Honeywell V5016A Manual

5 (1)
Copyright © 2009 Honeywell Inc. • All Rights Reserved EN0B-0440GE51 R0709
V5016A
FLANGED LINEAR VALVE PN16
SPECIFICATION DATA
GENERAL
These single-seated valves are suitable for use in conjunction
closed heating, ventilating, and air conditioning systems. They
are designed especially for use in high differential pressure
applications (e.g. district heating) and can be operated by
linear actuators ML6420/ML6425, ML7420/ML7425, or
M6421/M7421 or by pneumatic actuators MP953.
FEATURES
Pressure-balanced plug
Nodular iron body with flanged end connections
Low seat leakage rate
Metal-to-metal seating for long life span
Self-adjusting packing
Accurate positioning to ensure state-of-the-art
temperature control
Easy mounting of direct-coupled electric and
pneumatic actuators
Approved according to DIN EN 14597 in DN15...80 in
combination with ML6425/ML7425
SPECIFICATIONS
Action Stem down to close
Nominal pressure rating PN16
Flow characteristic Equal percentage
Rangeability 50:1
Leakage rate 0.05% of k
VS
(DN15...80)
0.1% of k
VS
(DN100...150)
Stroke 20 mm (DN15...80)
38 mm (DN100...150)
Valve body
End connections Flanged per ISO 7005-2
Material Nodular iron (GGG40.3)
Dimensions See Fig. 1 on page 3
Trim
Seat Stainless steel
Stem Stainless steel
Plug Stainless steel, skirt-guided
Packing Spring-loaded PTFE cone rings
Medium temperature
and pressure
2...180 °C (max. 1600 kPa)
Max. temp. differential 60 K (alternating hot/coldwater)
Medium water, water-glycol (max. 50%),
steam
V5016A FLANGED LINEAR VALVE PN16
EN0B-0440GE51 R0709 2
SIZES AND FLOW CAPACITIES
Order Number Valve Size k
VS
V5016A1010 DN15 0.40
V5016A1028 DN15 0.63
V5016A1036 DN15 1.0
V5016A1044 DN15 1.6
V5016A1051 DN15 2.5
V5016A1069 DN15 4.0
V5016A1077 DN20 6.3
V5016A1085 DN25 10.0
V5016A1093 DN32 16.0
V5016A1101 DN40 25.0
V5016A1119 DN50 40.0
V5016A1127 DN65 63.0
V5016A1135 DN80 100.0
V5016A1143 DN100 160.0
V5016A1150 DN125 250.0
V5016A1168 DN150 360.0
INSTALLATION
Water should meet VDI 2035 requirements.
Do not install valve with stem below the horizontal.
Fluid flow must correspond with the arrow direction on the
valve body.
The installation of a strainer is strongly recommended.
REPAIR PACKING KIT
Part No.: R43176755004 (DN15...80)
R43176755005 (DN100...150)
ACTUATORS
Electric Actuators
600 N (20 mm)
600 N (20 mm),
spring return
1800 N (38 mm)
ML6420A ML6425A,B ML6421B
ML7420A ML7425A,B ML7421B
Pneumatic Actuators
actuator stroke acting
model size direct reverse
positioner
5", 8" 20 mm
MP953A
13" 38 mm
X
MP953B 7" 20 mm X
yes
5", 8" 20 mm
MP953C
13" 38 mm
X
MP953D 7" 20 mm X
no
CLOSE-OFF PRESSURE RATINGS (in kPa)
Electric Actuators
actuator valve size
model stroke force DN15 DN20 DN25 DN32 DN40 DN50 DN65 DN80 DN100 DN125 DN150
ML6420A, ML6425A,B,
ML7420A, ML7425A,B
20 mm 600 N 1600 1600 1600 1600 1600 1600 1600 1600 -- -- --
ML6421B, ML6421B 38 mm 1800 N -- -- -- -- -- -- -- -- 1600 1600 1600
Pneumatic Actuators
actuator valve size
model
spring
range
air
pressure
DN15 DN20 DN25 DN32 DN40 DN50 DN65 DN80 DN100 DN125 DN150
MP953A,C (5")
28...77 kPa
(4...11 psi)
115 kPa 1600 1600 1600 1600 1600 1200 -- -- -- -- --
MP953A,C (8")
28...77 kPa
(4...11 psi)
115 kPa 1600 1600 1600 1600 1600 1600 1600 1600 -- -- --
MP953B,D (7")
55...90 kPa
(8...13 psi)
0 kPa 1600 1600 1600 1600 1600 1600 1600 1600 -- -- --
MP953A,C (13")
28...77 kPa
(4...11 psi)
115 kPa -- -- -- -- -- -- -- -- 1600 1600 1600
Loading...