MINIATURE RELAY FOR |
HJ-RELAYS |
WIDER APPLICATIONS |
FEATURES |
TYPICAL APPLICATIONS |
• 2 contact arrangements |
Control panels |
4 Form C (for 5 A 250 V AC), |
Power supply units |
2 Form C (for 7 A 250 V AC) |
Molding machines |
• Excellent contact reliability by Au |
Machine tools |
plating |
Welding equipment |
• Environmentally friendly Cd-free |
Agricultural equipment |
contacts |
Office equipment |
• Coil breakdown detection function |
Vending machines |
(AC type with LED only) |
Communications equipment |
• Convenient Screw terminal sockets |
Amusement machines |
with finger protection also available |
|
• Test button type available |
|
• Built-in diode and CR for surge |
|
suppression type available |
|
ORDERING INFORMATION
Ex. HJ
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Contact arrangement |
Operation indication |
|
|
Test button |
|
|
|
Coil voltage |
Surge suppression |
Contact surface |
||||||||||||||||||||||||
2: 2 Form C |
Nil: Without LED indication |
Nil: Without test button |
|
AC 12, 24, 48, 100, 120, |
Nil: Without |
Nil: Without |
||||||||||||||||||||||||||||
4: 4 Form C |
L: With LED indication |
T: With test button |
|
|
200, 220/240 V |
D: |
With diode |
6: With Au plating |
||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
DC 12, 24, 48, 110 V |
R: |
With CR |
|
|
|
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
SPECIFICATIONS
Contacts
Arrangement |
|
2 Form C |
4 Form C |
||
Initial contact resistance, max. |
50mΩ |
||||
(By voltage drop 6 V DC 1 A) |
|||||
|
|
||||
|
|
|
Au plating Silver alloy |
||
Contact material |
(Au plating type) |
||||
Silver alloy |
|||||
|
|
|
|||
|
|
|
(without Au plating type) |
||
|
|
Nominal switching |
7A 250V AC |
5A 250V AC |
|
|
|
capacity |
|||
|
|
|
|
||
Rating |
|
Max. switching power |
1,750 VA |
1,250 VA |
|
(resistive |
|
Max. switching voltage |
250 V AC |
||
load) |
|
||||
|
|
Max. switching current |
7 A |
5 A |
|
|
|
Min. switching current*9 |
1 V |
1 mA |
|
|
|
Mechanical (at 180 cpm) |
2 × 107 |
||
Expected |
|
|
105 |
105 |
|
life (min. |
|
Electrical (at 20 cpm) |
(7A 250 V AC) |
(5A 250 V AC) |
|
operations) |
|
(resistive load) |
5 × 105 |
2 × 105 |
|
|
|
|
(5A 250 V AC) |
(3A 250 V AC) |
Coil
Nominal operating power |
0.9W 1.2V A |
|
Remarks |
|
|
* |
Specifications will vary with foreign standards certification ratings. |
|
*1 |
Measurement at same location as “Initial breakdown voltage” section |
|
*2 |
Detection current: 10mA |
|
*3 Excluding contact bounce time
*4 For the AC coil types, the operate/release time will differ depending on the phase. *5 Half-wave pulse of sine wave: 11ms; detection time: 10 s
*6 Half-wave pulse of sine wave: 6ms *7 Detection time: 10 s
*8 Refer to 4. Conditions for operation, transport and storage mentioned in NOTES *9 This value can change due to the switching frequency, environmental conditions and desired reliability level, therefore it is recommended to check this with the
actual load.
Characteristics
|
|
|
|
2 Form C |
4 Form C |
|
Max. operating speed |
|
20 cpm (at max. rating) |
||||
Initial insulation resistance*1 |
Min. 100 MΩ at 500 V DC |
|||||
|
Between open |
1,000 Vrms for 1 min. |
||||
|
contacts |
|||||
|
|
|
||||
Initial breakdown |
Between contact |
2,000 Vrms for 1 min. |
||||
voltage*2 |
sets |
|
||||
|
|
|
||||
|
Between contact |
2,000 Vrms for 1 min. |
||||
|
and coil |
|
||||
|
|
|
|
|||
Operate time*3 (at nominal voltage) |
Max. 20 ms*4 |
|||||
Release time (without diode)*3 |
Max. 20 ms*4 |
|||||
(at nominal voltage) |
|
|||||
Temperature rise, max. (at 70°C) |
60°C |
|||||
(at nominal voltage) |
|
|||||
|
|
|
||||
Shock |
Functional*5 |
Min. 100 m/s2 {10 G} |
||||
resistance |
Destructive*6 |
Min. 1,000 m/s2 {100 G} |
||||
|
Functional*7 |
10 to 55 Hz at double amplitude |
||||
Vibration |
of 1.0 mm |
|||||
|
|
|
||||
resistance |
Destructive |
10 to 55 Hz at double amplitude |
||||
|
of 1.0 mm |
|||||
|
|
|
|
|||
Conditions for operation, |
|
Ambient |
–40°C to +70°C |
|||
transport and storage*8 |
|
temp. |
–40°F to +158°F |
|||
(Not freezing and |
|
|
|
|
|
|
condensing at low |
|
|
Humidity |
5 to 85% R.H. |
||
temperature) |
|
|
|
|
|
|
|
Without |
|
Approx. 31g |
Approx. 32g |
||
Unit weight |
test button |
1.09 oz |
1.13 oz |
|||
Test button |
Approx. 34g |
Approx. 34g |
||||
|
||||||
|
1.20 oz |
1.20 oz |
||||
|
|
|
|
|||
|
|
|
|
|
|
HJ RELAY |
New |
ASCT1B259E ’03.2 |
|
|
1 |
http://www.naisrelay.com/
HJ
TYPES
[Au plating type] |
|
|
|
|
|
|
|
1. Plug-in type |
|
|
|
2. Plug-in type (with LED indication) |
|
||
|
|
|
|
|
|
|
|
Coil voltage |
|
2 Form C |
4 Form C |
|
Coil voltage |
2 Form C |
4 Form C |
|
Part No. |
Part No. |
|
Part No. |
Part No. |
||
|
|
|
|
||||
12V DC |
|
HJ2-DC 12V-6 |
HJ4-DC 12V-6 |
|
12V DC |
HJ2-L-DC 12V-6 |
HJ4-L-DC 12V-6 |
24V DC |
|
HJ2-DC 24V-6 |
HJ4-DC 24V-6 |
|
24V DC |
HJ2-L-DC 24V-6 |
HJ4-L-DC 24V-6 |
48V DC |
|
HJ2-DC 48V-6 |
HJ4-DC 48V-6 |
|
48V DC |
HJ2-L-DC 48V-6 |
HJ4-L-DC 48V-6 |
110V DC |
|
HJ2-DC110V-6 |
HJ4-DC110V-6 |
|
110V DC |
HJ2-L-DC110V-6 |
HJ4-L-DC110V-6 |
12V AC |
|
HJ2-AC 12V-6 |
HJ4-AC 12V-6 |
|
12V AC |
HJ2-L-AC 12V-6 |
HJ4-L-AC 12V-6 |
24V AC |
|
HJ2-AC 24V-6 |
HJ4-AC 24V-6 |
|
24V AC |
HJ2-L-AC 24V-6 |
HJ4-L-AC 24V-6 |
48V AC |
|
HJ2-AC 48V-6 |
HJ4-AC 48V-6 |
|
48V AC |
HJ2-L-AC 48V-6 |
HJ4-L-AC 48V-6 |
100V AC |
|
HJ2-AC100V-6 |
HJ4-AC100V-6 |
|
100V AC |
HJ2-L-AC100V-6 |
HJ4-L-AC100V-6 |
120V AC |
|
HJ2-AC120V-6 |
HJ4-AC120V-6 |
|
120V AC |
HJ2-L-AC120V-6 |
HJ4-L-AC120V-6 |
200V AC |
|
HJ2-AC200V-6 |
HJ4-AC200V-6 |
|
200V AC |
HJ2-L-AC200V-6 |
HJ4-L-AC200V-6 |
220/240V AC |
|
HJ2-AC220/240V-6 |
HJ4-AC220/240V-6 |
|
220/240V AC |
HJ2-L-AC220/240V-6 |
HJ4-L-AC220/240V-6 |
|
|
|
|
|
|
|
|
3. Plug-in type (with diode) |
|
|
4. Plug-in type (with diode and LED indication) |
|||
Coil voltage |
2 Form C |
4 Form C |
|
Coil voltage |
2 Form C |
4 Form C |
Part No. |
Part No. |
|
Part No. |
Part No. |
||
|
|
|
||||
12V DC |
HJ2-DC 12V-D-6 |
HJ4-DC 12V-D-6 |
|
12V DC |
HJ2-L-DC 12V-D-6 |
HJ4-L-DC 12V-D-6 |
24V DC |
HJ2-DC 24V-D-6 |
HJ4-DC 24V-D-6 |
|
24V DC |
HJ2-L-DC 24V-D-6 |
HJ4-L-DC 24V-D-6 |
48V DC |
HJ2-DC 48V-D-6 |
HJ4-DC 48V-D-6 |
|
48V DC |
HJ2-L-DC 48V-D-6 |
HJ4-L-DC 48V-D-6 |
110V DC |
HJ2-DC110V-D-6 |
HJ4-DC110V-D-6 |
|
110V DC |
HJ2-L-DC110V-D-6 |
HJ4-L-DC110V-D-6 |
|
|
|
|
|
|
|
5. Plug-in type (with CR) |
|
|
6. Plug-in type (with CR and LED indication) |
|||
Coil voltage |
2 Form C |
4 Form C |
|
Coil voltage |
2 Form C |
4 Form C |
Part No. |
Part No. |
|
Part No. |
Part No. |
||
|
|
|
||||
100V AC |
HJ2-AC100V-R-6 |
HJ4-AC100V-R-6 |
|
100V AC |
HJ2-L-AC100V-R-6 |
HJ4-L-AC100V-R-6 |
120V AC |
HJ2-AC120V-R-6 |
HJ4-AC120V-R-6 |
|
120V AC |
HJ2-L-AC120V-R-6 |
HJ4-L-AC120V-R-6 |
200V AC |
HJ2-AC200V-R-6 |
HJ4-AC200V-R-6 |
|
200V AC |
HJ2-L-AC200V-R-6 |
HJ4-L-AC200V-R-6 |
220/240V AC |
HJ2-AC220/240V-R-6 |
HJ4-AC220/240V-R-6 |
|
220/240V AC |
HJ2-L-AC220/240V-R-6 |
HJ4-L-AC220/240V-R-6 |
Note) Packing quantity: 20pcs. (Inner carton), 200pcs. (Outer carton)
[Without Au plating type] 1. Plug-in type
Coil voltage |
2 Form C |
4 Form C |
|
Part No. |
Part No. |
||
|
|||
12V DC |
HJ2-DC 12V |
HJ4-DC 12V |
|
24V DC |
HJ2-DC 24V |
HJ4-DC 24V |
|
48V DC |
HJ2-DC 48V |
HJ4-DC 48V |
|
110V DC |
HJ2-DC110V |
HJ4-DC110V |
|
12V AC |
HJ2-AC 12V |
HJ4-AC 12V |
|
24V AC |
HJ2-AC 24V |
HJ4-AC 24V |
|
48V AC |
HJ2-AC 48V |
HJ4-AC 48V |
|
100V AC |
HJ2-AC100V |
HJ4-AC100V |
|
120V AC |
HJ2-AC120V |
HJ4-AC120V |
|
200V AC |
HJ2-AC200V |
HJ4-AC200V |
|
220/240V AC |
HJ2-AC220/240V |
HJ4-AC220/240V |
2. Plug-in type (with LED indication)
Coil voltage |
2 Form C |
4 Form C |
|
Part No. |
Part No. |
||
|
|||
12V DC |
HJ2-L-DC 12V |
HJ4-L-DC 12V |
|
24V DC |
HJ2-L-DC 24V |
HJ4-L-DC 24V |
|
48V DC |
HJ2-L-DC 48V |
HJ4-L-DC 48V |
|
110V DC |
HJ2-L-DC110V |
HJ4-L-DC110V |
|
12V AC |
HJ2-L-AC 12V |
HJ4-L-AC 12V |
|
24V AC |
HJ2-L-AC 24V |
HJ4-L-AC 24V |
|
48V AC |
HJ2-L-AC 48V |
HJ4-L-AC 48V |
|
100V AC |
HJ2-L-AC100V |
HJ4-L-AC100V |
|
120V AC |
HJ2-L-AC120V |
HJ4-L-AC120V |
|
200V AC |
HJ2-L-AC200V |
HJ4-L-AC200V |
|
220/240V AC |
HJ2-L-AC220/240V |
HJ4-L-AC220/240V |
3. Plug-in type (with test button)
Coil voltage |
2 Form C |
4 Form C |
|
Part No. |
Part No. |
||
|
|||
12V DC |
HJ2-T-DC 12V |
HJ4-T-DC 12V |
|
24V DC |
HJ2-T-DC 24V |
HJ4-T-DC 24V |
|
48V DC |
HJ2-T-DC 48V |
HJ4-T-DC 48V |
|
110V DC |
HJ2-T-DC110V |
HJ4-T-DC110V |
|
12V AC |
HJ2-T-AC 12V |
HJ4-T-AC 12V |
|
24V AC |
HJ2-T-AC 24V |
HJ4-T-AC 24V |
|
48V AC |
HJ2-T-AC 48V |
HJ4-T-AC 48V |
|
100V AC |
HJ2-T-AC100V |
HJ4-T-AC100V |
|
120V AC |
HJ2-T-AC120V |
HJ4-T-AC120V |
|
200V AC |
HJ2-T-AC200V |
HJ4-T-AC200V |
|
220/240V AC |
HJ2-T-AC220/240V |
HJ4-T-AC220/240V |
4. Plug-in type (with LED indication and test button)
Coil voltage |
2 Form C |
4 Form C |
|
Part No. |
Part No. |
||
|
|||
12V DC |
HJ2-L-T-DC 12V |
HJ4-L-T-DC 12V |
|
24V DC |
HJ2-L-T-DC 24V |
HJ4-L-T-DC 24V |
|
48V DC |
HJ2-L-T-DC 48V |
HJ4-L-T-DC 48V |
|
110V DC |
HJ2-L-T-DC110V |
HJ4-L-T-DC110V |
|
12V AC |
HJ2-L-T-AC 12V |
HJ4-L-T-AC 12V |
|
24V AC |
HJ2-L-T-AC 24V |
HJ4-L-T-AC 24V |
|
48V AC |
HJ2-L-T-AC 48V |
HJ4-L-T-AC 48V |
|
100V AC |
HJ2-L-T-AC100V |
HJ4-L-T-AC100V |
|
120V AC |
HJ2-L-T-AC120V |
HJ4-L-T-AC120V |
|
200V AC |
HJ2-L-T-AC200V |
HJ4-L-T-AC200V |
|
220/240V AC |
HJ2-L-T-AC220/240V |
HJ4-L-T-AC220/240V |
2
|
|
|
|
|
|
HJ |
5. Plug-in type (with diode) |
|
|
6. Plug-in type (with diode and LED indication) |
|||
|
|
|
|
|
|
|
Coil voltage |
2 Form C |
4 Form C |
|
Coil voltage |
2 Form C |
4 Form C |
Part No. |
Part No. |
|
Part No. |
Part No. |
||
|
|
|
||||
12V DC |
HJ2-DC 12V-D |
HJ4-DC 12V-D |
|
12V DC |
HJ2-L-DC 12V-D |
HJ4-L-DC 12V-D |
24V DC |
HJ2-DC 24V-D |
HJ4-DC 24V-D |
|
24V DC |
HJ2-L-DC 24V-D |
HJ4-L-DC 24V-D |
48V DC |
HJ2-DC 48V-D |
HJ4-DC 48V-D |
|
48V DC |
HJ2-L-DC 48V-D |
HJ4-L-DC 48V-D |
110V DC |
HJ2-DC110V-D |
HJ4-DC110V-D |
|
110V DC |
HJ2-L-DC110V-D |
HJ4-L-DC110V-D |
|
|
|
|
|||
7. Plug-in type (with CR) |
|
|
8. Plug-in type (with CR and LED indication) |
|||
|
|
|
|
|
|
|
Coil voltage |
2 Form C |
4 Form C |
|
Coil voltage |
2 Form C |
4 Form C |
Part No. |
Part No. |
|
Part No. |
Part No. |
||
|
|
|
||||
100V AC |
HJ2-AC100V-R |
HJ4-AC100V-R |
|
100V AC |
HJ2-L-AC100V-R |
HJ4-L-AC100V-R |
120V AC |
HJ2-AC120V-R |
HJ4-AC120V-R |
|
120V AC |
HJ2-L-AC120V-R |
HJ4-L-AC120V-R |
200V AC |
HJ2-AC200V-R |
HJ4-AC200V-R |
|
200V AC |
HJ2-L-AC200V-R |
HJ4-L-AC200V-R |
220/240V AC |
HJ2-AC220/240V-R |
HJ4-AC220/240V-R |
|
220/240V AC |
HJ2-L-AC220/240V-R |
HJ4-L-AC220/240V-R |
Note) Packing quantity: 20pcs. (Inner carton), 200pcs. (Outer carton)
[Accessories]
Type |
No. of channels |
Item |
Part No. |
|
|
2 channels |
HJ2 terminal socket |
HJ2-SFD |
|
|
|
|
||
Terminal socket |
HJ2 terminal socket (Finger protect type) |
HJ2-SFD-S |
||
|
||||
2/4 channels |
HJ4 terminal socket |
HJ4-SFD |
||
|
||||
|
(common) |
HJ4 terminal socket (Finger protect type) |
HJ4-SFD-S |
|
|
|
|
|
Notes) 1. Packing quantity: 10pcs. (Inner carton), 100pcs. (Outer carton)
2.Use the retainer that is shipped with the terminal socket.
3.Products conform to UL, CSA and TÜV, as standard.
4.In order to prevent breakage and disfiguring, the screw tightening torque for the terminal socket should be within the range of 0.5 to 0.8 N•m.
5.When attaching directly to a chassis, please use an M3.5 × 0.6 metric coarse screw thread, a spring washer, and a hexagonal nut.
6.For S1DX timer, use the retainer (Part No. ADX18012).
COIL DATA
DC coils
Coil voltage |
Pick-up voltage, |
Drop-out voltage, |
Nominal coil |
Coil resistance, Ω |
Nominal operating |
Max. allowable |
|
V DC (max.) |
V DC (max.) |
||||||
current, mA |
(at 20°C 68°F) |
power, |
voltage, V DC |
||||
V DC |
(at 20°C 68°F) |
(at 20°C 68°F) |
|||||
(±20%) |
(±20%) |
W (±20%) |
(at 70°C 158°F) |
||||
|
(Initial) |
(Initial) |
|||||
|
|
|
|
|
|||
12 |
9.6 |
1.2 |
75 |
160 (±10%) |
0.9 |
13.2 |
|
24 |
19.2 |
2.4 |
37 |
650 (±10%) |
0.9 |
26.4 |
|
48 |
38.4 |
4.8 |
18 |
2,600 (±15%) |
0.9 |
52.8 |
|
110 |
88 |
11 |
10 |
11,000 (±15%) |
1.1 |
121 |
AC coils (50/60Hz)
|
Pick-up voltage, |
Drop-out voltage, |
Nominal coil current, mA |
Nominal operating power, V A |
Max. allowable |
||||
Coil voltage |
V AC (max.) |
V AC (max.) |
|
(±20%) |
|
(±20%) |
|||
|
|
voltage, V AC |
|||||||
V AC |
(at 20°C 68°F) |
(at 20°C 68°F) |
50Hz |
|
60Hz |
50Hz |
|
60Hz |
(at 70°C 158°F) |
|
(Initial) |
(Initial) |
|
|
|||||
|
|
|
|
|
|
|
|
||
12 |
9.6 |
3.6 |
102.9 |
|
85.4 |
|
|
|
13.2 |
24 |
19.2 |
7.2 |
54.5 |
|
45.6 |
|
|
|
26.4 |
|
|
|
|
|
|
|
|
|
|
48 |
38.4 |
14.4 |
30.7 |
|
25.9 |
Approx. |
|
Approx. |
52.8 |
100 |
80 |
30 |
11.8 |
|
10.0 |
|
110 |
||
|
1.2 to 1.5 |
|
1.0 to 1.3 |
||||||
120 |
96 |
36 |
12.5 |
|
10.3 |
|
132 |
||
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
200 |
160 |
60 |
6.8 |
|
5.7 |
|
|
|
220 |
220/240 |
176 |
72 |
6.8/7.8 |
|
5.6/6.4 |
|
|
|
264 |
3