at the proposed mounting location is adequate, perform a Go/No Go Test, described in the Testing the System section.

2.Install transmitters in accordance with the instructions provided with each.

3.Set 5827, 5827BD, 5804BD wireless keypads to the programmed House ID (field *24), using its DIP switches (5827) or follow the instructions provided with the device.

ULC NOTE: In accordance with ULC standards, the RF supervision period for the VISTA-10P is three hours for Fire zones (Zone Type 9 and 16) and 12 hours for all other zone types.

NOTES

Refer to the table of compatible devices at the back of this manual.

Supervised transmitterssend check-in signals to the receiver at 70-90 minute intervals. If at least

one check-in message is not received from each transmitter within a 12-hour period, the “missing” transmitter number(s) and “CHECK” is displayed.

Hand-held transmitters (e.g., 5802, 5802CP, 5804, 5804BD, 5827, 5827BD) do not send check-in signals.

UL The following transmitters are not intended for use in UL installations: 5802MN, 5802MN2, 5804, 5804BD, 5814, 5816TEMP, 5819, 5819WHS & BRS, and 5850.

The 5827BD and 5800TM can be used in UL Listed Residential Burglar installations.

Transmitter Battery Life

See Wireless Transmitter paragraph in the Limitations of This Alarm System statement located at the end of this manual for information on transmitter battery life.

Some transmitters (e.g., 5802 and 5802CP) contain long-life but non-replaceable batteries, and no battery installation is required. At the end of their life, the complete unit must be replaced (and a new serial number enrolled by the control).

Button-type transmitters (such as 5801, 5802, and 5802CP) should be periodically tested for battery life.

The 5802MN and 5804 Button Transmitters have replaceable batteries.

Do not install batteries in wireless transmitters until you are ready to enroll during system programming. After enrolling, batteries need not be removed.

Installing a Keyswitch

1.Connect the 4146 keyswitch's normally open momentary switch to a zone’s terminals. Remove the 2000 ohm EOL resistor if connected across the selected zone.

2.Using a standard keypad cable as shown:

Connect the yellow and white keyswitch wires to trigger connector pin 3 (+12V).

Connect the Red and Green LED wires to the appropriate output 17/output 18 trigger connector pins.

3.Connect a 2000 ohm EOL resistor across the momentary switch.

4.You can wire an optional closed-circuit tamper switch (model 112) in series with the zone. If the switchplate is then removed from the wall, the tamper will open, disabling keyswitch operation until the system is next disarmed from the keypad.

If the tamper is opened when the system is armed, an alarm will occur.

NOTES

Use 4146 keyswitch or any N.O. keyswitch.

When using a keyswitch, the zone it is connected to is no longer available for use as a protective zone.

Use *56 Menu mode to program the keyswitch zone and assign it zone type 77.

Use *80 Menu mode to program the LED functions: program outputs 17 and 18 for system operation zone type 78 (red LED) and 79 (green LED) as appropriate (see Output Device Programming section).

2-8

Mounting and Wiring the Control

UL A UL Listed keyswitch is required for fire installations and UL commercial and residential burglar alarm installations.

If a keyswitch is used on:

an installation that transmits opening and closing signals, the keyswitch zone must be programmed to send opening and closing signals.

a UL commercial burglar alarm installation, the keyswitch’s tamper switch must be connected in to the alarm system. This tamper switch zone must also be programmed for Zone Type 05 – Trouble by Day / Alarm by Night.

a fire alarm installation, the keyswitch must be located next to an alphanumeric display keypad.

The Ademco 4146 keyswitch is UL Listed.

5-PIN TRIGGER CONNECTOR

 

 

 

 

1

KEY

3

4

5

 

 

 

 

 

 

 

 

 

 

 

 

(YELLOW)

 

(RED)

(GREEN)

 

 

 

 

 

OUTPUT 17

 

+12 AUX.

OUTPUT 18

 

4-WIRE

4146 KEYSWITCH

 

 

 

 

 

 

 

 

 

 

 

 

CABLE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(ARMED)

 

 

 

 

 

 

 

 

RED

 

 

 

 

 

 

 

YELLOW

 

 

 

 

 

 

 

 

 

(READY)

 

 

 

 

 

 

 

 

GREEN

 

 

 

 

 

 

 

WHITE

 

 

 

 

 

 

 

 

 

820

820

 

 

 

 

 

 

 

ohms

ohms

 

 

 

 

 

 

BLACK

 

 

 

 

 

 

 

 

RED

 

 

 

 

 

 

 

 

 

TAMPER

 

 

 

 

 

 

 

 

SWITCH (N. C.)

 

 

 

 

11

 

BROWN

 

BROWN

 

 

 

 

 

 

 

 

 

 

 

TYPICAL ZONE

 

 

 

 

 

 

ON CONTROL

 

LOCK

 

 

 

 

 

BOARD

 

SWITCH (N. O.)

 

 

 

 

10

 

BLUE

 

BLUE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(use appropriate value)

-004-V3

 

 

 

 

 

 

trigcon-

 

 

 

 

 

 

EOLR

 

 

 

 

 

 

 

 

 

 

00

Figure 10. Keyswitch Wiring Connections

Connecting Relay Modules

1.Mount either remotely or in the control panel.

2.Connect to control’s keypad terminals using the connector harness supplied with the module. Use standard 4-conductor twisted cable for long wiring runs.

3.Set the module’s device address to address 12.

4.Connect the desired field wiring to the unit's relay contact terminals.

NOTES

Use 4204 module.

Supervision: 4204 module is supervised against removal. The module’s device address is displayed

as follows if a module is disconnected from the control’s terminals, or if the module cover is removed and the tamper jumper is installed:

Alpha:

CHECK xx Wire Expansion

 

FAULT xx Wire Expansion

ALARM xx Wire Expansion

Fixed-Glass: lxx (or 91 if field *199 set for 2-digit display); where “xx is the module’s address.

If communication/tamper failure occurs on a device with zones wired to it, all zones on the device will be displayed.

UL For UL installation requirements, refer to the Installation Instructions for the 4204.

4204

RELAY

12

C

DIP SWITCH

4

11

NC

TYPICAL

10

 

FOR SETTING DEVICE ADDRESS

NO

(SHOWN "OFF")

AND ENABLING/DISABLING TAMPER

 

 

RELAY

9

C

 

 

COVER TAMPER (REED) SWITCH

3

8

NC

7

NO

 

 

 

 

 

4-PIN TOUCHPAD PLUG

RELAY

6

C

 

 

2

5

NC

EITHER OR BOTH

 

4

NO

CAN BE USED

RELAY

3

C

 

 

TB1

1

2

NC

 

 

13 14 15 16

 

1

NO

 

 

YEL

DATA IN

 

TB2

 

FROM CONTROL

 

 

BLK

(–) GROUND

 

 

 

 

 

GRN

DATA OUT

 

 

RED

TO CONTROL

 

 

(+) 12V

4204_conn-1-V0

 

Figure 11. 4204 Connections to Control

2-9

Installation Instructions

On-Board Triggers

Connect field wiring to the desired trigger pin on the 8-pin trigger connector centrally located above the terminal strip.

You can use a 4-wire cable as shown.

UL If on-board triggers are used, the wiring between the control unit and the UL Listed device must be run in conduit, be no more than 3 feet apart and have no intervening barriers or walls.

5-PIN TRIGGER CONNECTOR

1

KEY

3

4

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(YELLOW)

 

(RED)

(BLACK)

(GREEN)

OUTPUT 17

 

+12 AUX.

GND (-)

OUTPUT 18

4-WIRE CABLE

00-trigcon-005-V3

Figure 12.

On-Board Trigger Connector with 4-Wire Cable

NOTES

There are two on-board triggers that can be used to activate output devices.

These outputs are normally high, and go low upon programmed condition.

Outputs can be programmed for inverted operation (normally low, go high) using *79 Menu mode.

Program these triggers using *80/*81 Menu modes as you would for any other relay output.

When using these outputs, note:

pin 1 = output number 17 (trigger 1):

15 ohms to ground when closed (output low), open when off (output high, normal default); can be used to reset smoke detector power (must set “output normal low = yes” in *79 Menu mode,

and set for zone type 54, fire zone reset, in *80 Menu mode); or can support 12V relay modulethat draws less than 100mA

pin 5 = output number 18 (trigger 2):

100 ohms to ground when closed (output low); open when off (output high, normal default); or can support 12V relay module that draws less than 20mA

† e.g., Altronix AX-RBS

Phone Line/Phone Module Connections

1.Connect incoming phone line and handset wiring to the main terminal block (via an RJ31X jack) as shown in the Summary of Connections diagram at the back of this manual. Wire colors

represent the colors of the cable to the RJ31X jack.

If using a phone module, continue with the following steps.

2.Make 12V (+) and (–) and data in and data out connections from the phone module to the control, using the connector cable supplied with the phone module, then insert the keyed connector at the other end of the connector cable into the header on the phone module.

3.Connect Phone Module terminals as shown below. Use an RJ31X jack with a direct-connect cord and make all connections exactly as shown.

4.Caller ID Units: If a Caller ID unit is being used, connect the unit directly to the “Handset” terminals (21 & 22) on the control, as shown.

NOTES

Use 4285 or 4286 Phone Modules.

Compatibility: 4286 Phone Modules must have software version WA4286-15.1 or higher (refer to the label on the square 4286 microprocessor chip).

Only one phone module can be used.

The phone lines must be in service for the phone module to function, even when accessing the system from an on-premises phone.

If you are also using an Audio Alarm Verification (AAV) unit, refer to Audio Alarm Verification (AAV) section for special wiring connections.

CAUTION: To reduce the risk of fire, use only No. 26 AWG or larger telecommunication line cord for phone line connections.

2-10

Mounting and Wiring the Control

UL The 4285 and 4286 modules are UL Listed only for use on residential fire and UL residential burglar alarm installations.

Phone Module Problems

If no touch tones are produced following access to the security system from on-premises (this problem may arise in rare cases), it may be necessary to reverse the wires connected to terminals 3 and 4 on the phone module and the wires connected to terminals (21) & (22) on the control. The wiring diagram shows the wiring connections that will provide proper operation in most cases.

Connection to the incoming telco line via a RJ31X jack and direct-connect cord, as shown, is essential, even if the system is not connected to a central station. Otherwise the 4285/4286 will not function and an error signal (fast busy signal) will occur when accessing the system via the phone.

The house phone lines (gray and brown wires) must be wired to the phone module terminals; not to the control terminals. Otherwise, an error signal (fast busy signal) will occur when trying to access the system from an on-premises phone.

 

 

HANDSET

INCOMING

GROUND

 

 

 

TELCO LINE

 

 

 

 

TERMINALS

{ {

 

 

 

 

21

22

23

24

25

TO EARTH GROUND (COLD WATER PIPE, ETC.)

 

ON CONTROL

 

 

 

 

 

 

 

 

CALLER ID

 

 

GREEN(TIP)

RED(RING)

 

TIP RING

INCOMING TELCO LINE

(TIP)

(RING)

 

 

EXISTING INSTALLATIONS:

 

RING

 

UNIT

 

 

 

 

DIRECT

 

 

 

 

 

 

 

 

CONNECT

 

 

IMPORTANT NOTE FOR

 

 

 

 

CORD

 

TIP

 

 

 

 

 

RJ31X

 

 

 

 

 

 

 

 

EXISTING WIRES

 

 

 

 

 

JACK

 

 

 

 

 

 

 

 

CONNECTED TO THE

 

 

 

 

 

CA38A

 

"HANDSET" TERMINALS ON

 

 

 

 

 

PREMISES ANSWERING

 

 

 

 

PLUG

IN

CONTROL MUST BE MOVED

 

 

 

 

MACHINE AND PHONES

 

 

 

 

CANADA

FROM THERE TO TERMINALS

 

 

 

 

 

 

 

 

 

 

 

 

 

3 AND 4 ON THE 4285/4286.

 

 

 

BROWN (T)

 

 

ANSWERING

 

 

 

 

 

 

 

 

 

 

 

GREY (R)

 

 

MACHINE

VIP MODULE

657

 

 

 

*

 

4285/4286

 

 

 

 

 

 

 

LOUDER

 

1 2 3 4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*

VOLUME

 

 

 

 

 

 

 

 

(4286

KEYED

 

 

 

 

* NOTE: IF THE TELEPHONE HAS BUILT-IN CALLER ID,

ONLY)

HEADER

 

 

 

 

 

 

 

 

 

 

THE CALLER ID FUNCTION MAY NOT WORK .

 

 

 

 

 

 

 

UNUSED

 

 

 

 

 

 

 

 

 

 

4285/4286

 

 

 

 

 

 

 

TO CONTROL

 

 

TERMINAL ASSIGNMENTS

 

 

 

YELLOW: TO DATA OUT (term. 7)

 

1 - TIP

 

 

 

NO CONNECTION

 

PANEL

CONNECTOR

 

 

RED:

TO AUX (+) (term. 5)

 

TERMINALS

2

- RING } PHONE INPUT

 

 

 

3

- TIP

 

 

 

BLACK:

TO AUX. GROUND (–) (term.4)

 

 

WITH FLYING

 

 

GREEN:

TO DATA IN (term. 6)

 

 

USED FOR

4 - RING } PHONE OUTPUT

LEADS

 

 

 

 

KEYPAD

5

- NO CONNECTION

 

 

 

 

 

 

 

CONNECTIONS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

-

AUDIO OUT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

-

} 4286 ONLY

4286_cntrl-001-V0

Figure 13. 4285/4286 Phone Module Wiring Connections

Long Range Radio Connections

Connect the data in/data out terminals and voltage input terminals of the Long Range Radio to the control's keypad connection points.

Set the radio’s address to “03” following the instructions provided with the radio. Use compatible Long Range Radios (e.g., 7720PLUS, 7820, 7835C, or 7845C).

2-11

Honeywell VISTA-10PSIA, VISTA-10P User Manual

Installation Instructions

Audio Alarm Verification Connections (AAV, “listen-In”)

Refer to the connection diagrams below. One diagram shows connections when a 4285/4286 Phone Module is used, the other shows connections when the 4285/4286 is not used.

Connections use one of the on-board triggers.

UL UL installations using the AAV feature must use the ADEMCO UVCM module (part of the ADEMCO UVS system)

Suggested AAV Module: ADEMCO UVS (shown) or Eagle 1250

NOTES

Set field *91 for AAV and program the appropriate output (output 17 or 18) using *80 Menu mode: select zone type 60 and output action 1 (close for 2 seconds) or action 2 (stay closed).

For voice session monitoring, connect a zone to UVCM module terminals 6 & 7, and program the zone as zone type 81 (*56 Menu mode).

E.g., Using output 18 for the trigger, program an output function in *80 Menu mode as: ZT = 60, P = 0, Action = 1, Device = 18

 

 

 

 

 

 

 

 

5

TRIGGER

 

 

 

 

 

 

 

 

 

 

 

 

 

CONNECTOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

18

 

ZONE

 

 

 

 

EARTH

 

 

 

 

 

 

CONTROL

OUTPUT

 

 

 

 

 

GROUND

 

 

 

 

 

 

 

 

TERMINALS

 

 

 

 

 

 

 

 

AUXILIARY

4

5

 

21

22

23

24

25

 

 

 

 

AUDIO LEVEL

 

 

 

 

 

 

 

 

 

 

 

 

ADJUSTMENT

GND

+12VDC

 

 

 

 

 

 

 

 

 

 

 

TRIM POT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EOL

 

 

 

 

 

 

 

UVCM

 

 

 

34

 

 

RING

 

 

 

 

 

 

 

MODULE

 

 

 

TIP

 

 

 

 

 

 

 

 

33

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RED (R)

 

 

 

 

 

 

 

32

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

31

 

 

 

 

 

 

GREEN (T)

 

 

 

 

 

 

 

30

 

 

 

 

 

 

GREY (R)

RJ31X

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE:

 

 

 

 

 

29

 

 

 

 

 

 

BROWN (T)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

REFER TO UVCM MODULE

 

 

 

 

 

 

 

 

 

 

 

 

 

INSTRUCTIONS FOR

 

 

 

 

 

 

 

 

 

 

 

 

 

CONNECTIONS TO AUDIO

 

 

 

 

11

 

 

OPTIONAL

 

 

 

 

 

SPEAKERS AND MICROPHONE.

 

 

 

 

 

 

 

 

 

 

 

 

765 8

BANK2

 

 

 

 

MONITORING ZONE

 

 

 

 

 

 

 

 

910

 

 

 

 

 

 

 

 

 

 

 

 

CONNECTION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(USE ZONE TYPE 81)

 

 

 

 

2 = OFF

2 = ON

ON

4321

SWITCH

 

876

 

 

 

 

 

 

TO

INCOMING

SWITCH

SWITCH

 

 

 

 

 

 

 

 

 

 

 

PREMISES

 

BANK 1

BANK 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HANDSET

 

1 = OFF

1 = ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 = OFF

3 = OFF

 

 

 

FALLING VOICE TRIG

5

 

 

 

 

 

 

 

PHONE LINE

4 = OFF

4 = ON

 

8

1

 

 

 

 

 

 

 

 

5 = OFF

5 = ON

ON

6543217

BANKSWITCH

 

4321

 

 

 

 

 

 

 

003V0-

6 = OFF

6 = ON

 

 

 

 

 

 

 

 

 

 

 

 

 

7 = OFF

7 = ON

 

 

 

 

 

 

 

 

 

 

 

 

 

8 = ON

8 = ON

 

 

 

GND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+12VDC IN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

aav uvcm-

Figure 14. Connection of AAV Unit When Not Using a 4285/4286 Phone Module

NOTE:

REFER TO UVCM MODULE INSTRUCTIONS FOR CONNECTIONS TO AUDIO SPEAKERS AND MICROPHONE.

SWITCH

SWITCH

BANK 1

BANK 2

1

= OFF

1

= ON

2

= OFF

2

= ON

3

= OFF

3

= OFF

4

= OFF

4

= ON

5

= OFF

5

= ON

6

= OFF

6

= ON

7

= OFF

7

= ON

8

= ON

8

= ON

AUXILIARY AUDIO LEVEL ADJUSTMENT TRIM POT

UVCM MODULE

 

8

2

 

5 6 7

BANK

ON

1 2 3 4

SWITCH

 

8

1

 

5 6 7

BANK

ON

1 2 3 4

SWITCH

RING

34

TIP

33

 

32

 

31

 

30

 

29

 

11

 

10

 

9

 

8

 

7

 

6

FALLING VOICE TRIG

5

 

4

 

3

GND

2

 

+12VDC IN

1

CONTROL

4 5

GND

+12VDC

5

OUTPUT 18

TRIGGER

 

 

 

 

CONNECTOR

 

 

 

 

 

 

 

 

EARTH

ZONE

 

 

 

GROUND

TERMINALS

 

 

 

 

21

22

23

24

25

EOL

 

 

RING

 

 

TIP

 

 

 

RED (R)

 

 

GREEN (T)

 

 

GREY (R)

RJ31X

OPTIONAL

BROWN (T)

 

MONITORING

 

 

 

ZONE

 

 

CONNECTION

 

 

(USE ZONE

 

 

TYPE 81)

 

 

 

TO

 

 

PREMISES

 

 

HANDSET

 

 

 

INCOMING

 

 

PHONE LINE

4285/4286

4

 

3

-V0

2

uvcm-004

1

 

aav_

Figure 15. Connection of AAV Unit When Using a 4285 or 4286 Phone Module

2-12

S E C T I O N 3

Programming Overview

• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •

About Programming

You can program the system at any time, even at the installer's premises prior to the actual installation. Programming can also be performed remotely from the installer’s office/home, using an IBM personal computer, a modem, and Compass downloading software.

The following is a list of the various Programming modes used to program this system:

Programming Mode…

Used to …

Data Field Programming

Program basic data fields used for setting the various system options.

 

 

Most of the data fields in this system have been programmed for specific

 

 

default values. However, some fields must be programmed for each particular

 

 

installation to establish its specific alarm and reporting features.

56 Zone Programming

Assign zone characteristics, report codes, alpha descriptors, and serial

 

 

numbers for 5800 RF transmitters.

57 Function Key Programming

Program each of the four alphabet function keys to perform one of several

 

 

system operations.

58 Zone Programming

Assign zone attributes similar to 56 mode, but provides a faster

(Expert Mode)

programming procedure and is intended for those more experienced in

 

 

programming controls of this type.

79

Output Device Mapping

Assign device address of the 4204 Relay module and map the specific relays

80

Output Definitions

Define up to 12 output definitions which can control the output relays mapped

 

 

using *79 Output Device Mapping mode.

81

Zone List Programming

Create Zone Lists for relay zones, chime, night-stay, cross zones, and pager

 

 

zones.

82

Alpha Programming

Create alpha descriptors for easy zone identification.

Scheduling Mode (code + [#] +64)

Create schedules to automate various system functions.

Keypads

Keypads are identified by predefined addresses (starting at address 16) as follows:

Address

Keypad

Program Field

 

 

 

 

NOTE: First keypad is address 16.

16

keypad 1

always enabled, all sounds enabled.

17

keypad 2

data field *190

 

18

keypad 3

data field *191

 

19

keypad 4

data field *192

 

20

keypad 5

data field *193

 

21

keypad 6

data field *194

 

22

keypad 7

data field *195

 

23

keypad 8

data field *196

 

To enable keypads:

1.Set desired address at keypad (refer to keypad’s instructions for setting the address).

2.Use data field program mode to enable keypad addresses and enable sound options in fields *190- *196 as shown in the table above.

3.Set the following keypad-related data fields as required by the installation: *21 Quick Arm Enable; *23 Forced Bypass; *84 Auto STAY Arm

3-1

These fields must be enabled for Residential Fire, UL Residential Burglar Alarm, and UL Commercial Burglar Alarm installations.

Installation Instructions

Wireless Receiver, Transmitters, and Wireless Keys (keyfobs)

Receiver: Set the receiver’s address to “00” using its DIP switches, then set the following options: *22 RF Jam Option

*24 RF House ID Code (if using wireless keypads)

*67 Transmitter Low Battery Report Code

*75 Transmitter Low battery restore report code

*173 RF Reporting Options

Transmitters: Use *56 or *58 Zone Programming Menu modes to program zone information and enroll transmitters.

Wireless Keys: Use Wireless Key Programming Templates section of the *58 Zone Programming Menu mode to program zone information and enroll each button of the wireless keys used. Once a wireless key is enrolled, it must be assigned to a user before it becomes active. See Adding/Deleting Security Codes section for procedure.

Pager Programming

The system can send various reports to a pager.

To program pager reporting, do the following:

1.Enter the appropriate information in the following data fields: *160, Pager Phone Number

*161, Pager Prefix Characters *162, Pager Reporting Options

2.Enable Pager Delay, if desired, in field *172

3.Make sure appropriate user open/close pager reports are enabled using the user attribute

command (see Security Codes, Assigning Attributes in Section 6. System Communication and Operation).

4.If using latchkey pager report, define the latchkey report schedule using Scheduling mode (master code + [#] [6] [4] then select event type “03”). System must be armed for the Latchkey report to be sent.

5.If using a function key to manually send a message to a pager, see Function Keys paragraph on the next page.

6.If reporting zone alarms and troubles to a pager, use *81 Zone List menu mode to assign the zones associated with each pager (zone lists 9).

Function Keys

To assign functions to the function keys, use *57 Function Key menu mode.

To assign emergency key functions (function key option “00”), first program the respective emergency zone number (95 for “A” key, 96 for “C” key, 99 for “B” key) with the desired zone type using *56 Zone Programming mode, then use *57 Function Key menu mode to assign the desired key.

If using a function key to activate a relay action (*57 Menu mode key function 07), use *79 Menu mode to map the output, and use *80 Menu mode to define the output’s action; select system operation type “66.”

If using a function key for a user macro, use *57 menu mode to activate the desired key, then define the actual macro functions using the user code + [#] + [6] [6] command.

Output Devices

To program a device for manual activation (user code + [#] [7] / [#] [8] + 2-digit device number) or for scheduled automatic activation, simply map the device using *79 Menu mode.

To program a device to automatically activate upon a system event (or function key), use *79 Menu mode to map the device, then use *80 Menu mode to define the automated device action.

If the device action is based on more than one zone, use *81 Zone List menu mode to assign the zones.

3-2

Zone Type Definitions

You must assign a zone type to each zone, which defines the way in which the system responds to faults in that zone. Zone types are defined below.

Zone Type

Description

Type 00

Program a zone with this zone type if the zone is not used.

Zone Not Used

 

Type 01

• Assign to zones that are used for primary entry and exit.

Entry/Exit Burglary #1

• Provides entry delay when zone is faulted if control is armed in the Away, Stay,

 

or Night-Stay modes.

 

• No entry delay provided when the panel is armed in the Instant/Maximum mode.

 

• Entry delay 1 is programmable.

 

• Exit delay begins whenever the control is armed, regardless of the arming mode

 

selected, and is programmable.

Type 02

• Assign to zones that are used for entry and exit and require more time than the

Entry/Exit Burglary #2

primary entry/exit point.

 

• Provides a secondary entry delay, in same manner as entry delay #1.

 

• Entry delay 2 is programmable.

 

• Exit delay is same as described for Type 01.

Type 03

• Assign to all sensors or contacts on exterior doors and windows.

Perimeter Burglary

• Provides an instant alarm if the zone is faulted when the panel is armed in the

 

Away, Stay, Night-Stay, Instant or Maximum modes.

Type 04

• Assign to a zone covering an area such as a foyer, lobby, or hallway through

Interior Follower

which one must pass upon entry (to and from the keypad).

 

• Provides a delayed alarm (using the programmed entry 1 time) if the entry/exit

 

zone is faulted first. Otherwise this zone type gives an instant alarm.

 

• Active when the panel is armed in the Away mode.

 

• Bypassed automatically when the panel is armed in the Stay or Instant modes;

 

if armed in Night-Stay mode, zones assigned to zone list 05 (night-stay zone list)

 

are not bypassed when system armed in Night-Stay mode.

Type 05

• Assign to a zone that contains a foil-protected door or window (such as in a store),

Trouble by Day/

or to a zone covering a sensitive area such as a stock room, drug supply room, etc.

Alarm by Night

• Can also be used on a sensor or contact in an area where immediate notification

 

of an entry is desired.

 

• Provides an instant alarm if faulted when armed in the Away, Stay, Night-Stay,

 

Instant or Maximum (night) modes.

 

• During the disarmed state (day), the system will provide a latched trouble

 

sounding from the keypad (and a central station report, if desired).

Type 06

• Usually assigned to a zone containing an emergency button.

24-hour Silent Alarm

• Sends a report to the central station but provides no keypad display or sounding.

 

 

Type 07

• Assign to a zone that has an emergency button.

24-hour Audible Alarm

• Sends a report to the central station, and provides an alarm sound at the keypad,

 

and an audible external alarm.

Type 08

• Assign to a zone containing an emergency button, or to a zone containing

24-hour

monitoring devices such as water or temperature sensors.

Auxiliary Alarm

• Sends a report to the central station and provides an alarm sound at the keypad.

 

(No bell output is provided.)

Type 09

• Provides a fire alarm on short circuit and a trouble condition on open circuit. A

Supervised Fire

fire alarm produces a pulsing bell output.

 

• This zone type is always active and cannot be bypassed.

 

 

Type 10

• Provides entry delay (using the programmed entry time), if tripped when the

Interior w/Delay

panel is armed in the Away mode.

 

• Entry Delay 1 begins whenever sensors in this zone are violated, regardless of

 

whether or not an entry/exit delay zone was tripped first.

 

• Bypassed when the panel is armed in the Stay or Instant modes; if armed in

 

Night-Stay mode, zones assigned to zone list 05 (night-stay zone list) are not

 

bypassed when system armed in Night-Stay mode.

3-3

Installation Instructions

Type 12

• Works as a dynamic monitor of a zone fault/trouble (not alarm). In the case of a

Monitor Zone

short/open, the message, "*ALARM*-24 Hr. Non-Burg. -#XXX " (where XXX is the

 

zone number) will be sent to the Central Station. The system keypad will display

 

a “check” message indicating the appropriate zone (but keypad beeping does not

 

occur). Upon restoral of the zone, the message, "*RESTORE*-24 Hr. Non-Burg. -

 

#XXX " will be sent to the Central Station.

 

• The “check” message will automatically disappear from the keypad dynamically,

 

when the zone restores; a user code + off sequence is not needed to reset the zone.

 

• Faults of this zone type are independent of the system, and can exist at the time

 

of arming without interference.

 

• Since this is a “trouble” zone type, do not use this zone type with relays set to

 

activate upon “alarm.”

Type 14

• Assigned to any zone with a carbon monoxide detector.

24 Hour Carbon

• The bell output will pulse when this zone type is alarmed.

Monoxide Monitor

• Always active and cannot be bypassed.

Type 16

• Provides a fire alarm when zone is shorted, but only after alarm verified.

Fire w/Verification

• System verifies alarm by resetting zones for 12 seconds after short is detected. A

 

subsequent short circuit within 90 seconds triggers fire alarm.

 

• Provides a trouble response when zone is open.

Type 20

• Arms the system in Stay mode when the zone is activated.

Arm-Stay (BR only)

• Pushbutton units send the user number to the central station when arming or

 

disarming.

 

• User number for button must be assigned.

Type 21

• Arms the system in Away mode when the zone is activated.

Arm-Away (BR only)

• Pushbutton units send the user number to the central station when arming or

 

disarming.

 

• User number for button must be assigned.

Type 22

• Disarms the system when the zone is activated.

Disarm (BR only)

• User number for button must be assigned.

 

 

Type 23 *

• Can be used on a zone when an output relay action is desired, but with no

No Alarm Response

accompanying alarm (e.g., lobby door access).

 

 

Type 24

• Usually assigned to all sensors or contacts on exterior doors and windows where

Silent Burglary

bells and/or sirens are NOT desired.

 

• Provides an instant alarm, with NO audible indication at any keypad or external

 

sounder, if the zone is faulted when the system is armed in the Away, Stay,

 

Instant, or Maximum modes.

 

• A report is sent to the central station.

Type 77

• Assign to zone wired to a keyswitch.

Keyswitch

• Do not use devices assigned as input type “BR” with this zone type.

Type 81

• Assign to zone connected to AAV module.

AAV Monitor Zone

• Monitors 2-way voice sessions as follows:

 

- When the zone is faulted, all alarm sounding and dialer reporting stops, except

 

for fire alarms, which immediately terminate the voice session and cause

 

a fire report to be sent.

 

- When the zone is restored (session ended), sounding resumes (if bell timeout

 

has not expired) and reports that were stopped are sent.

Types 90

Allows for a custom zone response. Options include response to entry/exit delays,

Configurable

response opens/shorts, types of alarm/trouble sounding, dial delay, and unique

 

Contact ID report code.

 

UL installations: Zone Type 90 may not be used as fire or burglar alarm zones on

 

fire or UL burglar alarm installations.

* The system can still be armed when these zone types are in a faulted condition.

NOTE: All of the zone types described are available for the wireless portion of the system, if used.

3-4

Loading...
+ 50 hidden pages