Bosch B9512G, B6512, B8512G, B5512, B4512 Installation Manual

...
0 (0)
Control Panels
B9512G/B8512G/B6512/B5512/B4512/B3512 (B9512G‑E/ B8512G‑E/B5512E/B4512E/B3512E)
en ULC Installation Manual
Control Panels ULC Installation Guide | en 3
1 ULC Installation Guide
During any ULC installation described within this document, follow all rules for safe installation specified in the CEC (Canadian Electrical Code).
Control panels
Use this guide with the following control panel models (unless otherwise stated) and the model’s installation guide: – B9512G/B9512G-E v3.02.006 and higher – B8512G/B8512G-E v3.02.006 and higher – B6512 – B5512/B5512E v3.02.007 and higher – B4512/B4512E v3.02.007 and higher – B3512/B3512E v3.02.007 and higher The listed control panels are approved as ULC-S559 Fire Alarm Signal Communicators.
Notice! Control panel mounting
For mounting on the exterior of vault, safe, or stockroom, install a vibration detector (s304, 8.1.5).
Combination ULC-S559 and ULC-S304 control panels
The following control panel models can be configured as combination control panels: – B9512G/B9512G-E v3.02.006 and higher – B8512G/B8512G-E v3.02.006 and higher When used a combination control panel, Fire and Burg points must reside in separate areas.
Keypads
Use this guide with the following keypad models and the model’s installation guide: – B915/B915I v1.00.017 or higher – B920 v1.05.004 or higher
Transformers
For transformers, use:
Bosch Security Systems B.V. 2019.06 | 02 | F.01U.321.698
4 en | ULC Installation Guide Control Panels
B9512G/B9512G-E, B8512G/B8512G-E. Plug-in or hardwire
120 VAC primary, 16.5 VAC 37-40 VA secondary Class 2 Power Limited CSA/cUL listed.
B6512, B5512/B5512E, B4512/B4512E, B3512/B3512E.
Plug-in 120 VAC primary, 18 VAC 22 VA secondary class 2 power limited CSA/cUL Listed. Hardwire 120 VAC primary,
16.5 VAC 40 VA secondary Class 2 Power Limited CSA/cUL
listed. Refer to Compatible transformers, page 15. Install with ULC Listed devices where applicable.
Wiring
Use unshielded cable only.
Copyright
This document is the intellectual property of Bosch Security Systems, Inc. and is protected by copyright. All rights reserved.
Trademarks
All hardware and software product names used in this document are likely to be registered trademarks and must be treated accordingly.
Bosch Security Systems, Inc. product manufacturing dates
Use the serial number located on the product label and refer to the Bosch Security Systems, Inc. website at http:// www.boschsecurity.com/datecodes/.

1.1 Requirements

Key: P = Programmable R = Required O = Optional E = Enable
2019.06 | 02 | F.01U.321.698 Bosch Security Systems B.V.
Control Panels ULC Installation Guide | en 5
CAN/ULC S303 -
Local
Burglary
CAN/ULC S304 -
Signal Receiving
Centre and Premise
CAN/ULC S545 -
Residential
Fire
ULC-ORD C1023 -
Household
Burglary
ULC-ORD C1076 -
Proprietary
Burglary
CAN/ULC S559 -
Fire Signal Receiving
Centres and Systems
Requirements
Minimum battery standby
Battery size
1
Entry delay ≤ 45 sec P N/A N/A ≤ 45
Exit delay ≤ 45 sec P N/A N/A ≤ 60
Minimum Bell
24 hours 24
hours24hours
24 hours 4 hours 4
hours
B6512/B5512/B4512/B3512: 1 x 12 V/7 Ah, 1 x 12 V/18 Ah, 2x 12 V/7 Ah B9512G/B8512G: 2x 12 V/18 Ah
2
≤ 45
sec
sec
≤ 45
P P 5 min N/A
3
sec
4 min N/A
sec
cutoff time
Communicator E E E E E E
AC power
Tamper
4 4 4 5 4 4
R R O O O R
protection
Enclosures For compatible enclosures, refer to Compatibilities,
page 9.
1
Select battery capacity based on calculated AUX current consumption for
the system, including all accessories.
2
Do not use 2 x 12 V/18 Ah with a Solex 16.5 VAC 37 VA transformer.
3
Bell should not sound.
4
Plug-in transformer, optional hardwired connection.
5
In ULC-S559 applications, the control panel AC input shall be hard-wired
in accordance with Sec. 32 of CSA C22.1, Canadian Electrical Code..
Bosch Security Systems B.V. 2019.06 | 02 | F.01U.321.698
6 en | ULC Installation Guide Control Panels
Communication Channel Security (applicable to Commercial Burglary/Financial installations)
Notice! Active and passive communication
Systems are passive-only communication systems when the only communication method is over PSTN using the B430 module. Systems that use the on-board Ethernet, B426 module, or a cellular module are active or passive communication systems depending on the programmed poll rates.
Applicable for both IP and cellular communication.
Requirement Parameter
Supervision interval for IP and Cellular communication is 200 seconds (UL)
Supervision interval for IP and Cellular communication is 180 seconds (ULC)
Panel Wide Parameters > Enhanced Communications > Receiver Supervision Time set to 200 seconds
Panel Wide Parameters > Enhanced Communications > Receiver Supervision Time set to Custom, Poll Rate set to 89, ACK Wait Time set to 15, and Retry Count set to 5
Passive levels*
P1 For transmitters at the protected
P2 Medium
P3 High
Transmitters and supervision Receivers Risk
Levels
premises and supervision of
D6600 or D6100IPv6
Low
communication channels, refer to the figures in Fire monitoring communication systems wiring diagrams, page 18.
*Test the transmission on each communication channel every 24 hours.
2019.06 | 02 | F.01U.321.698 Bosch Security Systems B.V.
Control Panels ULC Installation Guide | en 7
Passive levels*
Transmitters and supervision Receivers Risk
Levels
The telephone service should be of a type that provides for timed release disconnect. In order to give the digital alarm communicator transmitter (dialer) the ability to disconnect an incoming call to the protected premises.
Active levels*
Transmitters and supervision
Receivers Risk
Levels
Backup requirements for network equipment
A1 For transmitters at the
A2 Medium
A3 High
A4 Very
protected premises and supervision of communication channels, refer to the figures in Fire
monitoring communication
D6600 or D6100IPv6
Low 24 hr standby
or dialer as backup
24 hr standby
high
systems wiring diagrams, page 18.
*Check-in/polling signal required every 180 seconds. For equipment used at the protected premises intended to facilitate communications (hubs, routers, NIM, cable modems) 24-hour backup power is required. Where such cannot be facilitated a secondary (backup) communication channel is required. For using private, corporate, and high speed data networks, network access and domain access policies must restrict unauthorized network access, and “spoofing” or “denial of service” attacks. Select the internet service providers that have redundant servers/systems, backup power, routers with firewalls enabled, and methods to identify and protect against “denial of service” attacks. For using public switched and wireless data networks, communication channels must be facilitated such that the communicator will restrict unauthorized access which could otherwise compromise security.
Bosch Security Systems B.V. 2019.06 | 02 | F.01U.321.698
8 en | ULC Installation Guide Control Panels
Fire Monitoring Communication Systems
Refer to Wiring, page 15. The central station receiver must receive fire alarms in 60 seconds and trouble signals in 90 seconds.
Type Transmitters and supervision Receivers
Passive
Active
1
2
For transmitters at the protected premises and supervision of communication
D6600 or D6100IPv6
channels, refer to the figures in Fire
monitoring communication systems wiring diagrams, page 18.
1
Test the transmission on each communication channel every 24 hours.
2
Check-in/polling signal required every 90 seconds. To monitor a complete fire system, each ULC labeled intrusion system must be connected to a ULC labeled fire alarm control panel. The system must transmit system fire alarms, and supervisory and troubles signals to the central station receiver.
Programming
You must follow the notes in the installation and programming sections describing the system configurations for ULC Listed installations.
Protecting the control panel – Burglary
The local control panel and local power supply must be protected in one of the following ways: – The control panel and power supply must be located within
the area of greatest protection on a tamper protected circuit.
When arming, each area must arm the area that is
protecting the control panel and any external power supply running an audible device. This might require duplicate protection armed by each area. Access to this protected area, without causing an alarm, requires that all areas are disarmed.
2019.06 | 02 | F.01U.321.698 Bosch Security Systems B.V.
Control Panels ULC Installation Guide | en 9
CAN/ULC S303 -
Local
Burglary
CAN/ULC S304 -
Signal Receiving
Centre and Premise
CAN/ULC S545 -
Residential
Fire
ULC-ORD C1023 -
Household
Burglary
ULC-ORD C1076 -
Proprietary
Burglary
CAN/ULC S559 -
Fire Signal Receiving
Centres and Systems
Additionally, the protected area for the control panel must be programmed so that it cannot be bypassed, and must be installed in accordance with CAN/ULC-S302 or CAN/ULC-S310.
User information
Inform the users of and note the following in the owner’s manual: – Service organization name and telephone number – The programmed exit time – The programmed entry time – Safety precautions specified for the connected equipment.

1.2 Compatibilities

Accessory compatibility
The following table lists accessories that are compatible with the control panel. An X in a column indicates the accessory is compatible with the standard.
Model number
Desc­ription
Keypads
B915/
Basic X X X X X X
B915I*
B920* 2-line X X X X X X
B921C*1Capacit
X X
ive
B925F* Fire/
X X X X X
Burg
B926F* Fire X
Bosch Security Systems B.V. 2019.06 | 02 | F.01U.321.698
10 en | ULC Installation Guide Control Panels
CAN/ULC S303 -
Local
Burglary
CAN/ULC S304 -
Signal Receiving
Centre and Premise
CAN/ULC S545 -
Residential
Fire
ULC-ORD C1023 -
Household
Burglary
ULC-ORD C1076 -
Proprietary
Burglary
CAN/ULC S559 -
Fire Signal Receiving
Centres and Systems
Model number
Desc­ription
B930* ATM
style
B942/ B942W*
Touch screen
B520 Power
supply
D122/ D122L
Battery harnes s
D135A Low-
battery discon nect
X X X X X
X X X X X
Transformers, batteries, power supplies, etc.
X X X X X
Suitable for use on approved applications.
Suitable for use on approved applications
D126
Battery Suitable for use on approved applications. (12.0 VDC, 7 Ah)
D1218
Battery Suitable for use on approved applications. (12 V, 18 Ah)
D1640-CATransfo
Suitable for use on approved applications in Canada.
rmer
2019.06 | 02 | F.01U.321.698 Bosch Security Systems B.V.
Control Panels ULC Installation Guide | en 11
CAN/ULC S303 -
Local
Burglary
CAN/ULC S304 -
Signal Receiving
Centre and Premise
CAN/ULC S545 -
Residential
Fire
ULC-ORD C1023 -
Household
Burglary
ULC-ORD C1076 -
Proprietary
Burglary
CAN/ULC S559 -
Fire Signal Receiving
Centres and Systems
Model number
ICP­TR1822-
Desc­ription
Transfo rmer
Suitable for use on approved applications in Canada.
CAN
Enclosures
B10***2MediumX X X X X X
2
B11
B8103***Large,
Small X X X X X X
X X X X X X
white
D8103***Large,
X X X X X X
grey
D8109***Fire X X X X X X
D8108A***Attack
X X X X X X resista nt
Expansion modules
B208 Octo-
X X X X input
B299 POPEX X X X X X
B308 Octo-
X X X X output
Bosch Security Systems B.V. 2019.06 | 02 | F.01U.321.698
12 en | ULC Installation Guide Control Panels
CAN/ULC S303 -
Local
Burglary
CAN/ULC S304 -
Signal Receiving
Centre and Premise
CAN/ULC S545 -
Residential
Fire
ULC-ORD C1023 -
Household
Burglary
ULC-ORD C1076 -
Proprietary
Burglary
CAN/ULC S559 -
Fire Signal Receiving
Centres and Systems
Model number
Desc­ription
B600 ZONEX X X X X X
D125B3Dual
X X X X initiatin g B
D129 Dual
X X X initiatin g A
D192G NAC X X X
D8125 POPEX X X X X
D8125MUXMultiplexX X X X
D8128D OctoP
X X X X OPIT
D8129 Octo-
X X X X relay
D8130 Door
X X X release
D9127U/TPOPIT X X X X
Communicators
B426 EthernetX X X X X
2019.06 | 02 | F.01U.321.698 Bosch Security Systems B.V.
Loading...