Honeywell Vista-50P, Vista-50PUL User Manual

0 (0)

$'(0&2 9,67$ 6(5,(6 9,67$ 3 9,67$ 38/

&RPPHUFLDO %XUJODU\ 3DUWLWLRQHG 6HFXULW\ 6\VWHP :LWK 6FKHGXOLQJ

3URJUDPPLQJ *XLGH

VISTA50P-PRV2 5/04 Rev A

Table of Contents

Recommended Programming Procedure.................

3

Relay Programming ................................................

25

Program Field Index .................................................

4

Relay Voice Descriptors .........................................

28

VISTA-50P/VISTA-50PUL Programming Form........

5

Relay Voice Descriptors and Custom Word

 

Partition-Specific Fields

10

Substitutes Vocabulary........................................

29

Custom Word Substitutes for VIP Module

 

Programming With #93 Menu Mode

12

 

Annunciation

30

Zone Programming

13

System Layout Worksheets

31

5800 Series Transmitters Loop Designations

15

Relay Devices Worksheets

39

Expert Mode Zone Programming

16

Scheduling Menu Prompts

41

Alpha Descriptors Programming

20

Scheduling Worksheets

42

Alpha Descriptor Vocabulary

23

VISTA-50P/VISTA-50PUL Summary of

 

Device Programming

24

 

Connections Diagram

47

 

 

The purpose of this document is to provide a quick and easy way to program your entire system. A recommended programming procedure is included, followed by a list of program fields with the corresponding program group they belong to (system-wide, partition-specific, scheduling, etc.). Two program forms are included. One contains all the programming fields, and the other contains the partition-specific fields. If you are setting up a single-partition system, the partition-specific fields become system-wide fields.

Following the program forms are system layout worksheets. We recommend that you use these sheets to plan your system before programming is performed. If you need further information about specific programming options, see the ADEMCO VISTA-50P/VISTA-50PUL Installation and Setup Guide.

Make sure that one two-line alpha keypad is connected to the control and is set to device address "00."

Single-Partition System

The system default is for a single-partition system. Use the VISTA-50P/VISTA-50PUL SINGLE PARTITION PROGRAMMING FORM when programming for single-partition usage. Follow the steps outlined in RECOMMENDED PROGRAMMING PROCEDURE of this document for proper programming procedure.

Multiple-Partition System

You must enter the number of partitions you are using in data field 2*00 to set the system for multiple partitions. Use the VISTA-50P/VISTA-50PUL SINGLE PARTITION and the PARTITION-SPECIFIC PROGRAM FORMS when programming the system for multiple partitions. Follow the steps outlined in RECOMMENDED PROGRAMMING PROCEDURE of this document for proper programming procedure.

SUMMARY OF PROGRAMMING COMMANDS

To enter program mode, enter installer code + [8] + [0] + [0]

To set standard defaults, press 97

To change to next page of program fields, press 94

To return to previous set of fields, press 99

To erase account and phone number field entries, press [ ] + field number + [ ]

To assign zone descriptors, press #93 + follow menu prompts

To add custom words, press #93 + follow menu prompts

To enter Installer's Message, press #93 + follow menu prompts

To exit program mode, enter 99 OR 98: 99 allows re-access to programming mode by installer code.98 prevents re-access to programming mode by installer code.

Standard default ( 97) values are shown in brackets [ ], otherwise default = 0.

– 2 –

Recommended Programming Procedure

The following is a step-by-step procedure recommended for programming your VISTA-50P/VISTA-50PUL system.

1.Set the keypads (and other peripheral devices) to the appropriate addresses.

2.Set factory defaults by pressing 97.

This will automatically enable keypad addresses 00-03, so be sure at least one keypad is set to one of these addresses.

3.Program system-wide (global) data fields.

Using the programming form as a guide, enter program mode and program all system-wide programming fields. These options affect the entire system, regardless of partitions. They include control options, downloader and dialer options, RF options, event logging options, etc. Refer to the Program Field Index for a listing of the program fields and their function.

Note that field 2 00 (number of partitions) must be programmed before continuing.

4.Program partition-specific fields.

When the system-wide fields have been programmed, program all partition-specific programming fields by first pressing 91 to select a partition (while still in data field program mode). Then enter the first partitionspecific field number 09. When you are finished, the next partition-specific field is automatically displayed. Partition-specific fields can have different values for each partition. To program the fields for the next partition, press 91, enter the desired partition number, then enter field 09. Refer to the PROGRAMMING section in the ADEMCO VISTA-50P/VISTA-50PUL Installation and Setup Guide for detailed instructions.

5.Use #93 Menu Mode for device programming.

Refer to Device Programming in this guide to assign keypad ID numbers and default partitions for each keypad, and to selectively suppress certain keypad sounding options. Also use this mode to assign RF receivers, relay modules, the VIP module, the ECP Long Range Radio, and the VISTA Gateway Module.

6.Use #93 Menu Mode for zone programming.

Refer to Zone Programming in this guide to program zone response types, assign right loop zones and wireless zones, assign zones to partitions, and to program alarm report codes.

7.Use #93 Menu Mode for programming outputs.

Refer to Output Programming in this guide to program desired output operation.

8.Program Communication options.

Refer to System Communication section in the ADEMCO VISTA-50P/VISTA-50PUL Installation and Setup Guide for detailed instructions. Then use #93 menu mode to program report codes.

9.Use #93 Menu Mode for programming alpha descriptors.

Refer to Alpha Programming in this guide to enter zone and partition descriptors and a custom installer’s message.

10.Use #93 Menu Mode for relay voice descriptors and custom word substitutes.

Refer to Relay Voice Descriptors in this guide for further instructions for programming relay descriptors to be annunciated by the VIP module, as well as the Custom Index section for custom word substitutes.

11.Use #80 Mode for programming schedules.

Refer to the Scheduling Menu Prompts in the ADEMCO VISTA-50P/VISTA-50PUL Installation and Setup Guide to program open/close schedules, temporary and holiday schedules, limitation of access schedules, and time-driven events.

12.Define user access codes.

Refer to User Access Codes in the ADEMCO VISTA-50P/VISTA-50PUL Installation and Setup Guide to program authority level, O/C reporting option, partition assignments, and RF key assignments for each user.

13.Exit Programming Mode.

Exit programming mode by pressing either 98 or 99. Additional entries of 99 are required if the exit is being done from fields 1 00 and above.

To prevent re-access to programming mode using the Installer’s code, use 98. The only way to re-access programming mode is by depressing both the [ ] and [#] keys at the same time within 30 seconds of powerup.

Exiting by using 99 always allows reentry into programming mode using the Installer code. Either way of exiting allows access via downloading. Note that if local programming lockout is set via downloading, programming mode cannot be entered at the keypad.

3 –

Program Field Index

On the following pages, the programming fields have been arranged in numerical order. Use this index to cross-reference the fields on the programming form.

Field

Group

 

 

Field

Group

 

 

Field

Group

 

 

 

 

 

 

 

 

 

 

*00

System-Wide

 

*57

Communications

 

1*28

System-Wide

*02

# 93 Menu Mode

 

*58

Communications

 

1*29

System-Wide

*03

# 93 Menu Mode

 

*59

Communications

 

1*30

System-Wide

*04

# 93 Menu Mode

 

*60

Communications

 

1*31

System-Wide

*05

# 93 Menu Mode

 

*61

Communications

 

1*33

Communications

*09

Partition-Specific

 

*62

Communications

 

1*34

Communications

*10

Partition-Specific

 

*63

Communications

 

1*35

Communications

*11

Partition-Specific

 

*64

Communications

 

1*36

Communications

*12

Partition-Specific

 

*65

Communications

 

1*37

Communications

*13

Partition-Specific

 

*66

Communications

 

1*38

Communications

*14

System-Wide

 

*67

Communications

 

1*39

Communications

*15

System-Wide

 

*68

Communications

 

1*40

Communications

*16

Partition-Specific

 

*69

Communications

 

1*41

Communications

*17

System-Wide

 

*70

Communications

 

1*42

Communications

*19

System-Wide

 

*71

Communications

 

1*43

Partition-Specific

*20

System-Wide

 

*72

Communications

 

1*44

System-Wide

*21

System-Wide

 

*73

Communications

 

1*45

Partition-Specific

*22

Partition-Specific

 

*74

Communications

 

1*46

System-Wide

*23

Partition-Specific

 

*75

Communications

 

1*47

Partition-Specific

*24

System-Wide

 

*76

Communications

 

1*48

System-Wide

*25

System-Wide

 

*77

Communications

 

1*49

System-Wide

*26

Communications

 

*78

Communications

 

1*52

Partition-Specific

*27

Communications

 

*79

Communications

 

1*53

System-Wide

*28

System-Wide

 

*80

Communications

 

1*57

System-Wide

*29

Partition-Specific

 

*81

Communications

 

1*58

System-Wide

*30

Communications

 

*82

Communications

 

1*60

System-Wide

*31

Communications

 

*83

Communications

 

1*70

System-Wide

*32

Partition-Specific

 

*84

Partition-Specific

 

1*71

System-Wide

*33

Communications

 

*85

Partition-Specific

 

1*72

System-Wide

*34

Communications

 

*87

Partition-Specific

 

1*73

System-Wide

*35

System-Wide

 

*88

Partition-Specific

 

1*74

System-Wide

*36

System-Wide

 

*89

Communications

 

1*75

System-Wide

*37

System-Wide

 

*90

Partition-Specific

 

1*76

Partition-Specific

*38

Partition-Specific

 

1*01

# 93 Menu Mode

 

2*00

System-Wide

*39

Partition-Specific

 

1*02

# 93 Menu Mode

 

2*01

System-Wide

*40

Communications

 

1*03

# 93 Menu Mode

 

2*02

System-Wide

*41

System-Wide

 

1*04

# 93 Menu Mode

 

2*05

Partition-Specific

*42

Communications

 

1*05

# 93 Menu Mode

 

2*06

Partition-Specific

*43

Communications

 

1*06

# 93 Menu Mode

 

2*07

Partition-Specific

*44

Communications

 

1*07

# 93 Menu Mode

 

2*08

Partition-Specific

*45

Communications

 

1*08

# 93 Menu Mode

 

2*09

Partition-Specific

*46

Communications

 

1*09

# 93 Menu Mode

 

2*10

Partition-Specific

*47

Communications

 

1*17

System-Wide

 

2*11

System-Wide

*48

Communications

 

1*18

Partition-Specific

 

2*13

Communications

*49

Communications

 

1*19

Partition-Specific

 

2*14

Communications

*50

Communications

 

1*20

System-Wide

 

2*18

Partition-Specific

*51

Communications

 

1*21

System-Wide

 

2*19

System-Wide

*52

Communications

 

1*22

System-Wide

 

2*20

Partition-Specific

*53

Communications

 

1*23

System-Wide

 

2*21

System-Wide

*54

System-Wide

 

1*24

System-Wide

 

 

 

 

*56

Communications

 

1*25

System-Wide

 

 

 

 

– 4 –

VISTA-50P/VISTA-50PUL Programming Form

Some fields are programmed for each partition (shown as shaded fields). If you are programming a multiple-partition system, see the Partition-Specific Fields section for programming these fields. Standard default (*97) values are shown in brackets [ ].

*00

INSTALLER CODE

 

| |

|

 

 

Enter 4 digits, 0-9 [4140]

 

 

 

 

*02

 

*05 RESPONSE TYPES FOR ZONES

 

 

 

 

 

 

 

 

 

 

 

Skip these fields. Use #93 Menu Mode, Zone

 

 

 

 

Programming to program the response types.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*09

ENTRY DELAY #1

[02]

 

|

 

 

 

 

 

 

 

 

 

 

00, 02-15 times 15 seconds

 

 

 

 

 

Maximum "03" for UL.

 

 

 

 

 

 

 

 

 

 

*10

EXIT DELAY #1

[03]

 

|

 

 

 

 

 

 

 

 

 

 

00, 03-15 times 15 seconds

 

 

 

 

 

Maximum "04" for UL installations.

 

 

 

 

 

 

 

 

 

 

*11

ENTRY DELAY #2

[06]

 

|

 

 

 

 

 

 

 

 

 

 

00, 02-15 times 15 seconds (must be longer than Entry Delay

 

#1). Maximum "03" for UL installations.

 

 

 

 

 

 

 

 

 

 

*12

EXIT DELAY #2

[08]

 

|

 

 

 

 

 

 

 

 

 

 

00, 03-15 times 15 seconds (must be longer than Exit Delay

 

#1). Maximum "04" for UL installations.

 

 

 

 

 

 

 

 

 

 

*13

ALARM SOUNDER DURATION

[04]

 

|

 

 

 

 

 

 

 

 

 

 

01-15 times 2 minutes. Must be minimum 16 minutes for UL

 

installations.

 

 

 

 

*14

ZONE 9 RESPONSE TIME

[0]

 

 

 

 

*25

BURG.TRIGGER FOR RESPONSE TYPE 8

[1]

 

 

 

1=enable; 0=disable

 

 

 

 

 

 

 

 

 

 

*26

INTELLIGENT TEST REPORTING

 

[0]

 

 

 

 

 

 

1=yes (no report sent if any other report was recently sent);

 

 

0=no (send report at programmed interval, field *27)

 

 

 

 

 

Must be 0 for UL installations.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*27

TEST REPORT INTERVAL

 

[024]

 

 

|

| |

 

 

Enter interval in hours, 001-999; 0000=no report;

 

 

 

 

 

 

Max. 024 for UL installations.

 

 

 

 

 

 

 

 

 

 

*28

POWER UP IN PREVIOUS STATE

 

[1]

 

 

 

 

 

 

1=yes; 0=no; "1" for UL installations.

 

 

 

 

 

 

 

 

 

*29

QUICK ARM

 

 

 

 

 

 

[1]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1=yes; 0=no

 

 

 

 

 

 

 

 

 

 

*30

TOUCHTONE OR ROTARY DIAL

 

[0]

 

 

 

 

 

 

1=TouchTone; 0=rotary

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*31

PABX ACCESS CODE

 

|

 

|

 

 

|

 

|

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

00-09; B-F (11-15)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*32

PRIM. SUBS. ACCT #

 

|

 

|

 

 

|

 

|

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Enter 00-09; B-F (11-15) [15 15

15

15]

 

 

 

 

 

 

 

*33

PRIMARY PHONE NUMBER

 

 

 

 

 

 

 

 

 

 

Enter 1 for fast response time 10ms

Enter 0 for normal response time 350ms.

Must be 0 for UL installations.

*15

KEYSWITCH ASSIGNMENT

 

 

[0]

 

 

 

Enter partition in which keyswitch used,

 

 

 

 

 

 

 

 

 

1-8; 0=disable

 

 

 

 

 

 

 

 

 

 

*16

CONFIRMATION OF ARMING DING

[0]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1=enable; 0=disable.

 

 

 

 

 

 

 

 

 

 

 

Must be "1" for UL Installations.

 

 

 

 

 

 

 

 

 

 

*17

AC LOSS KEYPAD SOUNDING

 

 

[0]

 

 

 

 

 

 

 

1=yes; 0=no

 

 

 

 

 

 

 

 

 

 

*19

RANDOMIZE AC LOSS REPORT

[0]

 

 

 

 

 

1=10-40 min; 0=normal report (about 2 min. after AC loss).

 

 

 

 

 

 

 

 

 

 

 

 

*20

VIP MODULE PHONE CODE

 

 

|

 

 

 

 

|

 

 

Enter 01 - 09 for the first digit; enter

 

 

[00],

 

 

 

[11]

 

 

11 for “*” or 12 for “#” for the second digit.

 

 

 

 

 

 

 

 

 

Must be set to "0" for UL installations.

 

 

 

 

 

 

 

 

 

 

*21

PREVENT FIRE TIMEOUT

 

 

[0]

 

 

 

 

 

 

 

1=No timeout; 0=Timeout.

 

 

 

 

 

 

 

 

 

 

*22

KEYPAD PANIC ENABLES

[001]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1=enable; 0=disable

995 996

999

 

*23

MULTIPLE ALARMS

 

 

[1]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1=yes; 0=no

 

 

 

 

 

 

 

 

 

 

*24

IGNORE EXPANSION ZONE TAMPER

[0]

 

 

 

 

1=Ignore; 0=Enable tamper for RF and RPMs.

Must be "0" for UL installations if using these devices.

Enter 0-9 for each digit. Enter #11 for *, #12 for #, #13 for 2 second pause

*34 SECONDARY PHONE NUMBER

Enter 0-9 for each digit. Enter #11 for *, #12 for #, #13 for 2 second pause

*35 DOWNLOAD PHONE NO.

Enter 0-9 for each digit. Enter #11 for *, #12 for #, #13 for 2 second pause

*36 DOWNLOAD ID NO.

|

 

|

 

|

 

|

 

|

 

|

 

|

 

|

Enter 00-09; A-F (10-15) [15 15 15 15 15 15 15 15]

*37 DOWNLOAD COMMAND ENABLES

0

Dlr ShtdwnSys ShtdwnNot UsedRmt BypRmt DisarmRmt ArmUpld PgmDwnld Pgm

See field 1*53 for Callback disable option; [1=enable]; 0=disable. For UL installations, all entries must be "0."

 

 

 

 

*38 PREVENT ZONE XX BYPASS

[00]

|

 

 

 

 

 

01-86; 00 if all zones (except fire zones) can be bypassed

– 5 –

*39

ENABLE OPEN/CLOSE REPORT FOR

[0]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INSTALLER CODE 1=enable; 0=disable

 

 

 

 

*40

OPEN/CLOSE REPORT FOR KEYSWITCH

[0]

 

 

 

 

 

1=enable; 0=disable

 

 

 

 

 

 

 

*41

NORMALLY CLOSED or EOLR (Zones 2-8)

[1]

 

 

 

 

 

1=N.C.loops; 0=EOLR supervision.

 

 

 

 

 

 

 

 

Must be "0" for UL installations.

 

 

 

 

 

 

 

*42

DIAL TONE PAUSE

 

 

 

[0]

 

 

 

 

 

 

 

 

0=5 seconds; 1=11 seconds; 2=30 seconds.

 

 

 

 

 

Must be "0" UL Installations.

 

 

 

 

 

 

 

*43

DIAL TONE DETECTION

 

 

 

[1]

 

 

 

 

 

 

 

 

1=wait for true dial tone; 0=pause, then dial

 

 

 

 

 

 

 

 

 

 

 

 

*44

RING DETECTION COUNT

[00]

 

|

 

 

01-14; 15=answering machine; 00=no detection.

 

 

 

 

 

Must be "00" for UL Burglary.

 

 

 

 

 

 

 

*45

PRIMARY FORMAT

 

 

 

[1]

 

 

 

 

 

 

 

 

0=Low Speed; 1=Contact ID; 2=ADEMCO High Speed;

 

3= ADEMCO Express

 

 

 

 

 

 

 

*46

LOW SPEED FORMAT (Primary)

 

 

 

[0]

 

 

 

 

 

 

 

 

0= ADEMCO Low Speed; 1=Sescoa/Radionics

 

 

 

 

*47

SECONDARY FORMAT

 

 

 

[1]

 

 

 

 

 

 

 

 

0=Low Speed; 1=Contact ID; 2= ADEMCO High Speed;

 

3= ADEMCO Express

 

 

 

 

 

 

 

*48

LOW SPEED FORMAT (Sec.)

 

 

 

[0]

 

 

 

 

 

 

 

 

0= ADEMCO Low Speed; 1=Sescoa/Radionics

 

 

 

 

*49

CHECKSUM VERIFICATION

[0] [0]

 

 

 

 

 

 

 

 

 

 

 

 

 

1=yes; 0=no

Prim

 

 

Sec

*50

SESCOA/RADIONICS SELECT

 

 

 

[0]

 

 

 

 

 

 

 

 

1=Sescoa; 0=Radionics

 

 

 

 

 

 

 

*51

DUAL REPORTING

 

 

 

[0]

 

 

 

 

 

 

 

1=yes; 0=no If used with Spilt Reporting "1" option (1*34), alarms and alarm restores go to both primary & secondary numbers, while all other reports go to secondary only. If used with Split Reporting "2" option, alarms and alarm restores go to both, open/close and test messages go to secondary only, while all other reports go to primary.

*52 STANDARD/EXPANDED REPORT FOR PRIMARY

[0 0 0 0 0 0]

Alarm Rstr Byp Trbl O/C LoBat

0=standard; 1=expanded;

Note: Expanded overrides 4+2 format.

*53 STANDARD/EXPANDED REPORT FOR SECONDARY

[0 0 0 0 0 0]

Alarm Rstr Byp Trbl O/C LoBat

0=standard; 1=expanded;

*54 *57 ALARM REPORT CODES & ID DIGITS FOR ZONES 01-16.

Skip these fields. Use #93 Menu Mode, Zone Programming to program the report codes.

*58 SUPERVISORY AND RESTORE CODES FOR ZONES 01-16. Enter 00-09; B-F (11-15). Default = [00 00 00 00 00]

|

 

|

 

|

 

|

 

|

Alarm Rst

Trbl

 

Trbl Rst

 

Byp

 

Byp Rst

*59 *62 ALARM REPORT CODES & ID DIGITS FOR ZONES 17-32.

Skip these fields. Use #93 Menu Mode, Zone Programming to program the report codes.

*63 SUPERVISORY AND RESTORE CODES FOR ZONES 17-32. Enter 00-09; B-F (11-15). Default = [00 00 00 00 00]

|

 

|

 

|

 

|

 

|

Alarm Rst

Trbl

 

Trbl Rst

 

Byp

 

Byp Rst

*64 *67 ALARM REPORT CODES & ID DIGITS FOR ZONES 33-48.

Skip these fields. Use #93 Menu Mode, Zone Programming to program the report codes.

*68 SUPERVISORY AND RESTORE CODES FOR ZONES 33-48. Enter 00-09; B-F (11-15). Default = [00 00 00 00 00]

|

 

|

 

|

 

|

 

|

Alarm Rst

Trbl

 

Trbl Rst

 

Byp

 

Byp Rst

*69 *72 ALARM REPORT CODES & ID DIGITS FOR ZONES 49-64.

Skip these fields. Use #93 Menu Mode, Zone Programming to program the report codes.

*73 SUPERVISORY AND RESTORE CODES FOR ZONES 49-64. Enter 00-09; B-F (11-15). Default = [00 00 00 00 00]

|

 

|

 

|

 

|

 

|

Alarm Rst

Trbl

 

Trbl Rst

 

Byp

 

Byp Rst

*74 *77 ALARM REPORT CODES & ID DIGITS FOR ZONES 81-99.

Skip these fields. Use #93 Menu Mode, Zone Programming to program the report codes.

*78 SUPERVISORY AND RESTORE CODES FOR ZONES 81-99. Enter 00-09; B-F (11-15). Default = [00 00 00 00 00]

 

 

 

 

 

 

 

|

 

 

 

 

 

 

 

|

 

 

 

|

 

 

|

 

 

|

 

 

 

 

 

 

Alarm Rst

Trbl

 

Trbl Rst

 

Byp

Byp Rst

ZONE TYPE RESTORE ENABLES

 

 

 

 

 

 

 

 

 

 

 

*79 FOR ZONE TYPES 1-8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

3

4

 

 

5

 

 

 

6

 

 

7

8

 

 

 

 

 

 

 

 

1=enable; [0=disable]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*80 FOR TYPES 9, and 10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

10

1=enable; [0=disable]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

– 6 –

*80

 

*81

SYSTEM NON-ALARM CODES

 

 

 

 

Enter 00-09; B-F (11-15).

 

 

 

Default = 00 for all reports

*80 1st Digit

 

*81 2nd Digit

 

 

 

 

 

 

 

 

 

 

 

 

 

Close

|

 

 

 

 

 

 

 

|

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Open

|

 

 

 

 

 

 

 

|

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low Battery

|

 

 

 

 

 

 

 

|

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low Battery Restore

|

 

 

 

 

 

 

 

|

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Loss

|

 

 

 

 

 

 

 

|

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Restore

|

 

 

 

 

 

 

 

|

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Test

|

 

 

 

 

 

 

 

|

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power Up

|

 

 

 

 

 

 

 

|

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cancel

|

 

 

 

 

 

 

 

|

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Program Tamper

|

 

 

 

 

 

 

 

|

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*83 FIRST TEST REPORT TIME

 

|

 

 

 

|

 

 

|

 

 

[Day 00; hour 12; min 00] Days 01-07 Hours 00-23 Min 0059; 00 in all boxes = instant (Day 01= Monday)

 

 

 

 

*84 SWINGER SUPPRESSION

[01]

|

 

 

 

 

 

01-15 alarms

Must be "00" (disabled) for UL.

*85 ENABLE DIALER REPORTS FOR PANICS & DURESS

1=enable; [0=disable]

995 996 999 Duress

*87

ENTRY WARNING

 

 

 

 

 

 

 

 

[1]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1=continuous; 0=3 beeps

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*88

BURG. ALARM COMM. DELAY

 

 

 

 

[0]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1=16 seconds; 0=no delay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Must be "0" for UL installations.

 

 

 

 

 

 

 

 

 

 

*89

RESTORE REPORT TIMING

 

 

 

 

[0]

 

 

 

 

 

 

 

 

 

 

 

0=Instant; 1=After bell timeout if zone is restored; 2=when

 

system is disarmed. Must be "0" for UL installations.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*90

SEC. SUBS. ACCT #

 

|

 

 

|

 

 

|

 

 

|

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Enter 00-09; B-F (11-15)

[15 15 15 15]

 

 

 

 

 

 

 

 

 

 

2nd Page Programming Fields (press *94)

 

 

 

 

 

 

 

1*01

 

 

1*09 ASSIGN RESPONSE TYPE FOR ZONES.

 

 

 

 

 

Skip these fields. Use #93 Menu Mode, Zone

 

 

 

Programming to program the response types.

1*17

 

LOBBY PARTITION

 

 

 

 

 

 

 

 

[0]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Enter the "common lobby" partition (1-8)

 

 

 

 

 

 

 

 

 

 

1*18

 

AFFECTS LOBBY

 

 

 

 

 

 

 

 

[0]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Enter 1 if this partition affects the common lobby;

enter 0 if it

 

 

 

does not.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Must be "0" for UL installations.

 

 

 

 

 

 

 

 

 

 

1*19

 

ARMS LOBBY

 

 

 

 

 

 

 

 

[0]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Enter 1 if arming this partition attempts to arm lobby; enter 0

 

 

 

if it does not.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Must be "0" for UL installations.

 

 

 

 

 

 

 

 

 

 

1*20 EXIT ERROR LOGIC ENABLE

[0]

 

 

 

 

 

 

 

 

0=No; 1=Bypass E/E and Interior zones faulted after exit

delay.

 

 

 

Must be "0" for UL installations.

 

 

 

1*21 EXIT DELAY RESET [0]

0=No; 1=Resets Exit Delay to programmed value after zone is closed and then faulted prior to end of exit delay.

Must be "0" for UL installations.

FIELDS 1 22-1 25: Allow four sets of two zones each to be linked so that both must fault within a five minute period to cause an alarm. Default for these fields = [000], [000].

1*22

CROSS-ZONING PAIR ONE

|

 

|

 

 

 

 

1*23

CROSS-ZONING PAIR TWO

|

 

|

 

 

 

 

1*24

CROSS-ZONING PAIR THREE

|

 

|

 

 

 

 

1*25

CROSS-ZONING PAIR FOUR

|

 

|

MISCELLANEOUS WIRELESS OPTIONS

Fields 1*28 - 1*31 are not applicable for UL installations.

1*28

RF TX LOW BATTERY SOUND

 

[0]

 

 

1=immediate; 0=when disarmed

 

 

 

 

1*29

RF TX LOW BATTERY REPORTING

 

[0]

 

 

1=enable; 0=disable

 

 

 

 

 

 

 

 

 

 

1*30

RF RCVR CHECK-IN INTERVAL

[06]

 

|

 

02-15 times 2 hours; 00 disables supervision

 

 

 

 

 

 

 

 

 

1*31

RF XMITTER CHECK-IN INTERVAL

[12]

 

|

 

02-15 times 2 hours; 00 disables transmitter supervision

1*33

TOUCHTONE W/ROTARY BACKUP

 

[0]

 

 

 

 

1=enable; 0=disable

 

 

 

 

1*34

COMM. SPLIT REPORTING

 

[0]

 

0=no; 1=alarms and alarm restores primary, others secondary; 2=open/close, test secondary, others primary. See 751 for comments if using with dual reporting.

1*35 1*38 ALARM REPORT CODES & ID DIGITS FOR ZONES 65-80.

Skip these fields. Use #93 Menu Mode, Zone Programming to program the report codes.

1*39 SUPERVISORY AND RESTORE CODES FOR ZONES 65-80. Enter 00-09; B-F (11-15).

Default = [00 00 00 00 00]

|

 

|

 

|

 

|

 

|

Alarm Rst

Trbl

 

Trbl Rst

 

Byp

 

Byp Rst

– 7 –

1*40

 

1*41 NON-ALARM DIALER CODES

 

 

 

 

 

 

 

 

 

 

 

 

 

Enter 00-09; B-F (11-15).

 

 

 

 

 

 

 

 

 

Default = 00 for all reports

 

 

 

 

 

 

 

 

 

1*40 1st Digit

1*41 2nd Digit

 

 

 

 

 

 

 

 

 

 

 

 

 

Armed STAY

 

|

 

 

|

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Time/Date Set or Event Log Reset

 

|

 

 

|

 

 

 

 

 

 

 

 

 

 

 

 

 

Event Log 50% & 90% Full

 

|

 

 

|

 

 

 

 

 

 

 

 

 

 

 

 

 

Event Log Overflow

 

|

 

 

|

 

 

 

 

 

 

 

 

 

 

 

 

 

Exit Error (Zone)

 

|

 

 

|

 

 

 

 

 

 

 

 

 

 

 

 

 

Exit Error (User)

 

|

 

 

|

 

 

 

 

 

 

 

 

 

 

 

 

 

Recent Close

 

|

 

 

|

 

 

1*42

CALL WAITING DEFEAT

 

 

[0]

 

 

 

 

 

 

 

 

 

1=Yes; 0=No

 

 

 

 

 

 

 

1*43

PERM. KEYPAD BACKLIGHT

 

 

[0]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1=enable; 0=disable When disabled, display lights when any

 

key is pressed, and turns off after period of keypad inactivity.

1*44

WIRELESS KEYPAD TAMPER

 

 

[0]

 

 

 

 

 

 

 

 

 

DETECTION

 

 

 

 

 

 

 

 

1=enable; 0=disable.

 

 

 

 

 

 

 

 

Must be "0" for UL installations.

 

 

 

 

 

 

 

1*45

EXIT DELAY SOUNDING

 

 

[0]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1=enable; 0=disable. Produces quick beeping during exit

 

delay if enabled.

 

 

 

 

 

 

 

1*46

AUXILIARY OUTPUT MODE

 

 

[0]

 

 

 

 

 

 

 

 

Enter 0 for ground start output.

Enter 1 for open/close trigger (is produced only if all partitions are armed.

Enter 2 for keypad-like sounding. Applies to the partition enabled in field *15.

Enter 3 if AAV module is being used.

NOTE: Only one of the above options may be active within the system.

1*47

CHIME ON EXTERNAL SIREN

[0]

 

 

 

 

 

 

 

 

 

 

1=enable; 0=disable

 

 

 

1*48

WIRELESS KEYPAD ASSIGNMENT

[0]

 

 

 

 

 

0=disable; enter partition in which RF keypad used, 1-8.

 

Must be "0" for UL installations.

 

 

 

1*49

SUPPRESS TX SUPERVISION SOUND

[1]

 

 

 

 

 

1=disable; 0=enable.

 

 

 

 

Must be "0" for UL installations.

 

 

 

1*52

SEND CANCEL IF ALARM + OFF

[1]

 

 

 

 

 

 

 

 

 

 

1=no restriction; 0=within bell timeout period only

 

 

 

1*53

DOWNLOAD CALLBACK

[0]

 

 

 

 

 

1=callback not required; 0=callback required.

 

 

 

 

Must be "0" for UL installations.

 

 

 

1*57

5800 RF BUTTON GLOBAL ARM

[0]

 

 

 

 

 

1=enable; 0=disable

 

 

 

1*58 5800 RF BUTTON FORCE ARM

[0]

Enter "1" to enable. If a zone is faulted after pressing button, keypad will beep once. Pressing the button again within 4 sec. bypasses the zone. Enter "0" to disable.

Must be "0" for UL installations.

1*60 ZONE 5 AUDIO ALARM VERIFICATION [0]

Enter 1 If 2-way audio (AAV) is being used; Enter 0 if it is not.

Must be "0" for UL installations.

1*69 PRINTER TYPE

[0]

Enter 0 if you are using a parallel printer connected to the VA8201 Alpha Pager Module.

Enter 1 if you are using a serial printer.

1*70 EVENT LOG TYPES

[1 0 0 0 1]

Alarm Chk Byp O/C Syst

1=enable; 0=disable

1*71

12/24 HOUR TIME STAMP FORMAT

[0]

 

 

0=12 hour; 1=24 hour

 

 

1*72

EVENT LOG PRINTER ON-LINE

[0]

 

 

 

0=disable; 1=enable

 

 

1*73

PRINTER BAUD RATE

[0]

 

 

 

1=300; 0=1200

 

 

 

 

 

 

1*74

RELAY TIMEOUT XXX MINUTES [000]

|

|

 

Enter the relay timeout, 000-127 in multiples of 2 minutes,

 

desired for #80 Menu Mode time-driven event relay

 

 

command numbers "04/09" and #93 Menu Mode Output

 

Programming output command "56."

 

 

 

 

 

 

1*75

RELAY TIMEOUT YYY SECONDS [000]

|

|

Enter the relay timeout, 000-127 seconds, desired for #80 Menu Mode time driven event relay command numbers "05/10" and #93 Menu Mode Output Programming command "57."

 

 

 

 

1*76 ACCESS CONTROL RELAY

[00]

|

 

 

 

 

 

Relay will be pulsed for 2 seconds whenever code + [0] is

pressed. Enter 00-16; 00=none.

 

 

 

Must be "00" for UL.

 

 

 

3rd Page Programming Fields (press *94)

 

 

 

2*00

NUMBER OF PARTITIONS

 

 

 

 

[1]

 

 

 

Enter 1-8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2*01

DAYLIGHT SAVING TIME

[04, 10]

 

|

 

|

 

 

START/END MONTH

 

 

Start

End

 

00-12; if no daylight saving time, enter 00,00

 

 

 

 

 

 

 

 

 

 

2*02

DAYLIGHT SAVING TIME

[1, 5]

|

 

 

START/END WEEKEND

 

 

Start | End

 

Enter 1-7. 1=first; 2=second; 3=third; 4=fourth; 5=last;

 

6=next to last; 7=3rd from last [1,5]

 

 

 

 

 

 

 

 

 

 

 

 

2*05

AUTO-ARM DELAY

 

 

[15]

|

 

 

 

 

 

 

 

 

 

 

 

Enter the time between the end of the arming window and

 

the start of auto-arming warning period, in values of 1-14

 

times 4 minutes 00=instant; [15=no auto arm

at all]. When

this delay expires, the Auto-Arm Warning Period begins.

– 8 –

 

 

 

 

2*06 AUTO-ARM WARNING PERIOD

[15]

|

 

 

 

 

 

This is the time during which the user is warned to exit the premises prior to the auto-arming of the system (beeps every

15 seconds; "ALERT" displayed). Enter 01-15 minutes.

00=instant at end of arming delay.

 

 

 

 

2*07 AUTO-DISARM DELAY

[15]

|

 

 

 

 

 

This is the time between the end of the disarming window and the start of auto-disarming. Enter 01-14 times 4 minutes; 00=instant at end of window; 15=no auto-disarm.

2*08 ENABLE FORCE ARM FOR AUTO-ARM [0]

0=disable; 1=enable

2*09 OPEN/CLOSE REPORTS BY EXCEPTION [0]

1=enable; 0=disable

If enabled, only openings and closings occurring outside the scheduled opening/closing windows will trigger dialer reports. Opening reports will also be suppressed during the closing window, in order to prevent false reports when the user arms the system and then reenters the premises to

retrieve a forgotten item.

2*10 ALLOW DISARMING ONLY DURING

[0]

 

 

 

 

 

 

 

 

ARMING/DISARMING WINDOWS

0=disable; 1=enable

See system-wide field 2*11 if enabling field 2*10. This feature adds high security to the installation.

2*11 ALLOW DISARM OUTSIDE WINDOW

[0]

IF ALARM OCCURS

Used only if field 2*10 (partition-specific field) is set to "1." If this field is enabled ("1") the system can be disarmed outside the disarm window if an alarm has occurred. If "0," disarming can only be done during the disarm window. If field 2*10 is set to "0" for a partition, this field has no effect for that partition.

2*13 2*14 SCHEDULING RELATED REPORT CODES

Enter 00-09; B-F (11-15).

 

 

 

 

 

Default = 00 for all reports

 

 

 

 

 

2*13 1st Digit

2*14 2nd Digit

 

 

 

 

 

 

 

Early Opening

 

|

 

 

|

 

 

 

 

 

 

Early Closing

 

|

 

 

|

 

 

 

 

 

 

Late Opening

 

|

 

 

|

 

 

 

 

 

 

Late Closing

 

|

 

 

|

 

 

 

 

 

 

No Opening (late to open)

 

|

 

 

|

 

 

 

 

 

 

No Closing (late to close)

 

|

 

 

|

 

 

 

 

 

 

Auto-Arm Failure

 

|

 

 

|

 

 

 

 

 

 

Access Schedule Changed

 

|

 

 

|

 

2*18

ENABLE GOTO FOR THIS PARTITION

[0]

 

 

 

 

 

 

 

 

 

 

 

 

1=Allow log-on from other partitions; 0=disable

 

 

 

2*19

USE PARTITION DESCRIPTORS

 

 

[0]

 

 

 

 

 

 

 

0=disable; 1=enable

 

 

 

 

 

2*20

ENABLE J7 TRIGGERS FOR PARTITION

[1]

 

 

 

 

 

 

 

 

 

 

 

 

0=disable for displayed partition; 1=enable for displayed

 

partition

 

 

 

 

 

2*21

ENABLE SUPERVISION PULSES FOR LRR

 

 

 

 

 

 

 

 

 

 

 

TRIGGER OUTPUTS

[000]

 

|

|

 

 

Used for supervised connection to 7920SE. F

B

P

 

Enter 0 to disable or 1 to enable the listed outputs.

 

 

 

F= Fire; B= Burglary; P= Silent Panic/Duress.

Must be 1 for UL. Installations.

SUMMARY OF PROGRAMMING COMMANDS

To enter program mode, enter installer code + [8] + [0] + [0]

To set standard defaults, press *97

To change to next page of program fields, press *94

To return to previous set of fields, press *99

To erase account and phone number field entries, press [*] + field number + [*]

To assign zone descriptors, press #93 + follow menu prompts

To add custom words, press #93 + follow menu prompts

To enter Installer's Message, press #93 + follow menu prompts

To exit program mode, enter *99 OR *98: *99 allows reaccess to programming mode by installer code. *98 prevents re-access to programming mode by installer code.

– 9 –

Partition-Specific Fields

(Duplicate this page for each partition in the installation.)

To program these fields,

1.Press *91 to select a partition.

2.Enter a partition-specific field number (ex. *09).

3.Make the required entry.

4.Repeat steps 1-3 for each partition in the system.

PARTITION #____ PROGRAM FIELDS

1st Page Fields

*87

ENTRY WARNING

[1]

 

*09 ENTRY DELAY #1

[02]

|

 

1=continuous; 0=3 beeps

 

00, 02-15 times 15 seconds.

Maximum 03 for UL Listed installations.

*10

EXIT DELAY #1

 

 

 

[03]

 

 

|

 

 

00, 03-15 times 15 seconds.

 

 

 

 

 

 

 

 

 

 

 

 

Maximum 04 for UL Listed installations.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*11

ENTRY DELAY #2

 

 

 

[06]

 

 

|

 

 

00, 02-15 times 15 seconds.

 

 

 

 

 

 

 

 

 

 

 

 

Maximum 03 for UL installations.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*12

EXIT DELAY #2

 

 

 

[08]

 

 

|

 

 

00, 03-15 times 15 seconds.

 

 

 

 

 

 

 

 

 

 

 

 

Maximum 04 for UL installations.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*13

ALARM SOUNDER DURATION

[04]

 

 

|

 

 

01-15 times 2 minutes.

 

 

 

 

 

 

 

 

 

 

 

 

 

Must be minimum 16 minutes for UL installations.

 

 

*16

CONFIRMATION OF ARMING DING

[0]

 

 

 

 

 

1=enable; 0=disable.

 

 

 

 

 

 

 

 

 

 

 

 

 

Must be "1" for UL installations.

 

 

 

 

 

 

 

 

 

 

 

*22

KEYPAD PANIC ENABLES

[001]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1=enable; 0=disable

 

 

 

995 996

 

999

*23

MULTIPLE ALARMS

 

 

 

[1]

 

 

 

 

 

 

 

 

1=yes; 0=no.

 

 

 

 

 

 

 

 

 

 

 

 

 

Must be 1 for UL installations.

 

 

 

 

 

 

 

 

 

 

 

*29

QUICK ARM

 

 

 

[1]

 

 

 

 

 

 

 

 

1=yes; 0=no

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*32

PRIM. SUBS. ACCT #

|

 

|

 

 

|

 

 

|

 

 

Enter 00-09; B-F (11-15)

[15 15

15 15]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*38

PREVENT ZONE XX BYPASS

[00]

 

 

|

 

 

01-86; 000 if all zones (except fire zones)

can be bypassed

*39

ENABLE OPEN/CLOSE REPORT

[0]

 

 

 

 

 

FOR INSTALLER CODE

 

 

 

 

 

 

 

 

 

 

 

 

1=enable; 0=disable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*84

SWINGER SUPPRESSION

 

 

[01]

 

 

|

 

 

01-15 alarms;

 

 

 

 

 

 

 

 

 

 

 

 

*85

Must be "00" (disabled) for UL installations..

 

 

ENABLE DIALER REPORTS FOR PANICS & DURESS

1=enable; [0=disable]

995 996 999 Duress

*88

BURG. ALARM COMM. DELAY

 

 

 

[0]

 

 

 

 

1=16 seconds; 0=no delay.

 

 

 

 

 

 

 

 

 

 

 

 

Must be "0" for UL installations. Must be “1” for SIA

 

 

 

 

 

 

installations.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*90

SEC. SUBS. ACCT #

 

|

 

 

|

 

|

 

 

|

 

Enter 00-09; B-F (11-15)

[15 15 15 15]

 

 

 

 

 

 

 

2nd Page Programming Fields (press *94)

 

 

 

 

 

 

 

1*18

AFFECTS LOBBY

 

 

 

 

 

 

[0]

 

 

 

 

 

 

 

 

 

 

 

 

Enter 1 if this partition affects the common lobby; enter 0 if it does not.

1*19 ARMS LOBBY

[0]

Enter 1 if arming this partition attempts to arm lobby; enter 0 if it does not

1*20 EXIT ERROR LOGIC ENABLE

[0]

0=No; 1=Bypass E/E and Interior zones faulted after exit delay.

Must be "0" for UL installations.

1*21 EXIT DELAY RESET

[0]

0=No; 1=Resets Exit Delay to programmed value after zone is closed and then faulted prior to end of exit delay.

Must be "0" for UL installations.

1*43 PERM. KEYPAD BACKLIGHT

[0]

 

1=enable; 0=disable. When disabled, display lights when

any key is pressed, and turns off after period of keypad

inactivity.

 

 

1*45

EXIT DELAY SOUNDING

[0]

 

 

 

1=enable; 0=disable. Produces quick beeping during exit

 

 

delay if enabled.

 

 

 

 

1*47

CHIME ON EXTERNAL SIREN

[0]

 

 

 

 

 

1=enable; 0=disable

 

 

 

 

1*52

SEND CANCEL IF ALARM + OFF

[1]

 

 

 

 

 

1=no restriction; 0=within Bell Timeout period only

 

 

 

 

 

 

 

 

1*76

ACCESS CONTROL RELAY FOR PART.[00]

|

 

 

Relay will be pulsed for 2 seconds whenever code + [0] is

 

 

pressed. Enter 00-16; 00=none.

 

 

 

 

 

Must be "00" for UL installations.

 

 

 

 

– 10 –

3rd Page Programming Fields (press *94)

2*05 AUTO-ARM DELAY

[15]

|

Enter the time between the end of the arming window and the start of auto-arming warning period, in values of 1-14 times 4 minutes 00=instant; [15=no auto arm at all]. When this delay expires, the Auto-Arm Warning Period begins.

2*06 AUTO-ARM WARNING PERIOD

[15]

|

This is the time during which the user is warned to exit the premises prior to the auto-arming of the system (beeps every 15 seconds; "ALERT" displayed). Enter 01-15 minutes. 00=instant at end of arming delay .

2*07 AUTO-DISARM DELAY

[15]

|

This is the time between the end of the disarming window and the start of auto-disarming. Enter 01-14 times 4 minutes; 00=instant at end of window; 15=no auto-disarm

2*08 ENABLE FORCE ARM FOR AUTO-ARM [0]

0=disable; 1=enable

2*09 OPEN/CLOSE REPORTS BY EXCEPTION [0]

1=enable; 0=disable If enabled, only openings and closings occurring outside the scheduled opening/closing windows will trigger dialer reports. Opening reports will also be suppressed during the closing window, in order to prevent false reports when the user arms the system and then reenters the premises to retrieve a forgotten item.

2*10 ALLOW DISARMING ONLY DURING

[0]

ARMING/DISARMING WINDOWS

See system-wide field 2*11 if enabling field 2*10. This feature adds high security to the installation. 0=disable; 1=enable

2*18

ENABLE GOTO FOR THIS PARTITION

[0]

 

1=Allow log-on from other partitions; 0=disable

 

2*20

ENABLE J7 TRIGGERS BY PARTITION

[1]

0=disable for displayed partition; 1=enable for displayed partition

SUMMARY OF PROGRAMMING COMMANDS

To enter program mode, enter installer code + [8] + [0] + [0]

To set standard defaults, press *97

To change to next page of program fields, press *94

To return to previous set of fields, press *99

To erase account and phone number field entries, press [*] + field number + [*]

To assign zone descriptors, press #93 + follow menu prompts

To add custom words, press #93 + follow menu prompts

To enter Installer's Message, press #93 + follow menu prompts

To exit program mode, enter *99 OR *98: *99 allows reaccess to programming mode by installer code. *98 prevents re-access to programming mode by installer code.

– 11 –

Programming With #93 Menu Mode

NOTE: The following field should be preset before beginning: 2*00 Number of Partitions. In addition, receivers should be programmed via Device programming.

After programming all system related programming fields in the usual way, press #93 while still in programming mode to display the first choice of the menu driven programming functions. Press 0 (NO) or 1 (YES) in response to the displayed menu selection. Pressing 0 will display the next choice in sequence.

#93 MENU MODE KEY COMMANDS

The following is a list of commands used while in the menu mode. #93 Enters Menu mode

[4] Serves as ENTER key. Press to have keypad accept entry. [#] Backs up to previous screen.

0Press to answer NO

1Press to answer YES

01-09 All data entries are either 1-digit or 2-digit entries.

00 Exits menu mode, back into field programming mode, when entered at the first question for each category.

Menu selections are as follows:

 

 

PROMPT

 

 

 

EXPLANATION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

For programming the following:

 

 

ZONE PROG?

 

 

 

 

 

 

 

 

Zone Number

 

 

 

1 = YES 0 = NO

0

 

 

 

 

 

 

 

 

 

 

 

 

Zone Response Type

 

 

 

 

 

 

 

 

• Partition Number for Zone

• Dialer report code for zone

• Input Device Type for zone (whether RF, polling loop, etc.)

• Enrolling serial numbers of 5800 Series transmitters & serial polling loop devices into the system.

 

EXPERT MODE?

 

 

1 = YES

0 = NO

0

 

 

 

 

 

 

 

 

ALPHA PROG?

 

 

1 = YES

0 = NO

0

 

Same as Zone Programming except:

Done with a minimum number of keystrokes.

Can program wireless keys using pre-defined templates.

For entering alpha descriptors for the following:

Zone Descriptors

Installer's Message

Custom Words

Partition Descriptors

Relay Descriptors

 

DEVICE PROG?

 

 

For defining the following device characteristics for addressable devices, including keypads, RF receivers

 

 

 

(5881), output relay modules (4204), and 4285/4286 VIP Module:

 

1 = YES 0 = NO

0

 

 

 

 

Device Address

 

 

 

 

 

 

 

 

Device Type

 

 

 

 

Keypad Options (incl. partition assignment)

 

 

 

 

RF House ID

 

 

 

 

 

 

 

 

 

 

 

 

 

RELAY PGM?

 

 

1 = YES

0 = NO

0

 

 

 

 

 

 

 

 

RLY VOICE DESCR?

 

 

1 = YES

0 = NO

0

 

 

 

 

 

 

 

 

CUSTOM INDEX ?

 

 

1 = YES

0 = NO

0

 

 

 

 

 

For defining output relay functions.

For entering voice descriptors for relays to be used with the 4285/4286 VIP Module.

For creating custom word substitutes for VIP Module annunciation.

– 12 –

Zone Programming

If using 5800 Series transmitters, do not the install batteries until you are ready to enroll them. After enrolling the transmitter, the battery need not be removed. This is to prevent enrolling the wrong serial number.

 

 

PROMPT

 

 

 

EXPLANATION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Press 1 to enter ZONE PROGRAMMING mode. The following screens appear. Press [ ] to display the next

 

 

ZONE PROG?

 

 

 

 

 

 

screen. Press # to display a previous screen.

 

 

 

1 = YES

0 = NO

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

This prompt appears once upon entering Zone Programming Mode.

 

 

SET TO CONFIRM?

 

 

 

 

 

 

If “Yes,” Confirmation prompts will be displayed after the device’s Serial and Loop numbers have been

 

 

 

1 = YES

0 = NO

0

 

 

 

 

 

 

 

 

 

entered later.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ENTER ZONE NO.

 

00 = QUIT

10

Zone 10 entered

10 ZT P RC In L

0 0

1

1 0

0 0 1

10 ZONE TYPE PERIMETER 03

Zone number 10 and Zone Type 03 entry shown

† These are special zone types used with 5800 Series Wireless Pushbutton Units that result in arming the system in the STAY or AWAY mode, or disarming the system, depending on the selection made.

Enter the 2-digit zone number to be programmed, as follows: Protection Zones = 01–86

System Supervisory Zones = 88, 89, 90, 91, 92 (duress), 97 and 98 (bell supervision) Keypad Panic Zones = 95, 96, 99

Press [ ] to continue.

This display appears, showing a summary of the zone's current programming. ZT = Zone Type, P = Partition, RC = Report Code, In = the input type of device, and L = the device's loop number to which the sensor is connected.

Some devices can support more than one zone by means of individual loops (for example, 5801, 5804, 5816, 5817, etc.). If the zone is not programmed, the display appears as shown here. If you are checking a zone's programming, and it is programmed satisfactorily, press [#] to back up one step and enter another zone number, if desired.

Press [ ] to continue.

Each zone must be assigned a zone type, which defines the way in which the system responds to faults in that zone. Refer to the Zone Type Definitions section in the ADEMCO VISTA-50P/VISTA-50PUL Installation and Setup Guide for detailed definitions of each zone type. Enter the zone type desired (or change it, if necessary). Available zone types are listed below.

00

= Assign for Unused Zones

08

= 24 Hr. Auxiliary

01

= Entry/Exit #1, Burglary

09

= Fire Without Verification

02

= Entry/Exit #2, Burglary

10

= Interior Delay, Burglary

03

= Perimeter, Burglary

20

= Arm–STAY†

04

= Interior Follower, Burglary

21

= Arm AWAY†

05

= Trouble Day/Alarm Night

22

= Disarm†

06

= 24

Hr. Silent Alarm

23

= No Alarm Response

07

= 24

Hr. Audible Alarm

 

(e.g., relay activation)

Press [ ] to continue.

 

10

Partition

 

Enter the partition number (1–8) you are assigning this zone to.

 

 

Press [ ] to continue.

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Enter the report code. The report code consists of 2 hexadecimal digits, each in turn consisting of 2

 

10 REPORT CODE

 

 

 

numerical digits. For example, for a report code of "3C," enter 03 for "3" and 12 for "C."

 

1st

03 2nd 12

3C

 

 

(Refer to the System Communication section in the Installation and Setup Guide for more information about

 

 

 

 

 

 

 

 

report codes and reporting formats.)

 

 

 

 

Press [ ] to continue.

 

 

 

 

 

– 13 –

 

PROMPT

 

EXPLANATION

 

 

 

 

 

 

 

 

 

 

 

 

10 INPUT TYPE

 

RF Xmitter

3

Input types 4 & 5 are valid for certain 5800 Series transmitters only (e.g., 5801, 5802, 5802CP & 5803).

10 INPUT S/N:

L

AXXX-XXXX

1

10 INPUT S/N:

L

A022-4064

1

 

10 INPUT S/N:

L

 

A022-4064

1

 

 

 

 

Enter the input device type as follows: 00 = not used

01 = hardwired

03 = supervised RF transmitter (RF type)

04 = unsupervised RF transmitter (UR type)

05 = RF button-type transmitter (BR type)

06 = serial number polling loop device (SL type)

07 = DIP switch-type polling loop device

08 = right loop of DIP switch type device

Right loops refer to the use of the right loop on a 4190WH Zone Expander Module and/or 4278 PIR, which allow hardwired devices to be monitored by the polling loop.

If you are programming hardwired or DIP switch polling loop devices, the summary display appears after completing this entry.

Press [ ] to continue.

For Serial Number entry and Loop Number entry, do one of the following:

a.Transmit two open and close (or close and open) sequences. For a button-type transmitter, press and release the button, wait approximately 4 seconds, then press and release the button a second time.

OR

b.Manually enter the 7-digit serial number printed on a label on the transmitter, using the Alpha keypad. Then press the [ ] key, the cursor moves to the “L” position. You can edit the loop number, if necessary. When the loop number is acceptable, press [ ].

OR

c.Press key [C] to copy the last serial number enrolled (used when programming a transmitter with several input loops).

Press [ ] to accept.

The cursor will then move to the Loop column (L) with the previously entered/transmitted serial number displayed.

Enter the loop number (refer to 5800 Series Transmitters Loop Designations below).

To Delete an Existing Serial Number, enter “0“ in the loop number field. The serial number will change to “0”s.

If “0” was entered in error, simply re-enter the loop number or press [#], and the serial number will return to the display.

Press [ ] to accept.

The system will then check for a duplicate serial/loop number combination.

If a duplicate serial/loop number combination is found, the keypad will emit a single long beep, and display the serial number along with a “?” for the loop number, allowing you to re-enter the correct loop number.

If the serial/loop number combination is not a duplicate in the system, a display appears showing the serial number and loop number entry.

Press [ ] to continue.

– 14 –

Honeywell Vista-50P, Vista-50PUL User Manual

5800 Series Transmitters Loop Designations

 

LOOP 3

 

 

 

LOOP 2

 

 

 

LOOP 1

 

 

 

 

 

LOOP

 

LOOP 4

 

1

 

 

 

 

YOU MUST

 

 

 

ENROLL THIS

 

 

 

BUTTON

 

 

 

5801

 

5 8 0 2 M N

ENROLL AS "UR" OR "RF"

ENROLL AS "UR" OR "RF"

YOU MUST

LOOP 3

 

 

 

 

 

ENROLL THIS

 

 

 

BUTTON

LOOP 2

 

 

LOOP 4

 

 

LOOP 1

 

 

 

 

LOOP 2

 

 

 

YOU MUST

 

 

 

ENROLL THIS

 

 

 

BUTTON

 

 

 

LOOP 4

 

 

 

LOOP 1

 

LOOP 3

 

 

 

5 8 0 4

•••

 

 

ENROLL

 

 

•••••

SET

 

 

• ••••

 

AS "BR"

• • •

HOUSE

 

•••

CODE

5804BD

ENROLL AS "BR"

LOOP 1

5809

ENROLL AS "RF"

 

LOOP 2

 

(REED)

LOOP

 

1

LOOP 1

 

(TERMINALS)

5808

5 8 1 6

ENROLL AS "RF"

ENROLL AS "RF"

 

 

LOOP 2

 

LOOP 1

 

 

(REED)

 

 

 

 

(PRIMARY)

 

 

 

 

 

 

 

 

LOOP 2

 

 

 

 

(AUX. CENTER)

 

 

LOOP 1

 

 

 

 

(TERMINALS)

LOOP 3

 

 

 

 

ALTERNATE

 

 

 

(AUX. RIGHT)

POSITION

 

5 8 1 6 M N

 

5 8 1 7

FOR LOOP 2

 

 

 

ENROLL AS "RF"

 

ENROLL AS "RF"

 

 

 

 

LOOP 2

 

LOOP

 

 

(REED)

 

 

LOOP 1

 

 

2

 

 

 

 

(TERMINALS)

 

 

(REED)

 

 

 

 

 

 

 

 

 

 

 

LOOP 1

 

 

 

LOOP 3

(INTERNAL

 

 

(TERMINALS)

SHOCK

 

 

 

 

SENSOR)

LOOP 3

 

 

 

 

(TERMINALS)

 

 

 

 

 

5 8 1 9

 

5819S (WHS & BRS)

ENROLL AS "RF"

 

ENROLL AS "RF"

 

5 8 2 7

 

 

5 8 2 7 B D

SET HOUSE CODE

 

SET HOUSE CODE

LOOP 1 (MOTION)

(Green) (Red) (Yellow)

5850 (GBD)

5 8 9 0

ENROLL AS "RF"

ENROLL AS "RF"

5800_trans_loop-V0

Note: For information on any transmitter not shown above, refer to the instructions accompanying that transmitter for details regarding loop numbers, etc.

 

 

UL

The 5802MN, 5802MN2, 5804, 5804BD, 5814, 5816TEMP, 5819, 5819WHS & BRS, 5827BD,

 

 

and 5850 transmitters are not intended for use in UL installations.

 

 

 

 

 

 

 

 

 

 

 

 

 

PROMPT

 

 

EXPLANATION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

XMIT TO CONFIRM PRESS TO SKIP

Confirmation Option: This prompt only appears if you answered “Yes” at the first prompt. The system enters a confirmation mode so that the operation of the actual programmed input can be confirmed. Activate the loop input or button that corresponds to this zone. At any time during this step, you may press the [ ] key on the keypad to save the serial and loop number combination without confirming.

 

Entd

A022-4063

1

 

If the serial number transmitted does not match the serial number entered, a display similar to the one

 

 

at the left appears. If the loop number does not match, it is also displayed.

 

Rcvd

A022-4064

 

 

 

 

 

 

 

If so, activate the loop input or button on the transmitter once again. If a match is not obtained (i.e., summary

 

 

 

 

 

 

 

 

 

 

display does not appear), press the [#] key twice and then enter or transmit the correct serial number.

 

 

 

 

 

 

 

 

 

 

 

 

10 ZT P RC In L

03 1 3C RF 1s

If the serial number transmitted does match the serial number entered, the system beeps 3 times and a summary display appears, showing that zone’s programming. Note that an “s” indicates that a transmitter’s serial number has been enrolled.

Press [ ] to accept the zone information.

– 15 –

Loading...
+ 33 hidden pages