ANNEX

ANNEX for ATV312

 

 

 

 

Quick Start Guide

S1B1632800

Short-Circuit Current Ratings (SCCR) and branch circuit protection

The table shows recommended fuse ratings for UL and CSA requirements. The components are for use together in accordance with standard UL508

 

 

 

 

 

 

ATV312 Drive

 

 

Short-Circuit Current Ratings

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input

 

 

 

 

 

 

 

Output

With Circuit

With GVpP

With Fuses

 

Voltage

 

 

 

Input AIC

Minimun

Line

Breaker

 

 

 

Reference 6

Interrupt

 

 

 

 

 

+10%/-15%

(kW)

(HP)

Rating

Inductance

Reactor

 

SCCR

GV2P/3P

 

 

 

SCCR

Rating:

PowerPact

SCCR

Fuse (A)

5

 

60 Hz

 

 

 

 

(kA)

(mH)

Reference

(kA) 3

Type E 3, 4

 

(kA) 2,3

 

Y

 

 

 

 

 

 

 

(kA) 1

Z1, Z2

X

Z1, Z2

(kA)

Z1, Z2

 

X

 

 

 

 

 

 

 

Three

-phase with

or without line reactor

 

 

 

 

 

 

 

 

 

 

0.18

0.25

ATV312H018M3

5

-

-

100

HxL36015

22

-

-

3

 

22

 

 

 

 

0.37

0.5

ATV312H037M3

5

-

-

100

HxL36015

22

-

-

6

 

22

 

 

 

 

0.55

0.75

ATV312H055M3

5

-

-

100

HxL36015

22

-

-

10

 

22

 

 

 

 

0.75

1

ATV312H075M3

5

-

-

100

HxL36015

22

-

-

10

 

22

 

 

Without line

 

1.1

1.5

ATV312HU11M3

5

-

-

100

HxL36015

22

-

-

15

 

22

 

 

reactor

1.5

2

ATV312HU15M3

5

-

-

100

HxL36015

22

-

-

15

 

22

 

 

2.2

3

ATV312HU22M3

5

-

-

100

HxL36020

22

-

-

20

 

22

 

 

3

-

ATV312HU30M3

5

-

-

100

HxL36020

22

-

-

25

 

22

 

 

 

4

5

ATV312HU40M3

5

-

-

100

HxL36030

22

-

-

35

 

22

 

 

 

 

 

 

 

 

 

5.5

7.5

ATV312HU55M3

22

-

-

100

HxL36040

22

-

-

50

 

22

 

 

 

 

7.5

10

ATV312HU75M3

22

-

-

100

HxL36060

22

-

-

60

 

22

208/230V

Three-phase

 

 

11

15

ATV312HD11M3

22

-

-

100

HxL36070

22

-

-

80

 

22

 

 

15

20

ATV312HD15M3

22

-

-

100

HxL36090

22

-

-

110

 

22

 

 

0.18

0.25

ATV312H018M3

5

3

RL-00401

100

HxL36015

65

GV2P07

65

3

 

22

 

 

0.37

0.5

ATV312H037M3

5

3

RL-00401

100

HxL36015

65

GV2P08

65

6

 

22

 

 

0.55

0.75

ATV312H055M3

5

3

RL-00401

100

HxL36015

65

GV2P10

65

10

 

22

 

 

 

 

0.75

1

ATV312H075M3

5

3

RL-00401

100

HxL36015

65

GV2P10

65

10

 

22

 

 

 

 

1.1

1.5

ATV312HU11M3

5

1.5

RL-00801

100

HxL36015

65

GV2P14

65

15

 

22

 

 

With line

reactor

1.5

2

ATV312HU15M3

5

1.5

RL-00801

100

HxL36015

65

GV2P14

65

15

 

22

 

 

2.2

3

ATV312HU22M3

5

1.25

RL-01201

100

HxL36020

65

GV3P18 /

65

20

 

22

 

 

13

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

-

ATV312HU30M3

5

1.25

RL-01801

100

HxL36020

65

GV3P18

65

25

 

22

 

 

 

 

4

5

ATV312HU40M3

5

1.25

RL-01801

100

HxL36030

65

GV3P25

65

35

 

22

 

 

 

 

5.5

7.5

ATV312HU55M3

22

0.5

RL-02501

100

HxL36040

65

GV3P40/

65

50

 

22

 

 

 

 

32

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7.5

10

ATV312HU75M3

22

0.4

RL-03501

100

HxL36060

65

GV3P50

65

60

 

22

 

 

 

 

11

15

ATV312HD11M3

22

0.3

RL-04501

100

HxL36070

65

GV3P65

65

80

 

22

 

 

 

 

15

20

ATV312HD15M3

22

0.2

RL-08001

100

HxL36090

65

-

-

110

 

22

 

 

 

 

0.37

0.5

ATV312H037N4

5

-

-

100

HxL36015

22

-

-

3

 

22

 

 

 

 

0.55

0.75

ATV312H055N4

5

-

-

100

HxL36015

22

-

-

6

 

22

 

 

 

 

0.75

1

ATV312H075N4

5

-

-

100

HxL36015

22

-

-

6

 

22

 

 

Without line

 

1.1

1.5

ATV312HU11N4

5

-

-

100

HxL36015

22

-

-

10

 

22

 

 

reactor

1.5

2

ATV312HU15N4

5

-

-

100

HxL36015

22

-

-

10

 

22

 

 

2.2

3

ATV312HU22N4

5

-

-

100

HxL36015

22

-

-

15

 

22

 

 

3

-

ATV312HU30N4

5

-

-

100

HxL36015

22

-

-

15

 

22

 

 

4

5

ATV312HU40N4

5

-

-

100

HxL36015

22

-

-

20

 

22

 

 

 

 

5.5

7.5

ATV312HU55N4

22

-

-

100

HxL36020

22

-

-

30

 

22

400/480 V

Three-phase

 

 

7.5

10

ATV312HU75N4

22

-

-

100

HxL36030

22

-

-

35

 

22

 

 

11

15

ATV312HD11N4

22

-

-

100

HxL36035

22

-

-

50

 

22

 

 

15

20

ATV312HD15N4

22

-

-

100

HxL36050

22

-

-

70

 

22

 

 

0.37

0.5

ATV312H037N4

5

12

RL00201

100

HxL36015

65

GV2P07

65

3

 

100

 

 

0.55

0.75

ATV312H055N4

5

12

RL00201

100

HxL36015

65

GV2P07

65

6

 

100

 

 

 

0.75

1

ATV312H075N4

5

12

RL00201

100

HxL36015

65

GV2P08

65

6

 

100

 

 

 

 

 

 

 

 

 

1.1

1.5

ATV312HU11N4

5

6.5

RL00402

100

HxL36015

65

GV2P08

65

10

 

100

 

 

With line

reactor

1.5

2

ATV312HU15N4

5

6.5

RL00402

100

HxL36015

65

GV2P10

65

10

 

100

 

 

2.2

3

ATV312HU22N4

5

5

RL00803

100

HxL36015

65

GV2P14

65

15

 

100

 

 

3

-

ATV312HU30N4

5

3

RL00802

100

HxL36015

65

GV2P14

65

15

 

100

 

 

4

5

ATV312HU40N4

5

3

RL00802

100

HxL36015

65

GV3P13

65

20

 

100

 

 

 

 

 

 

 

 

 

5.5

7.5

ATV312HU55N4

22

2.5

RL01202

100

HxL36020

65

GV3P18

65

30

 

100

 

 

 

 

7.5

10

ATV312HU75N4

22

1.5

RL01802

100

HxL36030

65

GV3P25

65

35

 

100

 

 

 

 

11

15

ATV312HD11N4

22

1.2

RL02502

100

HxL36035

65

GV3P32

65

50

 

100

 

 

 

 

15

20

ATV312HD15N4

22

0.8

RL03502

100

HxL36050

65

GV3P40

65

70

 

100

Footnotes are on the reverse side.

 

 

 

 

 

www.schneider-electric.com

1/4

S1B16328 - 02/2012

 

 

 

 

 

 

 

ATV312 Drive

 

 

Short-Circuit Current Ratings

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input

 

 

 

 

 

 

 

Output

With Circuit

With GVpP

With Fuses

 

Voltage

 

 

 

Input AIC

Minimun

Line

Breaker

 

 

 

Reference 6

Interrupt

 

 

 

 

 

+10%/-15%

(kW)

(HP)

Rating

Inductance

Reactor

 

SCCR

GV2P/3P

 

 

 

SCCR

Rating:

PowerPact

SCCR

Fuse (A)

5

 

60 Hz

 

 

 

 

(kA)

(mH)

Reference

(kA) 3

Type E 3, 4

 

(kA) 2,3

 

 

Y

 

 

 

 

 

 

 

(kA) 1

Z1, Z2

X

Z1, Z2

(kA)

Z1, Z2

 

X

 

 

 

 

 

 

 

 

 

Three-phase with line reactor

 

 

 

 

 

 

 

 

 

 

 

 

0.75

1

ATV312H075S6

5

20

RL-00202

100

FAL36015

22

-

-

6

 

22

 

phase-Three

 

 

 

1.5

2

ATV312HU15S6

5

9

RL-00403

100

FAL36015

22

-

-

6

 

22

575/600V

 

lineWith

reactor

2.2

3

ATV312HU22S6

5

6.5

RL-00402

100

FAL36015

22

-

-

10

 

22

 

 

 

 

 

 

 

 

 

 

 

4

5

ATV312HU40S6

5

5

RL-00803

100

FAL36025

22

-

-

15

 

22

 

 

 

 

 

5.5

7.5

ATV312HU55S6

22

2.5

RL-01202

100

FAL36040

22

-

-

20

 

22

 

 

 

 

 

7.5

10

ATV312HU75S6

22

2.5

RL-01202

100

FAL36050

22

-

-

25

 

22

 

 

 

 

 

11

15

ATV312HD11S6

22

1.5

RL-01802

100

FAL36070

22

-

-

35

 

22

 

 

 

 

 

15

20

ATV312HD15S6

22

1.2

RL-02502

100

FAL36080

22

-

-

45

 

22

 

 

 

 

 

 

 

 

Single-phase with or without line reactor

 

 

 

 

 

 

 

 

 

 

 

0.18

0.25

ATV312H018M2

1

-

-

100

-

-

-

-

6

 

22

 

 

 

 

 

0.37

0.5

ATV312H037M2

1

-

-

100

-

-

-

-

10

 

22

 

 

 

Withoutline

 

0.55

0.75

ATV312H055M2

1

-

-

100

-

-

-

-

10

 

22

 

 

 

reactor

0.75

1

ATV312H075M2

1

-

-

100

-

-

-

-

15

 

22

V208/230

phase-Single

 

1.1

1.5

ATV312HU11M2

1

-

-

100

-

-

-

-

20

 

22

 

 

 

 

 

 

 

 

 

 

 

1.5

2

ATV312HU15M2

1

-

-

100

-

-

-

-

20

 

22

 

 

 

 

 

2.2

3

ATV312HU22M2

1

-

-

100

-

-

-

-

30

 

22

 

 

 

 

 

4

5

ATV312HU75M3

2

-

-

100

HxL36060

22

-

-

60

 

22

 

 

 

 

 

5.5

7.5

ATV312HD11M3

2

-

-

100

HxL36070

22

-

-

80

 

22

 

 

 

 

 

7.5

10

ATV312HD15M3

2

-

-

100

HxL36090

22

-

-

110

 

22

 

 

 

Withline

reactor

4

5

ATV312HU75M3

22

0.75

RL-03502

100

HxL36060

65

GV3P50

65

60

 

22

 

 

 

5.5

7.5

ATV312HD11M3

22

0.375

RL-05502

100

HxL36070

65

GV3P65

65

80

 

22

 

 

 

 

 

 

 

 

 

 

 

7.5

10

ATV312HD15M3

22

0.278

RL-08002

100

HxL36090

65

-

-

110

 

22

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.37

0.5

ATV312H075N4

5

-

-

100

HxL36015

22

-

-

6

 

22

 

 

 

 

 

0.55

0.75

ATV312HU11N4

5

-

-

100

HxL36015

22

-

-

10

 

22

 

 

 

Withoutline

 

0.75

1

ATV312HU15N4

5

-

-

100

HxL36015

22

-

-

10

 

22

 

 

 

reactor

1.1

1.5

ATV312HU22N4

5

-

-

100

HxL36015

22

-

-

15

 

22

 

 

 

1.5

2

ATV312HU30N4

5

-

-

100

HxL36015

22

-

-

15

 

22

 

 

 

 

 

 

 

 

 

 

 

2.2

3

ATV312HU40N4

5

-

-

100

HxL36015

22

-

-

20

 

22

 

 

 

 

 

2.2

3

ATV312HU55N4

22

-

-

100

HxL36020

22

-

-

30

 

22

400/480V

phase-Single

 

 

 

4

5

ATV312HU75N4

22

-

-

100

HxL36030

22

-

-

35

 

22

 

 

 

5.5

7.5

ATV312HD11N4

22

-

-

100

HxL36035

22

-

-

50

 

22

 

 

 

7.5

10

ATV312HD15N4

22

-

-

100

HxL36050

22

-

-

70

 

22

 

 

 

 

 

 

 

 

 

 

 

0.37

0.5

ATV312H075N4

5

5.79

RL-00402

100

HxL36015

65

GV2P08

65

6

 

22

 

 

 

 

 

0.55

0.75

ATV312HU11N4

5

4.27

RL-00402

100

HxL36015

65

GV2P08

65

10

 

22

 

 

 

 

 

0.75

1

ATV312HU15N4

5

4.27

RL-00803

100

HxL36015

65

GV2P10

65

10

 

22

 

 

 

lineWith

reactor

1.1

1.5

ATV312HU22N4

5

2.77

RL-00802

100

HxL36015

65

GV2P14

65

15

 

22

 

 

 

1.5

2

ATV312HU30N4

5

2.77

RL-00802

100

HxL36015

65

GV2P14

65

15

 

22

 

 

 

 

 

 

 

 

 

 

 

2.2

3

ATV312HU40N4

5

1.68

RL-01202

100

HxL36015

65

GV3P13

65

20

 

22

 

 

 

 

 

2.2

3

ATV312HU55N4

22

1.29

RL-01802

100

HxL36020

65

GV3P18

65

30

 

22

 

 

 

 

 

4

5

ATV312HU75N4

22

0.912

RL-02502

100

HxL36030

65

GV3P25

65

35

 

22

 

 

 

 

 

5.5

7.5

ATV312HD11N4

22

0.694

RL-03502

100

HxL36035

65

GV3P32

65

50

 

22

 

 

 

 

 

7.5

10

ATV312HD15N4

22

0.569

RL-04502

100

HxL36050

65

GV3P40

65

70

 

22

Suitable for use on a circuit capable of delivering not more than___X___rms symmetrical kiloAmperes,___Y___Volts maximum, when protected by___Z1___with a maximum rating of___Z2___.

1.The Altivar 312 has a 100k SCC rating on the output of the drive as many other drives are rated. In addition to providing a rating based on shorting the output of the drive, these short-circuit rating have been obtained by testing the weakest point internal to the ATV312 per UL508C. These ratings allow proper coordination of short-circuit protection. The amp rating of the short-circuit protection devices in the table are maximum values.

Smaller amp sizes may be used.

2.Ratings also apply to ATV312 Type 1 product, ie: an ATV312 fitted with a conduit box.

3.Ratings apply to an ATV312 mounted in a non-ventilated Type 1, 3R, 4(X) or 12 rated enclosure. Minimum enclosure volume is 3.375 times the drive volume .

4.480 V ratings are for Wye connected electrical distribution systems. GV2Ppp self protected manual combination starter must be used with GV2GH7 insulating barrier to meet UL 508 Type E rating. GV3Ppp must be used with GV3G66 and GVAM11 in order to meet UL508 rating.

5.Fuse type can be Class J, fast acting or time delay, or Class CC.

6.Available also for B products. Example: ATV312H018M3B