Honeywell V2250, V2260, V2240, V2230 PRODUCT DATA

0 (0)

V2230, V2240, V2250, V2260 Thermostatic Distribution Valves

THERMOSTATIC VALVES FOR DISTRIBUTION SYSTEMS

PRODUCT DATA

M

 

N

 

G

 

W

 

G

 

E

 

R Y

 

MAN

 

Internal threads

M

N

G

W

 

 

G

 

E

 

R Y

 

MAN

 

Internal threads with

 

injection lance

M

 

N

 

G

 

W

 

G

 

E

 

R Y

 

MAN

 

External threads

M

N

G

 

W

 

G

 

E

 

R Y

 

MAN

 

External threads with

 

injection lance

Design

The flowshare valve consists of:

Valve housing PN10, DN15

with external threads, or

with internal threads to DIN2999 (ISO7) for threaded pipe or copper/precision steel pipe 10...18 mm using compression pipe fittings (see ‘Accessories’)

Thermostatic valve insert

Union-nut and radiator tailpiece

Colour protection cap

Materials

Valve housing made of nickel-plated brass

Valve insert made of brass with EPDM O-rings and soft seals and stainless steel spindle

Union-nut and tailpiece made of brass, union-nut nickelplated

Protection cap made of plastic

Application

Together with a radiator thermostat Thermostatic Distribution Valves are used to control temperature in oneor two-pipe distribution systems. They are used in combination with an F type Distribution Valve and/or a Verafix lockshield valve. The valve can be shutoff with the protection cap, or later with the radiator thermostat (not supplied with the valve).

By using distribution valves connections under the floor or in the wall are avoided.

Features

No connections under the floor necessary

Shutoff does not affect other radiators in the loop

Installation in supply or return (observe flow direction)

Valve seat can be cleaned and/or valve insert replaced without draining the system

Available with R 1/2" internal or G 3/4" external threads

Specifications

Medium

Heating water, water quality to

 

VDI2035

 

pH-value

8...9.5

 

Operating temperature

max. 130°C (266°F)

Operating pressure

max. 10 bar (145 psi)

Differential pressure

max. 1 bar (14.5 psi) –

 

max. 0.2 bar (2.9 psi) recommended

 

for quiet operation

 

kvs-values*

two-pipe

0.14 (0.16)

 

 

0.36 (0.42)

 

 

0.62 (0.73)

 

 

0.80 (0.94)

 

one-pipe

1.70 (1.99)

Radiator proportion

50 % (one pipe)

 

Thermostat connection

M30 x 1.5

 

Closing dimension

11.5 mm

 

Stroke

2.5 mm

 

NOTE: Protection cap is colour-coded for easy identification

Honeywell y Subject to change

EN0H-2402GE25 R1206

Honeywell V2250, V2260, V2240, V2230 PRODUCT DATA

V2230, V2240, V2250, V2260 THERMOSTATIC DISTRIBUTION VALVES

Function

Thermostatic radiator valves enable individual control of room temperature and thus save energy.

The TRV body is controlled by the radiator thermostat. Air from the room passing over the sensor of the radiator thermostat causes the sensor to expand when the temperature rises. The sensor acts onto the valve spindle and this causes the TRV

Dimensions and Ordering Information

Fig. 1. External threads version

Fig. 3. Internal threads version

NOTE: All dimensions in mm unless stated otherwise.

Please Note:

To avoid stone deposit and corrosion the composition of the medium should conform with VDI-Guideline 2035

Additives have to be suitable for EPDM sealings

System has to be flushed thoroughly before initial operation with all valves fully open

Any complaints or costs resulting from non-compliance with above rules will not be accepted by Honeywell

Please contact us if you should have any special requirements or needs

body to close. When the temperature falls the sensor contracts and the spring-loaded valve spindle is opened. The TRV opens in proportion to the temperature of the sensor. Only the amount of water required to maintain the room temperature set on the radiator thermostat can flow into the radiator.

Fig. 2. External threads version with injection lance

Fig. 4. Internal threads version with injection lance

EN0H-2402GE25 R1206

2

Honeywell y Subject to change

Loading...
+ 2 hidden pages