Honeywell TH1110DN, TH1210DN, TH2110DH User Manual

0 (0)

Installation

Guide

PRO TH2000DH/TH1000DH Series

Thermostats

This manual covers the following models

TH1100DH: For Heat only systems

TH2110DH/TH1110DH: For 1 Heat/1 Cool systems

TH2210DH/TH1210DH: For 2 Heat/1 Cool heat pump systems only (Pull thermostat from wallplate and turn over to find model number.)

System Types

TH2110DH/TH1110DH:

Gas, oil, or electric heat with air conditioning

Warm air, hot water, high-efficiency furnaces, 1 Heat/1 Cool heat pumps, steam, gravity

Heat only

Heat only with fan

Cool only

750 mV heating systems

TH2210DH/TH1210DH:

2 Heat/1 Cool heat pumps

TH1100DH:

Gas, oil, or electric heat

Warm air, hot water, steam, gravity

Heat only

750 mV heating systems

Must be installed by a trained, experienced technician

Read these instructions carefully. Failure to follow these instructions can damage the product or cause a hazardous condition.

Need Help?

For assistance with this product please visit http://customer.honeywell.com or call Honeywell Customer Care toll-free at 1-800-468-1502

® U.S. Registered Trademark. Patents pending.

 

Copyright © 2011 Honeywell International Inc.

 

All rights reserved.

69-2609EFS-03

 

Installation Guide

Wallplate installation

Pull at bottom to remove thermostat from wallplate.

TO REMOVE WALLPLATE

PULL HERE

M32731

Remove the wallplate from the thermostat as shown at left, then follow directions below for mounting.

1.Pull wires through wire hole.

2.Position wallplate on wall, level and mark hole positions with pencil.

3.Drill holes at marked positions as shown below, then tap in supplied wall anchors.

4.Place wallplate over anchors, insert and tighten mounting screws.

Drill 3/16" holes for drywall. Drill 7/32" holes for plaster.

Wire hole

Mounting screws

Wall anchors

ENGLISH

M32805

CAUTION: ELECTRICAL HAZARD

Can cause electrical shock or equipment damage. Disconnect power before beginning installation.

MERCURY NOTICE

If this product is replacing a control that contains mercury in a sealed tube, do not place the old control in the trash. Contact the Thermostat Recycling Corporation at www.thermostat-recycle.org or 800-238-8192 for information on how and where to properly and safely dispose of your old thermostat.

69-2609EFS—03

2

PRO TH2000DH/TH1000DH Series

Power options

KEEP WIRES IN

THIS SHADED AREA INSERT BATTERIES FOR

REMOVE FACOTRY- PRIMARY OR BACKUP POWER

INSTALLED JUMPER

ONLY FOR TWO-

TRANSFORMER

SYSTEMS

XXXX

TH2110DH TERMINAL

BLOCK SHOWN

W C

CONNECT C FOR PRIMARY

 

AC POWER (OPTIONAL IF

M32807

BATTERIES ARE INSTALLED)

M32806

 

Wiring

Terminal designations

TH2110DH/TH1110DH:

BChangeover valve energized in heating

OChangeover valve energized in cooling

G Fan relay

Y Compressor contactor

W Heat relay

C24 Vac common. For 2-transformer systems, use common wire from cooling transformer.

R24 Vac power from heating transformer

Rc 24 Vac power from cooling transformer

TH2110DH/

TH1110DH

B

O G Y W C R Rc

 

M32808

TH1100DH:

W

Heat relay

TH1100DH

C

24 Vac common

 

R

24 Vac power

W C R Not

 

 

Used

 

 

M32810

TH2210DH/TH1210DH:

BChangeover valve energized in heating

OChangeover valve energized in cooling

G Fan relay

Y Compressor contactor

Aux/E Auxiliary heat relay

C 24 Vac common

R 24 Vac power

TH2210DH/TH1210DH

B O G Y Aux/ C R

Not

E

Used

M32809

ENGLISH

3

69-2609EFS—03

Honeywell TH1110DN, TH1210DN, TH2110DH User Manual

Installation Guide

Wiring

Wiring guide — conventional and heat pump systems

2H/1C Heat

 

 

 

Pump System

B O G

Y Aux/ C R

Not

TH2210DH/TH1210DH

E

Used

 

 

 

M32809

BChangeover valve energized in heating [5]

OChangeover valve energized in cooling [5]

G Fan relay

Y Compressor contactor

Aux/E Auxiliary heat relay

C 24 Vac common [3]

R Power [1]

1H/1C System

 

 

 

 

TH2110DH/

 

 

 

 

TH1110DH

 

 

 

 

(1 transformer)

G

Y

W C R Rc

G

Fan relay

 

 

 

M32811

Y

Compressor contactor

 

 

 

W

Heat relay

 

 

 

 

C

24 Vac common [3]

 

 

 

 

R

[R+Rc joined by jumper]

 

 

Rc

Power [1]

 

 

 

 

1H/1C System

 

 

 

 

TH2110DH/

 

 

 

 

TH1110DH

G

Y

W

C R Rc

(2 transformers)

 

 

 

M32812

G Fan relay

Y Compressor contactor

W Heat relay

C 24 Vac common [3, 4]

R Power (heating transformer) [1, 2]

Rc Power (cooling transformer) [1, 2]

ENGLISH TH1100DH

W C R UsedNot

Heat Only System

 

W

Heat relay

M32817

C

24Vac common [3]

 

R

Power [1]

 

See [notes] below

NOTES

Wire specifications:

Use 18to 22-gauge thermostat wire. Shielded cable is not required.

[1]Power supply. Provide disconnect means and overload protection as required.

[2]Remove jumper for 2-transformer systems.

[3]Optional 24 Vac common connection.

1H/1C Heat

 

 

Pump System

B O G Y W C R Rc

TH2110DH/TH1110DH [7]

M32813

 

 

BChangeover valve energized in heating [5]

OChangeover valve energized in cooling [5]

G Fan relay

Y Compressor contactor [6]

W [W+Y joined by jumper]

C 24 Vac common [3]

R [R+Rc joined by jumper]

Rc Power [1]

Heat Only

System W C R Rc

TH2110DH/TH1110DH M32814

W Heat relay

C 24Vac common [3]

R [R+Rc joined by jumper]

Rc Power [1]

Heat Only

 

 

System with

G

W C R Rc

Fan TH2110DH/TH1110DH

M32815

G Fan relay

W Heat relay

C 24 Vac common [3]

R [R+Rc joined by jumper]

Rc Power [1]

Cool Only

 

 

System

G Y

C R Rc

TH2110DH/TH1110DH

 

M32816

 

 

G Fan relay

Y Compressor contactor

C 24 Vac common [3]

R [R+Rc joined by jumper]

Rc Power [1]

[4]Common connection must come from cooling transformer.

[5]Use either O or B terminals for changeover valve.

[6]Use a small piece of wire (not supplied) to connect W and Y terminals.

[7]Set fan operation switch to Heat Pump (see page 5).

69-2609EFS—03

4

PRO TH2000DH/TH1000DH Series

Fan operation settings

TH2110DH/TH1110DH only:

Gas or Oil: For gas or oil heating systems, leave the fan operation switch in this factoryset position. (This setting is for systems that control the fan in a call for heat.)

Electric or Heat Pump: Change the switch to this setting for heat pump or electric heat systems.

(This setting is for systems that allow the thermostat to control the fan in a call for heat, if a fan wire is connected to the G terminal.)

Set fan operation switch.

XXXX

GAS OR OIL

ELECTRIC OR HEAT PUMP

GAS OR OIL

ELECTRIC OR HEAT PUMP

M32818

Thermostat mounting

Align the 2 tabs at the top of the wallplate with corresponding slots on the back of the thermostat, then push gently until the thermostat snaps in place.

W/ Not

Aux Used

Push excess wire back into the wall opening.

Plug wall opening with non-flammable insulation.

 

Fan

Heat Off Cool

Auto On

M32757

W/ Not

Aux Used

ENGLISH

 

Fan

Heat Off Cool

Auto On

M32705

5

69-2609EFS—03

Installation Guide

Installer setup

Follow the procedure below to configure the thermostat to match the installed heating/cooling system, and customize feature operation as desired.

To begin, press and hold the σ and τ buttons until the display changes.

ENGLISH

 

Fan

 

Fan

Heat Off Cool

Auto On

Heat Off Cool

Auto On

5

5

Setting

 

 

 

 

 

M32819

Function number

Press the σ or τ button to change the setting.

Press the σ and τ buttons simultaneously for one second to advance to the next function.

Press and hold the σ and τ buttons to exit and save settings.

NOTE: If you do not press any button for 60 seconds while you are in the setup menu, the thermostat automatically saves any changes made and exits the menu.

69-2609EFS—03

6

PRO TH2000DH/TH1000DH Series

Installer setup

Setup function

Settings & options (factory default in bold)

5

Heating cycle rate

5

For gas or oil furnaces of less than 90% efficiency

 

(CPH: cycles/hour)

1

For steam or gravity systems

 

TH2110DH, TH1110DH

3

For hot water systems & furnaces of over 90% efficiency

 

and TH1100DH

6

For electric furnaces

 

 

 

[Other cycle rate options: 2 or 4 CPH]

6

Auxiliary heat

5

For gas or oil furnaces of less than 90% efficiency

 

cycle rate (CPH)

1

For steam or gravity systems

 

TH2210DH and

3

For hot water systems & furnaces of over 90% efficiency

 

TH1210DH

6

For electric furnaces

 

 

 

[Other cycle rate options: 2 or 4 CPH]

9

Compressor

3

Recommended for most compressors

 

cycle rate (CPH)

 

[Other cycle rate options: 1, 2, 4, 5, or 6 CPH]

13

Early Start (TH2110DH

1

On **See page 8

 

and TH2210DH)

0

Off

14

Temperature

0

Fahrenheit

 

display

1

Celsius

15

Compressor

5

Five-minute compressor off time (See page 8)

 

protection

0

No compressor off time

20

Clock display

0

12-hour display

 

(TH2110DH and

1

24-hour display

 

TH2210DH)

 

 

25

Lower temperature

0

Standard range 40°F to 90°F (4.5°C to 32°C)

 

range (TH1100DH only)

1

Lower range (for garage mode) 35°F to 90°F

 

 

 

(1.5°C to 32°C)

40

Restore program

0

Off

 

schedule to default

1

On - program schedule default settings are listed in the

 

(TH2110DH and

 

operating manual

 

TH2210DH)

 

 

CAUTION: EQUIPMENT DAMAGE HAZARD

Compressor protection is bypassed during testing. To prevent equipment damage, avoid cycling the compressor quickly.

ENGLISH

7

69-2609EFS—03

Installation Guide

Special functions

Early Start (Setup Function 13): Early start allows the heating or cooling to turn on before the program start time, so the temperature is reached at the time you set.

Compressor Protection (Setup Function 15): Forces the compressor to wait a few minutes before restarting, to prevent damage. During the wait time, the message Cool On or Heat On (heat pumps only) will flash on the display.

Accessories & replacement parts

Please contact your distributor to order replacement parts.

Cover plate assembly*......................................

Part Number 50002883-001

*Use to cover marks left by old thermostats.

 

Specifications

Temperature Ranges

Heat: 40° to 90°F (4.5° to 32°C)

Cool: 50° to 99°F (10° to 37°C)

Operating Ambient Temperature

32° to 120°F (0° to 48.9°C)

Shipping Temperature

-20° to 120°F (-28.9° to 48.9°C)

Electrical Ratings

 

System

Voltage (50/60Hz)

Running Current

Heat (1st stage)

20-30 Vac

0.02-1.0 A

(Powerpile)

750 mV DC

100 mA DC

Auxiliary heat

20-30 Vac

0.02-1.0 A

Cooling

20-30 Vac

0.02-1.0 A

Operating Relative Humidity

5% to 90% (non-condensing)

Physical Dimensions

3-7/16”H x 4-10/16”W x 1-3/16”D 87mm H x 119mm W x 30mm D