NAIS AEV25324, AEV25312, AEV25124, AEV25112, AEV25024 Datasheet

...
0 (0)
346
EV-RELAYS
COMPACT BUT CUT OFF DC POWER CURRENT, POWER CAPSULE CONTACT RELAY.
150A 2a 150A 1a
60a 30a
FEATURES
• Small size & light weight: size 1/4, weight 1/2(compared to conventional contactors)
• No arc space is required: size includ­ing arc space 1/9 (compared to con­ventional contactors)
The arc is not exposed to the outside, therefore, no arc space is not required.
• Safety construction
The arc is not exposed, therefore, the contactor is explosion proof and intrinsi­cally safe.
• Quiet: operation noise 1/4 (compared to conventional contactors).
Along with the above-mentioned miniatur­ization, the operation noise has been re­duced to 70dB, and, in addition, the
operation noise remains unchanged when a current of 1000A or more is inter­rupted.
• High contact reliability
The contact part is hermetically sealed with H
2
mixed gas, hence the contact re­sistance remains stable regardless of the ambient conditions.
• Mounting direction is not specified
The weight of the movable parts is light, and also the restoring force is large, hence the contactor is relatively unaffect­ed by gravity.
• Line-up of indicator Type (150A Type only)
A line-up of relays with indicator that can monitor the relay operation.
SPECIFICATIONS
Contact
Characteristics
Type 150A type 60A type 30A type Arrangement 1 Form A, 2 Form A 1 Form A 1 Form A
Rating
Nominal switching capacity (resistive load)
150A 400V DC
60A 400V DC 30A 400V DC
Short term current 300A (10min) (40mm
2
) 120A (15min) (15mm
2
) 60A (5min) (5.5mm
2
)
Max. cut-off current
2,500A 300V DC
(3 cycles)
#1
600A 300V DC
(5 cycles)
Overload opening/closing rating
600A 300V DC
(25 cycles)
120A 400V DC
(50 cycles)
120A 400V DC
(50 cycles)
Contact voltage drop (Max.)
0.1V (When current
(is 150A
per 1)
contact set)
0.1V (When current (is 60A per 1) contact set)
0.2V (When current (is 30A per 1) contact set)
Nominal operating power
35W (Inrush, approx 0.1s)
5W (Stable)
Max. 5W Max. 5W
Expected life (min. operations)
Mechanical
1 Form A: 10
5
2 Form A: 5 × 10
4
10
5
Electrical
150A 400V DC
10
3
L/R
q
1ms
60A 400V DC 10
3
L/R
q
1ms
30A 400V DC 3 × 10
4
L/R
q
1ms
Initial insulation resistance Min. 100 M Ω (at 500 V DC)
*1
Initial breakdown voltage
Between open contacts AC 2,500 Vrms for 1 min.
*2
Between contact and coil AC 2,500 Vrms for 1 min.
*2
Operate time (at 20 ° C) (at nominal voltage) Max. 50ms
*3
Reset time (without diode) (at 20 ° C) (at nominal voltage) Max. 30ms
*4
Shock resistance
Functional Min. 196 m/s
2
{20 G}
*5
Destructive Min. 490 m/s
2
{50 G}
*6
Vibration resistance
Functional 43 m/s
2
{4.4 G} 10 to 200Hz
*7
Destructive 43 m/s
2
{4.4 G} 10 to 200 Hz
*8
Conditions for operation, transport and storage (Not freezing and condensing at low temperature)
Ambient temperature –40 ° C to +80 ° C –40 ° F to +176 ° F
*9
Humidity 5 to 85% R.H.
Unit weight
150 A 1 Form A: 660 g 21.16oz 150 A 2 Form A: 1,100 g 38.80oz
60 A: 330 g 11.64oz 30 A: 310 g 10.93oz
Remarks
* Specifications will vary with foreign standards certification ratings.
*1
Measurement at same location as "Initial breakdown voltage" section.
*2
Detection current: 10mA.
*3
Nominal voltage applied to the coil,excluding bounce time.
*4
Nominal voltage applied to the coil.
*5
Half-wave pulse of sine wave: 11 ms; detection time: 10 µ s.
*6
Half-wave pulse of sine wave: 6 ms.
*7
Detection time: 10 µ s.
*8
3 directions, each 4 hours.
*9
Storage: Max.85 ° C 185 ° F.
Notes:
Same specifications as the 12 V type.
#1
Condition: Nominal switching 100cycles, each cut off 2,500A
EV
347
Indicator ratings
Note:
Indicator type is only available for the 150 A type.
Arrangement 1 Form A 1 Form B Material Gold-clad Rating (resistive load) 0.1 A 30 V DC Contact resistance Max. 100 m M Ω
TYPICAL APPLICATIONS
• Electric Vehicle
• Hybrid Electric Vehicle
ORDERING INFORMATION
Product Name
EV
Contact arrangement Contact rating Coil voltage
1: 1 Form A 2: 2 Form A
3: 30A 5: 150A 6: 60A
0: without indicator contact 1: a contact (150A type only) 3: b contact (150A type only)
Indicator contact
arrangement
12: 12V DC 24: 24V DC
Ex. A EV 1 5 0 12
Packing quantity
Types Inner Outer 150A 2 Form A 1pc. 5pcs. 150A 1 Form A 1pc. 10pcs. 60A 1 Form A 1pc. 20pcs. 30A 1 Form A 1pc. 20pcs.
SPARE PARTS
Installing parts Part No. Packing Quantity M8 nut with washer for 150A type AEV801 2pcs. M5 screw for 60A type AEV802 2pcs. M4 screw for 30A type AEV803 2pcs. Bus bar for 60A type AEV804 1pcs.
TYPES AND COIL DATA (at 20 ° C 68 ° F)
Note:
* Same coil data as Indicator type.
Part No.
Coil voltage,
V DC
Pick-up voltage,
V DC (max.)
Drop-out voltage,
V DC (min.)
Nominal coil current, mA
( ± 10%)
Operating power,
W (12 V DC)
Max. allowable
voltage,
V DC
AEV25012*
12 V DC 9 V DC 1 V DC
2.8 A (at peak)*
35W (Inrush, approx. 0.1S)
5W (Stable)
16 V DC
AEV15012* AEV16012
0.415 A Max. 5W
AEV13012 AEV25024*
24 V DC 18 V DC 2 V DC
1.9 A (at peak)*
35W (Inrush, approx. 0.1S)
Max. 5W (1 Form A) Max. 6W (2 Form A)
32 V DC
AEV15024* 2.2 A (at peak)* AEV16024
0.208 A Max. 5W
AEV13024