Honeywell THX9421, THX9321 User Manual

5 (2)

THX9321 Prestige® 2.0 and

THX9421 Prestige® IAQ 2.0 with EIM

PRODUCT DATA

• Delta T Alerts and Diagnostics

APPLICATION

The Prestige 2.0 and Prestige IAQ 2.0 Systems feature an effortless, 7-Day programmable color touchscreen thermostat that provides control of temperature, humidification, dehumidification, and ventilation for up to 4 Heat/2 Cool heat pump systems or up to 3 Heat/2 Cool conventional systems for residential and commercial applications.

FEATURES

RedLINK™ Compatible

Increase your content and profit per job by including RedLINK™ accessories that meet your customers comfort and convenience needs. RedLINK accessories include the Wireless Outdoor Sensor, Portable Comfort Control (PCC), Equipment Interface Module (EIM), RedLINK Internet Gateway, Wireless Indoor Sensor, TrueSTEAM™ humidifier with Wireless Adapter, TrueZONE™ zoning panel with Wireless Adapter, Vent Boost Remote and Entry/Exit Remote.

Customizable Service Reminders

Set up to 10 service reminders. Choose from the pre-set options or customize your own. Reminders based on date, outdoor temperature or a dry contact input will alert customers with instructions to contact you for assistance.

Alerts give customers a sense of security while also enabling you to service or replace the equipment prior to a loss of heating or cooling. Based on limits you set at installation, customers can be alerted when their system is not operating as expected. The system alert will instruct customers to contact you for assistance. Requires EIM.

Delta T Installer Test

Save time by viewing Delta T while running a system test to verify proper operation. Requires EIM.

Universal Inputs – S1 and S2

Assignable inputs allow you to configure Indoor and Outdoor Temperature Sensors, Discharge and Return Air Sensors or Dry Contact Devices. Dry Contact Devices can be used to trip pre-set or customized alerts on the thermostat home screen. Requires EIM.

User Interaction Log

The interaction log stores history of thermostat setting changes including temperature, system and installer setup. You can use the interaction log to save time by determining if the issue is a system error or an accidental user error.

Configurable for Residential and Light Commercial Applications

One thermostat does it all to meet the needs of Residential and Light Commercial applications. Simply select Residential or Commercial during the installer setup. If Commercial is selected, the thermostat will use commercial language, meet building codes and offer 365 day holiday scheduling.

USB Port for Quick Installer Setup

Save time by using a USB stick to upload installer settings and service reminders in one simple step.

Selectable Sensors

When paired with a Wireless Indoor Sensor(s) you have the ability to choose which sensor(s) to use for temperature, humidification and dehumidification. They can be used in combination for temperature averaging—or individ- ually—to condition humidity levels in separate spaces.

TM

68-0311-01

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ 2.0 WITH EIM

CONTENTS

 

Application ...........................................

1

Specifications ......................................

3

Ordering Information ...........................

2

System Installation ..............................

6

When Installing this Product... .....................

6

Installing Equipment Interface Module (if used) 6

Wiring 24 Vac Common ................................

6

Discharge and Return Air Temperature Sensor

Mounting Locations ......................................

6

Discharge and Return Air Temperature Sensor Mounting

Locations .............................................................

6

Return Air Temperature Sensor Mounting Location

7

Selecting Thermostat Location ....................

8

Installing Wallplate ........................................

8

Install Optional Accessories ..............

9

Power Optional RedLINK™ Accessories ....

9

Link thermostat to EIM or TrueZONE® Wireless

Adapter ...........................................................

10

Link Optional RedLINK™ Accessories .......

11

Mount Optional Accessories ........................

13

Alerts and Diagnostics .......................

50

Delta T Diagnostics .......................................

50

Before You Set Up Delta T Diagnostics .......

51

Setting up Alerts and Diagnostics ...............

51

Delta T Alerts .................................................

54

Delta T Alerts and Utility Saver Switches ...

54

Data Logs .......................................................

55

Alerts Log .............................................................

55

User Interactions Log ...........................................

56

Dry Contact Alerts ........................................

57

Installer Setup ......................................

14

Set Date and Time .........................................

49

Fan settings ...................................................

50

System Settings ............................................

50

Installer Tests ......................................

48

How to Use the Equipment Test ..................

48

How to Use the Wireless Signal Strength Test 49

Indoor Air Quality (IAQ) Control .........

64

Humidification ...............................................

64

Set up Humidification ...........................................

64

Control Humidification Level .................................

66

Dehumidification - Residential .....................

66

Set up Dehumidification With Cooling System .....

67

Set up Dehumidification With Whole House Dehumidifier

68

 

Set up Dehumidification Away Mode ....................

69

Control Dehumidification Level .............................

70

Dehumidification - Commercial ...................

70

Set up Dehumidification With Cooling System .....

71

Set up Dehumidification With Dehumidifier ..........

72

Control Dehumidification Level .............................

74

Ventilation ......................................................

74

Set up Ventilation .................................................

75

IAQ Reminders .....................................

78

Customizable Reminders ...................

79

USB Port ...............................................

81

Operation .............................................

82

Residential Operation ...................................

84

Program Schedules ..............................................

84

To adjust program schedules ...............................

84

Program Schedule Override .................................

85

Utility Scheduling ..................................................

86

System Status Information ...................................

82

Vacation Scheduling .............................................

85

Commercial Operation ..................................

87

Program Schedules ..............................................

87

Program Schedule Override .................................

87

Program Override Modes .............................

88

Holiday/Event Scheduling .....................................

88

Holiday Override ...................................................

88

Initiate Occupancy mode ......................................

89

Menu: Preferences ........................................

82

Menu: Temporary Schedule Changes .........

85

Menu: Clean Screen ......................................

82

Menu: Security Settings ...............................

83

Menu: Dealer Information .............................

83

Advanced Features .......................................

84

Adaptive Intelligent Recovery (residential use only)

84

Compressor Protection .........................................

84

Heat Pump and Backup Heat Operation 62

Portable Comfort Control ...................

95

Remote Indoor Sensors ......................

96

Commercial Features ..........................

87

ORDERING INFORMATION

When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number. If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:

1.Your local Honeywell Environmental and Combustion Controls Sales Office (check white pages of your phone directory).

2.Honeywell Customer Care 1885 Douglas Drive North

Minneapolis, Minnesota 55422-4386

3.http://customer.honeywell.com or http://customer.honeywell.ca

International Sales and Service Offices in all principal cities of the world. Manufacturing in Belgium, Canada, China, Czech Republic, Germany, Hungary, Italy, Mexico, Netherlands, United Kingdom, and United States.

68-0311—01

2

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ 2.0 WITH EIM

Ramp Rates ....................................................

89

Custom Names ..............................................

90

Remote Setback .............................................

90

Economizer and Time of Day (TOD) Operation 91

Pre-Occupancy Purge ...................................

92

Staging Control ..............................................

59

Optional Accessories ..........................

94

Troubleshooting ...................................

124

Wiring ...................................................

102

EIM Wiring Diagrams .....................................

104

Geothermal Radiant Heat ..............................

62

THX9321 Thermostat Wiring Diagrams .......

107

THX9321 Thermostat Wiring Diagrams Using Uni-

versal Relays to Control Heating or Cooling 108

Wiring guide — IAQ Equipment (EIM or Thermo-

stat) .................................................................

115

Economizer Module Wiring Diagrams .........

116

Wiring C7089U1006 Outdoor Sensor ...........

118

Wiring guide — Wired Indoor Sensors ........

119

Regulatory Information .......................

124

SPECIFICATIONS

Accessories and Replacement Parts:

Item

Part Number

Prestige 2.0 Thermostat

THX9321R5030

 

 

Prestige IAQ 2.0 Thermostat

THX9421R5013

 

 

Equipment Interface Module

THM5421R1013

 

 

Wireless Adapter for TrueSTEAM and

THM4000R1000

TrueZONE

 

 

 

RedLINK Internet Gateway

THM6000R1002

 

 

Portable Comfort Control

REM5000R1001

 

 

Entry / Exit Remote

REM1000R1003

 

 

Vent Boost Remote

HVC20A1000

 

 

Occupancy Sensor for Remote Setback

WSK-24

 

 

Wireless Outdoor Sensor

C7089R1013

 

 

Wireless Indoor Sensor

C7189R1004

 

 

Wired Outdoor Sensor (10K ohm NTC -

C7089U1006

Negative Temperature Coefficient)

 

 

 

Wired Wall Mount Indoor Sensor (10K

C7189U1005

ohm NTC - Negative Temperature

 

Coefficient)

 

 

 

Wired Wall Mount Indoor Sensor (20K

TR21

ohm NTC - Negative Temperature

 

Coefficient)

 

 

 

Wired Wall Mount Indoor Sensor (10K

TR21-A

ohm NTC - Negative Temperature

 

Coefficient)

 

 

 

Wired Flush Mount Indoor Sensor (20K

C7772A1004

ohm NTC - Negative Temperature

 

Coefficient)

 

 

 

Wired Flush Mount Indoor Sensor (20K

C7772A1012

ohm NTC - Negative Temperature

 

Coefficient)

 

 

 

Discharge or Return Air Sensor (10K ohm

C7735A1000*

NTC - Negative Temperature Coefficient)

 

 

 

Discharge or Return Air Sensor (20K ohm

C7041

NTC - Negative Temperature Coefficient)

 

 

 

Discharge or Return Air Sensor (20K ohm

C7770A1006

NTC - Negative Temperature Coefficient)

 

 

 

Cover Plate (covers marks left by old

50028399-001

thermostats)

 

 

 

Battery Pack (for demo use only)

THP1000A1007

 

 

Wire Saver Module

THP9045A1023

 

 

*Prestige IAQ 2.0 Kits are packaged with 50062329-001 Discharge and Return Air Sensors. Replacement Discharge/ Return Air Sensor part number is C7735A1000.

3

68-0311—01

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ 2.0 WITH EIM

Thermostat Description:

Feature

 

 

Description

Powering method

Common wire only

 

 

 

 

 

 

 

System types (up to

Gas, oil or electric heat with air

4 heat/2 cool heat

 

conditioning

 

 

pump and up to 3

Warm air, hot water, high-efficiency

heat/2 cool

 

furnaces, heat pumps, steam and

conventional)

gravity

 

 

 

Cool only

 

 

 

 

 

 

 

Changeover

Manual or Auto changeover selectable

 

 

 

 

 

System setting

Em Heat-Heat-Off-Cool-Auto

 

 

 

 

 

Fan setting

Auto-On-Circ-Follow Schedule

 

 

 

 

 

 

Electrical Ratings:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage

Max. Current

 

Terminal

 

 

(50/60 Hz)

Rating

 

 

 

 

 

 

 

W - O/B

 

 

18 to 30 VAC and

1.00A

 

 

 

 

750 mVDC

 

 

 

 

 

 

 

 

Y (cooling)

 

 

18 to 30 VAC

1.00A

 

 

 

 

 

 

 

G (fan)

 

 

18 to 30 VAC

0.50A

 

 

 

 

 

 

 

W2 - Aux 1 (heating)

 

 

18 to 30 VAC

0.60A

 

 

 

 

 

 

 

Y2 (cooling)

 

 

18 to 30 VAC

0.60A

 

 

 

 

 

 

 

W3 - Aux 2

 

 

18 to 30 VAC

1.00A

 

 

 

 

 

 

 

A-L/A (Output)

 

 

18 to 30 VAC

1.00A

 

 

 

 

 

 

 

U1, U1

 

 

18 to 30 VAC

0.50A

 

 

 

 

 

 

 

U2, U2

 

 

18 to 30 VAC

0.50A

 

 

 

 

 

 

 

U3, U3

 

 

18 to 30 VAC

0.50A

 

 

 

 

 

 

 

Power Consumption of THX9421/THX9321:

Full brightness = 3.0 VA 1/2 brightness = 2.1 VA Backlight off = 1.9 VA

Operating Ambient Temperature:

THX9421/THX9321: 32 to 120 °F (0 to 48.9 °C) THM5421R1013: -40 to 165 °F (-40 to 73.9 °C) THM6000R1002: 32 to 120 °F (0 to 48.9 °C)

REM5000R1001: 32 to 120 °F (0 to 48.9 °C) REM1000R1003: 32 to 120 °F (0 to 48.9 °C) HVC20A1000: 32 to 120 °F (0 to 48.9 °C)

C7089R1013: -40 to 140 °F (-40 to 60 °C) C7089U1006: -40 to 120 °F (-40 to 48.9 °C) C7189R1004: 0 to 120 °F (-17.8 to 48.9 °C)

— For Optimal Battery Life: 35 to 114 °F (1.7 to 45.6 °C) C7189U1005: 45 to 88 °F (7 to 32 °C)

C7772A1004: 45 to 99 °F (7 to 37 °C) C7772A1012: 45 to 99 °F (7 to 37 °C) TR21: 45 to 99 °F (7 to 37 °C)

TR21-A: 45 to 99 °F (7 to 37 °C) C7735A1000: 0 to 200 °F (-17.8 to 93.3 °C) C7041:

C7770A1006: 45 to 99 °F (7 to 37 °C) THP1000A1007: 0 to 130 °F (-17.8 to 54.4 °C) THP9045A1023: -40 to 163 °F (-40 to 73 °C)

Shipping Temperature:

THX9421/THX9321: -20 to 120 °F (-28.9 to 48.9 °C) THM5421R1013: -20 to 165 °F (-28.9 to 73.9 °C) THM6000R1002: -20 to 120 °F (-28.9 to 48.9 °C) REM5000R1001: -20 to 120 °F (-28.9 to 48.9 °C)

REM1000R1003: -20 to 120 °F (-28.9 to 48.9 °C) HVC20A1000: -20 to 120 °F (-28.9 to 48.9 °C) C7089R1013: -40 to 120 °F (-40 to 48.9 °C) C7089U1006: -40 to 130 °F (-40 to 54.4 °C) C7189R1004: -20 to 120 °F (-28.9 to 48.9 °C) C7189U1005: -20 to 120 °F (-28.9 to 48.9 °C) C7772A1004: -40 to 150 °F (-40 to 65.5 °C) C7772A1012: -40 to 150 °F (-40 to 65.5 °C) TR21: -40 to 150 °F (-40 to 65.5 °C)

TR21-A: -40 to 150 °F (-40 to 65.5 °C) C7735A1000: -20 to 120 °F (-28.9 to 48.9 °C) C7041:

C7770A1006: -40 to 150 °F (-40 to 65.5 °C) THP1000A1007: 0 to 130 °F (-17.8 to 54.4 °C) THP9045A1023: -40 to 185 °F (-40 to 85 °C)

Operating Relative Humidity:

THX9421/THX9321: 5 to 90% non-condensing

THM5421R1013: 5 to 95% non-condensing

THM6000R1002: 5 to 90% non-condensing

REM5000R1001: 5 to 90% non-condensing

REM1000R1003: 5 to 90% non-condensing

HVC20A1000: 5 to 90% non-condensing

C7089R1013: 0 to 100% condensing

C7089U1006: 5 to 95% non-condensing

C7189R1004: 5 to 90% non-condensing

C7189U1005: 5 to 95% non-condensing

C7772A1004: 5 to 95% non-condensing

C7772A1012: 5 to 95% non-condensing

TR21: 5 to 95% non-condensing

TR21-A: 5 to 95% non-condensing

C7770A1006: 5 to 95% non-condensing

THP1000A1007: 5 to 90% non-condensing

THP9045A1023: 5 to 90% non-condensing

Temperature Setting Range:

Heating: 40 to 90 °F (4.5 to 32 °C).

Cooling: 50 to 99 °F (10 to 37 °C).

Humidification Setting Range:

10% to 60% RH.

Dehumidification Setting Range:

40% to 80% RH.

Humidity Display Range:

0% to 99%.

Cool Indication:

Prestige 2.0 and Prestige IAQ 2.0 displays “Cool On” when the thermostat turns the cooling on.

Heat Indication:

Prestige 2.0 and Prestige IAQ 2.0 displays “Heat On” when the thermostat turns the heating on.

Auxiliary Heat Indication:

Prestige 2.0 and Prestige IAQ 2.0 displays “Auxiliary Heat On” when the thermostat turns the auxiliary heat on.

Interstage Differential:

Comfort: The thermostat keeps the indoor temperature within 1 degree of the setpoint (droop less control). The thermostat turns on stage 2 when the capacity on stage 1 reaches 90%.

When the interstage differential is set to 1.0 or higher, the thermostat stages the equipment based on how far the indoor temperature is from the setpoint (ISU 3030 to 3090). See page 21 for more information.

68-0311—01

4

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ 2.0 WITH EIM

Clock Accuracy: ± 1 minute per month at 77 °F (25 °C). ± 2 minutes per month over the operating ambient temperature range.

Color/Finish:

THX9421/THX9321: Arctic White

THM5421R1013: Gray

THM6000R1002: Black

REM5000R1001: Arctic White / Gray

REM1000R1003: Arctic White

HVC20A1000: Arctic White

C7089R1013: Gray

C7189R1004: Arctic White

C7189U1005: Premier White

C7772A1004: Brushed Stainless Steel

C7772A1012: Brushed Stainless Steel

TR21: White

TR21-A: White

C7735A1000: Gray

50028399-001: Arctic White

THP1000A1007: Gray

THP9045A1023: Gray

Mounting Means:

Thermostat mounts directly on the wall in the living space using mounting screws and anchors provided. Fits a horizontal 2 x 4 in. junction box.

Equipment Interface Module (EIM) mounts on HVAC equipment or on a wall in the equipment room.

Dimensions:

THX9421 / THX9321: 3-7/8 x 6-13/16 x 1-7/16 inches (99 x 173 x 36 mm)

THM5421R1013: 9-5/16 x 4-13/16 x 1-19/32 inches (237 x 122 x 40.5 mm)

THM6000R1002: 6 x 4-7/8 x 2-1/2 inches (152 x 124 x 64 mm)

REM5000R1001: 6-1/4 x 3-1/8 x 1-5/8 inches (158 x 80 x 38 mm)

REM1000R1003: 3-15/16 x 1-15/16 x 5/8 inches (101 x 50 x 16 mm)

HVC20A1000: 3-15/16 x 1-15/16 x 5/8 inches (101 x 50 x 16 mm)

C7089R1013: 5 x 3-1/2 x 1-11/16 inches (127 x 89 x 43 mm)

C7089U1006 (mounting clip): 1-1/2 inches (38 mm)

C7189R1004: 2-7/8 x 1-7/8 x 15/16 inches (74 x 48 x24 mm)

C7189U1005: 2-9/32 x 1-1/2 x 11/16 inches (58 x 38 x 18 mm)

C7772A1004: 4-1/2 x 2-3/4 x 5/16 inches (114 x 70 x 8 mm)

C7772A1012: 4-1/2 x 2-3/4 x 5/16 inches (114 x 70 x 8 mm)

TR21:4-9/16 x 3 x 7/8 inches (116 x 76.5 x 22 mm)

TR21-A: 4-9/16 x 3 x 7/8 inches (116 x 76.5 x 22 mm)

C7735A1000: Probe: 3-3/4 x 1/4 inches (77 x 6.4 mm)

C7735A1000: Cap Diameter: 2-7/16 inches (62 mm)

C7041: 4-3/16 x 2-5/16 x 1-11/16 inches (107 x 59 x 43 mm)

C7770A1006: Probe: 6 x 1/4 inches (152 mm x 6.4 mm)

50028399-001: 5-1/2 x 7-7/8 (141 x 201 mm)

THP1000A1007: 6-1/2 x 3-11/16 x 1-1/8 inches (165 x 93.5 x 29 mm)

THP9045A1023: 2-7/8 x 3-3/8 x 15/16 inches (73 x 86 x 23 mm)

6-51/64 (173)

 

3-29/32

 

(99)

3-19/64 (84)

1-13/32

(36)

 

M33329

Fig. 1. Dimensions of thermostat in in. (mm).

7-29/32 (201)

3-19/64 (84)

5-1/2

(140)

M33330

Fig. 2. Dimensions of Prestige cover plate in in. (mm).

5

68-0311—01

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ 2.0 WITH EIM

4-53/64 (123)

1-19/32

(41)

 

8-7/8

(225)

9-11/32

(237)

M33331

Fig. 3. Dimensions of Equipment Interface Module in in. (mm).

SYSTEM INSTALLATION

When Installing this Product...

1.Read these instructions carefully. Failure to follow the instructions can damage the product or cause a hazardous condition.

2.Check the ratings given in the instructions to make sure the product is suitable for your application.

3.Installer must be a trained, experienced service technician.

4.After completing installation, use these instructions to verify the product operation.

Installing Equipment Interface Module (if used)

If no Equipment Interface Module is used, skip to “Selecting Thermostat Location” beginning on page 8.

CAUTION

Electrical Hazard.

Can cause electrical shock or equipment damage.

Disconnect power before wiring.

The Equipment Interface Module (EIM) can be mounted vertically on the HVAC equipment or on a wall in the equipment room.

1.Use screws & anchors as appropriate for the mounting surface. Mount the EIM near the HVAC equipment, or on the equipment itself.

2.To wire the EIM, strip 1/4” insulation, then insert wires (see Fig. 4). For wiring diagrams, see “Wiring” beginning on page 102.

R

 

C

 

W O/B

W2

AUX1

W3

AUX2

Y

 

Y2

G

 

L

 

MCR32389

MCR32388

Fig. 4.

Wiring 24 Vac Common

Single-Transformer System—Connect the common side of the transformer to the C screw terminal of the EIM. Leave the metal jumper wires in place between R, Rc, and RH.

Two-Transformer System—Connect the common side of the cooling transformer to the C screw terminal of the EIM. Remove the metal jumper wire between Rc and Rh. Connect the hot side of heating transformer to Rh and leave the jumper wire between R and Rc and connect the hot side of cooling transformer to R or Rc.

Discharge and Return Air Temperature Sensor Mounting Locations

Refer to the guidelines below and Fig. 5–9 for mounting locations of the Discharge and Return Air Temperature Sensors.

Discharge Air Temperature Sensor

Mounting Location

1.Mount the Discharge Air Temperature Sensor on the supply duct in a location where the air is mixed well. Mount the Discharge Air Temperature Sensor out of sight of the A-Coil/Heat Exchanger when possible. See Fig. 5.

2.When possible, mount the Discharge Air Temperature Sensor upstream of a Steam Humidifier, a Fan Powered Humidifier or a Dehumidifier that is ducted to the supply. See Fig. 6–7.

3.If space does not allow a Discharge Air Temperature Sensor upstream of a Steam Humidifier or Fan Powered Humidifier, mount the Discharge Air Temperature Sensor downstream of the Humidifier. See Fig. 6. When setting the Delta T Limits (see “Set Delta T Limits” on page 53), be sure to consider the affect that the humidifier has on Delta T.

4.If a Bypass Humidifier is installed, mount the Discharge Air Temperature Sensor downstream of the Bypass Humidifier. See Fig. 8–9.

68-0311—01

6

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ 2.0 WITH EIM

Return Air Temperature Sensor

Mounting Location

1.Install the Return Air Temperature Sensor on the return duct in a location where the air is mixed well. Mount the Return Air Temperature Sensor downstream of a Bypass Humidifier, Dehumidifier or Ventilator. See Fig. 5–9.

MOUNT DISCHARGE

SENSOR HERE

A-COIL

VENTILATOR

OR

DEHUMIDIFIER

MOUNT RETURN

SENSOR HERE

DOWNSTREAM OF

VENTILATOR OR

DEHUMIDIFIER

Fig. 5.

ALTERNATE MOUNTING LOCATION FOR DISCHARGE SENSOR. WHEN SETTING THE LIMITS, BE SURE TO CONSIDER THE AFFECT THAT THE HUMIDIFIER HAS ON DELTA T.

VENTILATOR

OR

DEHUMIDIFIER

MOUNT RETURN

SENSOR HERE

DOWNSTREAM OF

VENTILATOR OR

DEHUMIDIFIER

HEAT

EXCHANGER

BLOWER

M33074

STEAM OR

FAN

POWERED

HUMIDIFIER

MOUNT DISCHARGE SENSOR HERE

 

ABOVE CENTER

 

OF A-COIL

HEAT

UPSTREAM OF

STEAM OR FAN

EXCHANGER

POWERED

 

 

HUMIDIFIER

BLOWER

 

 

M33075A

ALTERNATE MOUNTING LOCATION FOR DISCHARGE

SENSOR. WHEN SETTING THE LIMITS, BE SURE

TO CONSIDER THE AFFECT THAT THE DEHUMIDIFIER

HAS ON DELTA T.

DEHUMIDIFIER

 

 

 

OF A-COIL

MOUNT RETURN

 

 

UPSTREAM OF

 

HEAT

DEHUMIDIFIER

SENSOR HERE

 

 

 

EXCHANGER

 

 

 

 

DOWNSTREAM OF

 

 

 

DEHUMIDIFIER

 

BLOWER

 

 

 

 

 

 

 

 

 

M33076A

 

 

 

Fig. 7.

VENTILATOR

OR

DEHUMIDIFIER

MOUNT RETURN

SENSOR HERE

MOUNT DOWNSTREAM OF BYPASS HUMIDIFIER, DEHUMIDIFIER OR VENTILATOR

 

MOUNT

BYPASS

DISCHARGE

SENSOR HERE

HUMIDIFIER

 

 

MOUNT

 

DOWNSTREAM

 

OF BYPASS

 

HUMIDIFIER

HEAT

EXCHANGER

BLOWER

M33078A

Fig. 8.

Fig. 6.

7

68-0311—01

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ 2.0 WITH EIM

 

MOUNT

 

BYPASS

DISCHARGE

NO

SENSOR HERE

HUMIDIFIER

YES

 

 

 

 

NO

VENTILATOR

 

 

OR

 

5 FEET

DEHUMIDIFIER

 

[1.5 METERS]

MOUNT RETURN

SENSOR HERE HEAT

EXCHANGER

MOUNT DOWNSTREAM

OF BYPASS HUMIDIFIER,

DEHUMIDIFIER OR

VENTILATOR

BLOWER

M33079A

Fig. 9.

INSTALLATION

Use the following steps to mount the Discharge/Return Air Sensors:

1.Attach plastic cover to the sensor probe.

2.Drill 1/4-inch hole for the sensor probe and mount it to the ductwork with enclosed screws (see Fig. 10).

3.Connect wires to S1 or S2 terminals at the EIM.

4.Configure the S1 or S2 terminals in the Installer Setup at the thermostat.

M32995

Fig. 10. Mounting Discharge/Return Air Sensor.

Selecting Thermostat Location

Install the thermostat about 5 ft. (1.5m) above the floor in an area with good air circulation at average temperature. See Fig. 11.

M19925

Fig. 11. Selecting thermostat location.

Do not install the thermostat where it can be affected by:

Drafts or dead spots behind doors and in corners.

Hot or cold air from ducts.

Radiant heat from sun or appliances.

Concealed pipes and chimneys.

Unheated (uncooled) areas such as an outside wall behind the thermostat.

Installing Wallplate

CAUTION

Electrical Hazard.

Can cause electrical shock or equipment damage.

Disconnect power before wiring.

The thermostat can be mounted horizontally on the wall or on a 4 in. x 2 in. (101.6 mm x 50.8 mm) wiring box.

1.Position and level the wallplate (for appearance only).

2.Use a pencil to mark the mounting holes.

3.Remove the wallplate from the wall and, if drywall, drill two 3/16-in. holes in the wall, as marked. For firmer material such as plaster, drill two 7/32-in. holes. Gently tap anchors (provided) into the drilled holes until flush with the wall.

4.Position the wallplate over the holes, pulling wires through the wiring opening. See Fig. 12.

5.Insert the mounting screws into the holes and tighten.

MCR29241

MCR32386

Fig. 12. Mounting wallplate.

68-0311—01

8

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ 2.0 WITH EIM

THX9421 Installation

INSTALLATION WITH EQUIPMENT INTERFACE MODULE (EIM)

1.Wire to C and R terminals of the EIM or to a separate 24 volt transformer (not provided). See Fig. 13.

2.Snap thermostat onto wallplate after wiring is complete.

INSTALLATION WITH TRUEZONE WIRELESS ADAPTER

1.Wire to C and R terminals of the TrueZONE panel or to a separate 24 volt transformer (not provided). See Fig. 13.

2.Snap thermostat onto wallplate after wiring is complete.

THX9321 Installation

THERMOSTAT WIRED DIRECTLY TO THE HVAC EQUIPMENT OR ZONE PANEL

1.Refer to “THX9321 Thermostat Wiring Diagrams” beginning on page 107.

2.Snap thermostat onto wallplate after wiring is complete.

INSTALLATION WITH EQUIPMENT INTERFACE MODULE (EIM)

1.Wire to C and R terminals of the EIM or to a separate 24 volt transformer (not provided). See Fig. 13.

2.Snap thermostat onto wallplate after wiring is complete.

NOTE: Note: When the THX9321 thermostat is used with an EIM, the relays in the thermostat do not function.

INSTALL OPTIONAL

ACCESSORIES

Power Optional RedLINK™

Accessories

1.If no wireless accessories are used, skip to “Link thermostat to EIM or TrueZONE® Wireless Adapter” beginning on page 10.

2.If no wireless accessories are used and there is no EIM or TrueZONE Wireless Adapter, skip to “Installer Setup” beginning on page 14.

3.Install batteries in the wireless accessories.

Outdoor air sensor

1.Install 2 fresh AA lithium batteries.

MCR32937

INSTALLATION WITH TRUEZONE WIRELESS ADAPTER

1.Wire to C and R terminals of the TrueZONE panel or to a separate 24 volt transformer (not provided). See Fig. 13.

2.Snap thermostat onto wallplate after wiring is complete.

NOTE: When the THX9321 thermostat is used with a TrueZONE Wireless Adapter, the relays in the thermostat do not function.

MCR32387

Fig. 13. Inserting wires in thermostat terminal block.

Fig. 14.

Portable Comfort Control

1.Install 3 fresh AA alkaline batteries.

MCR32939

Fig. 15.

Indoor air sensor

1.Install 2 fresh AAA alkaline batteries.

MCR32938

Fig. 16.

9

68-0311—01

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ 2.0 WITH EIM

RedLINK™ Internet Gateway

1.Connect power cord to an electrical outlet not controlled by a wall switch.

2.Connect ethernet cable to router and the RedLINK Internet Gateway.

Entry/Exit Remote or Vent Boost Remote

1.Remove the cover.

2.Insert the CR2450 coin cell battery (included) into the slot at the bottom of the remote. See polarity marking on the remote.

M32940

Fig. 17.

TrueSTEAM

1.Wire and power TrueSTEAM.

2.Connect the ABCD terminals between TrueSTEAM and the THM4000 Wireless Adapter.

3.Adjust the DIP Switches on TrueSTEAM as follows when using the Wireless Adapter:

DIP3: UP

DIP4: UP

DIP5: DOWN

TrueSTEAM

THM4000R1000

1

2

3

4

5

6

ON

OFF

MCR31476

Fig. 18. Powering TrueSTEAM wireless adapter.

MCR33269

Fig. 19. Installing Entry/Exit Remote or Vent Boost Remote battery.

3.The LED will briefly flash green. If it flashes red, battery is not good.

Link thermostat to EIM or TrueZONE® Wireless Adapter

If no EIM or TrueZONE® Wireless Adapter are used, skip to “Link Optional RedLINK™ Accessories” beginning on page 11.

1.Press and release the CONNECT button at the EIM or Wireless Adapter, and make sure the “Connected” light is flashing green.

CONNECTED

S2

S2

CONNECT

S1

S1

MCR32941

Fig. 20. EIM CONNECT button.

2.If the “Connected” light does not flash, make sure no other RedLINK devices are in Wireless Setup mode, then try again.

NOTE: If the “Power” light at the Wireless Adapter does not turn on, consult the TrueZONE manual for help.

3.While the “Connected” light is flashing, follow the prompts on the thermostat screen until you reach the Wireless Setup screen.

4.Press NEXT to link the thermostat. After a brief delay, the screen will display “Device Connected.”

68-0311—01

10

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ 2.0 WITH EIM

Fig. 21.

NOTE: If the thermostat did not connect to the EIM or Wireless Adapter, verify the “Connected” LED is still flashing and the thermostat is at least 2 feet away from the EIM or Wireless Adapter, and repeat steps 1–4 above.

“Connected” Status Light (Fig. 20)

Green flashing: In Wireless Setup mode.

Green steady: RedLINK device(s) are communicating.

Red: RedLINK device(s) not communicating. Check EIM and RedLINK devices.

Link Optional RedLINK™ Accessories

NOTE: If you are not connecting any RedLINK devices, skip to “Installer Setup” beginning on page 14.

1.While the Add Device screen (see Fig. 22) is displayed on the thermostat, press and release the CONNECT button on each wireless device. Accessories need to be at least 2 feet away from the thermostat, EIM, or TrueZONE Wireless Adapter during the linking process.

Fig. 22. Add Device screen.

2.Press DONE on the Add Device screen after ALL devices have been linked (see Fig. 22).

NOTE: If you need to return to the “Add Device” screen to add devices later, press MENU and scroll down to INSTALLER OPTIONS. Enter the date code (password) when prompted. The date code is printed on the back of the thermostat or

press MENU > EQUIPMENT STATUS to find the date code. Scroll down to WIRELESS DEVICE MANAGER and then select ADD DEVICE.

Link Wireless Outdoor Sensor

1.Press and release the CONNECT button. After a short delay, the thermostat will display “Wireless Outdoor Sensor added” on the Add Device screen.

MCR28847A

Fig. 23. Wireless outdoor sensor connect button.

Link Portable Comfort Control

1.Press CONNECT on the Portable Comfort Control display screen.

CONNECT

WIRELESS SETUP

MCR32942

Fig. 24. Portable Comfort Control connect button.

2.Press DONE on the Portable Comfort Control when it displays “Connected.”

3.Press “No” at the next screen to save and exit, or press “Yes” if you need to connect additional thermostats to the Portable Comfort Control. See Fig. 25.

NOTE: The Portable Comfort Control can control up to 16 thermostats.

YES NO

CONNECT MORE?

M28482

Fig. 25. Connect additional thermostats to Portable Comfort Control.

4.Follow the same linking procedure as above to connect additional thermostats.

11

68-0311—01

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ 2.0 WITH EIM

ERROR MESSAGES:

E1 29: Incompatible device cannot be connected.

E1 34: Low RF signal. Move device to a different location and try again.

E1 38: Make sure the thermostat, EIM, or TrueZONE Wireless Adapter is in Wireless Setup mode, and the Portable Comfort Control is at least 2 feet away (600 mm).

NOTE: The linking procedure will time out if there is no keypress for 30 minutes. To begin again, press and hold in the lower right corner of the screen until the display changes (about 3 seconds). See Fig. 26.

Link TrueSTEAM

1.Press and release the CONNECT button on THM4000 Wireless Adapter. After a short delay, the CONNECTED status light will glow steady green.

Link Wireless Indoor Sensor

1.Press and release the CONNECT button. After a short delay, the status light (see Fig. 25) will glow green for 15 seconds. If the status light turns red, the sensor did not link with the thermostat.

Press and hold the blank space (or arrow may be present)

Fig. 26. Restarting the linking process.

MCR32934

MCR32935

Fig. 28. Wireless indoor sensor connect button and status light.

NOTE: In normal operation, the status light remains off. If it begins flashing red, batteries are low (power will be depleted after 2–3 weeks).

2.If you are installing more than 1 wireless indoor sensor, give each sensor a name as you install it. Press Name Device, as shown in Fig. 29.

Link RedLINK Internet Gateway

1.Press and release the button on the bottom of the Internet Gateway. After a short delay, the RedLINK status light will glow steady green.

MCR32943

Fig. 27. RedLINK Internet Gateway connect button.

NOTE: The Internet Gateway must be registered online before use at www.mytotalconnectcomfort.com. Enter the MAC ID and MAC CRC numbers located on the bottom of the Internet Gateway. For additional information, see instructions provided with the device.

Fig. 29.

3.Type the sensor name and press Done. The sensor names are used when selecting which sensor to use for temperature, humidification, and dehumidification control.

Fig. 30.

68-0311—01

12

Honeywell THX9421, THX9321 User Manual

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ 2.0 WITH EIM

NOTE: If you link more than 1 wireless indoor sensor, and forget to name them, you will be prompted to name each wireless indoor sensor after you exit wireless setup. See Fig. 31.

Fig. 31.

Link Entry/Exit Remote or Vent Boost Remote

1.Press and release CONNECT button.

• where snow, ice or debris can cover it.

MOUNTING C7089R1013 WIRELESS OUTDOOR SENSOR

Use the following steps to mount the sensor (see Fig. 33):

1.Mount the sensor on a vertical exterior wall, at least 6 inches below any overhang. Choose a location protected from direct sunlight.

2.Place sensor securely in bracket, facing away from wall.

M28491

MCR33096

Fig. 32. Connect button and status light on Entry/Exit Remote or Vent Boost Remote.

2.After a short delay, the status light will glow green for 15 seconds. If the status light turns red, the remote did not link with the thermostat for the connection process.

NOTE: The thermostat can work with up to 3 Entry/Exit remotes. Each Entry/Exit remote can control up to 16 thermostats.

NOTE: The thermostat can work with up to 6 Vent Boost remotes.

Mount Optional Accessories

Mounting Outdoor Sensor

Mount the sensor where:

it cannot be tampered with.

there is good air circulation.

it can measure true outdoor ambient temperature and humidity.

wire distance between C7089U1006 and EIM is less than 200 feet (wired sensor only).

Do not mount the sensor:

in direct sunlight.

where hot or cold air blows on the sensor. Discharge line from an outdoor compressor unit, vent or fan causes inaccurate temperature readings.

M28849A

Fig. 33. Mounting Outdoor Sensor.

MOUNTING C7089U1006 WIRED OUTDOOR

TEMPERATURE SENSOR

Use the following steps to mount the sensor:

1.Remove the sensor from the mounting clip.

2.Mark the area on the location selected for mounting the sensor mounting clip.

3.Mount the clip.

4.See “Wiring C7089U1006 Outdoor Sensor” on page 118.

M7514

Fig. 34. Typical locations for C7089U1006 Outdoor Sensor.

13

68-0311—01

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ 2.0 WITH EIM

Mounting C7189R1004 Wireless Indoor

Sensor

Use the following steps to mount the sensor (see Fig. 35):

1.Remove the wallplate and mount it 4 to 6 feet above the floor on an interior wall. Drill 3/16-inch holes for drywall, 7/32-inch for plaster.

2.Attach sensor securely to wallplate as shown.

M32936

Fig. 35. Mounting Indoor Sensor.

M24057

Fig. 37. Mount wallplate to wall.

6.Replace the cover on the remote sensor.

7.When you finish linking wireless devices, the thermostat automatically enters Installer Setup. See “Installer Setup” beginning on page 14.

Mounting Entry/Exit Remote or Vent Boost Remote

Mounting C7189U1005 Wired Indoor Sensor

Use the following steps to mount the sensor:

1.Remove the cover from the remote sensor (see Fig. 36).

Mounting the remote is optional.

1.Remove the front cover from the remote.

2.Use provided screws and wall anchors to fasten the remote to the wall. Drill 3/16-inch holes for drywall, 7/32inch for plaster.

M24056

Fig. 36. Remove the cover.

2.Pull wires through wire hole.

3.Position wallplate on wall, level and mark screw hole positions with pencil.

4.Drill holes at marked positions, then tap in supplied wall anchors.

5.Place wallplate over anchors, insert and tighten mounting screws (see Fig. 37).

M33095

Fig. 38. Mounting Entry/Exit Remote or Vent Boost Remote.

3.Replace the cover on the remote.

INSTALLER SETUP

When you finish linking wireless devices, the thermostat automatically enters Installer Setup. The steps below explain how to enter Installer Setup from the Home screen.

To set up the thermostat, press MENU and scroll down to INSTALLER OPTIONS. Enter the date code (password) when prompted. The date code is printed on the back of the thermostat or press MENU > EQUIPMENT STATUS to find the date code.

1.Press CREATE SETUP to set all system settings one by one.

2.Press VIEW/EDIT CURRENT SETUP to select a specific function and make quick changes.

68-0311—01

14

 

 

 

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ 2.0 WITH EIM

 

 

 

 

 

 

Table 1. Installer Options.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Menu Item

 

 

Description

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Create Setup

 

Press CREATE SETUP to set all system

 

 

 

 

 

 

 

 

settings one by one.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

View/Edit

 

Press VIEW/EDIT CURRENT SETUP to

 

 

 

 

 

Current Setup

 

select a specific function and make quick

 

 

 

 

 

 

 

 

changes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Set Up

 

Press SET UP DIAGNOSTICS to set up

 

 

 

 

 

Diagnostics

 

and test Delta T diagnostics.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Installer Test

 

Press INSTALLER TEST to quickly

 

 

 

 

 

 

 

 

determine if the heat, cool, fan and

 

 

 

 

 

 

 

 

thermostat are operating properly. Minimum

 

 

 

 

 

 

 

 

off timers are ignored during the test

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Data Logs

 

Press DATA LOGS to view the Alerts Log

 

 

 

 

 

 

 

 

and User Interactions Log.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wireless Device

Press WIRELESS DEVICE MANAGER to

 

 

 

 

 

Manager

 

add or remove wireless accessories

 

 

Fig. 39. Installer Options screen.

 

 

 

 

 

 

 

 

 

Advanced

 

Press ADVANCED OPTIONS to setup the

 

 

 

 

 

Options

 

thermostat using a USB device or to restore

 

 

 

 

 

 

 

 

the thermostat to the factory default

 

 

 

 

 

 

 

 

settings.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: You can use the thermostat USB port to download

 

 

 

 

 

all Installer Setup settings, including your com-

 

 

 

 

 

pany name and contact information. You can

 

 

 

 

 

upload this data to each thermostat you install, to

 

 

 

 

 

save time.

 

 

 

 

Table 2. Installer Setup (ISU) Table.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Residential,

 

 

 

 

ISU

 

 

 

 

Commercial

Requires

 

 

Number

Installer Setup Name

Settings

Default

 

or Both

 

EIM

Notes

 

 

 

 

 

 

 

 

 

 

1000

Language

English

English

 

Both

No

 

 

 

 

 

Français

 

 

 

 

 

 

 

 

 

Español

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1010

Application

Residential

Residential

 

Both

No

 

 

 

 

 

Commercial

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1020

Zone Number

1-16

1

 

Both

No

 

This ISU is only displayed on a thermostat that is

 

 

 

 

 

 

 

 

controlling a zone panel through the THM4000

 

 

 

 

 

 

 

 

Wireless Adapter.

 

 

 

 

 

 

 

 

 

1030

Device Name

[Enter Device Name]

Thermostat

 

Both

No

 

The Portable Comfort Control remote and Web

 

 

 

 

 

 

 

 

Interface displays the name of the thermostat that

 

 

 

 

 

 

 

 

you enter on this screen.

 

 

 

 

 

 

 

 

 

1030

Display on Home

No

No

 

Commercial

No

 

Thermostat location (name) can be displayed on the

 

Screen

Yes

 

 

 

 

 

home screen. This feature is typically used when

 

 

 

 

 

 

 

multiple thermostat's are mounted in a manager's

 

 

 

 

 

 

 

 

 

 

(select check box)

 

 

 

 

 

office or equipment room. This allows you to

 

 

 

 

 

 

 

 

quickly identify which thermostat is in control of a

 

 

 

 

 

 

 

 

specific zone or area.

 

 

 

 

 

 

 

 

 

 

1040

Scheduling Options

Non-Programmable

Programmable

 

Both

No

 

 

 

 

 

Programmable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1050

Temperature

Fahrenheit

Fahrenheit

 

Both

No

 

 

 

 

Indication Scale

Celsius

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

68-0311—01

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ 2.0 WITH EIM

Table 2. Installer Setup (ISU) Table. (Continued)

 

 

 

 

Residential,

 

 

ISU

 

 

 

Commercial

Requires

 

Number

Installer Setup Name

Settings

Default

or Both

EIM

Notes

1060

Outdoor Air Sensor

No

No

Both

No

This ISU automatically defaults to Yes when a

 

 

Yes

 

 

 

Wireless Outdoor Sensor is connected.

 

 

 

 

 

 

 

 

 

 

 

 

An Outdoor Sensor is required to set the following

 

 

 

 

 

 

ISUs:

 

 

 

 

 

 

ISU 3120 Outdoor Temperature Lockouts

 

 

 

 

 

 

(Compressor Lockout and Backup Heat Lockout)

 

 

 

 

 

 

ISU 4050 Outdoor Temperature used with Minimum

 

 

 

 

 

 

Heat Recovery Ramp Rate

 

 

 

 

 

 

ISU 4060 Outdoor Temperature used with

 

 

 

 

 

 

Maximum Heat Recovery Ramp Rate

 

 

 

 

 

 

ISU 4070 Outdoor Temperature used with Minimum

 

 

 

 

 

 

Cool Recovery Ramp Rate

 

 

 

 

 

 

ISU 4080 Outdoor Temperature used with

 

 

 

 

 

 

Maximum Cool Recovery Ramp Rate

 

 

 

 

 

 

ISU 8050 Humidification - Window Protection

 

 

 

 

 

 

ISU 10130 Ventilation Low Temperature Lockout

 

 

 

 

 

 

ISU 10130 Ventilation High Temperature Lockout

 

 

 

 

 

 

ISU 10130 Ventilation High Dew Point Lockout

 

 

 

 

 

 

(requires Wireless Outdoor Sensor)

 

 

 

 

 

 

ISU 13070 Allow Heat Delta T Diagnostics when

 

 

 

 

 

 

Outdoor Temperature is [Out. Temp. Range]

 

 

 

 

 

 

ISU 13080 Allow Heat Delta T Diagnostics when

 

 

 

 

 

 

Outdoor Humidity is [Out. Humidity Range]

 

 

 

 

 

 

ISU 13110 Allow Backup Heat Delta T Diag. when

 

 

 

 

 

 

Outdoor Temperature is [Out. Temp. Range]

 

 

 

 

 

 

ISU 13120 Allow Backup Heat Delta T Diagnostics

 

 

 

 

 

 

when Outdoor Humidity is [Out. Humidity Range]

 

 

 

 

 

 

ISU 13150 Allow Cool Delta T Diagnostics when

 

 

 

 

 

 

Outdoor Temperature is [Out. Temp. Range]

 

 

 

 

 

 

ISU 13160 Allow Cool Delta T Diagnostics when

 

 

 

 

 

 

Outdoor Temperature is [Out. Humidity Range]

 

 

 

 

 

 

 

2000

Heating System Type

Conventional Forced Air Heat

Conventional

Both

No

 

 

 

Heat Pump

Forced Air Heat

 

 

 

 

 

 

 

 

 

 

 

Radiant Heat

 

 

 

 

 

 

Other

 

 

 

 

 

 

None (Cool Only)

 

 

 

 

 

 

 

 

 

 

 

2010

Heating Equipment

Conventional Forced Air Heat:

Default varies

Both

No

Cycle Rate and Fan Operation automatically default

 

Type

Standard Efficiency Gas Forced Air

based on

 

 

to the correct settings based on the equipment type

 

 

High Efficiency Gas Forced Air

previous

 

 

selected.

 

 

selections

 

 

This ISU is not displayed when ISU 2000 Heating

 

 

Oil Forced Air

 

 

 

 

 

 

 

 

System Type is set to None (Cool Only).

 

 

Electric Forced Air

 

 

 

 

 

 

 

 

See “Geothermal Radiant Heat” beginning on

 

 

Hot Water Fan Coil

 

 

 

 

 

 

 

 

page 62.

 

 

Other

 

 

 

 

 

 

 

 

 

 

 

Heat Pump:

 

 

 

 

 

 

Air to Air Heat Pump

 

 

 

 

 

 

Geothermal Heat Pump

 

 

 

 

 

 

Geothermal Radiant Heat

 

 

 

 

 

 

Radiant Heat:

 

 

 

 

 

 

Hot Water Radiant Heat

 

 

 

 

 

 

Geothermal Radiant Heat

 

 

 

 

 

 

Steam

 

 

 

 

 

 

Other

 

 

 

 

 

 

Other:

 

 

 

 

 

 

Gravity

 

 

 

 

 

 

Other

 

 

 

 

 

 

 

 

 

 

 

68-0311—01

16

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ 2.0 WITH EIM

Table 2. Installer Setup (ISU) Table. (Continued)

 

 

 

 

Residential,

 

 

ISU

 

 

 

Commercial

Requires

 

Number

Installer Setup Name

Settings

Default

or Both

EIM

Notes

2030

What Terminals are

None

Default varies

Both

No

This ISU is only displayed when ISU 2010 Heating

 

Wired to Radiant

U1

based on

 

 

Equipment Type is Geothermal Radiant Heat.

 

Heat?

previous

 

 

 

 

 

 

 

 

 

 

U2

selections

 

 

Geothermal Radiant Heat must be wired to a

 

 

U3

 

 

 

universal terminal (U1, U2, or U3).

 

 

 

 

 

 

 

 

 

 

 

 

U1, U2 and U3 are normally open dry contacts when

 

 

 

 

 

 

configured for a stage of Heat. U1, U2 and U3

 

 

 

 

 

 

require power from the system transformer or a

 

 

 

 

 

 

separate transformer.

 

 

 

 

 

 

U3 is only available on the Equipment Interface

 

 

 

 

 

 

Module (EIM).

 

 

 

 

 

 

 

2040

What Terminals are

None

Default varies

Both

No

This ISU is only displayed when ISU 2010 Heating

 

Wired to Radiant Heat

U1

based on

 

 

Equipment Type is Geothermal Radiant Heat.

 

- Stage 2?

 

previous

 

 

 

 

 

U2

selections

 

 

Geothermal Radiant Heat must be wired to a

 

 

U3

 

 

 

universal terminal (U1, U2, or U3).

 

 

 

 

 

 

 

 

 

 

 

 

U1, U2 and U3 are normally open dry contacts when

 

 

 

 

 

 

configured for a stage of Heat. U1, U2 and U3

 

 

 

 

 

 

require power from the system transformer or a

 

 

 

 

 

 

separate transformer.

 

 

 

 

 

 

U3 is only available on the Equipment Interface

 

 

 

 

 

 

Module (EIM).

 

 

 

 

 

 

 

2050

Geothermal Forced

None

Used for Heating

Both

No

This thermostat has the capability of controlling

 

Air System

Used for Cooling Only

and Cooling

 

 

Geothermal Radiant Heat, Geothermal Forced Air

 

 

 

 

 

and Backup Heat.

 

 

Used for Heating and Cooling

 

 

 

 

 

 

 

 

If this thermostat is not controlling the Geothermal

 

 

 

 

 

 

 

 

 

 

 

 

Forced Air System, select None. This setting is

 

 

 

 

 

 

typically used if the thermostat is only controlling

 

 

 

 

 

 

Geothermal Radiant Heat.

 

 

 

 

 

 

If this thermostat is using the Geothermal Forced

 

 

 

 

 

 

Air System for cooling and not for heating, select

 

 

 

 

 

 

Used for Cooling Only.

 

 

 

 

 

 

If this thermostat is using the Geothermal Forced

 

 

 

 

 

 

Air System for both heating and cooling, select

 

 

 

 

 

 

Used for Heating and Cooling.

 

 

 

 

 

 

 

2060

Reversing Valve O/B

O (O/B on Cool)

O/B on Cool

Both

No

Only displayed if the equipment type is Air to Air

 

 

B (O/B on Heat)

 

 

 

Heat Pump, Geothermal Heat Pump or Geothermal

 

 

 

 

 

Radiant Heat.

 

 

 

 

 

 

 

 

 

 

 

 

 

2070

Cool Stages /

1-4

1 if ISU 1010 is

Both

No

Conventional:

 

Compressor Stages

 

Residential

 

 

Cool Stage 3 and 4 are only available if ISU 1010 is

 

 

 

2 if ISU 1010 is

 

 

Commercial.

 

 

 

 

 

 

 

 

 

Commercial

 

 

Cool Stage 3 and 4 must be wired to a universal

 

 

 

 

 

 

terminal (U1, U2 or U3).

 

 

 

 

 

 

Heat Pumps:

 

 

 

 

 

 

Maximum of 2 Compressor Stages for heat pump

 

 

 

 

 

 

systems.

 

 

 

 

 

 

 

2020,

Heat Stages / Backup

1 - 3

Default is 1 stage

Both

No

Maximum of 3 Heat Stages for conventional

2070

Heat Stages

 

if ISU 1010

 

 

systems.

 

 

 

Application is

 

 

Maximum of 2 Backup Heat Stages for systems with

 

 

 

Residential

 

 

 

 

 

Default is 2

 

 

more than 1 heating equipment type.

 

 

 

 

 

 

 

 

 

stages if ISU

 

 

 

 

 

 

1010 Application

 

 

 

 

 

 

is Commercial

 

 

 

 

 

 

 

 

 

 

17

68-0311—01

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ 2.0 WITH EIM

Table 2. Installer Setup (ISU) Table. (Continued)

 

 

 

 

Residential,

 

 

ISU

 

 

 

Commercial

Requires

 

Number

Installer Setup Name

Settings

Default

or Both

EIM

Notes

2080

What Terminals are

None

Default varies

Commercial

No

Cool Stage 3 is only available if ISU 1010 is

 

Wired to Cool - Stage

U1

based on

 

 

Commercial.

 

3?

 

previous

 

 

 

 

 

U2

selections

 

 

Cool Stage 3 must be wired to a universal terminal

 

 

U3

 

 

 

(U1, U2 or U3).

 

 

 

 

 

 

 

 

 

 

 

 

U1, U2 and U3 are normally open dry contacts when

 

 

 

 

 

 

configured for a stage of Cool. U1, U2 and U3

 

 

 

 

 

 

require power from a system transformer or a

 

 

 

 

 

 

separate transformer.

 

 

 

 

 

 

U3 is only available on the Equipment Interface

 

 

 

 

 

 

Module (EIM).

 

 

 

 

 

 

 

2090

What Terminals are

None

Default varies

Commercial

No

Cool Stage 4 is only available if ISU 1010 is

 

Wired to Cool - Stage

U1

based on

 

 

Commercial.

 

4?

 

previous

 

 

 

 

 

U2

selections

 

 

Cool Stage 4 must be wired to a universal terminal

 

 

U3

 

 

 

(U1, U2 or U3).

 

 

 

 

 

 

 

 

 

 

 

 

U1, U2 and U3 are normally open dry contacts when

 

 

 

 

 

 

configured for a stage of Cool. U1, U2 and U3

 

 

 

 

 

 

require power from a system transformer or a

 

 

 

 

 

 

separate transformer.

 

 

 

 

 

 

U3 is only available on the Equipment Interface

 

 

 

 

 

 

Module (EIM).

 

 

 

 

 

 

 

2100

What Terminals are

None

Default varies

Both

No

THX9321 Thermostat Only:

 

Wired to Heat - Stage

U1

based on

 

 

This ISU is only displayed on the THX9321

 

3?

 

previous

 

 

thermostat when it is wired directly to the

 

 

U2

selections

 

 

equipment (Equipment Interface Module is NOT

 

 

U3

 

 

 

used).

 

 

 

 

 

 

 

 

 

 

 

 

Heat Stage 3 must be wired to a universal terminal

 

 

 

 

 

 

(U1 or U2).

 

 

 

 

 

 

U1 and U2 are normally open dry contacts when

 

 

 

 

 

 

configured for a stage of Heat. U1 and U2 require

 

 

 

 

 

 

power from a system transformer or a separate

 

 

 

 

 

 

transformer.

 

 

 

 

 

 

 

2110

Fan Operation in Heat

No Fan

Thermostat

Both

No

This ISU is only displayed when ISU 2010 Heating

 

 

Equipment Controls Fan

Controls Fan

 

 

Equipment Type is Electric Forced Air, Hot Water

 

 

 

 

 

Fan Coil or Other.

 

 

Thermostat Controls Fan

 

 

 

 

 

 

 

 

The thermostat automatically defaults to Equipment

 

 

 

 

 

 

 

 

 

 

 

 

Controls Fan when ISU 2010 Heating Equipment

 

 

 

 

 

 

Type is Standard Efficiency Gas Forced Air, High

 

 

 

 

 

 

Efficiency Gas Forced Air or Oil Forced Air.

 

 

 

 

 

 

No Fan is only displayed when ISU 2010 Heating

 

 

 

 

 

 

Equipment Type is Other.

 

 

 

 

 

 

 

2120

Backup Heat Type

None

None

Both

No

This ISU is only displayed when ISU 2010 Heating

 

 

Standard Efficiency Gas Forced Air

 

 

 

Equipment Type is Hot Water Radiant Heat,

 

 

 

 

 

Steam, Hot Water Fan Coil, Electric Forced Air or

 

 

High Efficiency Gas Forced Air

 

 

 

 

 

 

 

 

Other.

 

 

Oil Forced Air

 

 

 

The list of Backup Heat Types will vary based on the

 

 

Electric Forced Air

 

 

 

 

 

 

 

 

type of primary heat selected at ISU 2010 Heating

 

 

Hot Water Fan Coil

 

 

 

Equipment Type.

 

 

 

 

 

 

 

 

Hot Water Radiant Heat

 

 

 

When ISU 2010 Heating Equipment Type is Hot

 

 

Other

 

 

 

Water Radiant Heat, the thermostat keeps the Hot

 

 

 

 

 

Water Radiant Heat on when it calls for Backup

 

 

 

 

 

 

 

 

 

 

 

 

Heat.

 

 

 

 

 

 

When ISU 2010 Heating Equipment Type is Steam,

 

 

 

 

 

 

the thermostat keeps the Steam Heat on when it

 

 

 

 

 

 

calls for Backup Heat.

 

 

 

 

 

 

When ISU 2010 Heating Equipment Type is Hot

 

 

 

 

 

 

Water Fan Coil, Electric Forced Air or Other, you

 

 

 

 

 

 

can select how the backup operates. See ISU 2150

 

 

 

 

 

 

Backup Heat Operation.

 

 

 

 

 

 

 

2130

Backup Heat Stages

0 - 2

1

Both

No

This ISU is only displayed when a backup heat

 

 

 

 

 

 

source is selected at ISU 2120 Backup Heat Type.

 

 

 

 

 

 

Maximum of 2 Backup Heat stages.

 

 

 

 

 

 

 

68-0311—01

18

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ 2.0 WITH EIM

Table 2. Installer Setup (ISU) Table. (Continued)

 

 

 

 

Residential,

 

 

ISU

 

 

 

Commercial

Requires

 

Number

Installer Setup Name

Settings

Default

or Both

EIM

Notes

2140

What Terminals are

None

Default varies

Both

No

THX9321 Thermostat Only:

 

Wired to Backup

U1

based on

 

 

This ISU is only displayed on the THX9321

 

Heat?

previous

 

 

thermostat when it is wired directly to the

 

 

 

 

 

 

U2

selections

 

 

equipment (Equipment Interface Module is NOT

 

 

 

 

 

 

used).

 

 

 

 

 

 

The thermostat can support up to 3 conventional

 

 

 

 

 

 

heat stages. When there are a total of 3

 

 

 

 

 

 

conventional heat stages, the last stage of heat

 

 

 

 

 

 

must be wired to U1 or U2.

 

 

 

 

 

 

U1 and U2 are normally open dry contacts when

 

 

 

 

 

 

configured for a stage of Heat. U1 and U2 require

 

 

 

 

 

 

power from a system transformer or a separate

 

 

 

 

 

 

transformer.

 

 

 

 

 

 

 

2150

Backup Heat

NOT Allowed to Run with Primary

NOT allowed to

Both

No

This ISU is only displayed when ISU 2010 Heating

 

Operation

Heat

run with Primary

 

 

Equipment Type is Hot Water Fan Coil, Electric

 

 

Allowed to Run with Primary Heat

Heat

 

 

Forced Air or Other.

 

 

 

 

 

 

When ISU 2010 Heating Equipment Type is Hot

 

 

 

 

 

 

Water Fan Coil, Electric Forced Air or Other, you

 

 

 

 

 

 

can select how the Backup Heat operates. The

 

 

 

 

 

 

thermostat can be setup to keep the primary heat

 

 

 

 

 

 

source on when it calls for Backup Heat or the

 

 

 

 

 

 

thermostat can be setup to turn off the primary heat

 

 

 

 

 

 

source when it calls for Backup Heat.

 

 

 

 

 

 

When ISU 2010 Heating Equipment Type is Hot

 

 

 

 

 

 

Water Radiant Heat, the thermostat keeps the Hot

 

 

 

 

 

 

Water Radiant Heat on when it calls for Backup

 

 

 

 

 

 

Heat.

 

 

 

 

 

 

When ISU 2010 Heating Equipment Type is Steam,

 

 

 

 

 

 

the thermostat keeps the Steam Heat on when it

 

 

 

 

 

 

calls for Backup Heat.

 

 

 

 

 

 

 

2160

Backup Heat Fan

No Fan

Thermostat

Both

No

This ISU is only displayed for conventional systems

 

Operation

Equipment Controls Fan

Controls Fan

 

 

when ISU 2120 Backup Heat Type is Electric Forced

 

 

 

 

 

Air, Hot Water Fan Coil or Other.

 

 

Thermostat Controls Fan

 

 

 

 

 

 

 

 

Backup Heat Fan Operation automatically defaults to

 

 

 

 

 

 

 

 

 

 

 

 

Equipment Controls Fan when ISU 2120 Backup

 

 

 

 

 

 

Heat Type is Standard Efficiency Gas Forced Air,

 

 

 

 

 

 

High Efficiency Gas Forced Air or Oil Forced Air.

 

 

 

 

 

 

No Fan is only displayed when ISU 2120 Backup

 

 

 

 

 

 

Heat Type is Other.

 

 

 

 

 

 

 

2170

What Terminals are

None

Default varies

Both

No

THX9321 Thermostat Only:

 

Wired to Backup Heat

U1

based on

 

 

This ISU is only displayed on the THX9321

 

- Stage 2?

 

previous

 

 

thermostat when it is wired directly to the

 

 

U2

selections

 

 

equipment (Equipment Interface Module is NOT

 

 

 

 

 

 

used).

 

 

 

 

 

 

The thermostat can support up to 2 backup heat

 

 

 

 

 

 

stages for heat pump applications. When there are 2

 

 

 

 

 

 

backup heat stages, backup heat stage 2 must be

 

 

 

 

 

 

wired to U1 or U2.

 

 

 

 

 

 

U1 and U2 are normally open dry contacts when

 

 

 

 

 

 

configured for a stage of Heat. U1 and U2 require

 

 

 

 

 

 

power from a system transformer or a separate

 

 

 

 

 

 

transformer.

 

 

 

 

 

 

 

2180

Backup Heat Type

Electric Forced Air

Electric Forced

Both

No

This ISU is only displayed when ISU 2010 Heating

 

 

Standard Efficiency Gas Forced Air

Air

 

 

Equipment Type is Air to Air Heat Pump,

 

 

High Efficiency Gas Forced Air

 

 

 

Geothermal Heat Pump or Geothermal Radiant

 

 

 

 

 

Heat and there is at least one stage of backup heat.

 

 

Oil Forced Air

 

 

 

See “Heat Pump and Backup Heat Operation”

 

 

 

 

 

 

 

 

Hot Water Fan Coil

 

 

 

beginning on page 62.

 

 

Hot Water Radiant Heat

 

 

 

 

 

 

Other

 

 

 

 

 

 

 

 

 

 

 

19

68-0311—01

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ 2.0 WITH EIM

Table 2. Installer Setup (ISU) Table. (Continued)

 

 

 

 

Residential,

 

 

ISU

 

 

 

Commercial

Requires

 

Number

Installer Setup Name

Settings

Default

or Both

EIM

Notes

2190

External Fossil Fuel

Thermostat Controls Backup Heat

Thermostat

Both

No

This ISU is only displayed when ISU 2010 Heating

 

Kit

External Fossil Fuel Kit Controls

Controls Backup

 

 

Equipment Type is Air to Air Heat Pump,

 

 

Heat

 

 

Geothermal Heat Pump or Geothermal Radiant

 

 

Backup Heat

 

 

 

 

 

 

 

Heat and ISU 2180 Backup Heat Type is Standard

 

 

 

 

 

 

 

 

 

 

 

 

Efficiency Gas Forced Air, High Efficiency Gas

 

 

 

 

 

 

Forced Air or Oil Forced Air.

 

 

 

 

 

 

 

2200

Backup Heat

NOT allowed to Run with Heat

Default varies

Both

No

This ISU is only displayed when ISU 2010 Heating

 

Operation

Pump

based on

 

 

Equipment Type is Air to Air Heat Pump,

 

 

Allowed to Run with Heat Pump

previous

 

 

Geothermal Heat Pump or Geothermal Radiant

 

 

selections

 

 

Heat and ISU 2180 Backup Heat Type is Hot Water

 

 

 

 

 

 

 

 

 

 

 

Fan Coil or Other.

 

 

 

 

 

 

Not Allowed to Run with Heat Pump: The

 

 

 

 

 

 

thermostat turns off the heat pump when it calls for

 

 

 

 

 

 

backup heat.

 

 

 

 

 

 

Allowed to Run with Heat Pump: The thermostat

 

 

 

 

 

 

keeps the heat pump on when it calls for backup

 

 

 

 

 

 

heat.

 

 

 

 

 

 

 

2210

Backup Heat Fan

No Fan

Default varies

Both

No

This ISU is only displayed for heat pumps when ISU

 

Operation

Equipment Controls Fan

based on

 

 

2180 Backup Heat Type is Other.

 

 

previous

 

 

 

 

 

 

 

 

 

 

 

Thermostat Controls Fan

selections

 

 

Backup Heat Fan Operation:

 

 

 

 

 

 

Electric Forced Air: Thermostat Controls Fan

 

 

 

 

 

 

Standard Efficiency Gas Forced Air: Equipment

 

 

 

 

 

 

Controls Fan

 

 

 

 

 

 

High Efficiency Gas Forced Air: Equipment Controls

 

 

 

 

 

 

Fan

 

 

 

 

 

 

Oil Forced Air: Equipment Controls Fan

 

 

 

 

 

 

Hot Water Fan Coil: Thermostat Controls Fan

 

 

 

 

 

 

Hot Water Radiant Heat: Not Applicable

 

 

 

 

 

 

 

2220

A-L/A Terminal Setup

None

None

Commercial

No

This ISU is only displayed when ISU 1010

 

 

Time Of Day

 

 

 

Application is Commercial.

 

 

 

 

 

 

 

 

Economizer

 

 

 

None: The A-L/A terminal is not used.

 

 

Heat Pump Failure Indication

 

 

 

Time of Day: The A-L/A terminal is energized during

 

 

 

 

 

 

 

 

 

 

 

 

Occupied periods and when the user overrides the

 

 

 

 

 

 

temperature. The terminal is de-energized during

 

 

 

 

 

 

Unoccupied periods and in Standby mode.

 

 

 

 

 

 

Economizer: The thermostat controls an

 

 

 

 

 

 

economizer module to provide ventilation during

 

 

 

 

 

 

Occupied periods and free cooling when outdoor

 

 

 

 

 

 

conditions are favorable. The A-L/A terminal is

 

 

 

 

 

 

energized during Occupied periods and during a call

 

 

 

 

 

 

for cooling in Unoccupied periods. See “Economizer

 

 

 

 

 

 

and Time of Day (TOD) Operation” beginning on

 

 

 

 

 

 

page 91.

 

 

 

 

 

 

Notes: The economizer module determines when

 

 

 

 

 

 

outdoor conditions are favorable for free cooling.

 

 

 

 

 

 

Delta T Diagnostics is not available when the

 

 

 

 

 

 

thermostat is setup for an Economizer.

 

 

 

 

 

 

Heat Pump Failure Indication: When 24 volts is

 

 

 

 

 

 

detected on the L/A terminal (compressor monitor),

 

 

 

 

 

 

the thermostat displays a message to alert the user

 

 

 

 

 

 

when the heat pump requires service. The L/A

 

 

 

 

 

 

terminal sends a continuous output to a zone panel

 

 

 

 

 

 

when the thermostat is set to Emergency Heat

 

 

 

 

 

 

mode. The zone panel will not turn on the heat

 

 

 

 

 

 

pump when a zone is set to Emergency Heat mode.

 

 

 

 

 

 

 

3000

Changeover

Manual

Manual:

Both

No

Manual: The user must select heating or cooling as

 

 

Automatic

if ISU 1010 is

 

 

needed to maintain the desired indoor temperature.

 

 

Residential

 

 

 

 

 

 

 

 

Automatic: The user has the option to select Auto

 

 

 

 

 

 

 

 

 

Automatic:

 

 

for the system setting. In Auto mode, the

 

 

 

if ISU 1010 is

 

 

thermostat controls heating and cooling equipment

 

 

 

Commercial

 

 

as needed to maintain the desired indoor

 

 

 

 

 

 

temperature.

 

 

 

 

 

 

 

68-0311—01

20

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ 2.0 WITH EIM

Table 2. Installer Setup (ISU) Table. (Continued)

 

 

 

 

Residential,

 

 

ISU

 

 

 

Commercial

Requires

 

Number

Installer Setup Name

Settings

Default

or Both

EIM

Notes

3000

Deadband

2° F to 9° F (in 1° F increments)

3° F

Both

No

This ISU is only displayed when ISU 3000 is set to

 

 

 

 

 

 

Automatic.

 

 

 

 

 

 

Deadband is the minimum separation between heat

 

 

 

 

 

 

and cool settings when the thermostat is setup for

 

 

 

 

 

 

Auto Changeover. For example, if the deadband is

 

 

 

 

 

 

set to 3° F and the cool setpoint is 75° F, the

 

 

 

 

 

 

warmest heat setpoint allowed would be 72° F. If the

 

 

 

 

 

 

heat setpoint is adjusted above 72° F, it will

 

 

 

 

 

 

automatically adjust the cooling setpoint higher to

 

 

 

 

 

 

maintain the 3° F deadband.

 

 

 

 

 

 

 

3010

Temperature Control

Basic Options

Basic Options

Both

No

Basic Options: The Installer Setup displays basic

 

Options

Advanced Options

 

 

 

temperature control options which include Backup

 

 

 

 

 

Heat Differential, Backup Heat Upstage Timer and

 

 

 

 

 

 

 

 

Advanced Options + PID Settings

 

 

 

Outdoor Temperature Lockouts. Note: Outdoor

 

 

 

 

 

 

Temperature Lockouts only apply to Heat Pump

 

 

 

 

 

 

applications.

 

 

 

 

 

 

Advanced Options: The Installer Setup displays

 

 

 

 

 

 

both Basic and Advanced Options. Advanced

 

 

 

 

 

 

temperature control options include Finish With

 

 

 

 

 

 

High Cool Stage, Finish With High Heat Stage,

 

 

 

 

 

 

Temperature Differential settings between all stages

 

 

 

 

 

 

and Cycle Rate settings per stage.

 

 

 

 

 

 

Advanced Options+PID Settings: The Installer

 

 

 

 

 

 

Setup displays both Basic and Advanced Options

 

 

 

 

 

 

including PID settings which allow you to adjust the

 

 

 

 

 

 

integral, derivative and throttling range.

 

 

 

 

 

 

 

3020

Finish With High Cool

No

No

Both

No

ISU 3010 Temperature Control Options must be set

 

Stage

Yes

 

 

 

to Advanced to view or adjust Finish With High

 

 

 

 

 

Cool Stage.

 

 

 

 

 

 

 

 

 

 

 

 

This ISU is only displayed when the thermostat is

 

 

 

 

 

 

set for 2 or more cool stages.

 

 

 

 

 

 

When set to Yes, this feature keeps the high stage

 

 

 

 

 

 

of the cooling equipment running until the desired

 

 

 

 

 

 

setpoint is reached.

 

 

 

 

 

 

 

3021

Finish With High Heat

No

No

Both

No

ISU 3010 Temperature Control Options must be set

 

Stage

Yes

 

 

 

to Advanced to view or adjust Finish With High

 

 

 

 

 

Heat Stage.

 

 

 

 

 

 

 

 

 

 

 

 

This ISU is only displayed when the thermostat is

 

 

 

 

 

 

set for 2 or more heat stages.

 

 

 

 

 

 

When set to Yes, this feature keeps the high stage

 

 

 

 

 

 

of the heating equipment running until the desired

 

 

 

 

 

 

setpoint is reached.

 

 

 

 

 

 

 

3030

Staging Control -

Comfort

Comfort

Both

No

ISU 3010 Temperature Control Options must be set

 

Cool Differential

1.0° F to 3.5° F from setpoint (in

 

 

 

to Advanced to view or adjust this ISU.

 

Stage 2

 

 

 

 

 

0.5° F increments)

 

 

 

This ISU is only displayed when the thermostat is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

set to 2 cool stages.

 

 

 

 

 

 

The indoor temperature must rise to the selected

 

 

 

 

 

 

differential setting before the thermostat turns on

 

 

 

 

 

 

the stage of cooling. For example, if stage 2 is set to

 

 

 

 

 

 

2° F (1.0° C), the indoor temperature must be 2° F

 

 

 

 

 

 

(1.0° C) away from the setpoint before stage 2 turns

 

 

 

 

 

 

on. When set to Comfort, the thermostat uses the

 

 

 

 

 

 

stage of cooling as needed to keep the indoor

 

 

 

 

 

 

temperature within 1° F (0.5° C) degree of the

 

 

 

 

 

 

setpoint.

 

 

 

 

 

 

 

21

68-0311—01

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ 2.0 WITH EIM

Table 2. Installer Setup (ISU) Table. (Continued)

 

 

 

 

Residential,

 

 

ISU

 

 

 

Commercial

Requires

 

Number

Installer Setup Name

Settings

Default

or Both

EIM

Notes

3030

Staging Control -

Comfort

Comfort

Commercial

No

ISU 3010 Temperature Control Options must be set

 

Cool Differential

1.0°F - 4.0°F from setpoint (in

 

 

 

to Advanced to view or adjust this ISU.

 

Stage 3

 

 

 

 

 

0.5° F increments)

 

 

 

This ISU is only displayed when the thermostat is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

set to 3 cool stages.

 

 

 

 

 

 

The indoor temperature must rise to the selected

 

 

 

 

 

 

differential setting before the thermostat turns on

 

 

 

 

 

 

the stage of cooling. For example, if stage 3 is set to

 

 

 

 

 

 

2° F (1.0° C), the indoor temperature must be 2° F

 

 

 

 

 

 

(1.0° C) away from the setpoint before stage 3 turns

 

 

 

 

 

 

on. When set to Comfort, the thermostat uses the

 

 

 

 

 

 

stage of cooling as needed to keep the indoor

 

 

 

 

 

 

temperature within 1° F (0.5° C) degree of the

 

 

 

 

 

 

setpoint.

 

 

 

 

 

 

 

3030

Staging Control -

Comfort

Comfort

Commercial

No

ISU 3010 Temperature Control Options must be set

 

Cool Differential

1.0° F to 4.5° F from setpoint (in

 

 

 

to Advanced to view or adjust this ISU.

 

Stage 4

 

 

 

 

 

0.5° F increments)

 

 

 

This ISU is only displayed when the thermostat is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

set to 4 cool stages.

 

 

 

 

 

 

The indoor temperature must rise to the selected

 

 

 

 

 

 

differential setting before the thermostat turns on

 

 

 

 

 

 

the stage of cooling. For example, if stage 4 is set to

 

 

 

 

 

 

2° F (1.0° C), the indoor temperature must be 2° F

 

 

 

 

 

 

(1.0° C) away from the setpoint before stage 4 turns

 

 

 

 

 

 

on. When set to Comfort, the thermostat uses the

 

 

 

 

 

 

stage of cooling as needed to keep the indoor

 

 

 

 

 

 

temperature within 1° F (0.5° C) degree of the

 

 

 

 

 

 

setpoint.

 

 

 

 

 

 

 

3040

Staging Control -

Comfort

Comfort

Both

No

ISU 3010 Temperature Control Options must be set

 

Radiant Heat

1.0° F to 3.5° F from setpoint (in

 

 

 

to Advanced to view or adjust this ISU.

 

Differential Stage 2

 

 

 

 

 

0.5° F increments)

 

 

 

This ISU is only displayed if ISU 2010 Heating

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Equipment Type is Geothermal Radiant Heat and

 

 

 

 

 

 

there are 2 radiant heat stages.

 

 

 

 

 

 

The indoor temperature must drop to the selected

 

 

 

 

 

 

differential setting before the thermostat will turn on

 

 

 

 

 

 

the stage of heating. For example, if stage 2 is set to

 

 

 

 

 

 

2° F (1.0° C), the indoor temperature must be 2° F

 

 

 

 

 

 

(1.0° C) away from the setpoint before stage 2 turns

 

 

 

 

 

 

on. When set to Comfort, the thermostat will use the

 

 

 

 

 

 

stage of heating as needed to keep the indoor

 

 

 

 

 

 

temperature within 1° F (0.5° C) degree of the

 

 

 

 

 

 

setpoint.

 

 

 

 

 

 

 

3050

Staging Control -

Comfort

Comfort

Both

No

ISU 3010 Temperature Control Options must be set

 

Heat Differential

1.0° F to 3.5° F from setpoint (in

 

 

 

to Advanced to view or adjust this ISU.

 

Stage 2

 

 

 

 

 

0.5° F increments)

 

 

 

This ISU is only displayed for conventional systems

 

 

 

 

 

 

Note: Depending on

 

 

 

 

 

 

 

 

 

that have 2 heat stages.

 

the application, the

 

 

 

 

 

 

text displayed on the

 

 

 

 

The indoor temperature must drop to the selected

 

screen may show the

 

 

 

 

differential setting before the thermostat will turn on

 

specific heating

 

 

 

 

the stage of heating. For example, if stage 2 is set to

 

equipment type

 

 

 

 

2° F (1.0° C), the indoor temperature must be 2° F

 

 

 

 

 

 

(1.0° C) away from the setpoint before stage 2 turns

 

 

 

 

 

 

on. When set to Comfort, the thermostat will use the

 

 

 

 

 

 

stage of heating as needed to keep the indoor

 

 

 

 

 

 

temperature within 1° F (0.5° C) degree of the

 

 

 

 

 

 

setpoint.

 

 

 

 

 

 

 

3050

Staging Control -

Comfort

Comfort

Both

No

ISU 3010 Temperature Control Options must be set

 

Heat Differential

1.0° F to 4.0° F from setpoint (in

 

 

 

to Advanced to view or adjust this ISU.

 

Stage 3

 

 

 

 

 

0.5° F increments)

 

 

 

This ISU is only displayed for conventional systems

 

 

 

 

 

 

 

 

 

 

 

 

Note: Depending on

 

 

 

 

that have 3 heat stages.

 

the application, the

 

 

 

 

The indoor temperature must drop to the selected

 

text displayed on the

 

 

 

 

 

screen may show the

 

 

 

 

differential setting before the thermostat will turn on

 

specific heating

 

 

 

 

the stage of heating. For example, if stage 3 is set to

 

equipment type

 

 

 

 

2° F (1.0° C), the indoor temperature must be 2° F

 

 

 

 

 

 

(1.0° C) away from the setpoint before stage 3 turns

 

 

 

 

 

 

on. When set to Comfort, the thermostat will use the

 

 

 

 

 

 

stage of heating as needed to keep the indoor

 

 

 

 

 

 

temperature within 1° F (0.5° C) degree of the

 

 

 

 

 

 

setpoint.

 

 

 

 

 

 

 

68-0311—01

22

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ 2.0 WITH EIM

Table 2. Installer Setup (ISU) Table. (Continued)

 

 

 

 

Residential,

 

 

ISU

 

 

 

Commercial

Requires

 

Number

Installer Setup Name

Settings

Default

or Both

EIM

Notes

3060

Staging Control -

Comfort

Comfort

Both

No

ISU 3010 Temperature Control Options must be set

 

Compressor Heat

1.0° F to 4.0° F from setpoint (in

 

 

 

to Advanced to view or adjust this ISU.

 

Differential Stage 1

 

 

 

 

 

0.5° F increments)

 

 

 

This ISU is only displayed if ISU 2010 Heating

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Equipment Type is Geothermal Radiant Heat and

 

 

 

 

 

 

ISU 2050 Geothermal Forced Air System is set to

 

 

 

 

 

 

Used for Heating and Cooling.

 

 

 

 

 

 

The indoor temperature must drop to the selected

 

 

 

 

 

 

differential setting before the thermostat will turn on

 

 

 

 

 

 

the stage of heating. For example, if stage 1 is set to

 

 

 

 

 

 

2° F (1.0° C), the indoor temperature must be 2° F

 

 

 

 

 

 

(1.0° C) away from the setpoint before stage 1 turns

 

 

 

 

 

 

on. When set to Comfort, the thermostat will use the

 

 

 

 

 

 

stage of heating as needed to keep the indoor

 

 

 

 

 

 

temperature within 1° F (0.5° C) degree of the

 

 

 

 

 

 

setpoint.

 

 

 

 

 

 

 

3060

Staging Control -

Comfort

Comfort

Both

No

ISU 3010 Temperature Control Options must be set

 

Compressor Heat

1.0° F to 4.5° F from setpoint (in

 

 

 

to Advanced to view or adjust this ISU.

 

Differential Stage 2

 

 

 

 

 

0.5° F increments)

 

 

 

This ISU is only displayed if ISU 2010 Heating

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Equipment Type is Air to Air Heat Pump,

 

 

 

 

 

 

Geothermal Heat Pump or Geothermal Radiant

 

 

 

 

 

 

Heat and there are 2 compressor stages.

 

 

 

 

 

 

The indoor temperature must drop to the selected

 

 

 

 

 

 

differential setting before the thermostat will turn on

 

 

 

 

 

 

the stage of heating. For example, if stage 2 is set to

 

 

 

 

 

 

2° F (1.0° C), the indoor temperature must be 2° F

 

 

 

 

 

 

(1.0° C) away from the setpoint before stage 2 turns

 

 

 

 

 

 

on. When set to Comfort, the thermostat will use the

 

 

 

 

 

 

stage of heating as needed to keep the indoor

 

 

 

 

 

 

temperature within 1° F (0.5° C) degree of the

 

 

 

 

 

 

setpoint.

 

 

 

 

 

 

 

3080,

Staging Control -

Comfort

Comfort

Both

No

A backup heat differential can be set on any system

3090

Backup Heat

2.0° F to 15.0° F from setpoint (in

 

 

 

that has more than one heating equipment type.

 

Differential Stage 1

 

 

 

 

 

0.5° F increments)

 

 

 

See “Backup Heat Differential (Droop)” beginning

 

 

 

 

 

 

 

 

 

 

 

 

Note: “Stage 1" is not

 

 

 

 

on page 60.

 

displayed if there is

 

 

 

 

The Comfort setting is only available on systems

 

only 1 stage of

 

 

 

 

 

Backup Heat.

 

 

 

 

when the Backup Heat Type is Allowed to Run with

 

 

 

 

 

 

the Primary Heat (Heat Pump). For example, Heat

 

 

 

 

 

 

Pumps with Electric Forced Air Backup Heat.

 

 

 

 

 

 

The Comfort setting is NOT available for Dual Fuel

 

 

 

 

 

 

systems. For example, Heat Pumps with Gas Forced

 

 

 

 

 

 

Air.

 

 

 

 

 

 

 

3080,

Staging Control -

Comfort

Comfort

Both

No

ISU 3010 Temperature Control Options must be set

3090

Backup Heat

2.0° F to 15.5° F from setpoint (in

 

 

 

to Advanced to view or adjust Backup Heat

 

Differential Stage 2

 

 

 

Differential Stage 2.

 

0.5° F increments)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

This ISU is only displayed if there are 2 backup heat

 

 

 

 

 

 

stages.

 

 

 

 

 

 

The indoor temperature must drop to the selected

 

 

 

 

 

 

differential setting before the thermostat will turn on

 

 

 

 

 

 

backup heat stage 2. For example, if backup heat

 

 

 

 

 

 

stage 2 is set to 2° F (1.0° C), the indoor

 

 

 

 

 

 

temperature must be 2° F (1.0° C) away from the

 

 

 

 

 

 

setpoint before backup heat stage 2 turns on. When

 

 

 

 

 

 

set to Comfort, the thermostat will use backup heat

 

 

 

 

 

 

stage 2 as needed to keep the indoor temperature

 

 

 

 

 

 

within 1° F (0.5° C) degree of the setpoint.

 

 

 

 

 

 

 

3110

Backup Heat Upstage

Off

Off

Both

No

The Backup Heat Upstage Timer starts when the

 

Timer

(30, 45, 60, 75, 90) minutes

 

 

 

highest stage of the previous heating equipment

 

 

 

 

 

type turns on. Backup heat will be used (if needed)

 

 

 

 

 

 

 

 

(2, 3, 4, 5, 6, 8, 10, 12, 14, 16)

 

 

 

when the timer expires. See “Backup Heat Upstage

 

 

hours

 

 

 

Timer” beginning on page 61.

 

 

 

 

 

 

This ISU is only displayed when Backup Heat

 

 

 

 

 

 

Differential Stage 1 is set to 2 F or higher (ISU 3080,

 

 

 

 

 

 

3090).

 

 

 

 

 

 

 

23

68-0311—01

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ 2.0 WITH EIM

Table 2. Installer Setup (ISU) Table. (Continued)

 

 

 

 

Residential,

 

 

ISU

 

 

 

Commercial

Requires

 

Number

Installer Setup Name

Settings

Default

or Both

EIM

Notes

3120

Outdoor Temperature

Off

Off

Both

No

ISU 3120 Compressor Lockout / Balance Point

 

Lockouts:

5° F to 60° F (in 5° F increments)

(See Notes)

 

 

requires an outdoor sensor.

 

 

 

 

 

 

Compressor Lockout

 

 

 

Default is 40 F if ISU 2010 Heating Equipment Type

 

 

 

 

 

 

/ Balance Point

 

 

 

 

is Air to Air Heat Pump and ISU 2180 Backup Type

 

 

 

 

 

 

is gas or oil forced air.

 

 

 

 

 

 

Default is Off if ISU 2010 Heating Equipment Type is

 

 

 

 

 

 

Air to Air Heat Pump and ISU 2180 Backup Type is

 

 

 

 

 

 

electric forced air.

 

 

 

 

 

 

Default is Off if ISU 2010 Heating Equipment Type is

 

 

 

 

 

 

Geothermal Heat Pump or Geothermal Radiant

 

 

 

 

 

 

Heat.

 

 

 

 

 

 

Compressor Lockout / Balance Point is optional for

 

 

 

 

 

 

any type of heat pump (Air to Air Heat Pump,

 

 

 

 

 

 

Geothermal Heat Pump or Geothermal Radiant

 

 

 

 

 

 

Heat).

 

 

 

 

 

 

See “Heat pump with outdoor temperature

 

 

 

 

 

 

lockouts” beginning on page 62.

 

 

 

 

 

 

 

3120

Outdoor Temperature

Off

Off

Both

No

ISU 3120 Backup Heat Outdoor Temperature

 

Lockouts:

5° F to 65° F (in 5° F increments)

 

 

 

Lockout requires an outdoor sensor.

 

 

 

 

 

 

 

Backup Heat Lockout

 

 

 

 

This ISU is only displayed if ISU 2010 Heating

 

 

 

 

 

 

Equipment Type is Air to Air Heat Pump,

 

 

 

 

 

 

Geothermal Heat Pump or Geothermal Radiant

 

 

 

 

 

 

Heat and ISU 2190 External fossil fuel kit is set to

 

 

 

 

 

 

Thermostat Controls Backup Heat.

 

 

 

 

 

 

See “Heat pump with outdoor temperature

 

 

 

 

 

 

lockouts” beginning on page 62.

 

 

 

 

 

 

 

3130

Radiant Heat Cycles

1 to 12 CPH

3

Both

No

ISU 3010 Temperature Control Options must be set

 

Per Hour - Stage 1

 

 

 

 

to Advanced to view or adjust cycle rate.

 

Note: “Stage 1" is not

 

 

 

 

This ISU is only displayed when ISU 2010 Heating

 

displayed if there is

 

 

 

 

Equipment Type is Geothermal Radiant Heat.

 

only 1 stage of

 

 

 

 

 

 

Radiant Heat.

 

 

 

 

The thermostat automatically defaults to the

 

 

 

 

 

 

recommended setting for Geothermal Radiant Heat

 

 

 

 

 

 

(3 CPH).

 

 

 

 

 

 

Cycle rate limits the maximum number of times the

 

 

 

 

 

 

system can cycle in a 1 hour period measured at a

 

 

 

 

 

 

50% load. For example, when set to 3 CPH, at a

 

 

 

 

 

 

50% load, the most the system will cycle is 3 times

 

 

 

 

 

 

per hour (10 minutes on, 10 minutes off). The

 

 

 

 

 

 

system cycles less often when load conditions are

 

 

 

 

 

 

less than or greater than a 50% load.

 

 

 

 

 

 

 

3130

Radiant Heat Cycles

1 to 12 CPH

3

Both

No

ISU 3010 Temperature Control Options must be set

 

Per Hour - Stage 2

 

 

 

 

to Advanced to view or adjust cycle rate.

 

 

 

 

 

 

This ISU is only displayed when ISU 2010 Heating

 

 

 

 

 

 

Equipment Type is Geothermal Radiant Heat.

 

 

 

 

 

 

The thermostat automatically defaults to the

 

 

 

 

 

 

recommended setting for Geothermal Radiant Heat

 

 

 

 

 

 

(3 CPH).

 

 

 

 

 

 

Cycle rate limits the maximum number of times the

 

 

 

 

 

 

system can cycle in a 1 hour period measured at a

 

 

 

 

 

 

50% load. For example, when set to 3 CPH, at a

 

 

 

 

 

 

50% load, the most the system will cycle is 3 times

 

 

 

 

 

 

per hour (10 minutes on, 10 minutes off). The

 

 

 

 

 

 

system cycles less often when load conditions are

 

 

 

 

 

 

less than or greater than a 50% load.

 

 

 

 

 

 

 

68-0311—01

24

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ 2.0 WITH EIM

Table 2. Installer Setup (ISU) Table. (Continued)

 

 

 

 

Residential,

 

 

ISU

 

 

 

Commercial

Requires

 

Number

Installer Setup Name

Settings

Default

or Both

EIM

Notes

3140

Cool / Compressor

1 to 6 CPH

3

Both

No

ISU 3010 Temperature Control Options must be set

 

Cycles Per Hour -

 

 

 

 

to Advanced to view or adjust cycle rate.

 

Stage 1

 

 

 

 

This ISU is only displayed when ISU 2070 Cool /

 

 

 

 

 

 

 

Note: “Stage 1" is not

 

 

 

 

Compressor Stages is set to 1 stage.

 

displayed if there is

 

 

 

 

 

 

only 1 stage.

 

 

 

 

Cycle rate limits the maximum number of times the

 

 

 

 

 

 

system can cycle in a 1 hour period measured at a

 

 

 

 

 

 

50% load. For example, when set to 3 CPH, at a

 

 

 

 

 

 

50% load, the most the system will cycle is 3 times

 

 

 

 

 

 

per hour (10 minutes on, 10 minutes off). The

 

 

 

 

 

 

system cycles less often when load conditions are

 

 

 

 

 

 

less than or greater than a 50% load.

 

 

 

 

 

 

 

3140

Cool / Compressor

1 to 6 CPH

3

Both

No

ISU 3010 Temperature Control Options must be set

 

Cycles Per Hour -

 

 

 

 

to Advanced to view or adjust cycle rate.

 

Stage 2

 

 

 

 

This ISU is only displayed when ISU 2070 Cool /

 

 

 

 

 

 

 

 

 

 

 

 

Compressor Stages is set to 2 stages.

 

 

 

 

 

 

Cycle rate limits the maximum number of times the

 

 

 

 

 

 

system can cycle in a 1 hour period measured at a

 

 

 

 

 

 

50% load. For example, when set to 3 CPH, at a

 

 

 

 

 

 

50% load, the most the system will cycle is 3 times

 

 

 

 

 

 

per hour (10 minutes on, 10 minutes off). The

 

 

 

 

 

 

system cycles less often when load conditions are

 

 

 

 

 

 

less than or greater than a 50% load.

 

 

 

 

 

 

 

3140

Cool Cycles Per Hour

1 to 6 CPH

3

Commercial

No

ISU 3010 Temperature Control Options must be set

 

- Stage 3

 

 

 

 

to Advanced to view or adjust cycle rate.

 

 

 

 

 

 

This ISU is only displayed when ISU 1010

 

 

 

 

 

 

Application is set to Commercial and ISU 2070 Cool

 

 

 

 

 

 

Stages is set to 3 stages.

 

 

 

 

 

 

Cycle rate limits the maximum number of times the

 

 

 

 

 

 

system can cycle in a 1 hour period measured at a

 

 

 

 

 

 

50% load. For example, when set to 3 CPH, at a

 

 

 

 

 

 

50% load, the most the system will cycle is 3 times

 

 

 

 

 

 

per hour (10 minutes on, 10 minutes off). The

 

 

 

 

 

 

system cycles less often when load conditions are

 

 

 

 

 

 

less than or greater than a 50% load.

 

 

 

 

 

 

 

3140

Cool Cycles Per Hour

1 to 6 CPH

3

Commercial

No

ISU 3010 Temperature Control Options must be set

 

- Stage 4

 

 

 

 

to Advanced to view or adjust cycle rate.

 

 

 

 

 

 

This ISU is only displayed when ISU 1010

 

 

 

 

 

 

Application is set to Commercial and ISU 2070 Cool

 

 

 

 

 

 

Stages is set to 4 stages.

 

 

 

 

 

 

Cycle rate limits the maximum number of times the

 

 

 

 

 

 

system can cycle in a 1 hour period measured at a

 

 

 

 

 

 

50% load. For example, when set to 3 CPH, at a

 

 

 

 

 

 

50% load, the most the system will cycle is 3 times

 

 

 

 

 

 

per hour (10 minutes on, 10 minutes off). The

 

 

 

 

 

 

system cycles less often when load conditions are

 

 

 

 

 

 

less than or greater than a 50% load.

 

 

 

 

 

 

 

25

68-0311—01

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ 2.0 WITH EIM

Table 2. Installer Setup (ISU) Table. (Continued)

 

 

 

 

Residential,

 

 

ISU

 

 

 

Commercial

Requires

 

Number

Installer Setup Name

Settings

Default

or Both

EIM

Notes

3150

Heat Cycles Per Hour

1 to 12 CPH

Default varies

Both

No

ISU 3010 Temperature Control Options must be set

 

- Stage 1

 

based on heating

 

 

to Advanced to view or adjust cycle rate.

 

 

 

equipment type

 

 

 

 

Note: Depending on

 

selected

 

 

This ISU is only displayed when ISU 2070 Heat

 

the application, the

 

 

 

 

Stages is set to 1 stage.

 

text displayed on the

 

 

 

 

Cycle rate limits the maximum number of times the

 

screen may show the

 

 

 

 

 

specific heating

 

 

 

 

system can cycle in a 1 hour period measured at a

 

equipment type.

 

 

 

 

50% load. For example, when set to 3 CPH, at a

 

“Stage 1" is not

 

 

 

 

50% load, the most the system will cycle is 3 times

 

displayed if there is

 

 

 

 

per hour (10 minutes on, 10 minutes off). The

 

only 1 stage.

 

 

 

 

system cycles less often when load conditions are

 

 

 

 

 

 

less than or greater than a 50% load. The

 

 

 

 

 

 

thermostat automatically defaults to the

 

 

 

 

 

 

recommended cycle rate based on the heating

 

 

 

 

 

 

equipment type that is used. You can change the

 

 

 

 

 

 

cycle rate as needed. Defaults for commonly used

 

 

 

 

 

 

systems are shown below.

 

 

 

 

 

 

Standard Efficiency Gas Forced Air = 5 CPH

 

 

 

 

 

 

High Efficiency Gas Forced Air = 3 CPH

 

 

 

 

 

 

Oil Forced Air = 5 CPH

 

 

 

 

 

 

Electric Forced Air = 9 CPH

 

 

 

 

 

 

Hot Water Fan Coil = 3 CPH

 

 

 

 

 

 

Hot Water Radiant Heat = 3 CPH

 

 

 

 

 

 

Geothermal Radiant Heat = 3 CPH

 

 

 

 

 

 

Steam = 1 CPH

 

 

 

 

 

 

Gravity = 1 CPH

 

 

 

 

 

 

 

3150

Heat Cycles Per Hour

1 to 12 CPH

Default varies

Both

No

ISU 3010 Temperature Control Options must be set

 

- Stage 2

 

based on heating

 

 

to Advanced to view or adjust cycle rate.

 

 

 

equipment type

 

 

 

 

Note: Depending on

 

selected

 

 

This ISU is only displayed when ISU 2070 Heat

 

the application, the

 

 

 

 

Stages is set to 2 stages.

 

text displayed on the

 

 

 

 

Cycle rate limits the maximum number of times the

 

screen may show the

 

 

 

 

system can cycle in a 1 hour period measured at a

 

specific heating

 

 

 

 

50% load. For example, when set to 3 CPH, at a

 

equipment type.

 

 

 

 

50% load, the most the system will cycle is 3 times

 

 

 

 

 

 

per hour (10 minutes on, 10 minutes off). The

 

 

 

 

 

 

system cycles less often when load conditions are

 

 

 

 

 

 

less than or greater than a 50% load. The

 

 

 

 

 

 

thermostat automatically defaults to the

 

 

 

 

 

 

recommended cycle rate based on the heating

 

 

 

 

 

 

equipment type that is used. You can change the

 

 

 

 

 

 

cycle rate as needed. Defaults for commonly used

 

 

 

 

 

 

systems are shown below.

 

 

 

 

 

 

Standard Efficiency Gas Forced Air = 5 CPH

 

 

 

 

 

 

High Efficiency Gas Forced Air = 3 CPH

 

 

 

 

 

 

Oil Forced Air = 5 CPH

 

 

 

 

 

 

Electric Forced Air = 9 CPH

 

 

 

 

 

 

Hot Water Fan Coil = 3 CPH

 

 

 

 

 

 

Hot Water Radiant Heat = 3 CPH

 

 

 

 

 

 

Geothermal Radiant Heat = 3 CPH

 

 

 

 

 

 

Steam = 1 CPH

 

 

 

 

 

 

Gravity = 1 CPH

 

 

 

 

 

 

 

68-0311—01

26

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ 2.0 WITH EIM

Table 2. Installer Setup (ISU) Table. (Continued)

 

 

 

 

Residential,

 

 

ISU

 

 

 

Commercial

Requires

 

Number

Installer Setup Name

Settings

Default

or Both

EIM

Notes

3150

Heat Cycles Per Hour

1 to 12 CPH

Default varies

Both

No

ISU 3010 Temperature Control Options must be set

 

- Stage 3

 

based on heating

 

 

to Advanced to view or adjust cycle rate.

 

 

 

equipment type

 

 

 

 

Note: Depending on

 

selected

 

 

This ISU is only displayed when ISU 2070 Heat

 

the application, the

 

 

 

 

Stages is set to 3 stages.

 

text displayed on the

 

 

 

 

Cycle rate limits the maximum number of times the

 

screen may show the

 

 

 

 

 

specific heating

 

 

 

 

system can cycle in a 1 hour period measured at a

 

equipment type.

 

 

 

 

50% load. For example, when set to 3 CPH, at a

 

 

 

 

 

 

50% load, the most the system will cycle is 3 times

 

 

 

 

 

 

per hour (10 minutes on, 10 minutes off). The

 

 

 

 

 

 

system cycles less often when load conditions are

 

 

 

 

 

 

less than or greater than a 50% load. The

 

 

 

 

 

 

thermostat automatically defaults to the

 

 

 

 

 

 

recommended cycle rate based on the heating

 

 

 

 

 

 

equipment type that is used. You can change the

 

 

 

 

 

 

cycle rate as needed. Defaults for commonly used

 

 

 

 

 

 

systems are shown below.

 

 

 

 

 

 

Standard Efficiency Gas Forced Air = 5 CPH

 

 

 

 

 

 

High Efficiency Gas Forced Air = 3 CPH

 

 

 

 

 

 

Oil Forced Air = 5 CPH

 

 

 

 

 

 

Electric Forced Air = 9 CPH

 

 

 

 

 

 

Hot Water Fan Coil = 3 CPH

 

 

 

 

 

 

Hot Water Radiant Heat = 3 CPH

 

 

 

 

 

 

Geothermal Radiant Heat = 3 CPH

 

 

 

 

 

 

Steam = 1 CPH

 

 

 

 

 

 

Gravity = 1 CPH

 

 

 

 

 

 

 

3160

Backup Heat Cycles

1 to 12 CPH

Default varies

Both

No

ISU 3010 Temperature Control Options must be set

 

Per Hour - Stage 1

 

based on heating

 

 

to Advanced to view or adjust cycle rate.

 

 

 

equipment type

 

 

 

 

Note: “Stage 1" is not

 

selected

 

 

This ISU is only displayed when ISU 2070 or 2130

 

displayed if there is

 

 

 

 

Backup Heat Stages is set to 1 stage.

 

only 1 stage.

 

 

 

 

Cycle rate limits the maximum number of times the

 

 

 

 

 

 

 

 

 

 

 

 

system can cycle in a 1 hour period measured at a

 

 

 

 

 

 

50% load. For example, when set to 3 CPH, at a

 

 

 

 

 

 

50% load, the most the system will cycle is 3 times

 

 

 

 

 

 

per hour (10 minutes on, 10 minutes off). The

 

 

 

 

 

 

system cycles less often when load conditions are

 

 

 

 

 

 

less than or greater than a 50% load. The

 

 

 

 

 

 

thermostat automatically defaults to the

 

 

 

 

 

 

recommended cycle rate based on the heating

 

 

 

 

 

 

equipment type that is used. You can change the

 

 

 

 

 

 

cycle rate as needed. Defaults for commonly used

 

 

 

 

 

 

systems are shown below.

 

 

 

 

 

 

Standard Efficiency Gas Forced Air = 5 CPH

 

 

 

 

 

 

High Efficiency Gas Forced Air = 3 CPH

 

 

 

 

 

 

Oil Forced Air = 5 CPH

 

 

 

 

 

 

Electric Forced Air = 9 CPH

 

 

 

 

 

 

Hot Water Fan Coil = 3 CPH

 

 

 

 

 

 

Hot Water Radiant Heat = 3 CPH

 

 

 

 

 

 

Geothermal Radiant Heat = 3 CPH

 

 

 

 

 

 

Steam = 1 CPH

 

 

 

 

 

 

Gravity = 1 CPH

 

 

 

 

 

 

 

27

68-0311—01

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ 2.0 WITH EIM

Table 2. Installer Setup (ISU) Table. (Continued)

 

 

 

 

Residential,

 

 

ISU

 

 

 

Commercial

Requires

 

Number

Installer Setup Name

Settings

Default

or Both

EIM

Notes

3160

Backup Heat Cycles

1 to 12 CPH

Default varies

Both

No

ISU 3010 Temperature Control Options must be set

 

Per Hour - Stage 2

 

based on heating

 

 

to Advanced to view or adjust cycle rate.

 

 

 

equipment type

 

 

 

 

 

 

selected

 

 

This ISU is only displayed when ISU 2070 or 2130

 

 

 

 

 

 

Backup Heat Stages is set to 2 stages.

 

 

 

 

 

 

Cycle rate limits the maximum number of times the

 

 

 

 

 

 

system can cycle in a 1 hour period measured at a

 

 

 

 

 

 

50% load. For example, when set to 3 CPH, at a

 

 

 

 

 

 

50% load, the most the system will cycle is 3 times

 

 

 

 

 

 

per hour (10 minutes on, 10 minutes off). The

 

 

 

 

 

 

system cycles less often when load conditions are

 

 

 

 

 

 

less than or greater than a 50% load. The

 

 

 

 

 

 

thermostat automatically defaults to the

 

 

 

 

 

 

recommended cycle rate based on the heating

 

 

 

 

 

 

equipment type that is used. You can change the

 

 

 

 

 

 

cycle rate as needed. Default for commonly used

 

 

 

 

 

 

systems are shown below.

 

 

 

 

 

 

Standard Efficiency Gas Forced Air = 5 CPH

 

 

 

 

 

 

High Efficiency Gas Forced Air = 3 CPH

 

 

 

 

 

 

Oil Forced Air = 5 CPH

 

 

 

 

 

 

Electric Forced Air = 9 CPH

 

 

 

 

 

 

Hot Water Fan Coil = 3 CPH

 

 

 

 

 

 

Hot Water Radiant Heat = 3 CPH

 

 

 

 

 

 

Geothermal Radiant Heat = 3 CPH

 

 

 

 

 

 

Steam = 1 CPH

 

 

 

 

 

 

Gravity = 1 CPH

 

 

 

 

 

 

 

3170

Cooling Throttling

1° F to 30° F

2° F

Commercial

No

The default Cooling Throttling range is 2° F (1.5° C)

 

Range

 

 

 

 

which is appropriate for most applications. Do not

 

 

 

 

 

 

change this setting unless advised to do so by

 

 

 

 

 

 

Honeywell technical support.

 

 

 

 

 

 

The throttling range controls the cycling of the

 

 

 

 

 

 

system and helps to compensate for load changes,

 

 

 

 

 

 

equipment sizing and thermostat mounting

 

 

 

 

 

 

location.

 

 

 

 

 

 

 

3180

Cooling Integral

0, 100 to 25,000 sec

10,000 sec

Commercial

No

The default Cooling Integral is 10,000 seconds

 

 

 

 

 

 

which is appropriate for most applications. Do not

 

 

 

 

 

 

change this setting unless advised to do so by

 

 

 

 

 

 

Honeywell technical support.

 

 

 

 

 

 

The integral controls how much droop is used.

 

 

 

 

 

 

 

3190

Cooling Derivative

0, 100 to 25,000 sec

0 sec

Commercial

No

The default Cooling Derivative is 0 seconds which is

 

 

 

 

 

 

appropriate for most applications. Do not change

 

 

 

 

 

 

this setting unless advised to do so by Honeywell

 

 

 

 

 

 

technical support.

 

 

 

 

 

 

The derivative makes adjustments to the algorithm

 

 

 

 

 

 

for fast acting systems.

 

 

 

 

 

 

 

3200

Heating Throttling

1° F to 30° F

2° F

Commercial

No

The default Heating Throttling Range is 2° F (1.5° C)

 

Range

 

 

 

 

which is appropriate for most applications. Do not

 

 

 

 

 

 

change this setting unless advised to do so by

 

 

 

 

 

 

Honeywell technical support.

 

 

 

 

 

 

The throttling range controls the cycling of the

 

 

 

 

 

 

system and helps to compensate for load changes,

 

 

 

 

 

 

equipment sizing and thermostat mounting

 

 

 

 

 

 

location.

 

 

 

 

 

 

 

3210

Heating Integral

0, 100 to 25,000 sec

10,000 sec

Commercial

No

The default Heating Integral is 10,000 seconds

 

 

 

 

 

 

which is appropriate for most applications. Do not

 

 

 

 

 

 

change this setting unless advised to do so by

 

 

 

 

 

 

Honeywell technical support.

 

 

 

 

 

 

The integral controls how much droop is used.

 

 

 

 

 

 

 

3220

Heating Derivative

0, 100 to 25,000 sec

0 sec

Commercial

No

The default Heating Derivative is 0 seconds which is

 

 

 

 

 

 

appropriate for most applications. Do not change

 

 

 

 

 

 

this setting unless advised to do so by Honeywell

 

 

 

 

 

 

technical support.

 

 

 

 

 

 

The derivative makes adjustments to the algorithm

 

 

 

 

 

 

for fast acting systems.

 

 

 

 

 

 

 

3240

Minimum

Off

5 minutes

Both

No

The thermostat has a built in compressor protection

 

Compressor Off Time

1 - 5 minutes

 

 

 

(minimum off timer) that prevents the compressor

 

 

 

 

 

 

from restarting too early after a shutdown. The

 

 

 

 

 

 

minimum-off timer is activated after the

 

 

 

 

 

 

compressor turns off.

 

 

 

 

 

 

If there is a call during the minimum-off timer, the

 

 

 

 

 

 

thermostat shows “waiting for equipment” in the

 

 

 

 

 

 

display.

 

 

 

 

 

 

 

68-0311—01

28

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ 2.0 WITH EIM

Table 2. Installer Setup (ISU) Table. (Continued)

 

 

 

 

Residential,

 

 

ISU

 

 

 

Commercial

Requires

 

Number

Installer Setup Name

Settings

Default

or Both

EIM

Notes

3260

Extended Fan Run

0, 30, 60, 90 seconds, 2, 3, 4, 5,

0 seconds

Both

No

After the call for cooling ends, the thermostat keeps

 

Time in Cool

6, 7, 8, 9, 10, 11, 12, 13, 14, 15

 

 

 

the fan on for the selected amount of time for

 

 

minutes

 

 

 

increased efficiency. This may re-introduce

 

 

 

 

 

 

humidity into the living space.

 

 

 

 

 

 

 

3260

Extended Fan Run

0, 30, 60, 90 seconds, 2, 3, 4, 5,

0 seconds

Both

No

After the call for heating ends, the thermostat keeps

 

Time in Heat

6, 7, 8, 9, 10, 11, 12, 13, 14, 15

 

 

 

the fan on for the selected amount of time for

 

 

minutes

 

 

 

increased efficiency.

 

 

 

 

 

 

 

4000

Number Of Schedule

2 or 4 periods per day

4 periods per day

Both

No

Residential:

 

Periods

 

 

 

 

4 Periods = Wake, Leave, Return, Sleep

 

 

 

 

 

 

2 Periods = Wake, Sleep

 

 

 

 

 

 

Commercial:

 

 

 

 

 

 

4 Periods = Occupied 1, Unoccupied 1, Occupied 2,

 

 

 

 

 

 

Unoccupied 2

 

 

 

 

 

 

2 Periods = Occupied 1, Unoccupied 1

 

 

 

 

 

 

 

4010

Pre-Occupancy Purge

Off

Off

Commercial

No

Runs the fan 1 to 3 hours before each occupied

 

Duration

1 hour

 

 

 

period to provide a comfortable workplace upon

 

 

 

 

 

arrival.

 

 

2 hour

 

 

 

 

 

 

 

 

 

 

 

3 hour

 

 

 

 

 

 

 

 

 

 

 

4020

Type of Override

Standard

Standard

Commercial

No

Standard:

 

 

Initiate Occupancy

 

 

 

The system maintains temperatures programmed

 

 

 

 

 

for the occupied and unoccupied time periods.

 

 

 

 

 

 

 

 

 

 

 

 

Pressing OVERRIDE will allow the user to make a

 

 

 

 

 

 

temporary schedule change.

 

 

 

 

 

 

Initiate Occupancy:

 

 

 

 

 

 

The system maintains temperature at an energy

 

 

 

 

 

 

saving level until the Press to Start Occupancy

 

 

 

 

 

 

button is pressed by the user. The system will then

 

 

 

 

 

 

maintain a comfortable temperature until the

 

 

 

 

 

 

occupied period ends. This option is recommended

 

 

 

 

 

 

for cost savings when the workplace is used

 

 

 

 

 

 

infrequently or arrival times change from day to day

 

 

 

 

 

 

(example - schools). Once the occupancy is

 

 

 

 

 

 

activated by pressing the Press to Start Occupancy

 

 

 

 

 

 

button, the user will still be able to perform a

 

 

 

 

 

 

standard OVERRIDE of the schedule.

 

 

 

 

 

 

 

4030

Override Duration

No Limit

3 hours

Commercial

No

When the user presses the OVERRIDE button, the

 

 

1 to 12 Hours

 

 

 

thermostat will maintain the new temperature for at

 

 

 

 

 

least 1 hour. The user can adjust the Hold Until time

 

 

 

 

 

 

 

 

 

 

 

 

from 1 hour to the amount set for the Override

 

 

 

 

 

 

Duration (1-12 hours). Default setting is 3 hours. If

 

 

 

 

 

 

set to No Limit, the user can adjust the Hold Until

 

 

 

 

 

 

time up to 24 hours.

 

 

 

 

 

 

 

4050

Minimum Heat

Off

5° F/hr

Commercial

No

Off: The heating system will begin recovery at the

 

Recovery Ramp Rate

1° F/hr to 20° F/hr

 

 

 

time that is scheduled.

 

 

 

 

 

 

When a Minimum Recovery Ramp Rate is set, the

 

 

 

 

 

 

thermostat will begin recovery early to ensure the

 

 

 

 

 

 

temperature is reached at the scheduled time.

 

 

 

 

 

 

Set a Minimum Recovery Ramp Rate based on the

 

 

 

 

 

 

rate that the heating system can recover at for a

 

 

 

 

 

 

cold day in your region. Default setting is 5° F /

 

 

 

 

 

 

hour.

 

 

 

 

 

 

If an outdoor sensor is installed, set an Outdoor

 

 

 

 

 

 

Temperature that is representative of a cold day in

 

 

 

 

 

 

your region to be associated with the Minimum

 

 

 

 

 

 

Recovery Ramp Rate. The thermostat will begin

 

 

 

 

 

 

recovery at the optimal time based on a calculated

 

 

 

 

 

 

ramp rate, allowing the system to recover on time

 

 

 

 

 

 

and save energy during changing outdoor

 

 

 

 

 

 

conditions.

 

 

 

 

 

 

During recovery, the setpoint changes at a rate in

 

 

 

 

 

 

degrees per hour depending on the outdoor

 

 

 

 

 

 

temperature. If there is no outdoor sensor, the

 

 

 

 

 

 

Minimum Recovery Ramp Rate is used.

 

 

 

 

 

 

 

29

68-0311—01

THX9321 PRESTIGE® 2.0 AND THX9421 PRESTIGE® IAQ 2.0 WITH EIM

Table 2. Installer Setup (ISU) Table. (Continued)

 

 

 

 

Residential,

 

 

ISU

 

 

 

Commercial

Requires

 

Number

Installer Setup Name

Settings

Default

or Both

EIM

Notes

4050

Outdoor Temperature

Off

0° F

Commercial

No

Off: The heating system will begin recovery at the

 

used with Minimum

-20° F to 100°F

 

 

 

time that is scheduled.

 

Heat Recovery Ramp

 

 

 

 

 

Rate

 

 

 

 

When a Minimum Recovery Ramp Rate is set, the

 

 

 

 

 

 

thermostat will begin recovery early to ensure the

 

 

 

 

 

 

temperature is reached at the scheduled time.

 

 

 

 

 

 

Set a Minimum Recovery Ramp Rate based on the

 

 

 

 

 

 

rate that the heating system can recover at for a

 

 

 

 

 

 

cold day in your region. Default setting is 5° F /

 

 

 

 

 

 

hour.

 

 

 

 

 

 

If an outdoor sensor is installed, set an Outdoor

 

 

 

 

 

 

Temperature that is representative of a cold day in

 

 

 

 

 

 

your region to be associated with the Minimum

 

 

 

 

 

 

Recovery Ramp Rate. The thermostat will begin

 

 

 

 

 

 

recovery at the optimal time based on a calculated

 

 

 

 

 

 

ramp rate, allowing the system to recover on time

 

 

 

 

 

 

and save energy during changing outdoor

 

 

 

 

 

 

conditions.

 

 

 

 

 

 

During recovery, the setpoint changes at a rate in

 

 

 

 

 

 

degrees per hour depending on the outdoor

 

 

 

 

 

 

temperature. If there is no outdoor sensor, the

 

 

 

 

 

 

Minimum Recovery Ramp Rate is used.

 

 

 

 

 

 

 

4060

Maximum Heat

Off

8° F/hr

Commercial

No

Off: The heating system will begin recovery at the

 

Recovery Ramp Rate

1° F/hr to 20° F/hr

 

 

 

time that is scheduled.

 

 

 

 

 

 

When a Maximum Recovery Ramp Rate is set, the

 

 

 

 

 

 

thermostat will begin recovery early to ensure the

 

 

 

 

 

 

temperature is reached at the scheduled time.

 

 

 

 

 

 

Set a Maximum Recovery Ramp Rate based on the

 

 

 

 

 

 

rate that the heating system can recover at for a

 

 

 

 

 

 

mild day in your region. Default setting is 8° F /

 

 

 

 

 

 

hour.

 

 

 

 

 

 

Set an Outdoor Temperature that is representative

 

 

 

 

 

 

of a mild day in your region to be associated with

 

 

 

 

 

 

the Maximum Recovery Ramp Rate. The

 

 

 

 

 

 

thermostat will begin recovery at the optimal time

 

 

 

 

 

 

based on a calculated ramp rate, allowing the

 

 

 

 

 

 

system to recover on time and save energy during

 

 

 

 

 

 

changing outdoor conditions.

 

 

 

 

 

 

During recovery, the setpoint changes at a rate in

 

 

 

 

 

 

degrees per hour depending on the outdoor

 

 

 

 

 

 

temperature.

 

 

 

 

 

 

 

4060

Outdoor Temperature

Off

40° F

Commercial

No

Off: The heating system will begin recovery at the

 

used with Maximum

-20° F to 100° F

 

 

 

time that is scheduled.

 

Heat Recovery Ramp

 

 

 

 

 

Rate

 

 

 

 

When a Maximum Recovery Ramp Rate is set, the

 

 

 

 

 

 

thermostat will begin recovery early to ensure the

 

 

 

 

 

 

temperature is reached at the scheduled time.

 

 

 

 

 

 

Set a Maximum Recovery Ramp Rate based on the

 

 

 

 

 

 

rate that the heating system can recover at for a

 

 

 

 

 

 

mild day in your region. Default setting is 8° F /

 

 

 

 

 

 

hour.

 

 

 

 

 

 

Set an Outdoor Temperature that is representative

 

 

 

 

 

 

of a mild day in your region to be associated with

 

 

 

 

 

 

the Maximum Recovery Ramp Rate. The

 

 

 

 

 

 

thermostat will begin recovery at the optimal time

 

 

 

 

 

 

based on a calculated ramp rate, allowing the

 

 

 

 

 

 

system to recover on time and save energy during

 

 

 

 

 

 

changing outdoor conditions.

 

 

 

 

 

 

During recovery, the setpoint changes at a rate in

 

 

 

 

 

 

degrees per hour depending on the outdoor

 

 

 

 

 

 

temperature.

 

 

 

 

 

 

 

68-0311—01

30

Loading...
+ 96 hidden pages