INDOOR UNIT : CS-MKE7NKU
CS-MKE9NKU
CS-MKE12NKU
CS-MKE18NKU
CS-MKE24NKU
DC INVERTER MULTI-SYSTEM AIR CONDITIONER
Capacity |
Indoor Model No. |
Product Code No. |
|
|
|
7,500BTU / h |
CS-MKE7NKU |
1 852 360 99 |
|
|
|
9,000BTU / h |
CS-MKE9NKU |
1 852 361 00 |
11,900BTU / h |
CS-MKE12NKU |
1 852 361 01 |
17,500BTU / h |
CS-MKE18NKU |
1 852 361 02 |
24,200BTU / h |
CS-MKE24NKU |
1 852 361 03 |
Wall Mounted Type Indoor Unit
< Applicable Multi-Outdoor Units >
CU-3KE19NBU (3-room multi unit) CU-4KE24NBU (4-room multi unit) CU-4KE31NBU (4-room multi unit)
CS-MKE7NKU
CS-MKE9NKU
CS-MKE12NKU
IMPORTANT
These air conditioners employ new refrigerant R410A.
CS-MKE18NKU CS-MKE24NKU
Pay special attention when servicing the unit.
REFERENCE NO. SM700874
•Before doing repair work, please read the "SAFETY PRECAUTIONS" carefully and fully understand them.
•The precautionary items here are divided into "Warning" and "Caution" items.
Items in particular which may cause death or serious injury to the service personnel if the work is not performed correctly,
are included in the "Warning" table.
However, even precautionary items identified as " Caution" also have the potential for serious consequences if not performed correctly.
Important safety precautions are described for all items in both categories. Be sure to carefully follow all of them.
•Symbol Indication
: This symbol indicates items to which we need to pay attention. In this triangle, a definite precautionary item is described.
: This symbol indicates the item to be prohibited.
In or close to this circle, a prohibited item is described.
: This symbol indicates the items requiring special attention or instruction. In or close to this circle, a prohibited item is described.
•After doing repair work, perform a test run to confirm that there are no abnormalities. At the same time, explain the precautions in use to the user.
Warning
Before performing an overhaul, disconnect the power plug or power cable from the unit.
Performing the work with the power supplied to the unit, may cause an electric shock.
When repair work or circuit inspection that requires power supply for the air conditioner, is to be performed, |
|
do not touch the charging section. |
|
Doing so may cause an electric shock. |
Prohibit |
For the step-up capacitor attached to the electric section, perform the repair work after sufficiently discharging it. Insufficient capacitor discharge may cause an electric shock.
Do not perform repair work on the electric sections with wet hands.
Doing so may cause an electric shock.
Prohibit
Do not start or stop the air conditioner by means of connecting or disconnecting the power plug.
Doing so may cause an electric shock or fire.
Prohibit
When conducting repair work only use components included in the parts list for the corresponding unit and perform the work with the appropriate tools.
Incorrect or poor repair work may cause an electric shock or fire.
Never modify the unit.
Doing so may cause an electric shock or fire.
Prohibit
Perform all electric work according to local applicable regulations related to electrical equipment or interior wiring regulation and make sure to use the exclusive circuit.
Insufficient capacity to the electric circuit or defective arrangement results may cause an electric shock or fire.
Make sure to replace any power cable or lead wire showing any signs of scratch or deterioration.
Failure to do so may cause an electric shock, overheating or fire.
Make sure that there is no dust on or slack in the power plug and insert fully into the socket.
Dust or incomplete connections may cause an electric shock or fire.
Do not damage or process the power cord, as it may cause an electric shock or fire.
Prohibit
For the wiring between the indoor unit and outdoor unit, securely fix the specified cable onto the terminal plate. Poorly fixed wiring may cause a heat or fire.
After connecting the wiring between the indoor unit and outdoor unit, attach the terminal cover securely. Incomplete attachment of the terminal cover may cause overheating or fire.
2
Warning
If refrigerant gas blows off during the work, do not touch the refrigerant gas as it may cause frostbite.
Prohibit
If refrigerant gas leaks during the work, ventilate the room.
If refrigerant gas catches fire, harmful gas may be generated.
Do not mix any gas other than the specified refrigerant gas in the refrigerating cycle. |
|
If air or other contaminants mix with the gas, pressure will become extremely high in the refrigerating cycle, |
|
which may cause a unit breakdown." |
Prohibit |
When the welded section of the compressor intake or discharge pipe is to be disconnected, perform it in a well-ventilated place after sufficiently recovering the refrigerant gas.
Any residue gas may jet out refrigerant or refrigerating machine oil, which may cause an injury.
When the work is to be performed in a high place (About 2 meters or more), make sure to wear a safety helmet, gloves and safety belt. Insufficient safety gear may cause a serious injury in case of a fall.
When the unit is to be relocated, confirm that the new installation location has sufficient strength for the weight of the unit. Insufficient strength of the installation location and incomplete installation work may cause an injury due to
the unit falling.
When the remote controller batteries are replaced, dispose of the old batteries out of the reach of children.
If a child swallows a battery, make sure that the child gets immediate medical attention.
Caution
Do not wash the air conditioner with water, as this may cause an electric shock or fire.
Prohibit
For the repair work in places with high humidity or moisture, make sure to ground the unit.
Failure to do so may cause an electric shock.
Confirm that the component attachment position, wiring condition, soldering condition and connector connection are normal.
If not, it may cause overheating or fire.
Confirm that the temperature around the compressor is not too high, and then perform the repair work. Failure to do so may cause a burn.
Perform welding work in a place with good ventilation.
If the work is performed in a poorly ventilated area, it might cause a lack of oxygen.
If the installation plate or attachment frame has deteriorated due to corrosion, etc., replace it.
Failure to do so may cause an injury due to the unit falling.
When the cleaning is to be performed, make sure to turn off the power and pull out the plug.
Touching the fan that is rotating at high speed may result in an injury.
When the indoor unit is to be removed, do not place it on an incline.
Doing so may cause wet furniture because water left inside may trickle down.
Prohibit
Do not hold the sharp end of the unit or the aluminum fins, as it may cause an injury to your hand or finger.
Prohibit
After repairs, make sure to measure the insulation resistance and confirm that the value is 1 Mohm or more. Any insulation error may cause an electric shock.
After repairs, make sure to check the drainage of the indoor unit.
Inappropriate drainage may cause wet furniture and floors due to water leakage.
3
|
|
|
|
|
Page |
|
|
|
SAFETY PRECAUTIONS ............................................................................................................. |
2 |
|||
|
TABLE OF CONTENTS .................................................................................................................... |
4 |
||||
|
|
APPLICABLE MULTI-OUTDOOR UNITS ................................................................................... |
5 |
|||
|
|
|||||
|
|
|||||
|
1. OPERATING RANGE ................................................................................................................... |
6 |
||||
|
2. SPECIFICATIONS |
|
||||
|
2-1. |
Unit Specifications ............................................................................................................. |
7 |
|||
|
2-2. |
Major Component Specifications ....................................................................................... |
17 |
|||
|
2-3. |
Other Component Specifications ....................................................................................... |
22 |
|||
|
3. DIMENSIONAL DATA .................................................................................................................... |
23 |
||||
|
4. REFRIGERANT FLOW DIAGRAM |
|
||||
|
4-1. |
Refrigerant Flow Diagram .................................................................................................. |
25 |
|||
|
5. PERFORMANCE DATA |
|
||||
|
5-1. |
Air Throw Distance Charts ................................................................................................. |
26 |
|||
|
6. ELECTRICAL DATA |
|
||||
|
6-1. |
Electric Wiring Diagrams .................................................................................................... |
31 |
|||
|
7. FUNCTIONS |
|
|
|||
|
7-1. |
Operation Functions ........................................................................................................... |
32 |
|||
|
7-2. |
Protective Functions ........................................................................................................... |
34 |
|||
|
8. TROUBLESHOOTING (BEFORE CALLING FOR SERVICE) |
|
||||
|
8-1. |
Precautions before Performing Inspection or Repair .......................................................... |
35 |
|||
|
8-2. |
Method of Self-Diagnostics ................................................................................................. |
35 |
|||
|
8-3. |
Checking the Indoor and Outdoor Units .............................................................................. |
38 |
|||
|
8-4. |
Trouble Diagnosis of Fan Motor .......................................................................................... |
41 |
|||
|
8-5. |
Noise Malfunction and Electromagnetic Interference .......................................................... |
42 |
|||
|
|
|
Operating Instructions .......................................................................................... |
|
||
|
APPENDIX A |
|
A-1 |
|||
|
|
Operating Instructions .......................................................................................... |
|
|||
|
APPENDIX B |
|
A-2 |
|||
|
|
INSTALLATION INSTRUCTIONS .......................................................................... |
|
|||
|
APPENDIX C |
|
A-3 |
4
APPLICABLE MULTI-OUTDOOR UNITS
Multi-Outdoor Unit |
3-Room |
4-Room |
4-Room |
Indoor Unit |
CU-3KE19NBU |
CU-4KE24NBU |
CU-4KE31NBU |
CS-MKE7NKU |
YES |
YES |
YES |
CS-MKE9NKU |
YES |
YES |
YES |
CS-MKE12NKU |
YES |
YES |
YES |
CS-MKE18NKU |
YES |
YES |
YES |
CS-MKE24NKU |
NO |
YES |
YES |
5
|
Temperature |
Indoor Air Intake Temp. |
Outdoor Air Intake Temp. |
|
|
|
|
|
|
Cooling |
Maximum |
95 °F DB / 71 °F WB |
115° F DB |
|
|
|
|
||
Minimum |
67 °F DB / 57 °F WB |
14° F DB |
||
|
||||
|
|
|
|
|
Heating |
Maximum |
80 °F DB / 67 °F WB |
75° F DB / 65 °F WB |
|
|
|
|
||
Minimum |
– DB / – WB |
– DB / 0 °F WB |
||
|
6
2. |
SPECIFICATIONS |
|
|
|
|
|||
2-1. |
Unit Specifications |
|
|
|
|
|||
Indoor Unit |
CS-MKE7NKU |
|
|
|
|
|||
|
|
|
|
|
|
|
|
< 230V > |
|
|
|
|
|
|
|
|
|
Type |
|
|
|
|
Wall Mounted Type Indoor Unit |
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Voltage Rating |
|
|
|
|
230V Single-Phase 60Hz |
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Performance |
|
|
|
|
Cooling |
Heating |
||
|
|
|
|
|
|
|
|
|
|
Capacity |
|
|
|
BTU/h |
7,500 |
8,500 |
|
|
|
|
|
|
|
kW |
2.20 |
2.50 |
|
Air Circulation (Hi/Me/Lo) |
ft3/min (m3/h) |
241(410) / 224(381) / 212(360) |
271(460) / 241(410) / 218(370) |
||||
|
Moisture Removal (High) |
|
Pints/h |
2.77 |
- |
|||
|
|
|
|
|
|
|
||
Electrical Rating |
|
|
|
Cooling |
Heating |
|||
|
|
|
|
|
|
|
||
|
Available Voltage Range |
|
V |
187 to 253 |
||||
|
Running Amperes |
|
|
A |
0.11 |
0.11 |
||
|
Power Input |
|
|
|
W |
25 |
25 |
|
|
|
|
|
|
|
|
||
Features |
|
|
|
|
|
|
||
|
|
|
|
|
|
|
||
|
Control / Temperature Control |
|
|
Microprocessor / I.C. Thermistor |
||||
|
|
|
|
|
|
|
||
|
Control Unit |
|
|
|
|
Wireless Remote Control Unit |
||
|
|
|
|
|
|
|
||
|
Timer |
|
|
|
|
24-Hour ON or OFF Timer, 1-Hour OFF Timer |
||
|
Fan Speeds |
|
|
|
Indoor |
Auto and 3 steps |
||
|
Airflow Direction (Indoor) |
|
Horizontal |
Manual |
||||
|
|
|
|
|
|
Vertical |
Auto |
|
|
Air Filter |
|
|
|
|
Washable, Anti-Mold |
||
|
Refrigerant |
|
|
|
|
R410A |
||
|
|
|
|
|
|
|||
|
Operation Sound |
Indoor : Hi/Me/Lo/Qt* |
dB-A |
33 / 30 / 27 / 23 |
33 / 30 / 27 / 23 |
|||
|
(*Qt = Quiet mode) |
|
|
|
|
|
||
|
Refrigerant Tubing Connections |
|
|
Flare Type |
||||
|
Refrigerant |
|
Narrow tube |
|
inch (mm) |
1/4 (6.35) |
||
|
|
|
|
|
|
|||
|
Tube Diameter |
Wide tube |
|
inch (mm) |
3/8 (9.52) |
|||
|
Refrigerant Tubing Kit |
|
|
|
Optional |
|||
|
|
|
|
|
|
|
|
|
Dimensions & Weight |
|
|
|
|
|
|||
|
Unit Dimensions |
Height |
|
inch (mm) |
11-7/32 (285) |
|||
|
|
|
|
Width |
|
inch (mm) |
32-15/32 (825) |
|
|
|
|
|
Depth |
|
inch (mm) |
7-7/16 (189) |
|
|
Package Dimensions |
Height |
|
inch (mm) |
10-19/32 (269) |
|||
|
|
|
|
Width |
|
inch (mm) |
35-21/32 (906) |
|
|
|
|
|
Depth |
|
inch (mm) |
14-1/32 (356) |
|
|
Weight |
|
Net |
|
Ib. (kg) |
19.8 (9.0) |
||
|
|
|
|
Shipping |
|
Ib. (kg) |
24.3 (11.0) |
|
|
Shipping Volume |
|
|
cu.ft (m3) |
2.82 (0.08) |
|||
|
|
|
|
|
|
|
DATA SUBJECT TO CHANGE WITHOUT NOTICE. |
7
Indoor Unit |
CS-MKE7NKU |
|
|
|
|
||
|
|
|
|
|
|
|
< 208V > |
|
|
|
|
|
|
|
|
Type |
|
|
|
|
Wall Mounted Type Indoor Unit |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Voltage Rating |
|
|
|
|
208V Single-Phase 60Hz |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Performance |
|
|
|
|
Cooling |
Heating |
|
|
|
|
|
|
|
|
|
|
Capacity |
|
|
|
BTU/h |
7,500 |
8,500 |
|
|
|
|
|
kW |
2.20 |
2.50 |
|
Air Circulation (Hi/Me/Lo) |
ft3/min (m3/h) |
241(410) / 224(381) / 212(360) |
271(460) / 241(410) / 218(370) |
|||
|
Moisture Removal (High) |
|
Pints/h |
2.77 |
- |
||
|
|
|
|
|
|
|
|
Electrical Rating |
|
|
|
Cooling |
Heating |
||
|
|
|
|
|
|
|
|
|
Available Voltage Range |
|
V |
187 to 253 |
|||
|
Running Amperes |
|
|
A |
0.12 |
0.12 |
|
|
Power Input |
|
|
|
W |
25 |
25 |
|
|
|
|
|
|
|
|
Features |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Control / Temperature Control |
|
|
Microprocessor / I.C. Thermistor |
|||
|
|
|
|
|
|
|
|
|
Control Unit |
|
|
|
|
Wireless Remote Control Unit |
|
|
|
|
|
|
|
|
|
|
Timer |
|
|
|
|
24-Hour ON or OFF Timer, 1-Hour OFF Timer |
|
|
Fan Speeds |
|
|
|
Indoor |
Auto and 3 steps |
|
|
Airflow Direction (Indoor) |
|
Horizontal |
Manual |
|||
|
|
|
|
|
Vertical |
Auto |
|
|
Air Filter |
|
|
|
|
Washable, Anti-Mold |
|
|
Refrigerant |
|
|
|
|
R410A |
|
|
|
|
|
|
|
||
|
Operation Sound |
Indoor : Hi/Me/Lo/Qt* |
dB-A |
33 / 30 / 27 / 23 |
33 / 30 / 27 / 23 |
||
|
(*Qt = Quiet mode) |
|
|
|
|
|
|
|
Refrigerant Tubing Connections |
|
|
Flare Type |
|||
|
Refrigerant |
|
Narrow tube |
|
inch (mm) |
1/4 (6.35) |
|
|
|
|
|
|
|
||
|
Tube Diameter |
Wide tube |
|
inch (mm) |
3/8 (9.52) |
||
|
Refrigerant Tubing Kit |
|
|
|
Optional |
||
|
|
|
|
|
|
|
|
Dimensions & Weight |
|
|
|
|
|
||
|
Unit Dimensions |
Height |
|
inch (mm) |
11-7/32 (285) |
||
|
|
|
Width |
|
inch (mm) |
32-15/32 (825) |
|
|
|
|
Depth |
|
inch (mm) |
7-7/16 (189) |
|
|
Package Dimensions |
Height |
|
inch (mm) |
10-19/32 (269) |
||
|
|
|
Width |
|
inch (mm) |
35-21/32 (906) |
|
|
|
|
Depth |
|
inch (mm) |
14-1/32 (356) |
|
|
Weight |
|
Net |
|
Ib. (kg) |
19.8 (9.0) |
|
|
|
|
Shipping |
|
Ib. (kg) |
24.3 (11.0) |
|
|
Shipping Volume |
|
|
cu.ft (m3) |
2.82 (0.08) |
||
|
|
|
|
|
|
DATA SUBJECT TO CHANGE WITHOUT NOTICE. |
8
Indoor Unit |
CS-MKE9NKU |
|
|
|
|
||
|
|
|
|
|
|
|
< 230V > |
|
|
|
|
|
|
|
|
Type |
|
|
|
|
Wall Mounted Type Indoor Unit |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Voltage Rating |
|
|
|
|
230V Single-Phase 60Hz |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Performance |
|
|
|
|
Cooling |
Heating |
|
|
|
|
|
|
|
|
|
|
Capacity |
|
|
|
BTU/h |
9,000 |
12,200 |
|
|
|
|
|
kW |
2.65 |
3.60 |
|
Air Circulation (Hi/Me/Lo) |
ft3/min (m3/h) |
259(440) / 241(410) / 212(360) |
282(479) / 271(460) / 218(370) |
|||
|
Moisture Removal (High) |
|
Pints/h |
3.4 |
- |
||
|
|
|
|
|
|
|
|
Electrical Rating |
|
|
|
Cooling |
Heating |
||
|
|
|
|
|
|
|
|
|
Available Voltage Range |
|
V |
187 to 253 |
|||
|
Running Amperes |
|
|
A |
0.15 |
0.15 |
|
|
Power Input |
|
|
|
W |
35 |
35 |
|
|
|
|
|
|
|
|
Features |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Control / Temperature Control |
|
|
Microprocessor / I.C. Thermistor |
|||
|
|
|
|
|
|
|
|
|
Control Unit |
|
|
|
|
Wireless Remote Control Unit |
|
|
|
|
|
|
|
|
|
|
Timer |
|
|
|
|
24-Hour ON or OFF Timer, 1-Hour OFF Timer |
|
|
Fan Speeds |
|
|
|
Indoor |
Auto and 3 steps |
|
|
Airflow Direction (Indoor) |
|
Horizontal |
Manual |
|||
|
|
|
|
|
Vertical |
Auto |
|
|
Air Filter |
|
|
|
|
Washable, Anti-Mold |
|
|
Refrigerant |
|
|
|
|
R410A |
|
|
|
|
|
|
|
||
|
Operation Sound |
Indoor : Hi/Me/Lo/Qt* |
dB-A |
34 / 31 / 28 / 23 |
34 / 31 / 28 / 23 |
||
|
(*Qt = Quiet mode) |
|
|
|
|
|
|
|
Refrigerant Tubing Connections |
|
|
Flare Type |
|||
|
Refrigerant |
|
Narrow tube |
|
inch (mm) |
1/4 (6.35) |
|
|
|
|
|
|
|
||
|
Tube Diameter |
Wide tube |
|
inch (mm) |
3/8 (9.52) |
||
|
Refrigerant Tubing Kit |
|
|
|
Optional |
||
|
|
|
|
|
|
|
|
Dimensions & Weight |
|
|
|
|
|
||
|
Unit Dimensions |
Height |
|
inch (mm) |
11-7/32 (285) |
||
|
|
|
Width |
|
inch (mm) |
32-15/32 (825) |
|
|
|
|
Depth |
|
inch (mm) |
7-7/16 (189) |
|
|
Package Dimensions |
Height |
|
inch (mm) |
10-19/32 |
(269) |
|
|
|
|
Width |
|
inch (mm) |
35-21/32 |
(906) |
|
|
|
Depth |
|
inch (mm) |
14-1/32 |
(356) |
|
Weight |
|
Net |
|
Ib. (kg) |
19.8 (9.0) |
|
|
|
|
Shipping |
|
Ib. (kg) |
24.3 (11.0) |
|
|
Shipping Volume |
|
|
cu.ft (m3) |
2.82 (0.08) |
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
9
Indoor Unit |
CS-MKE9NKU |
|
|
|
|
||
|
|
|
|
|
|
|
< 208V > |
|
|
|
|
|
|
|
|
Type |
|
|
|
|
Wall Mounted Type Indoor Unit |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Voltage Rating |
|
|
|
|
208V Single-Phase 60Hz |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Performance |
|
|
|
|
Cooling |
Heating |
|
|
|
|
|
|
|
|
|
|
Capacity |
|
|
|
BTU/h |
9,000 |
12,200 |
|
|
|
|
|
kW |
2.65 |
3.60 |
|
Air Circulation (Hi/Me/Lo) |
ft3/min (m3/h) |
259(440) / 241(410) / 212(360) |
282(479) / 271(460) / 218(370) |
|||
|
Moisture Removal (High) |
|
Pints/h |
3.4 |
- |
||
|
|
|
|
|
|
|
|
Electrical Rating |
|
|
|
Cooling |
Heating |
||
|
|
|
|
|
|
|
|
|
Available Voltage Range |
|
V |
187 to 253 |
|||
|
Running Amperes |
|
|
A |
0.17 |
0.17 |
|
|
Power Input |
|
|
|
W |
35 |
35 |
|
|
|
|
|
|
|
|
Features |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Control / Temperature Control |
|
|
Microprocessor / I.C. Thermistor |
|||
|
|
|
|
|
|
|
|
|
Control Unit |
|
|
|
|
Wireless Remote Control Unit |
|
|
|
|
|
|
|
|
|
|
Timer |
|
|
|
|
24-Hour ON or OFF Timer, 1-Hour OFF Timer |
|
|
Fan Speeds |
|
|
|
Indoor |
Auto and 3 steps |
|
|
Airflow Direction (Indoor) |
|
Horizontal |
Manual |
|||
|
|
|
|
|
Vertical |
Auto |
|
|
Air Filter |
|
|
|
|
Washable, Anti-Mold |
|
|
Refrigerant |
|
|
|
|
R410A |
|
|
|
|
|
|
|
||
|
Operation Sound |
Indoor : Hi/Me/Lo/Qt* |
dB-A |
34 / 31 / 28 / 23 |
34 / 31 / 28 / 23 |
||
|
(*Qt = Quiet mode) |
|
|
|
|
|
|
|
Refrigerant Tubing Connections |
|
|
Flare Type |
|||
|
Refrigerant |
|
Narrow tube |
|
inch (mm) |
1/4 (6.35) |
|
|
|
|
|
|
|
||
|
Tube Diameter |
Wide tube |
|
inch (mm) |
3/8 (9.52) |
||
|
Refrigerant Tubing Kit |
|
|
|
Optional |
||
|
|
|
|
|
|
|
|
Dimensions & Weight |
|
|
|
|
|
||
|
Unit Dimensions |
Height |
|
inch (mm) |
11-7/32 (285) |
||
|
|
|
Width |
|
inch (mm) |
32-15/32 (825) |
|
|
|
|
Depth |
|
inch (mm) |
7-7/16 (189) |
|
|
Package Dimensions |
Height |
|
inch (mm) |
10-19/32 |
(269) |
|
|
|
|
Width |
|
inch (mm) |
35-21/32 |
(906) |
|
|
|
Depth |
|
inch (mm) |
14-1/32 |
(356) |
|
Weight |
|
Net |
|
Ib. (kg) |
19.8 (9.0) |
|
|
|
|
Shipping |
|
Ib. (kg) |
24.3 (11.0) |
|
|
Shipping Volume |
|
|
cu.ft (m3) |
2.82 (0.08) |
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
10
Indoor Unit |
CS-MKE12NKU |
|
|
|
|
||
|
|
|
|
|
|
|
< 230V > |
|
|
|
|
|
|
|
|
Type |
|
|
|
|
Wall Mounted Type Indoor Unit |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Voltage Rating |
|
|
|
|
230V Single-Phase 60Hz |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Performance |
|
|
|
|
Cooling |
Heating |
|
|
|
|
|
|
|
|
|
|
Capacity |
|
|
|
BTU/h |
11,900 |
14,300 |
|
|
|
|
|
kW |
3.50 |
4.20 |
|
Air Circulation (Hi/Me/Lo) |
ft3/min (m3/h) |
282(479) / 259(440) / 218(370) |
294(500) / 271(460) / 218(370) |
|||
|
Moisture Removal (High) |
|
Pints/h |
4.26 |
- |
||
|
|
|
|
|
|
|
|
Electrical Rating |
|
|
|
Cooling |
Heating |
||
|
|
|
|
|
|
|
|
|
Available Voltage Range |
|
V |
187 to 253 |
|||
|
Running Amperes |
|
|
A |
0.15 |
0.15 |
|
|
Power Input |
|
|
|
W |
35 |
35 |
|
|
|
|
|
|
|
|
Features |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Control / Temperature Control |
|
|
Microprocessor / I.C. Thermistor |
|||
|
|
|
|
|
|
|
|
|
Control Unit |
|
|
|
|
Wireless Remote Control Unit |
|
|
|
|
|
|
|
|
|
|
Timer |
|
|
|
|
24-Hour ON or OFF Timer, 1-Hour OFF Timer |
|
|
Fan Speeds |
|
|
|
Indoor |
Auto and 3 steps |
|
|
Airflow Direction (Indoor) |
|
Horizontal |
Manual |
|||
|
|
|
|
|
Vertical |
Auto |
|
|
Air Filter |
|
|
|
|
Washable, Anti-Mold |
|
|
Refrigerant |
|
|
|
|
R410A |
|
|
|
|
|
|
|
||
|
Operation Sound |
Indoor : Hi/Me/Lo/Qt* |
dB-A |
36 / 33 / 29 / 25 |
34 / 31 / 29 / 25 |
||
|
(*Qt = Quiet mode) |
|
|
|
|
|
|
|
Refrigerant Tubing Connections |
|
|
Flare Type |
|||
|
Refrigerant |
|
Narrow tube |
|
inch (mm) |
1/4 (6.35) |
|
|
|
|
|
|
|
||
|
Tube Diameter |
Wide tube |
|
inch (mm) |
3/8 (9.52) |
||
|
Refrigerant Tubing Kit |
|
|
|
Optional |
||
|
|
|
|
|
|
|
|
Dimensions & Weight |
|
|
|
|
|
||
|
Unit Dimensions |
Height |
|
inch (mm) |
11-7/32 (285) |
||
|
|
|
Width |
|
inch (mm) |
32-15/32 (825) |
|
|
|
|
Depth |
|
inch (mm) |
7-7/16 (189) |
|
|
Package Dimensions |
Height |
|
inch (mm) |
10-19/32 |
(269) |
|
|
|
|
Width |
|
inch (mm) |
35-21/32 |
(906) |
|
|
|
Depth |
|
inch (mm) |
14-1/32 |
(356) |
|
Weight |
|
Net |
|
Ib. (kg) |
19.8 (9.0) |
|
|
|
|
Shipping |
|
Ib. (kg) |
24.3 (11.0) |
|
|
Shipping Volume |
|
|
cu.ft (m3) |
2.82 (0.08) |
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
11
Indoor Unit |
CS-MKE12NKU |
|
|
|
|
||
|
|
|
|
|
|
|
< 208V > |
|
|
|
|
|
|
|
|
Type |
|
|
|
|
Wall Mounted Type Indoor Unit |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Voltage Rating |
|
|
|
|
208V Single-Phase 60Hz |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Performance |
|
|
|
|
Cooling |
Heating |
|
|
|
|
|
|
|
|
|
|
Capacity |
|
|
|
BTU/h |
11,900 |
14,300 |
|
|
|
|
|
kW |
3.50 |
4.20 |
|
Air Circulation (Hi/Me/Lo) |
ft3/min (m3/h) |
282(479) / 259(440) / 218(370) |
294(500) / 271(460) / 218(370) |
|||
|
Moisture Removal (High) |
|
Pints/h |
4.26 |
- |
||
|
|
|
|
|
|
|
|
Electrical Rating |
|
|
|
Cooling |
Heating |
||
|
|
|
|
|
|
|
|
|
Available Voltage Range |
|
V |
187 to 253 |
|||
|
Running Amperes |
|
|
A |
0.17 |
0.17 |
|
|
Power Input |
|
|
|
W |
35 |
35 |
|
|
|
|
|
|
|
|
Features |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Control / Temperature Control |
|
|
Microprocessor / I.C. Thermistor |
|||
|
|
|
|
|
|
|
|
|
Control Unit |
|
|
|
|
Wireless Remote Control Unit |
|
|
|
|
|
|
|
|
|
|
Timer |
|
|
|
|
24-Hour ON or OFF Timer, 1-Hour OFF Timer |
|
|
Fan Speeds |
|
|
|
Indoor |
Auto and 3 steps |
|
|
Airflow Direction (Indoor) |
|
Horizontal |
Manual |
|||
|
|
|
|
|
Vertical |
Auto |
|
|
Air Filter |
|
|
|
|
Washable, Anti-Mold |
|
|
Refrigerant |
|
|
|
|
R410A |
|
|
|
|
|
|
|
||
|
Operation Sound |
Indoor : Hi/Me/Lo/Qt* |
dB-A |
36 / 33 / 29 / 25 |
34 / 31 / 29 / 25 |
||
|
(*Qt = Quiet mode) |
|
|
|
|
|
|
|
Refrigerant Tubing Connections |
|
|
Flare Type |
|||
|
Refrigerant |
|
Narrow tube |
|
inch (mm) |
1/4 (6.35) |
|
|
|
|
|
|
|
||
|
Tube Diameter |
Wide tube |
|
inch (mm) |
3/8 (9.52) |
||
|
Refrigerant Tubing Kit |
|
|
|
Optional |
||
|
|
|
|
|
|
|
|
Dimensions & Weight |
|
|
|
|
|
||
|
Unit Dimensions |
Height |
|
inch (mm) |
11-7/32 (285) |
||
|
|
|
Width |
|
inch (mm) |
32-15/32 (825) |
|
|
|
|
Depth |
|
inch (mm) |
7-7/16 (189) |
|
|
Package Dimensions |
Height |
|
inch (mm) |
10-19/32 |
(269) |
|
|
|
|
Width |
|
inch (mm) |
35-21/32 |
(906) |
|
|
|
Depth |
|
inch (mm) |
14-1/32 |
(356) |
|
Weight |
|
Net |
|
Ib. (kg) |
19.8 (9.0) |
|
|
|
|
Shipping |
|
Ib. (kg) |
24.3 (11.0) |
|
|
Shipping Volume |
|
|
cu.ft (m3) |
2.82 (0.08) |
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
12
Indoor Unit |
CS-MKE18NKU |
|
|
|
|
||
|
|
|
|
|
|
|
< 230V > |
|
|
|
|
|
|
|
|
Type |
|
|
|
|
Wall Mounted Type Indoor Unit |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Voltage Rating |
|
|
|
|
230V Single-Phase 60Hz |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Performance |
|
|
|
|
Cooling |
Heating |
|
|
|
|
|
|
|
|
|
|
Capacity |
|
|
|
BTU/h |
17,500 |
20,400 |
|
|
|
|
|
kW |
5.15 |
6.00 |
|
Air Circulation (Hi/Me/Lo) |
ft3/min (m3/h) |
500(850) / 447(760) / 377(641) |
500(850) / 435(739) / 377(641) |
|||
|
Moisture Removal (High) |
|
Pints/h |
4.89 |
- |
||
|
|
|
|
|
|
|
|
Electrical Rating |
|
|
|
Cooling |
Heating |
||
|
|
|
|
|
|
|
|
|
Available Voltage Range |
|
V |
187 to 253 |
|||
|
Running Amperes |
|
|
A |
0.15 |
0.15 |
|
|
Power Input |
|
|
|
W |
35 |
35 |
|
|
|
|
|
|
|
|
Features |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Control / Temperature Control |
|
|
Microprocessor / I.C. Thermistor |
|||
|
|
|
|
|
|
|
|
|
Control Unit |
|
|
|
|
Wireless Remote Control Unit |
|
|
|
|
|
|
|
|
|
|
Timer |
|
|
|
|
24-Hour ON or OFF Timer, 1-Hour OFF Timer |
|
|
Fan Speeds |
|
|
|
Indoor |
Auto and 3 steps |
|
|
Airflow Direction (Indoor) |
|
Horizontal |
Manual |
|||
|
|
|
|
|
Vertical |
Auto |
|
|
Air Filter |
|
|
|
|
Washable, Anti-Mold |
|
|
Refrigerant |
|
|
|
|
R410A |
|
|
|
|
|
|
|
||
|
Operation Sound |
Indoor : Hi/Me/Lo/Qt* |
dB-A |
41 / 38 / 34 / 28 |
40 / 37 / 34 / 28 |
||
|
(*Qt = Quiet mode) |
|
|
|
|
|
|
|
Refrigerant Tubing Connections |
|
|
Flare Type |
|||
|
Refrigerant |
|
Narrow tube |
|
inch (mm) |
1/4 (6.35) |
|
|
|
|
|
|
|
||
|
Tube Diameter |
Wide tube |
|
inch (mm) |
1/2 (12.7) |
||
|
Refrigerant Tubing Kit |
|
|
|
Optional |
||
|
|
|
|
|
|
|
|
Dimensions & Weight |
|
|
|
|
|
||
|
Unit Dimensions |
Height |
|
inch (mm) |
11-23/32 (298) |
||
|
|
|
Width |
|
inch (mm) |
41-15/16 (1,065) |
|
|
|
|
Depth |
|
inch (mm) |
8-5/8 (219) |
|
|
Package Dimensions |
Height |
|
inch (mm) |
11-27/32 (301) |
||
|
|
|
Width |
|
inch (mm) |
45-1/8 (1,146) |
|
|
|
|
Depth |
|
inch (mm) |
15-5/32 (385) |
|
|
Weight |
|
Net |
|
Ib. (kg) |
26.5 (12.0) |
|
|
|
|
Shipping |
|
Ib. (kg) |
33.1 (15.0) |
|
|
Shipping Volume |
|
|
cu.ft (m3) |
4.59 (0.13) |
||
|
|
|
|
|
|
DATA SUBJECT TO CHANGE WITHOUT NOTICE. |
13
Indoor Unit |
CS-MKE18NKU |
|
|
|
|
||
|
|
|
|
|
|
|
< 208V > |
|
|
|
|
|
|
|
|
Type |
|
|
|
|
Wall Mounted Type Indoor Unit |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Voltage Rating |
|
|
|
|
208V Single-Phase 60Hz |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Performance |
|
|
|
|
Cooling |
Heating |
|
|
|
|
|
|
|
|
|
|
Capacity |
|
|
|
BTU/h |
17,500 |
20,400 |
|
|
|
|
|
kW |
5.15 |
6.00 |
|
Air Circulation (Hi/Me/Lo) |
ft3/min (m3/h) |
500(850) / 447(760) / 377(641) |
500(850) / 435(739) / 377(641) |
|||
|
Moisture Removal (High) |
|
Pints/h |
4.89 |
- |
||
|
|
|
|
|
|
|
|
Electrical Rating |
|
|
|
Cooling |
Heating |
||
|
|
|
|
|
|
|
|
|
Available Voltage Range |
|
V |
187 to 253 |
|||
|
Running Amperes |
|
|
A |
0.17 |
0.17 |
|
|
Power Input |
|
|
|
W |
35 |
35 |
|
|
|
|
|
|
|
|
Features |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Control / Temperature Control |
|
|
Microprocessor / I.C. Thermistor |
|||
|
|
|
|
|
|
|
|
|
Control Unit |
|
|
|
|
Wireless Remote Control Unit |
|
|
|
|
|
|
|
|
|
|
Timer |
|
|
|
|
24-Hour ON or OFF Timer, 1-Hour OFF Timer |
|
|
Fan Speeds |
|
|
|
Indoor |
Auto and 3 steps |
|
|
Airflow Direction (Indoor) |
|
Horizontal |
Manual |
|||
|
|
|
|
|
Vertical |
Auto |
|
|
Air Filter |
|
|
|
|
Washable, Anti-Mold |
|
|
Refrigerant |
|
|
|
|
R410A |
|
|
|
|
|
|
|
||
|
Operation Sound |
Indoor : Hi/Me/Lo/Qt* |
dB-A |
41 / 38 / 34 / 28 |
40 / 37 / 34 / 28 |
||
|
(*Qt = Quiet mode) |
|
|
|
|
|
|
|
Refrigerant Tubing Connections |
|
|
Flare Type |
|||
|
Refrigerant |
|
Narrow tube |
|
inch (mm) |
1/4 (6.35) |
|
|
|
|
|
|
|
||
|
Tube Diameter |
Wide tube |
|
inch (mm) |
1/2 (12.7) |
||
|
Refrigerant Tubing Kit |
|
|
|
Optional |
||
|
|
|
|
|
|
|
|
Dimensions & Weight |
|
|
|
|
|
||
|
Unit Dimensions |
Height |
|
inch (mm) |
11-23/32 (298) |
||
|
|
|
Width |
|
inch (mm) |
41-15/16 (1,065) |
|
|
|
|
Depth |
|
inch (mm) |
8-5/8 (219) |
|
|
Package Dimensions |
Height |
|
inch (mm) |
11-27/32 (301) |
||
|
|
|
Width |
|
inch (mm) |
45-1/8 (1,146) |
|
|
|
|
Depth |
|
inch (mm) |
15-5/32 (385) |
|
|
Weight |
|
Net |
|
Ib. (kg) |
26.5 (12.0) |
|
|
|
|
Shipping |
|
Ib. (kg) |
33.1 (15.0) |
|
|
Shipping Volume |
|
|
cu.ft (m3) |
4.59 (0.13) |
||
|
|
|
|
|
|
DATA SUBJECT TO CHANGE WITHOUT NOTICE. |
14
Indoor Unit |
CS-MKE24NKU |
|
|
|
|
||
|
|
|
|
|
|
|
< 230V > |
|
|
|
|
|
|
|
|
Type |
|
|
|
|
Wall Mounted Type Indoor Unit |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Voltage Rating |
|
|
|
|
230V Single-Phase 60Hz |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Performance |
|
|
|
|
Cooling |
Heating |
|
|
|
|
|
|
|
|
|
|
Capacity |
|
|
|
BTU/h |
24,200 |
29,000 |
|
|
|
|
|
kW |
7.10 |
8.50 |
|
Air Circulation (Hi/Me/Lo) |
ft3/min (m3/h) |
541(919) / 500(850) / 435(739) |
541(919) / 488(829) / 435(739) |
|||
|
Moisture Removal (High) |
|
Pints/h |
4.89 |
- |
||
|
|
|
|
|
|
|
|
Electrical Rating |
|
|
|
Cooling |
Heating |
||
|
|
|
|
|
|
|
|
|
Available Voltage Range |
|
V |
187 to 253 |
|||
|
Running Amperes |
|
|
A |
0.20 |
0.20 |
|
|
Power Input |
|
|
|
W |
45 |
45 |
|
|
|
|
|
|
|
|
Features |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Control / Temperature Control |
|
|
Microprocessor / I.C. Thermistor |
|||
|
|
|
|
|
|
|
|
|
Control Unit |
|
|
|
|
Wireless Remote Control Unit |
|
|
|
|
|
|
|
|
|
|
Timer |
|
|
|
|
24-Hour ON or OFF Timer, 1-Hour OFF Timer |
|
|
Fan Speeds |
|
|
|
Indoor |
Auto and 3 steps |
|
|
Airflow Direction (Indoor) |
|
Horizontal |
Manual |
|||
|
|
|
|
|
Vertical |
Auto |
|
|
Air Filter |
|
|
|
|
Washable, Anti-Mold |
|
|
Refrigerant |
|
|
|
|
R410A |
|
|
|
|
|
|
|
||
|
Operation Sound |
Indoor : Hi/Me/Lo/Qt* |
dB-A |
44 / 41 / 38 / 30 |
43 / 40 / 37 / 30 |
||
|
(*Qt = Quiet mode) |
|
|
|
|
|
|
|
Refrigerant Tubing Connections |
|
|
Flare Type |
|||
|
Refrigerant |
|
Narrow tube |
|
inch (mm) |
1/4 (6.35) |
|
|
|
|
|
|
|
||
|
Tube Diameter |
Wide tube |
|
inch (mm) |
5/8 (15.88) |
||
|
Refrigerant Tubing Kit |
|
|
|
Optional |
||
|
|
|
|
|
|
|
|
Dimensions & Weight |
|
|
|
|
|
||
|
Unit Dimensions |
Height |
|
inch (mm) |
11-23/32 (298) |
||
|
|
|
Width |
|
inch (mm) |
41-15/16 (1,065) |
|
|
|
|
Depth |
|
inch (mm) |
8-5/8 (219) |
|
|
Package Dimensions |
Height |
|
inch (mm) |
11-27/32 (301) |
||
|
|
|
Width |
|
inch (mm) |
45-1/8 (1,146) |
|
|
|
|
Depth |
|
inch (mm) |
15-5/32 (385) |
|
|
Weight |
|
Net |
|
Ib. (kg) |
26.5 (12.0) |
|
|
|
|
Shipping |
|
Ib. (kg) |
33.1 (15.0) |
|
|
Shipping Volume |
|
|
cu.ft (m3) |
4.59 (0.13) |
||
|
|
|
|
|
|
DATA SUBJECT TO CHANGE WITHOUT NOTICE. |
15
Indoor Unit |
CS-MKE24NKU |
|
|
|
|
||
|
|
|
|
|
|
|
< 208V > |
|
|
|
|
|
|
|
|
Type |
|
|
|
|
Wall Mounted Type Indoor Unit |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Voltage Rating |
|
|
|
|
208V Single-Phase 60Hz |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Performance |
|
|
|
|
Cooling |
Heating |
|
|
|
|
|
|
|
|
|
|
Capacity |
|
|
|
BTU/h |
24,200 |
29,000 |
|
|
|
|
|
kW |
7.10 |
8.50 |
|
Air Circulation (Hi/Me/Lo) |
ft3/min (m3/h) |
541(919) / 500(850) / 435(739) |
541(919) / 488(829) / 435(739) |
|||
|
Moisture Removal (High) |
|
Pints/h |
4.89 |
- |
||
|
|
|
|
|
|
|
|
Electrical Rating |
|
|
|
Cooling |
Heating |
||
|
|
|
|
|
|
|
|
|
Available Voltage Range |
|
V |
187 to 253 |
|||
|
Running Amperes |
|
|
A |
0.22 |
0.22 |
|
|
Power Input |
|
|
|
W |
45 |
45 |
|
|
|
|
|
|
|
|
Features |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Control / Temperature Control |
|
|
Microprocessor / I.C. Thermistor |
|||
|
|
|
|
|
|
|
|
|
Control Unit |
|
|
|
|
Wireless Remote Control Unit |
|
|
|
|
|
|
|
|
|
|
Timer |
|
|
|
|
24-Hour ON or OFF Timer, 1-Hour OFF Timer |
|
|
Fan Speeds |
|
|
|
Indoor |
Auto and 3 steps |
|
|
Airflow Direction (Indoor) |
|
Horizontal |
Manual |
|||
|
|
|
|
|
Vertical |
Auto |
|
|
Air Filter |
|
|
|
|
Washable, Anti-Mold |
|
|
Refrigerant |
|
|
|
|
R410A |
|
|
|
|
|
|
|
||
|
Operation Sound |
Indoor : Hi/Me/Lo/Qt* |
dB-A |
44 / 41 / 38 / 30 |
43 / 40 / 37 / 30 |
||
|
(*Qt = Quiet mode) |
|
|
|
|
|
|
|
Refrigerant Tubing Connections |
|
|
Flare Type |
|||
|
Refrigerant |
|
Narrow tube |
|
inch (mm) |
1/4 (6.35) |
|
|
|
|
|
|
|
||
|
Tube Diameter |
Wide tube |
|
inch (mm) |
5/8 (15.88) |
||
|
Refrigerant Tubing Kit |
|
|
|
Optional |
||
|
|
|
|
|
|
|
|
Dimensions & Weight |
|
|
|
|
|
||
|
Unit Dimensions |
Height |
|
inch (mm) |
11-23/32 (298) |
||
|
|
|
Width |
|
inch (mm) |
41-15/16 (1,065) |
|
|
|
|
Depth |
|
inch (mm) |
8-5/8 (219) |
|
|
Package Dimensions |
Height |
|
inch (mm) |
11-27/32 (301) |
||
|
|
|
Width |
|
inch (mm) |
45-1/8 (1,146) |
|
|
|
|
Depth |
|
inch (mm) |
15-5/32 (385) |
|
|
Weight |
|
Net |
|
Ib. (kg) |
26.5 (12.0) |
|
|
|
|
Shipping |
|
Ib. (kg) |
33.1 (15.0) |
|
|
Shipping Volume |
|
|
cu.ft (m3) |
4.59 (0.13) |
||
|
|
|
|
|
|
DATA SUBJECT TO CHANGE WITHOUT NOTICE. |
16
2-2-1. Indoor Unit
Indoor Unit |
CS-MKE7NKU |
|
|
|
|
|
|
|
|
|
|
Control PCB |
|
|
|
|
|
|
|
|
|
|
|
|
Part No. |
|
|
|
CB-CS-MKE7NKU |
|
Controls |
|
|
|
Microprocessor |
|
Control Circuit Fuse |
|
|
250V 3A |
|
|
|
|
|
|
|
Fan |
|
|
|
|
|
|
|
|
|
|
|
|
Type |
|
|
|
Cross-Flow |
|
Q'ty ... Dia. and Length |
inch (mm) |
1 ... D3-5/8 / L24-31/32 (D92/L634) |
||
|
|
|
|
|
|
Fan Motor |
|
|
|
|
|
|
|
|
|
|
|
|
Type |
|
|
|
DC Motor |
|
Model ... Q'ty |
|
|
SIC-41CVJ-D847-4 ... 1 |
|
|
No. of Poles |
|
|
8 |
|
|
Rough Measure RPM (Cool / Heat) |
|
|
1,050 / 1,100 |
|
|
Nominal Output |
|
W |
47 |
|
|
Coil Resistance |
|
Ohm |
- |
|
|
(Ambient Temp. 68 °F (20 °C)) |
|
|
|
|
|
Safety Device |
|
|
|
|
|
|
Type |
|
|
Internal Controller |
|
|
Over-Current Protection |
|
|
Yes |
|
|
Over-Heat Protection |
|
|
Yes |
|
Run Capacitor |
|
Micro F |
- |
|
|
|
|
|
VAC |
- |
|
|
|
|
|
|
Flap Motor |
|
|
|
|
|
|
|
|
|
|
|
|
Type |
|
|
|
Stepping Motor |
|
Model |
|
|
|
MP24Z3 |
|
Rating |
|
|
|
DC 12V |
|
Coil Resistance |
|
Ohm |
Each Pair of Terminal : 400 +/- 7% |
|
|
(Ambient Temp. 77 °F (25 °C)) |
|
|
|
|
|
|
|
|
||
Heat Exchanger Coil |
|
|
|
||
|
|
|
|
|
|
|
Coil |
|
|
|
Aluminum Plate Fin / Copper Tube |
|
Rows |
|
|
|
2 |
|
Fins per inch |
|
|
19.5 |
|
|
Face Area |
|
ft2 (m2) |
2.02 (0.188) |
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
17
Indoor Unit |
CS-MKE9NKU |
|
|
|
|
|
|
|
|
|
|
Control PCB |
|
|
|
|
|
|
|
|
|
|
|
|
Part No. |
|
|
|
CB-CS-MKE9NKU |
|
Controls |
|
|
|
Microprocessor |
|
Control Circuit Fuse |
|
|
250V 3A |
|
|
|
|
|
|
|
Fan |
|
|
|
|
|
|
|
|
|
|
|
|
Type |
|
|
|
Cross-Flow |
|
Q'ty ... Dia. and Length |
inch (mm) |
1 ... D3-5/8 / L24-31/32 (D92/L634) |
||
|
|
|
|
|
|
Fan Motor |
|
|
|
|
|
|
|
|
|
|
|
|
Type |
|
|
|
DC Motor |
|
Model ... Q'ty |
|
|
SIC-41CVJ-D847-4 ... 1 |
|
|
No. of Poles |
|
|
8 |
|
|
Rough Measure RPM (Cool / Heat) |
|
|
1,100 / 1,150 |
|
|
Nominal Output |
|
W |
47 |
|
|
Coil Resistance |
|
Ohm |
- |
|
|
(Ambient Temp. 68 °F (20 °C)) |
|
|
|
|
|
Safety Device |
|
|
|
|
|
|
Type |
|
|
Internal Controller |
|
|
Over-Current Protection |
|
|
Yes |
|
|
Over-Heat Protection |
|
|
Yes |
|
Run Capacitor |
|
Micro F |
- |
|
|
|
|
|
VAC |
- |
|
|
|
|
|
|
Flap Motor |
|
|
|
|
|
|
|
|
|
|
|
|
Type |
|
|
|
Stepping Motor |
|
Model |
|
|
|
MP24Z3 |
|
Rating |
|
|
|
DC 12V |
|
Coil Resistance |
|
Ohm |
Each Pair of Terminal : 400 +/- 7% |
|
|
(Ambient Temp. 77 °F (25 °C)) |
|
|
|
|
|
|
|
|
||
Heat Exchanger Coil |
|
|
|
||
|
|
|
|
|
|
|
Coil |
|
|
|
Aluminum Plate Fin / Copper Tube |
|
Rows |
|
|
|
2 |
|
Fins per inch |
|
|
19.5 |
|
|
Face Area |
|
ft2 (m2) |
2.02 (0.188) |
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
18
Indoor Unit |
CS-MKE12NKU |
|
|
|
|
|
|
|
|
|
|
Control PCB |
|
|
|
|
|
|
|
|
|
|
|
|
Part No. |
|
|
|
CB-CS-MKE12NKU |
|
Controls |
|
|
|
Microprocessor |
|
Control Circuit Fuse |
|
|
250V 3A |
|
|
|
|
|
|
|
Fan |
|
|
|
|
|
|
|
|
|
|
|
|
Type |
|
|
|
Cross-Flow |
|
Q'ty ... Dia. and Length |
inch (mm) |
1 ... D3-5/8 / L24-31/32 (D92/L634) |
||
|
|
|
|
|
|
Fan Motor |
|
|
|
|
|
|
|
|
|
|
|
|
Type |
|
|
|
DC Motor |
|
Model ... Q'ty |
|
|
SIC-41CVJ-D847-4 ... 1 |
|
|
No. of Poles |
|
|
8 |
|
|
Rough Measure RPM (Cool / Heat) |
|
|
1,200 / 1,200 |
|
|
Nominal Output |
|
W |
47 |
|
|
Coil Resistance |
|
Ohm |
- |
|
|
(Ambient Temp. 68 °F (20 °C)) |
|
|
|
|
|
Safety Device |
|
|
|
|
|
|
Type |
|
|
Internal Controller |
|
|
Over-Current Protection |
|
|
Yes |
|
|
Over-Heat Protection |
|
|
Yes |
|
Run Capacitor |
|
Micro F |
- |
|
|
|
|
|
VAC |
- |
|
|
|
|
|
|
Flap Motor |
|
|
|
|
|
|
|
|
|
|
|
|
Type |
|
|
|
Stepping Motor |
|
Model |
|
|
|
MP24Z3 |
|
Rating |
|
|
|
DC 12V |
|
Coil Resistance |
|
Ohm |
Each Pair of Terminal : 400 +/- 7% |
|
|
(Ambient Temp. 77 °F (25 °C)) |
|
|
|
|
|
|
|
|
||
Heat Exchanger Coil |
|
|
|
||
|
|
|
|
|
|
|
Coil |
|
|
|
Aluminum Plate Fin / Copper Tube |
|
Rows |
|
|
|
2 |
|
Fins per inch |
|
|
19.5 |
|
|
Face Area |
|
ft2 (m2) |
2.02 (0.188) |
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
19
Indoor Unit |
CS-MKE18NKU |
|
|
|
|
|
|
|
|
|
|
Control PCB |
|
|
|
|
|
|
|
|
|
|
|
|
Part No. |
|
|
|
CB-CS-MKE18NKU |
|
Controls |
|
|
|
Microprocessor |
|
Control Circuit Fuse |
|
|
250V 3A |
|
|
|
|
|
|
|
Fan |
|
|
|
|
|
|
|
|
|
|
|
|
Type |
|
|
|
Cross-Flow |
|
Q'ty ... Dia. and Length |
inch (mm) |
1 ... D3-5/8 / L33-9/32 (D92/L845) |
||
|
|
|
|
|
|
Fan Motor |
|
|
|
|
|
|
|
|
|
|
|
|
Type |
|
|
|
DC Motor |
|
Model ... Q'ty |
|
|
SIC-41CVJ-D847-3 ... 1 |
|
|
No. of Poles |
|
|
8 |
|
|
Rough Measure RPM (Cool / Heat) |
|
|
1,200 / 1,200 |
|
|
Nominal Output |
|
W |
30 |
|
|
Coil Resistance |
|
Ohm |
- |
|
|
(Ambient Temp. 68 °F (20 °C)) |
|
|
|
|
|
Safety Device |
|
|
|
|
|
|
Type |
|
|
Internal Controller |
|
|
Over-Current Protection |
|
|
Yes |
|
|
Over-Heat Protection |
|
|
Yes |
|
Run Capacitor |
|
Micro F |
- |
|
|
|
|
|
VAC |
- |
|
|
|
|
|
|
Flap Motor |
|
|
|
|
|
|
|
|
|
|
|
|
Type |
|
|
|
Stepping Motor |
|
Model |
|
|
|
MP24Z3 |
|
Rating |
|
|
|
DC 12V |
|
Coil Resistance |
|
Ohm |
Each Pair of Terminal : 400 +/- 7% |
|
|
(Ambient Temp. 77 °F (25 °C)) |
|
|
|
|
|
|
|
|
||
Heat Exchanger Coil |
|
|
|
||
|
|
|
|
|
|
|
Coil |
|
|
|
Aluminum Plate Fin / Copper Tube |
|
Rows |
|
|
|
2 |
|
Fins per inch |
|
|
19.5 |
|
|
Face Area |
|
ft2 (m2) |
3.07 (0.285) |
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
20
Indoor Unit |
CS-MKE24NKU |
|
|
|
|
|
|
|
|
|
|
Control PCB |
|
|
|
|
|
|
|
|
|
|
|
|
Part No. |
|
|
|
CB-CS-MKE24NKU |
|
Controls |
|
|
|
Microprocessor |
|
Control Circuit Fuse |
|
|
250V 3A |
|
|
|
|
|
|
|
Fan |
|
|
|
|
|
|
|
|
|
|
|
|
Type |
|
|
|
Cross-Flow |
|
Q'ty ... Dia. and Length |
inch (mm) |
1 ... D3-5/8 / L33-9/32 (D92/L845) |
||
|
|
|
|
|
|
Fan Motor |
|
|
|
|
|
|
|
|
|
|
|
|
Type |
|
|
|
DC Motor |
|
Model ... Q'ty |
|
|
SIC-41CVJ-D847-3 ... 1 |
|
|
No. of Poles |
|
|
8 |
|
|
Rough Measure RPM (Cool / Heat) |
|
|
1,300 / 1,300 |
|
|
Nominal Output |
|
W |
30 |
|
|
Coil Resistance |
|
Ohm |
- |
|
|
(Ambient Temp. 68 °F (20 °C)) |
|
|
|
|
|
Safety Device |
|
|
|
|
|
|
Type |
|
|
Internal Controller |
|
|
Over-Current Protection |
|
|
Yes |
|
|
Over-Heat Protection |
|
|
Yes |
|
Run Capacitor |
|
Micro F |
- |
|
|
|
|
|
VAC |
- |
|
|
|
|
|
|
Flap Motor |
|
|
|
|
|
|
|
|
|
|
|
|
Type |
|
|
|
Stepping Motor |
|
Model |
|
|
|
MP24Z3 |
|
Rating |
|
|
|
DC 12V |
|
Coil Resistance |
|
Ohm |
Each Pair of Terminal : 400 +/- 7% |
|
|
(Ambient Temp. 77 °F (25 °C)) |
|
|
|
|
|
|
|
|
||
Heat Exchanger Coil |
|
|
|
||
|
|
|
|
|
|
|
Coil |
|
|
|
Aluminum Plate Fin / Copper Tube |
|
Rows |
|
|
|
2 |
|
Fins per inch |
|
|
19.5 |
|
|
Face Area |
|
ft2 (m2) |
3.07 (0.285) |
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
21
|
Model No. |
|
Quantity of Sensor |
|
|
|||
Sensor Name |
|
|
|
|
|
|
||
of sensor |
CS-MKE7NKU |
CS-MKE9NKU |
CS-MKE12NKU |
CS-MKE18NKU |
CS-MKE24NKU |
|||
|
||||||||
|
|
|||||||
|
|
|
|
|
|
|
|
|
|
PTM-D51H- |
1 |
1 |
1 |
|
0 |
0 |
|
|
S4-1 TH2 |
|
||||||
Indoor air temp sensor |
|
|
|
|
|
|
||
PTM-D51H- |
0 |
0 |
0 |
|
1 |
1 |
||
|
|
|||||||
|
S4-2 TH2 |
|
||||||
|
|
|
|
|
|
|
Resistance (k ohm)
10 |
|
|
|
|
|
|
|
9 |
|
|
|
|
|
|
|
8 |
|
|
|
|
|
|
|
7 |
|
|
|
|
|
|
|
6 |
|
|
|
|
|
|
|
5 |
|
|
|
|
|
|
|
4 |
|
|
|
|
|
|
|
3 |
|
|
|
|
|
|
|
2 |
|
|
|
|
|
|
|
1 |
|
|
|
|
|
|
|
0 |
50 |
59 |
68 |
77 |
86 |
95 |
104 |
|
|||||||
|
(10) |
(15) |
(20) |
(25) |
(30) |
(35) |
(40) |
Temperature °F (°C)
|
Model No. |
|
Quantity of Sensor |
|
|
|||
Sensor Name |
|
|
|
|
|
|
||
of sensor |
CS-MKE7NKU |
CS-MKE9NKU |
CS-MKE12NKU |
CS-MKE18NKU |
CS-MKE24NKU |
|||
|
||||||||
|
|
|||||||
|
|
|
|
|
|
|
|
|
|
PTM-D51H- |
1 |
1 |
1 |
|
0 |
0 |
|
|
S4-1 TH1 |
|
||||||
Indoor heat exchanger sensor |
|
|
|
|
|
|
||
PTM-D51H- |
0 |
0 |
0 |
|
1 |
1 |
||
|
|
|||||||
|
S4-2 TH1 |
|
||||||
|
|
|
|
|
|
|
Resistance (k ohm)
200 |
|
|
|
|
180 |
|
|
|
|
160 |
|
|
|
|
140 |
|
|
|
|
120 |
|
|
|
|
100 |
|
|
|
|
80 |
|
|
|
|
60 |
|
|
|
|
40 |
|
|
|
|
20 |
|
|
|
|
0 |
50 |
68 |
86 |
104 122 140 158 176 194 |
32 |
||||
(0) |
(10) (20) (30) (40) (50) (60) (70) (80) (90) |
Temperature °F (°C)
22
Indoor Unit CS-MKE7NKU
CS-MKE9NKU
CS-MKE12NKU
Unit: inch(mm) (852-0-0010-215-00-0)
23
Indoor Unit CS-MKE18NKU
CS-MKE24NKU
Unit: inch(mm) (852-0-0010-216-00-0)
24
Indoor Unit CS-MKE7NKU
CS-MKE9NKU
CS-MKE12NKU
Indoor unit
O.D. 3/8" (9.52 mm)
Indoor heat exchanger
O.D. 1/4" (6.35 mm)
Indoor Unit CS-MKE18NKU
Indoor unit
O.D. 1/2" (12.7 mm)
Indoor heat exchanger
Cooling cycle Heating cycle
O.D. 1/4" (6.35 mm)
Cooling cycle
Heating cycle
Indoor Unit CS-MKE24NKU
Indoor unit
O.D. 5/8" (15.88 mm)
Indoor heat exchanger
O.D. 1/4" (6.35 mm)
Cooling cycle
Heating cycle
25
Indoor Unit CS-MKE7NKU
Room air temp.:80°F (26.7°C)
Cooling
Fan speed:High
Horizontal distance (ft.)
|
|
0 |
5 |
10 |
|
15 |
20 |
25 |
30 |
|
|
0 |
|
|
|
|
|
|
|
velocity (ft./sec.) |
distance (ft.) |
5 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
Axis air |
Vertical |
10 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
15 |
|
|
|
|
|
|
|
|
|
|
|
: Flap angle 0° |
, |
|
: Axis air velocity 0° |
|
|
|
|
|
|
: Flap angle 30° , |
|
: Axis air velocity 30° |
|
|
Room air temp.:70°F (21.1°C)
Heating
Fan speed:High
Horizontal distance (ft.)
|
|
0 |
5 |
10 |
|
15 |
20 |
25 |
30 |
|
|
0 |
|
|
|
|
|
|
|
velocity (ft./sec.) |
distance (ft.) |
5 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
Axis air |
Vertical |
10 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
15 |
|
|
|
|
|
|
|
|
|
|
|
: Flap angle 45° |
, |
|
: Axis air velocity 45° |
|
|
|
|
|
|
: Flap angle 60° |
, |
|
: Axis air velocity 60° |
|
|
|
|
|
|
|
|
26 |
|
|
|
Indoor Unit CS-MKE9NKU
Room air temp.:80°F (26.7°C)
Cooling
Fan speed:High
Horizontal distance (ft.)
|
|
0 |
5 |
10 |
|
15 |
20 |
25 |
30 |
|
|
0 |
|
|
|
|
|
|
|
velocity (ft./sec.) |
distance (ft.) |
5 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
Axis air |
Vertical |
10 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
15 |
|
: Flap angle 0° |
|
|
: Axis air velocity 0° |
|
|
|
|
|
|
, |
|
|
|
||
|
|
|
|
: Flap angle 30° , |
|
: Axis air velocity 30° |
|
|
Room air temp.:70°F (21.1°C)
Heating
Fan speed:High
Horizontal distance (ft.)
|
|
0 |
5 |
10 |
|
15 |
20 |
25 |
30 |
|
|
0 |
|
|
|
|
|
|
|
velocity (ft./sec.) |
distance (ft.) |
5 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
Axis air |
Vertical |
10 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
15 |
|
: Flap angle 45° |
|
|
: Axis air velocity 45° |
|
|
|
|
|
|
, |
|
|
|
||
|
|
|
|
: Flap angle 60° |
, |
|
: Axis air velocity 60° |
|
|
|
|
|
|
|
|
27 |
|
|
|
Indoor Unit CS-MKE12NKU
Room air temp.:80°F (26.7°C)
Cooling
Fan speed:High
Horizontal distance (ft.)
|
|
0 |
5 |
10 |
|
15 |
20 |
25 |
30 |
|
|
0 |
|
|
|
|
|
|
|
velocity (ft./sec.) |
distance (ft.) |
5 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
Axis air |
Vertical |
10 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
15 |
|
: Flap angle 0° |
|
|
: Axis air velocity 0° |
|
|
|
|
|
|
, |
|
|
|
||
|
|
|
|
: Flap angle 30° , |
|
: Axis air velocity 30° |
|
|
Room air temp.:70°F (21.1°C)
Heating
Fan speed:High
Horizontal distance (ft.)
|
|
0 |
5 |
10 |
|
15 |
20 |
25 |
30 |
|
|
0 |
|
|
|
|
|
|
|
velocity (ft./sec.) |
distance (ft.) |
5 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
Axis air |
Vertical |
10 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
15 |
|
: Flap angle 45° |
|
|
: Axis air velocity 45° |
|
|
|
|
|
|
, |
|
|
|
||
|
|
|
|
: Flap angle 60° |
, |
|
: Axis air velocity 60° |
|
|
|
|
|
|
|
|
28 |
|
|
|
Indoor Unit CS-MKE18NKU
Room air temp.:80°F (26.7°C)
Cooling
Fan speed:High
Horizontal distance (ft.)
|
|
0 |
5 |
10 |
|
15 |
20 |
25 |
30 |
|
|
0 |
|
|
|
|
|
|
|
velocity (ft./sec.) |
distance (ft.) |
5 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
Axis air |
Vertical |
10 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
15 |
|
: Flap angle 0° |
|
|
: Axis air velocity 0° |
|
|
|
|
|
|
, |
|
|
|
||
|
|
|
|
: Flap angle 30° , |
|
: Axis air velocity 30° |
|
|
Room air temp.:70°F (21.1°C)
Heating
Fan speed:High
Horizontal distance (ft.)
|
|
0 |
5 |
10 |
|
15 |
20 |
25 |
30 |
|
|
0 |
|
|
|
|
|
|
|
velocity (ft./sec.) |
distance (ft.) |
5 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
Axis air |
Vertical |
10 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
15 |
|
|
|
|
|
|
|
|
|
|
|
: Flap angle 45° |
, |
|
: Axis air velocity 45° |
|
|
|
|
|
|
: Flap angle 60° |
, |
|
: Axis air velocity 60° |
|
|
|
|
|
|
|
|
29 |
|
|
|
Indoor Unit CS-MKE24NKU
Room air temp.:80°F (26.7°C)
Cooling
Fan speed:High
Horizontal distance (ft.)
|
|
0 |
5 |
10 |
|
15 |
20 |
25 |
30 |
|
|
0 |
|
|
|
|
|
|
|
velocity (ft./sec.) |
distance (ft.) |
5 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
Axis air |
Vertical |
10 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
15 |
|
: Flap angle 0° |
, |
|
: Axis air velocity 0° |
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
: Flap angle 30° , |
|
: Axis air velocity 30° |
|
|
Room air temp.:70°F (21.1°C)
Heating
Fan speed:High
Horizontal distance (ft.)
|
|
0 |
5 |
10 |
|
15 |
20 |
25 |
30 |
|
|
0 |
|
|
|
|
|
|
|
velocity (ft./sec.) |
distance (ft.) |
5 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
Axis air |
Vertical |
10 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
15 |
|
: Flap angle 45° |
|
|
: Axis air velocity 45° |
|
|
|
|
|
|
, |
|
|
|
||
|
|
|
|
: Flap angle 60° |
, |
|
: Axis air velocity 60° |
|
|
|
|
|
|
|
|
30 |
|
|
|