iEM3100 / iEM3200 / iEM3300 series
Energy meters User manual
DOCA0005EN-04 04/2014
www.schneider-electric.com
iEM3100 / iEM3200 / iEM3300 series user manual
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither Schneider Electric nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein. If you have any suggestions for improvements or amendments or have found errors in this publication, please notify us.
No part of this document may be reproduced in any form or by any means, electronic or mechanical, including photocopying, without express written permission of Schneider Electric.
All pertinent state, regional, and local safety regulations must be observed when installing and using this product. For reasons of safety and to help ensure compliance with documented system data, only the manufacturer should perform repairs to components.
When devices are used for applications with technical safety requirements, the relevant instructions must be followed.
Failure to use Schneider Electric software or approved software with our hardware products may result in injury, harm, or improper operating results.
Failure to observe this information can result in injury or equipment damage.
© 2014 Schneider Electric. All rights reserved.
DOCA0005EN-04 |
3 |
iEM3100 / iEM3200 / iEM3300 series user manual
Read these instructions carefully and look at the equipment to become familiar with the device before trying to install, operate, service or maintain it. The following special messages may appear throughout this bulletin or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
The addition of either symbol to a “Danger” or “Warning” safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
DANGER
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
WARNING
WARNING indicates a potentially hazardous situation which, if not avoided, can result in death or serious injury.
CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoided, can result in minor or moderate injury.
NOTICE
NOTICE is used to address practices not related to physical injury. The safety alert symbol shall not be used with this signal word.
Electrical equipment should be installed, operated, serviced and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction, installation, and operation of electrical equipment and has received safety training to recognize and avoid the hazards involved.
4 |
DOCA0005EN-04 |
iEM3100 / iEM3200 / iEM3300 series user manual
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
•Reorient or relocate the receiving antenna.
•Increase the separation between the equipment and receiver.
•Connect the equipment to an outlet on a circuit different from that to which the receiver is connected.
•Consult the dealer or an experienced radio/TV technician for help.
This Class B digital apparatus complies with Canadian ICES-003.
DOCA0005EN-04 |
5 |
iEM3100 / iEM3200 / iEM3300 series user manual
Document scope
This manual is intended for use by designers, system builders and maintenance technicians with an understanding of electrical distribution systems and monitoring devices.
Validity note
The meters are used to measure the amount of active energy consumed by an installation or a part of an installation.
This function meets the requirements for:
•consumption monitoring,
•evaluation of energy items (cost, accounting, etc.).
This function may also satisfy the power-saving incentives implemented by many countries.
Title of documentation |
Reference number |
|
|
Installation sheet: iEM3100 / iEM3110 / iEM3115 |
S1B46581 / S1B62907 |
|
|
Installation sheet: iEM3150 / iEM3155 |
S1B46583 / S1B62908 |
|
|
Installation sheet: iEM3200 / iEM3210 / iEM3215 |
S1B46598 / S1B62910 |
|
|
Installation sheet: iEM3250 / iEM3255 |
S1B46602 / S1B62911 |
|
|
Installation sheet: iEM3135 |
HRB68964 / HRB72100 |
|
|
Installation sheet: iEM3165 |
HRB68991 / HRB72106 |
|
|
Installation sheet: iEM3175 |
HRB68988 / HRB72103 |
|
|
Installation sheet: iEM3235 |
HRB68995 / HRB72108 |
|
|
Installation sheet: iEM3265 |
HRB69003 / HRB72111 |
|
|
Installation sheet: iEM3275 |
HRB68999 / HRB72109 |
|
|
Installation sheet iEM3310 / iEM3350 |
HRB91204 / HRB91205 |
|
|
Installation sheet iEM3335 / iEM3355 / iEM3365 / iEM3375 |
HRB91202 / HRB91203 |
|
|
You can download these technical publications and other technical information from www.schneiderelectric.com.
6 |
DOCA0005EN-04 |
iEM3100 / iEM3200 / iEM3300 series user manual
Contents |
|
|
|
Safety information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
. 4 |
|
Notices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
5 |
|
About the book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
6 |
|
Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
.7 |
Chapter 1 |
Safety precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
9 |
Chapter 2 |
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
11 |
|
Overview of meter functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
11 |
|
Typical applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
13 |
Chapter 3 |
Hardware and installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
15 |
|
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
15 |
|
Hardware overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
16 |
|
DIN rail mounting and dismounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
22 |
|
Input, output and communications wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
24 |
|
Power system wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
26 |
Chapter 4 |
Front panel display and meter setup . . . . . . . . . . . . . . . . . . . . . . . . . . |
33 |
|
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
33 |
|
Data display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
33 |
|
Resets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
36 |
|
Multi Tariff feature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
36 |
|
Meter status information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
37 |
|
The device clock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
37 |
|
Device configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
38 |
|
Modifying parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
39 |
|
Configuration mode menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
40 |
Chapter 5 |
Communications via Modbus RS-485 . . . . . . . . . . . . . . . . . . . . . . . . . |
51 |
|
Modbus communication overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
51 |
|
Modbus functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
52 |
|
Command interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
53 |
|
Modbus register list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
57 |
|
Read Device Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
61 |
Chapter 6 |
Communications via LonWorks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
63 |
|
LonWorks communications overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
63 |
|
LonWorks communication implementation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
63 |
|
Standard network variable types (SNVTs) and configuration properties for reading |
|
|
data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
64 |
|
Meter configuration properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
68 |
|
Echelon LonMaker plug-in for data display and meter configuration . . . . . . . . . . . |
71 |
DOCA0005EN-04 |
7 |
|
iEM3100 / iEM3200 / iEM3300 series user manual |
|
Chapter 7 |
Communications via M-Bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
75 |
|
M-Bus communications overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
. 75 |
|
M-Bus protocol support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
. 76 |
|
M-Bus protocol implementation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
. 76 |
|
Variable data structure telegram information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
. 77 |
|
Telegram information for data records . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
. 79 |
|
Telegram information for meter configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
. 82 |
|
M-Bus tool for data display and meter configuration . . . . . . . . . . . . . . . . . . . . . . . . |
. 85 |
Chapter 8 |
Communications via BACnet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
89 |
|
BACnet communications overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
. 89 |
|
BACnet protocol support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
. 89 |
|
BACnet communications implementation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
. 90 |
|
BACnet object and property information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
. 91 |
Chapter 9 |
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
97 |
|
Electrical characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
. 97 |
|
Mechanical characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
. 99 |
|
Environmental characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
. 99 |
|
Measurement accuracy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
. 99 |
|
MID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
100 |
|
Internal clock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
100 |
|
Modbus communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
100 |
|
LonWorks communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
100 |
|
M-Bus communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
101 |
|
BACnet communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
101 |
Chapter 10 |
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
103 |
|
Diagnosis screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
103 |
|
Diagnostic codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
104 |
Chapter 11 |
Power, energy and power factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
105 |
|
Power (PQS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
105 |
|
Energy delivered (imported) / energy received (exported) . . . . . . . . . . . . . . . . . . . . |
106 |
|
Power factor (PF) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
106 |
|
Power factor register format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
108 |
8 |
DOCA0005EN-04 |
iEM3100 / iEM3200 / iEM3300 series user manual |
Safety precautions |
|
|
Installation, wiring, testing and service must be performed in accordance with all local and national electrical codes.
Carefully read and follow the safety precautions outlined below.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
•Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E in the USA or applicable local standards.
•This equipment must only be installed and serviced by qualified electrical personnel.
•Turn off all power supplying this device and the equipment in which it is installed before working on the device or equipment.
•Always use a properly rated voltage sensing device to confirm power is off.
•Before performing visual inspections, tests, or maintenance on this equipment, disconnect all sources of electric power. Assume that all circuits are live until they have been completely de-energized, tested and tagged. Pay particular attention to the design of the power system. Consider all power supply sources, particularly the potential for backfeed.
•Replace all devices, doors and covers before turning on power to this equipment.
•Do not exceed the device’s ratings for maximum limits.
Failure to follow these instructions will result in death or serious injury.
WARNING
UNINTENDED OPERATION
Do not use the meter for critical control or protection applications where human or equipment safety relies on the operation of the control circuit.
Failure to follow these instructions can result in death, serious injury or equipment damage.
WARNING
INACCURATE DATA RESULTS
•Do not rely solely on data displayed on the front panel or in software to determine if the device is functioning correctly or compliant with all applicable standards.
•Do not use data displayed on the front panel or in software as a substitute for proper workplace practices or equipment maintenance.
Failure to follow these instructions can result in death, serious injury or equipment damage.
DOCA0005EN-04 |
9 |
Safety precautions |
iEM3100 / iEM3200 / iEM3300 series user manual |
|
|
10 |
DOCA0005EN-04 |
iEM3100 / iEM3200 / iEM3300 series user manual |
Overview |
|
|
|
|
Chapter 2 |
Overview |
|
What is in this chapter?
This chapter contains the following topics:
Overview of meter functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Typical applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
The meters provide the essential measurement capabilities (for example, current, voltage, and energy) required to monitor a 1- or 3-phase electrical installation.
The key features of the meters are:
•measurement of active and reactive energy,
•Multi Tariffs (up to 4) controlled by internal clock, digital inputs or communication,
•MID compliance for many of the meters,
•pulse outputs,
•display (current, voltage, and energy measurements),
•communications via Modbus, LonWorks, M-Bus or BACnet protocols.
63 A meters
|
Function |
iEM3100 |
iEM3110 |
iEM3115 |
iEM3135 |
iEM3150 |
iEM3155 |
iEM3165 |
iEM3175 |
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
||
Direct measurement (up to 63 A) |
√ |
√ |
√ |
√ |
√ |
√ |
√ |
√ |
||
|
|
|
|
|
|
|
|
|
||
Active Energy measurement accuracy class (total and |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
||
partial kWh) |
|
|||||||||
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
||
Four Quadrant Energy measurements |
– |
– |
– |
√ |
– |
√ |
√ |
√ |
||
|
|
|
|
|
|
|
|
|
||
Electrical measurements (I, V, P, ...) |
– |
– |
– |
√ |
√ |
√ |
√ |
√ |
||
|
|
|
|
|
|
|
|
|
|
|
|
Controlled by internal clock |
– |
– |
4 |
4 |
– |
4 |
4 |
4 |
|
|
|
|
|
|
|
|
|
|
|
|
Multi Tariff |
Controlled by digital input(s) |
– |
– |
4 |
2 |
– |
2 |
2 |
2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
Controlled by communications |
– |
– |
– |
4 |
– |
4 |
4 |
4 |
|
|
|
|
|
|
|
|
|
|
|
|
Measurement display (number of lines) |
3 |
3 |
3 |
3 |
3 |
3 |
3 |
3 |
||
|
|
|
|
|
|
|
|
|
|
|
|
Programmable (status, tariff |
– |
– |
– |
1 |
– |
1 |
1 |
1 |
|
Digital inputs |
control, or input monitoring) |
|||||||||
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
||
|
Tariff control only |
– |
– |
2 |
– |
– |
– |
– |
– |
|
|
|
|
|
|
|
|
|
|
|
|
|
Programmable (energy pulsing |
– |
– |
– |
1 |
– |
1 |
1 |
– |
|
Digital outputs |
or overload alarm) |
|||||||||
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
||
|
Pulse output only |
– |
1 |
– |
– |
– |
– |
– |
– |
|
|
|
|
|
|
|
|
|
|
|
|
Overload alarm |
|
– |
– |
– |
√ |
– |
√ |
√ |
√ |
|
|
|
|
|
|
|
|
|
|
|
|
|
Modbus |
– |
– |
– |
– |
√ |
√ |
– |
– |
|
|
|
|
|
|
|
|
|
|
|
|
Communications |
LonWorks |
– |
– |
– |
– |
– |
– |
– |
√ |
|
|
|
|
|
|
|
|
|
|
||
M-Bus |
– |
– |
– |
√ |
– |
– |
– |
– |
||
|
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
BACnet |
– |
– |
– |
– |
– |
– |
√ |
– |
|
|
|
|
|
|
|
|
|
|
|
|
MID compliant |
|
– |
√ |
√ |
√ |
– |
√ |
√ |
√ |
|
|
|
|
|
|
|
|
|
|
||
Width (18 mm module in DIN rail mounting) |
5 |
5 |
5 |
5 |
5 |
5 |
5 |
5 |
||
|
|
|
|
|
|
|
|
|
|
DOCA0005EN-04 |
11 |
Overview iEM3100 / iEM3200 / iEM3300 series user manual
125 A meters
|
|
Function |
|
iEM3300 |
iEM3310 |
iEM3335 |
iEM3350 |
iEM3355 |
iEM3365 |
iEM3375 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Direct measurement (up to 125 A) |
|
√ |
√ |
√ |
√ |
√ |
√ |
√ |
||
|
|
|
|
|
|
|
|
|
|
|
Active Energy measurement accuracy class (total and partial |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
|||
kWh) |
|
|
|
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Four Quadrant Energy measurements |
|
– |
– |
√ |
– |
√ |
√ |
√ |
||
|
|
|
|
|
|
|
|
|
|
|
Electrical measurements (I, V, P, ...) |
|
– |
– |
√ |
√ |
√ |
√ |
√ |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
Controlled by internal clock |
|
– |
– |
4 |
– |
4 |
4 |
4 |
|
|
|
|
|
|
|
|
|
|
|
Multi Tariff |
|
Controlled by digital input(s) |
|
– |
– |
2 |
– |
2 |
2 |
2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
Controlled by communications |
|
– |
– |
4 |
– |
4 |
4 |
4 |
|
|
|
|
|
|
|
|
|
|
|
Measurement display (number of lines) |
|
3 |
3 |
3 |
3 |
3 |
3 |
3 |
||
|
|
|
|
|
|
|
|
|
|
|
Digital inputs (programmable for status, tariff control, or input |
– |
– |
1 |
– |
1 |
1 |
1 |
|||
monitoring) |
|
|
|
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Programmable (energy pulsing or |
– |
– |
1 |
– |
1 |
1 |
– |
|
Digital outputs |
|
overload alarm) |
|
|||||||
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
Pulse output only |
|
– |
1 |
– |
– |
– |
– |
– |
|
|
|
|
|
|
|
|
|
|
|
Overload alarm |
|
|
|
– |
– |
√ |
– |
√ |
√ |
√ |
|
|
|
|
|
|
|
|
|
|
|
|
|
Modbus |
|
– |
– |
– |
√ |
√ |
– |
– |
|
|
|
|
|
|
|
|
|
|
|
Communications |
|
LonWorks |
|
– |
– |
– |
– |
– |
– |
√ |
|
|
|
|
|
|
|
|
|
|
|
|
M-Bus |
|
– |
– |
√ |
– |
– |
– |
– |
|
|
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
BACnet |
|
– |
– |
– |
– |
– |
√ |
– |
|
|
|
|
|
|
|
|
|
|
|
MID compliant |
|
|
|
– |
√ |
√ |
– |
√ |
√ |
√ |
|
|
|
|
|
|
|
|
|
|
|
Width (18 mm module in DIN rail mounting) |
|
7 |
7 |
7 |
7 |
7 |
7 |
7 |
||
|
|
|
|
|
|
|
|
|
|
|
1 A / 5 A meters |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Function |
iEM3200 |
iEM3210 |
iEM3215 |
iEM3235 |
iEM3250 |
iEM3255 |
iEM3265 |
iEM3275 |
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
||
Measurement inputs through CTs (1 A, 5 A) |
√ |
√ |
√ |
√ |
√ |
√ |
√ |
√ |
||
|
|
|
|
|
|
|
|
|
||
Measurement inputs through VTs |
– |
– |
– |
√ |
√ |
√ |
√ |
√ |
||
|
|
|
|
|
|
|
|
|
||
Active Energy measurement accuracy class (total and |
0.5S |
0.5S |
0.5S |
0.5S |
0.5S |
0.5S |
0.5S |
0.5S |
||
partial kWh) |
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
Four Quadrant Energy measurements |
– |
– |
– |
√ |
– |
√ |
√ |
√ |
||
|
|
|
|
|
|
|
|
|
||
Electrical measurements (I, V, P, ...) |
– |
– |
– |
√ |
√ |
√ |
√ |
√ |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
Controlled by internal clock |
– |
– |
4 |
4 |
– |
4 |
4 |
4 |
|
|
|
|
|
|
|
|
|
|
|
Multi Tariff |
|
Controlled by digital input(s) |
– |
– |
4 |
2 |
– |
2 |
2 |
2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
Controlled by communications |
– |
– |
– |
4 |
– |
4 |
4 |
4 |
|
|
|
|
|
|
|
|
|
|
|
Measurement display (number of lines) |
3 |
3 |
3 |
3 |
3 |
3 |
3 |
3 |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
Programmable (status, tariff |
– |
– |
– |
1 |
– |
1 |
1 |
1 |
Digital inputs |
|
control, or input monitoring) |
||||||||
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
Tariff control only |
– |
– |
2 |
– |
– |
– |
– |
– |
|
|
|
|
|
|
|
|
|
|
|
|
|
Programmable (energy pulsing |
– |
– |
– |
1 |
– |
1 |
1 |
– |
Digital outputs |
|
or overload alarm) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Pulse output only |
– |
1 |
– |
– |
– |
– |
– |
– |
|
|
|
|
|
|
|
|
|
|
|
12 |
DOCA0005EN-04 |
iEM3100 / iEM3200 / iEM3300 series user manual |
|
|
|
|
|
|
Overview |
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Function |
iEM3200 |
iEM3210 |
iEM3215 |
iEM3235 |
iEM3250 |
iEM3255 |
iEM3265 |
iEM3275 |
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
Overload alarm |
– |
– |
– |
√ |
– |
√ |
√ |
√ |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Modbus |
– |
– |
– |
– |
√ |
√ |
– |
– |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Communications |
LonWorks |
– |
– |
– |
– |
– |
– |
– |
√ |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
M-Bus |
– |
– |
– |
√ |
– |
– |
– |
– |
|
|
|
|
|
|||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
BACnet |
– |
– |
– |
– |
– |
– |
√ |
– |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
MID compliant |
– |
√ |
√ |
√ |
– |
√ |
√ |
√ |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Width (18 mm module in DIN rail mounting) |
5 |
5 |
5 |
5 |
5 |
5 |
5 |
5 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
This range is a cost effective solution to monitor feeder circuits. These meters can monitor energy consumption by usage, by zone or by feeder in the cabinet. They can be used to monitor feeders in a main switchboard or to monitor the main in a distribution cabinet.
Functions |
Advantages |
|
|
|
|
Can directly measure feeders up to: |
Saves installation time and space in the cabinet |
|
iEM31••: 63 A |
||
No wiring to manage |
||
iEM33••: 125 A |
||
Clear distribution network |
||
Embedded current transformers (CTs) |
||
|
||
|
|
|
Adapted to be installed with Acti9 iC65 (iEM31••) or Acti9 C120 |
Can be used in three-phase systems with or without neutral |
|
(iEM33••) circuit breakers |
||
|
||
Can be used for single-phase multi-circuit monitoring |
3 single feeders can be monitored with a single meter |
|
iEM32•• series |
|
Functions |
Advantages |
|
|
CT and VT connection |
Can be used in low or medium voltage applications |
|
|
Flexible configuration |
Can be adapted to any distribution network with or without neutral |
|
|
The following table presents some of the functions of the different meters, the advantages and main applications.
Functions |
Advantages |
Applications |
Meter |
|
|
|
|
|
|
Total and partial energy counters |
Energy usage monitoring |
Sub-billing management |
All |
|
Metering applications |
||||
|
|
|
||
|
|
|
|
|
Internal clock |
Saves the date and time of last reset |
Provides the timestamp of the last reset of the |
All (except iEM3100 / |
|
partial energy accumulation |
iEM3200 / iEM3300) |
|||
|
|
|||
Pulse output with a configurable |
Collect pulses from the meter with a Smartlink |
Remote monitoring of energy consumption |
iEM3110 / iEM3310 / |
|
pulse weight of up to 1 pulse per |
Integrate the meter in to a system monitoring of |
|||
system, PLC or any basic acquisition system |
iEM3210 |
|||
1 Wh |
|
a large number of devices |
|
|
|
|
|
iEM3115 / iEM3135 / |
|
|
|
Energy demand management |
iEM3155 / iEM3165 / |
|
Manages up to four tariffs, |
Categorize energy consumption into On Peak and Off |
iEM3175 |
||
controlled by the digital input(s), |
Peak, working days and weekends, or by different |
Sub-billing management |
iEM3215 / iEM3235 / |
|
internal clock or communications |
electricity sources (for example, from the utility and |
Identification of local energy consumption |
iEM3255 / iEM3265 / |
|
(depending on meter model) |
an electrical generator) |
iEM3275 |
||
behavior by zone, by usage or by feeder |
||||
|
|
iEM3335 / iEM3355 / |
||
|
|
|
||
|
|
|
iEM3365 / iEM3375 |
|
|
|
|
iEM3135 / iEM3155 / |
|
Measures essential electrical |
Instantaneous measurements help you monitor the |
|
iEM3165 / iEM3175 |
|
imbalance between phases. |
Monitoring of feeders or any sub-cabinet |
iEM3235 / iEM3255 / |
||
parameters like current, average |
Total power allows you to monitor the feeder load |
iEM3265 / iEM3275 |
||
voltage and total power. |
|
|||
|
level. |
|
iEM3335 / iEM3355 / |
|
|
|
|
iEM3365 / iEM3375 |
DOCA0005EN-04 |
13 |
Overview |
|
iEM3100 / iEM3200 / iEM3300 series user manual |
||
|
|
|
|
|
|
|
|
|
|
Functions |
Advantages |
Applications |
Meter |
|
|
|
|
|
|
M-Bus communications |
Communicate advanced parameters using |
M-Bus network integration |
iEM3135 / iEM3235 / |
|
M-Bus protocol |
iEM3335 |
|||
|
|
|||
|
Communicate advanced parameters using Modbus |
|
iEM3150 / iEM3155 |
|
Modbus communications |
Modbus network integration |
iEM3250 / iEM3255 |
||
protocol |
||||
|
|
iEM3350 / iEM3355 |
||
|
|
|
||
|
|
|
|
|
BACnet communications |
Communicate advanced parameters using BACnet |
BACnet network integration |
iEM3165 / iEM3265 / |
|
MS/TP protocol |
iEM3365 |
|||
|
|
|||
LonWorks communications |
Communicate advanced parameters using LonWorks |
LonWorks network integration |
iEM3175 / iEM3275 / |
|
|
communications |
|
iEM3375 |
|
|
Identification of imported and exported active and |
Ideal for facilities with back-up generators or |
|
|
Four quadrant calculation |
reactive energy allows you to monitor energy flow in |
|
||
green power capabilities (for example, solar |
|
|||
both directions: delivered from the utility and |
|
|||
|
panels or wind turbines) |
|
||
|
produced on-site |
|
||
|
|
|
||
|
|
|
iEM3135 / iEM3155 / |
|
|
|
Manage energy consumption and make |
||
Measurement of active, reactive |
Allows you to monitor energy consumption and |
informed investment to reduce your energy bill |
iEM3165/ iEM3175 |
|
and apparent energy. |
production |
or penalties (for example, installing capacitor |
iEM3235 / iEM3255 / |
|
|
|
banks) |
iEM3265 / iEM3275 |
|
|
Can be programmed to: |
This allows for monitoring of: |
iEM3335 / iEM3355 / |
|
|
Count pulses from other meters (gas, water, etc.) |
WAGES |
iEM3365 / iEM3375 |
|
|
|
|||
Programmable digital input |
Monitor an external status |
Intrusion (for example, doors opening) or |
|
|
|
Reset the partial energy accumulation and start a |
equipment status |
|
|
|
|
|
||
|
new period of accumulation |
Energy usage |
|
|
|
|
|
|
|
|
Can be programmed to: |
This allows you to: |
iEM3135 / iEM3155 / |
|
|
Collect pulses from the meter with a Smartlink |
iEM3165 |
||
|
be an active energy (kWh) pulse output, with a |
|||
|
|
|||
Programmable digital output |
system, PLC or any basic acquisition system |
iEM3235 / iEM3255 / |
||
configurable pulse weight |
||||
Monitor power levels at a detailed level and to |
iEM3265 |
|||
|
Alarm on a power overload at a configurable pickup |
|||
|
|
|||
|
help detect an overload before the circuit |
iEM3335 / iEM3355 / |
||
|
setpoint |
|||
|
breaker trips |
iEM3365 |
||
|
|
14 |
DOCA0005EN-04 |
iEM3100 / iEM3200 / iEM3300 series user manual |
Hardware and installation |
|
|
What is in this chapter?
This chapter contains the following topics:
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Hardware overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 DIN rail mounting and dismounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Input, output and communications wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Power system wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
|
|
|
|
|
|
|
|
|
|
A |
Without communications |
|
|
|
|
|
|
|
|
|
|
B |
With communications |
mm |
|
|
|
|
|
|
|
|
|
|
|
in |
|
|
|
|
|
|
|
|
87 |
|
|
|
ON |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
3.43 |
|
|
|
500 |
/kWh |
|
|
|
|
|
|
45 |
|
|
|
|
|
|
|
|
|
|
|
1.77 |
95.0 |
101.5 |
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
OK |
|
ESC |
|
|
3.74 |
4.00 |
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
Config |
Reset |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
N |
N’ |
L1 |
L1’ |
L2 |
L2’ |
L3 |
L3’ |
|
|
|
|
|
|
|
|
|
|
|
|
63.5 |
|
|
|
|
|
|
90 |
|
|
|
69 |
2.50 |
|
|
|
|
|
|
3.54 |
|
|
|
2.71 |
|
|
|
|
iEM33•• meters
|
|
|
|
|
|
|
|
|
|
A |
Without communications |
|
|
|
|
|
|
|
|
|
|
B |
With communications |
mm |
|
|
|
|
|
|
|
|
93.8 |
|
|
in |
|
|
|
ON |
|
|
|
|
|
|
|
|
|
|
200 |
/kWh |
|
|
|
45 |
3.70 |
|
|
|
|
|
|
|
|
|
|
1.77 |
103.2 |
108.4 |
|
|
|
|
|
|
|
OK |
ESC |
|
4.06 |
4.27 |
|
|
|
|
|
|
|
Config |
Reset |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
N |
N’ |
L1 |
L1’ |
L2 |
L2’ |
L3 |
L3’ |
|
|
|
|
|
|
|
126.0 |
|
|
|
63.8 |
|
|
|
|
|
|
|
|
|
69.3 |
2.51 |
|
|
|
||
|
|
|
4.96 |
|
|
2.73 |
|
|
|
|
DOCA0005EN-04 |
15 |
Hardware and installation |
iEM3100 / iEM3200 / iEM3300 series user manual |
|
|
All meters have sealing covers and sealing points to help prevent access to inputs and outputs and current and voltage connections.
A |
Sealing points |
B |
Sealable covers |
ESC |
|
OK |
|
iEM3100 / iEM3110 / iEM3115 - Direct measurement up to 63 A |
The various features of the iEM3100 / iEM3110 / iEM3115 are shown in the diagram below:
C/- |
T1 |
T2 |
S0+ S0- |
|
|
|
ON |
|
|
500 |
/kWh |
|
|
|
|
OK |
|
ESC |
|
|
|
|
|
|
Config |
Reset |
|
|
|
|
|
|
|
|
|
N |
N’ |
L1 |
L1’ |
L2 |
L2’ |
L3 |
L3’ |
A |
Digital inputs for tariff control (iEM3115) |
B |
Display for measurement and configuration |
|
|
C |
Pulse output for remote transfer (iEM3110) |
|
|
D |
Cancel |
|
|
E |
Confirm |
|
|
F |
Scroll |
|
|
G |
Current and voltage inputs (direct measurement up to 63 A) |
|
|
H |
Energy pulsing LED (used to verify accuracy) |
|
|
I |
Status LED: on/off, error |
|
|
|
|
16 |
DOCA0005EN-04 |
iEM3100 / iEM3200 / iEM3300 series user manual |
Hardware and installation |
|
|
The various features of the iEM3135 are shown in the diagram below:
M-Bus
C/- DI |
C DO |
ON 500 /kWh
OK |
ESC |
|
Reset |
|
Config |
A |
Digital input |
B |
Digital output |
C |
Communication port |
D |
Communications LED |
E |
Display for measurement and configuration |
F |
Cancel |
G |
Confirm |
H |
Scroll |
I |
Current and voltage inputs (direct measurement up to 63 A) |
J |
Energy pulsing LED (used to verify accuracy) |
K |
Status LED: on/off, error |
N N’ L1 L1’ L2
L2’
L3 L3’
The various features of the iEM3150 / iEM3155 / iEM3165 are shown in the diagram below:
0V D0/- D1/+
RS485
C/- DI N.C. C DO N.C.
ON 500 /kWh
OK |
ESC |
|
Reset |
|
Config |
A |
Digital input (iEM3155/iEM3165) |
B |
Digital output (iEM3155/iEM3165) |
|
|
C |
Communication port |
|
|
D |
Communications LED |
|
|
E |
Display for measurement and configuration |
|
|
F |
Cancel |
|
|
G |
Confirm |
|
|
H |
Scroll |
|
|
I |
Current and voltage inputs (direct measurement up to 63 A) |
|
|
J |
Energy pulsing LED (used to verify accuracy) |
|
|
K |
Status LED: on/off, error |
|
|
N N’ L1 L1’ L2
L2’
L3 L3’
DOCA0005EN-04 |
17 |
Hardware and installation |
iEM3100 / iEM3200 / iEM3300 series user manual |
|
|
The various features of the iEM3175 are shown in the diagram below:
LON
C/- DI |
Service |
|
ON 500 /kWh
OK |
ESC |
Neuron ID: 000000000000 |
Reset |
S/N:0000000000 |
Config |
A |
Digital input |
B |
Communication port |
C |
Communications / LonWorks operations LED |
D |
Service pin |
E |
Display for measurement and configuration |
F |
Cancel |
G |
Confirm |
H |
Scroll |
I |
Current and voltage inputs (direct measurement up to 63 A) |
J |
Neuron ID |
K |
Energy pulsing LED (used to verify accuracy) |
L |
Status LED: on/off, error |
N N’ L1 L1’ L2
L2’
L3 L3’
The various features of the listed meters (CTs 1 A or 5 A) are shown in the diagram below:
C/- |
T1 |
T2 |
S0+ S0- |
ON 5000 /kWh
|
|
|
|
|
|
OK |
|
ESC |
|
|
|
|
|
|
|
|
Config |
Reset |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(I1) |
(I2) |
(I3) |
|
|
V1 |
V2 |
V3 |
Vn |
S1 |
S2 |
S1 |
S2 |
S1 |
S2 |
A |
Digital inputs for tariff control (iEM3215) |
B |
Display for measurement and configuration |
|
|
C |
Pulse out for remote transfer (iEM3210) |
|
|
D |
Current inputs (CTs 1 A or 5 A) |
|
|
E |
Cancel |
|
|
F |
Confirm |
|
|
G |
Scroll |
|
|
H |
Voltage inputs |
|
|
I |
Energy pulsing LED (used to verify accuracy) |
|
|
J |
Status LED: on/off, error |
|
|
|
|
18 |
DOCA0005EN-04 |
iEM3100 / iEM3200 / iEM3300 series user manual |
Hardware and installation |
|
|
The various features of the iEM3235 (CTs 1 A or 5 A with M-Bus communications) are shown in the diagram below:
|
M-Bus |
C/- DI |
C DO |
ON 5000 /kWh
|
|
OK |
ESC |
|
|
Config |
Reset |
|
|
|
|
|
(I1) |
(I2) |
(I3) |
V1 V2 V3 Vn |
S1 S2 |
S1 S2 |
S1 S2 |
A |
Digital input |
B |
Digital output |
|
|
C |
Communication port |
|
|
D |
Communications LED |
|
|
E |
Display for measurement and configuration |
|
|
F |
Current inputs (CTs 1 A and 5 A) |
|
|
G |
Cancel |
|
|
H |
Confirm |
|
|
I |
Scroll |
|
|
J |
Voltage inputs |
|
|
K |
Energy pulsing LED (used to verify accuracy) |
|
|
L |
Status LED: on/off, error |
|
|
|
|
The various features of the iEM3250 / iEM3255 / iEM3265 (CTs 1 A or 5 A with Modbus or BACnet communication) are shown in the diagram below:
|
0V |
D0/- D1/+ |
|
|
RS485 |
C/- DI N.C. C DO |
N.C. |
|
|
ON |
|
5000 |
/kWh |
|
|
|
OK |
ESC |
|
|
Config |
Reset |
|
|
|
|
|
(I1) |
(I2) |
(I3) |
V1 V2 V3 Vn |
S1 S2 |
S1 S2 |
S1 S2 |
A |
Digital input (iEM3255/iEM3265) |
B |
Digital output (iEM3255/iEM3265) |
|
|
C |
Communication port |
|
|
D |
Communications LED |
|
|
E |
Display for measurement and configuration |
|
|
F |
Current inputs (CTs 1 A and 5 A) |
|
|
G |
Cancel |
|
|
H |
Confirm |
|
|
I |
Scroll |
|
|
J |
Voltage inputs |
|
|
K |
Energy pulsing LED (used to verify accuracy) |
|
|
L |
Status LED: on/off, error |
|
|
|
|
DOCA0005EN-04 |
19 |
Hardware and installation |
iEM3100 / iEM3200 / iEM3300 series user manual |
|
|
The various features of the iEM3275 (CTs 1 A or 5 A with LonWorks communications) are shown in the diagram below:
LON
C/- DI
ON 5000 /kWh
Neuron ID: 000000000000 |
|
OK |
ESC |
|
Config |
Reset |
|
S/N: 0000000000 |
|
||
|
|
||
|
(I1) |
(I2) |
(I3) |
V1 V2 V3 Vn |
S1 S2 |
S1 S2 |
S1 S2 |
A |
Digital input |
B |
Communication port |
|
|
C |
Communications / LonWorks operation LED |
|
|
D |
Service pin |
|
|
E |
Display for measurement and configuration |
|
|
F |
Current inputs (CTs 1 A and 5 A) |
|
|
G |
Cancel |
|
|
H |
Confirm |
|
|
I |
Scroll |
|
|
J |
Voltage inputs |
|
|
K |
Neuron ID |
|
|
L |
Energy pulsing LED (used to verify accuracy) |
|
|
M |
Status LED: on/off, error |
|
|
|
|
The various features of the iEM3300 / iEM3310 are shown in the diagram below:
S0+ S0-
ON 200 /kWh
OK |
ESC |
|
Reset |
|
Config |
A |
Display for measurement and configuration |
B |
Pulse output for remote transfer (iEM3310) |
|
|
C |
Cancel |
|
|
D |
Confirm |
|
|
E |
Scroll |
|
|
F |
Current and voltage inputs (direct measurement up to 125 A) |
|
|
G |
Energy pulsing LED (used to verify accuracy) |
|
|
H |
Status LED: on/off, error |
|
|
|
N |
|
N’ |
|
L1 |
L1’ |
L2 |
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
L2’
L3 L3’
20 |
DOCA0005EN-04 |
iEM3100 / iEM3200 / iEM3300 series user manual |
Hardware and installation |
|
|
The various features of the iEM3335 are shown in the diagram below:
C/- DI |
C DO |
ON 200 /kWh
OK |
ESC |
|
Reset |
|
Config |
A |
Digital input |
B |
Digital output |
C |
Communication port |
D |
Communications LED |
E |
Display for measurement and configuration |
F |
Cancel |
G |
Confirm |
H |
Scroll |
I |
Current and voltage inputs (direct measurement up to 125 A) |
J |
Energy pulsing LED (used to verify accuracy) |
K |
Status LED: on/off, error |
|
|
N |
N’ |
|
L1 |
L1’ |
L2 |
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
L2’
L3 L3’
The various features of the iEM3350 / iEM3355 / iEM3365 are shown in the diagram below:
|
|
|
|
0V |
D0/- D1/+ |
|
|
|
|
|
|
|
RS485 |
|
|
|
|
C/- DI |
C DO |
|
|
|
|
|
|
|
|
ON |
|
|
|
|
|
|
200 |
/kWh |
|
|
|
|
|
|
|
|
|
OK |
ESC |
|
|
|
|
|
|
Config |
Reset |
|
|
|
|
|
|
|
|
N |
N’ |
L1 |
L1’ |
L2 |
L2’ |
L3 |
L3’ |
A |
Digital input (iEM3355 / iEM3365) |
B |
Digital output (iEM3355 / iEM3365) |
|
|
C |
Communication port |
|
|
D |
Communications LED |
|
|
E |
Display for measurement and configuration |
|
|
F |
Cancel |
|
|
G |
Confirm |
|
|
H |
Scroll |
|
|
I |
Current and voltage inputs (direct measurement up to 125 A) |
|
|
J |
Energy pulsing LED (used to verify accuracy) |
|
|
K |
Status LED: on/off, error |
|
|
|
|
DOCA0005EN-04 |
21 |
Hardware and installation |
iEM3100 / iEM3200 / iEM3300 series user manual |
|
|
The various features of the iEM3375 are shown in the diagram below:
|
|
C/- DI |
|
|
|
|
Service |
|
|
|
|
ON |
|
|
|
|
|
|
200 |
/kWh |
|
|
|
Neuron ID: 000000000000 |
|
|
|
OK |
|
ESC |
|
S/N:0000000000 |
|
|
|
|
Config |
Reset |
|
|
|
|
|
|
|||
N |
N’ |
L1 |
L1’ |
L2 |
L2’ |
L3 |
L3’ |
A |
Digital input |
B |
Communication port |
C |
Communications / LonWorks operations LED |
D |
Service pin |
E |
Display for measurement and configuration |
F |
Cancel |
G |
Confirm |
H |
Scroll |
I |
Current and voltage inputs (direct measurement up to 125 A) |
J |
Neuron ID |
K |
Energy pulsing LED (used to verify accuracy) |
L |
Status LED: on/off, error |
|
|
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
•Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E in the USA or applicable local standards.
•This equipment must only be installed and serviced by qualified electrical personnel.
•Turn off all power supplying this device and the equipment in which it is installed before working on the device or equipment.
•Always use a properly rated voltage sensing device to confirm power is off.
•Replace all devices, doors and covers before turning on power to this equipment.
•Do not exceed the device’s ratings for maximum limits.
Failure to follow these instructions will result in death or serious injury.
1. Position the 2 upper slots on the rear of the meter onto the DIN rail.
2.Press the meter against the DIN rail until the locking mechanism engages. The meter is now attached to the rail. Make sure that the device is not tilted following installation.
22 |
DOCA0005EN-04 |
iEM3100 / iEM3200 / iEM3300 series user manual |
Hardware and installation |
|
|
Click!
1.Use a flat-tip screwdriver (≤ 6.5 mm / 0.25 in) to lower the locking mechanism and release the meter.
2. Lift the meter out and up to free it from the DIN rail.
DOCA0005EN-04 |
23 |
Hardware and installation |
iEM3100 / iEM3200 / iEM3300 series user manual |
|
|
This section describes the wiring of the digital inputs, digital and pulse outputs and the communications (as applicable).
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
•Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E in the USA or applicable local standards.
•This equipment must only be installed and serviced by qualified electrical personnel.
•Turn off all power supplying this device and the equipment in which it is installed before working on the device or equipment.
•Always use a properly rated voltage sensing device to confirm power is off.
•Replace all devices, doors and covers before turning on power to this equipment.
•Do not exceed the device’s ratings for maximum limits.
Failure to follow these instructions will result in death or serious injury.
WARNING
UNINTENDED OPERATION
Do not use the meter for critical control or protection applications where human or equipment safety relies on the operation of the control circuit.
Failure to follow these instructions can result in death, serious injury or equipment damage.
Related topics
•See “Power system wiring” on page 26 for information on wiring the voltage and current connections.
|
Rin |
|
Radd |
5 – 30 V DC |
|
+ |
- |
|
S0+ S0- |
•The pulse output is compatible with S0 format.
•The pulse output can be directly connected to a 24 V DC (< 30 V DC) input on a Zelio or Twido PLC.
•The pulse output indicates the primary consumption with consideration of transformer ratios.
•For other concentrators, if V DC/Rin > 15 mA, add a resistor Radd = (V DC/0.01) - Rin Ω
11 – 40 V DC |
|
- + |
|
C/- T1 |
T2 |
24 |
DOCA0005EN-04 |
iEM3100 / iEM3200 / iEM3300 series user manual |
Hardware and installation |
|
|
11 – 40 V DC
- |
+ |
|
|
C/- DI |
N.C. |
• The digital input and output are electrically independent. |
5 – 40 V DC
-/+ +/-
Load
CDO N.C.
•The programmable digital output is compatible with S0 format when configured as a pulse output.
•The digital output is polarity-independent.
•The digital input and output are electrically independent.
0 V
D0 = A’ / Rx-, A / Tx-
D1 = B’ / Rx+, B / Tx+
0V D0/- D1/+
0 V
D0 = A’ / Rx-, A / Tx-
D1 = B’ / Rx+, B / Tx+
0V D0/- D1/+
•The M-Bus communications connection is polarity-independent.
DOCA0005EN-04 |
25 |
Hardware and installation |
iEM3100 / iEM3200 / iEM3300 series user manual |
|
|
Service
•The LON communications connection is polarity-independent.
The diagrams below illustrate how to connect the meters to a single-phase or three-phase 3-wire or 4-wire power system.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
•Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E in the USA or applicable local standards.
•This equipment must only be installed and serviced by qualified electrical personnel.
•Turn off all power supplying this device and the equipment in which it is installed before working on the device or equipment.
•Always use a properly rated voltage sensing device to confirm power is off.
•Replace all devices, doors and covers before turning on power to this equipment.
•Do not exceed the device’s ratings for maximum limits.
Failure to follow these instructions will result in death or serious injury.
Voltage input protection
The meter’s voltage inputs must be wired to fuses/breakers and a disconnect switch. If using a voltage transformer (VT), both primary and secondary sides of the VT must be fused and switched.
•Clearly label the device’s disconnect circuit mechanism and install it within easy reach of the operator.
•Fuses / circuit breakers must be:
—installed in accordance with all local and national electrical codes and standards, and
—rated for the installation voltage, available fault current, and sized for connected loads.
•Fuse for neutral is required if the source neutral connection is not grounded.
Current input protection for 1 A and 5 A meters
For all connected current inputs on 1 A and 5 A meters with external CTs, use a CT shorting block to short-circuit the secondary leads of the CTs before removing the current input connections to the meter.
NOTE: Ground any unused current inputs on 1 A and 5 A meters.
iEM31•• and iEM33•• devices associated with a contactor
Connection requirements for iEM3100 / iEM3110 / iEM3115 / iEM3135 / iEM3150 / iEM3155 / iEM3165 / iEM3175 / iEM3300 / iEM3310 / iEM3335 / iEM3350 / iEM3355 / iEM3365 / iEM3375:
•When the meter is associated with a contactor, connect the meter upstream of the contactor.
•The meter must be protected by a circuit breaker.
26 |
DOCA0005EN-04 |
iEM3100 / iEM3200 / iEM3300 series user manual |
Hardware and installation |
|
|
L |
L |
|
iEM |
iEM |
|
Load |
Load |
Related topics
•See “Input, output and communications wiring” on page 24 for information on wiring the digital inputs, digital or pulse outputs and communications for your device.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Do not allow the total additive current flowing through the device to exceed 63 A.
Failure to follow these instructions will result in death or serious injury.
Fuses and disconnect switch |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Power system |
|
|
|
|
|
|
Wiring |
|
|
|
|
|
|
|
|
N |
N’ |
L1 L1’ L2 |
L2’ |
L3 |
L3’ |
|
|
|
N |
N’ L1 L1’ L2 |
L2’ |
L3 |
L3’ |
1PH2W L-N |
L |
|
|
|
|
|
|
|
L |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
N |
≤277 V L-N |
|
|
|
|
|
N |
|
≤277 V L-N |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
N |
N’ L1 L1’ |
L2 |
L2’ L3 |
L3’ |
|
|
|
|
1PH2W L-L |
|
|
|
L1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
L2 |
|
|
≤480 V L-L |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
N |
N’ |
L1 L1’ L2 |
L2’ |
L3 |
L3’ |
|
|
|
N |
N’ L1 L1’ L2 |
L2’ |
L3 |
L3’ |
1PH3W L-L-N |
L1 |
|
|
|
|
|
|
|
L1 |
|
|
|
|
|
L2 |
|
|
|
|
|
|
|
L2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
N |
|
≤277 V L-N |
|
|
|
|
N |
|
≤277 V L-N |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
≤480 V L-L |
|
|
|
|
|
|
|
≤480 V L-L |
|
|
|
|
|
|
|
|
|
N |
N’ L1 L1’ |
L2 |
L2’ L3 |
L3’ |
|
|
|
|
3PH3W |
|
|
|
L1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
L2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
L3 |
|
|
≤480 V L-L |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
N |
N’ |
L1 L1’ L2 |
L2’ |
L3 |
L3’ |
|
|
|
N |
N’ L1 L1’ L2 |
L2’ |
L3 |
L3’ |
|
L1 |
|
|
|
|
|
|
|
L1 |
|
|
|
|
|
3PH4W |
L2 |
|
|
|
|
|
|
|
L2 |
|
|
|
|
|
|
L3 |
|
|
|
|
|
|
|
L3 |
|
|
|
|
|
|
N |
≤277 V L-N |
|
|
|
|
|
N |
|
≤277 V L-N |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
≤480 V L-L |
|
|
|
|
|
|
|
≤480 V L-L |
|
|
|
|
DOCA0005EN-04 |
|
|
|
|
|
|
|
|
|
|
|
|
|
27 |
Hardware and installation |
iEM3100 / iEM3200 / iEM3300 series user manual |
|
|
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Do not connect N’ to the load when setting the wiring type on the meter to 1PH4W Multi L-N.
Failure to follow these instructions will result in death or serious injury.
Power system |
|
|
Wiring |
|
|
N |
N’ |
L1 |
L1’ L2 L2’ |
L3 |
L3’ |
1PH multiple loads with neutral (1PH4W Multi L-N)1 |
|
|
|
|
|
1The 1PH4W Multi L-N wiring type is only available on the iEM3135, iEM3150, iEM3155, iEM3165 and iEM3175.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Do not allow the total additive current flowing through the device to exceed 125 A.
Failure to follow these instructions will result in death or serious injury.
Fuses and disconnect switch
Power system |
|
|
|
|
|
|
Wiring |
|
|
|
|
|
|
|
|
N |
N’ |
L1 L1’ L2 |
L2’ |
L3 |
L3’ |
|
|
|
N |
N’ L1 L1’ L2 |
L2’ |
L3 |
L3’ |
1PH2W L-N |
L |
|
|
|
|
|
|
|
L |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
N |
≤277 V L-N |
|
|
|
|
|
N |
|
≤277 V L-N |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
N |
N’ L1 L1’ |
L2 |
L2’ L3 |
L3’ |
|
|
|
|
1PH2W L-L |
|
|
|
L1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
L2 |
|
|
≤480 V L-L |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
N |
N’ |
L1 L1’ L2 |
L2’ |
L3 |
L3’ |
|
|
|
N |
N’ L1 L1’ L2 |
L2’ |
L3 |
L3’ |
1PH3W L-L-N |
L1 |
|
|
|
|
|
|
|
L1 |
|
|
|
|
|
L2 |
|
|
|
|
|
|
|
L2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
N |
|
≤277 V L-N |
|
|
|
|
N |
|
≤277 V L-N |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
≤480 V L-L |
|
|
|
|
|
|
|
≤480 V L-L |
|
|
|
|
|
|
|
|
|
N |
N’ L1 L1’ |
L2 |
L2’ L3 |
L3’ |
|
|
|
|
3PH3W |
|
|
|
L1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
L2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
L3 |
|
|
≤480 V L-L |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
28 |
DOCA0005EN-04 |
iEM3100 / iEM3200 / iEM3300 series user manual |
Hardware and installation |
|
|
Power system |
|
|
|
|
|
Wiring |
|
|
|
|
|
N |
N’ L1 L1’ L2 |
L2’ |
L3 |
L3’ |
N |
N’ L1 L1’ L2 |
L2’ |
L3 |
L3’ |
|
L1 |
|
|
|
|
L1 |
|
|
|
|
3PH4W |
L2 |
|
|
|
|
L2 |
|
|
|
|
|
L3 |
|
|
|
|
L3 |
|
|
|
|
|
N |
≤277 V L-N |
|
|
|
N |
≤277 V L-N |
|
|
|
|
|
|
|
|
|
|
|
|
≤480 V L-L |
≤480 V L-L |
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Do not connect N’ to the load when setting the wiring type on the meter to 1PH4W Multi L-N.
Failure to follow these instructions will result in death or serious injury.
Power system |
|
|
Wiring |
|
|
N |
N’ |
L1 |
L1’ L2 L2’ |
L3 |
L3’ |
1PH multiple loads with neutral (1PH4W Multi L-N)1 |
|
|
|
|
|
1The 1PH4W Multi L-N wiring type is only available on the iEM3335, iEM3350, iEM3355, iEM3365 and iEM3375.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
•Never short the secondary of a voltage transformer (VT).
•Never open circuit a current transformer (CT); use the shorting block to short circuit the leads of the CT before removing the connection from the meter.
•Always use grounded external CTs for current inputs.
Failure to follow these instructions will result in death or serious injury.
Single-phase systems with CTs |
|
|
|
|
250 mA fuses and disconnect switch |
|
|
|
|
Shorting block |
|
|
|
|
Power system |
|
Wiring |
|
|
|
V1 V2 V3Vn |
(I1) |
(I2) |
(I3) |
|
|
|
|
|
1PH2W L-N |
|
|
|
|
|
|
S1 |
S2 |
|
|
|
≤277 V L-N |
|
DOCA0005EN-04 |
29 |
Hardware and installation |
|
|
|
iEM3100 / iEM3200 / iEM3300 series user manual |
||||||
Power system |
|
|
|
|
Wiring |
|
|
|
|
|
|
|
V1 V2 V3Vn |
(I1) |
(I2) |
(I3) |
|
|
|
||
|
|
|
|
|
|
|
|
|||
1PH2W L-L |
|
|
|
|
|
|
|
|
|
|
|
|
L1 |
|
|
S1 |
S2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
L2 |
|
|
≤480 V L-L |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
V1 V2 V3Vn |
(I1) |
(I2) |
(I3) |
|
|
|
||
|
|
|
|
|
|
|
|
|||
1PH3W L-L-N |
|
|
|
|
S1 |
S2 |
|
|
|
|
|
|
L1 |
|
|
|
|
|
|
||
|
|
|
|
S1 |
S2 |
|
|
|
||
|
|
L2 |
|
|
|
|
|
|||
|
|
N |
|
|
≤277 V L-N |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
≤480 V L-L |
|
|
|
|
|
2CTs |
|
|
|
|
3CTs |
|
|
|
|
|
V1 V2 V3Vn |
(I1) |
(I2) |
(I3) |
|
|
|
V1 V2 V3Vn |
(I1) |
(I2) |
(I3) |
|
|
|
|
|
|
|
|
|
||
1PH multiple loads with neutral |
|
|
|
|
|
|
|
|
|
|
(1PH4W Multi L-N)1 |
|
|
|
|
|
|
|
|
|
|
|
≤277 V L-N |
|
|
|
|
|
≤277 V L-N |
|
||
|
|
|
|
|
|
|
|
|
||
1The 1PH4W Multi L-N wiring type is only available on the iEM3235, iEM3250, iEM3255, iEM3265 and iEM3275 |
|
Three-phase systems with CTs
250 mA fuses and disconnect switch
Shorting block
indicates wiring for a balanced system
Power system |
Wiring |
|
1 CT |
2CTs |
3CTs |
V1 V2 V3Vn |
V1 V2 V3Vn |
V1 V2 V3Vn |
|
||
3PH3W |
|
|
≤480 V L-L |
≤480 V L-L |
≤480 V L-L |
|
||
1 CT |
2 CTs |
3CTs |
V1 V2 V3Vn |
V1 V2 V3Vn |
V1 V2 V3Vn |
3PH4W |
|
|
≤277 V L-N |
≤277 V L-N |
≤277 V L-N |
30 |
|
DOCA0005EN-04 |