Honeywell PS1201A00, PS1202A00, PS2401A00 Installation Manual

0 (0)

PS1201A00, PS1202A00 and PS2401A00 Replacement Power Supplies for Electronic Air Cleaners

INSTALLATION INSTRUCTIONS

APPLICATION

This power supply board has a selectable ionizer current output. Selection of the correct ionizer current is accomplished by moving the P5 shorting bar to the proper position. See table below.

Table 1.

 

 

 

 

 

Output Ionizer

 

Input

 

 

Output

Current (mA)

 

Voltage

Input

 

Ionizer

(Selected by P5

Power

Range

Frequency

Input

Voltage

shorting bar

Supply

(Vac)

(Hz)

Current (A)

(Vdc)

position)

 

 

 

 

 

 

PS1201A00

102-132 Vac

50 / 60

0.4

7500/

2.1/1.65/1.29/1.05*/

 

 

 

 

8150*

0.9/0.25

 

 

 

 

 

 

PS1202A00

102-132 Vac

50 / 60

0.4

7500/

2.1/1.65/1.29/1.05*/

 

 

 

 

8150*

0.9/0.25

 

 

 

 

 

 

PS2401A00

204-264 Vac

50 / 60

0.2

7500/

2.1/1.65/1.29/1.05*/

 

 

 

 

8150*

0.9/0.25

 

 

 

 

 

 

*Default setting.

 

 

 

 

69-2673EFS-01

PS1201A00, PS1202A00 AND PS2401A00 REPLACEMENT POWER SUPPLIES

Table 2.

 

 

 

 

 

 

 

 

Electronic Air Cleaner

 

Nominal Size

Ionizer

Replacement

 

 

 

 

 

 

Current P5

Power Supply

Model

Voltage (Vac)

 

In.

Mm

 

Position (mA)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F50F

120

20

X 12.5

508 X 318

1.05*

PS1201A00

 

 

 

 

 

 

 

 

 

 

16

X 20

406

X 508

1.29

 

 

 

 

 

 

 

 

 

 

16 x 25

406

X 635

1.65

 

 

 

 

 

 

 

 

 

 

20 x 20

508

X 508

1.65

 

 

 

 

 

 

 

 

 

 

20 x 25

508

X 635

2.1

 

 

 

 

 

 

 

 

 

240

20

X 12.5

508 X 318

1.05*

PS2401A00

 

 

 

 

 

 

 

 

 

 

16

X 20

406

X 508

1.29

 

 

 

 

 

 

 

 

 

 

16 x 25

406

X 635

1.65

 

 

 

 

 

 

 

 

 

 

20 x 20

508

X 508

1.65

 

 

 

 

 

 

 

 

 

 

20 x 25

508

X 635

2.1

 

 

 

 

 

 

 

 

F300A,E

120

20

X 12.5

508 X 318

1.05*

PS1201A00

 

 

 

 

 

 

 

 

 

16

X 20

406 X 508

1.29

 

 

 

 

 

 

 

 

 

16 x 25

406 X 635

1.65

 

 

 

 

 

 

 

 

 

20 x 20

508 X 508

1.65

 

 

 

 

 

 

 

 

 

20 x 25

508 X 635

2.1

 

 

 

 

 

 

 

 

F300B

240

20

X 12.5

508 X 318

1.05*

PS2401A00

 

 

 

 

 

 

 

 

*Default setting.

 

 

 

 

 

 

INSTALLATION

When installing this product…

1.Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.

2.Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.

3.Installer must be a trained, experienced service technician.

4.After installation is complete, check out product operation as provided in these instructions.

CAUTION

Electric Shock Hazard. Can cause electrical shock or equipment damage. Disconnect power before installing replacement power supply.

69-2673EFS—01

2

PS1201A00, PS1202A00 AND PS2401A00 REPLACEMENT POWER SUPPLIES

STEP 1:

Remove old power supply and discard.

1

F50

2

 

M16638A

Fig. 1. Example

3

69-2673EFS—01

Honeywell PS1201A00, PS1202A00, PS2401A00 Installation Manual

PS1201A00, PS1202A00 AND PS2401A00 REPLACEMENT POWER SUPPLIES

 

 

OR

3

 

4

5

 

6

7

OR

8

 

 

Fig. 2. Example

69-2673EFS—01

4

PS1201A00, PS1202A00 AND PS2401A00 REPLACEMENT POWER SUPPLIES

STEP 2:

Install new power supply.

BLACK COLLECTOR

 

 

 

 

 

 

 

RED IONIZER

TEST

 

 

 

 

 

 

 

BUTTON

 

 

 

 

 

 

 

T1

RED

BLACK

P3

 

 

 

 

 

CONTACT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BOARD

4

 

 

 

 

 

 

 

BLACK

 

 

 

 

U4

 

 

 

 

BLACK

 

 

2

J8

 

 

 

 

 

7500V

8150V

0.9mA

 

 

 

 

 

 

 

 

 

 

P4

 

 

 

 

P5

 

 

 

 

 

 

 

 

 

0.25mA

 

 

 

7

P8

 

 

6

1.05mA

 

 

 

 

 

1.29mA

 

 

 

J4

 

 

 

 

 

1.65mA

 

 

 

 

 

 

 

 

2.1mA

 

 

 

 

 

 

 

 

POWER SUPPLY

 

 

 

5

 

3

 

 

 

P2

BROWN

 

 

 

 

 

J4

 

 

 

 

R16

 

 

 

 

 

 

J1

 

 

P1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLACK

 

 

 

JUMPER

ORANGE

 

 

 

 

 

 

 

GRAY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VIOLET

 

 

 

1

 

 

 

 

BLACK

 

 

 

 

 

1

INTERLOCK SWITCH.

 

 

 

 

 

 

 

 

 

 

 

 

 

2

SHORTING BAR FOR OZONE REDUCTION.

W4

W2

W1

W3

BLACK

BLACK

 

 

 

 

BLACK

WHITE

3

AIRFLOW SWITCH DISABLE JUMPER, R16.

 

 

 

 

 

 

AIRFLOW SWITCH PLUG, J3.

 

 

 

 

 

 

GREEN

 

 

 

 

 

 

 

 

4

NEON LIGHT.

 

 

 

 

 

 

 

5

 

AIRFLOW SWITCH BOARD

 

 

 

OPTIONAL W8600F AIR CLEANER MONITOR.

 

 

 

 

 

 

GREEN

GROUND CHOKE

6 JUMPER LOCATION FOR IONIZER CURRENT SELECTION.

7 JUMPER LOCATION FOR IONIZER VOLTAGE SELECTION.

M32904A

a.Position the P5 shorting bar for the size air cleaner you have.

b.Wire the power cord ground lead to the ground choke assembly using a wire nut. Secure ground connection to the green ground screw on the wiring compartment barrier.

CHECKOUT

With all components in place, turn on the air cleaner switch and energize the system blower. Check the following operation:

1.Be sure the neon light is on.

2.Turn off the system blower. The neon light should go off.

3.Turn the system blower back on. The neon light should come back on.

4.With the air cleaner energized, push the test button. A snapping sound indicates that collector section is energized.

5.With a multispeed blower, repeat steps 2 through 4.

6.If operation is not as described, refer to Troubleshooting and Service section.

5

69-2673EFS—01

PS1201A00, PS1202A00 AND PS2401A00 REPLACEMENT POWER SUPPLIES

TROUBLESHOOTING AND SERVICE

ELECTRONIC AIR CLEANER TROUBLESHOOTING GUIDE

START

MAKE SURE ELECTRONIC CELLS ARE CLEAN, DRY AND PROPERLY INSTALLED. MAKE SURE METAL PREFILTERS ARE POSITIONED ON THE SIDE WHERE

AIR ENTERS THE AIR CLEANER, AND THAT POST-FILTERS (IF ANY) ARE POSITIONED ON THE SIDE WHERE AIR LEAVES THE AIR CLEANER.

TURN THE POWER SWITCH ON THE AIR CLEANER ON, AND TURN THE HVAC FAN ON.

CHECK THE SYSTEM LIGHT

OFF

PUSH TEST BUTTON ON THE

ON THE AIR CLEANER.

 

 

AIR CLEANER DOOR AND

ON

 

 

 

LISTEN FOR SNAPPING SOUND.

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

TURN OFF AIR CLEANER POWER

PUSH TEST BUTTON ON THE

NO

SWITCH. REMOVE THE DOOR AND

AIR CLEANER DOOR AND

 

 

CHECK THAT THE CONTACTS ON

LISTEN FOR SNAPPING SOUND.

 

 

 

 

THE INSIDE OF THE TEST BUTTON

YES

 

 

 

ARE OK.

 

 

 

 

YES

 

AIR CLEANER IS

 

 

 

FUNCTIONING PROPERLY.

 

 

 

 

 

 

 

 

TO USE THIS CHART:

1.FOLLOW THE STEPS IN ORDER; DO NOT SKIP AROUND.

2.EACH TIME A PROBLEM IS FIXED, GO BACK TO START.

3.REPEAT ALL THE STEPS UNTIL THE AIR CLEANER CHECKS OUT OK.

NOTE: IF A W8600F AIR CLEANER MONITOR IS CONNECTED TO THE AIR CLEANER, DISCONNECT THE AIR CLEANER FROM THE W8600F BEFORE STARTING THIS PROCEDURE. THE W8600F CAN BE CHECKED SEPARATELY. SEE W8600F INSTRUCTION SHEET.

YES

REPLACE LIGHT/SWITCH ASSEMBLY.

NO

REPAIR CONTACTS ON TEST BUTTON.

INSPECT THE CELLS FOR

 

 

— BENT COLLECTOR PLATES

 

 

— BROKEN IONIZER WIRES

 

ON

— DIRT ACCUMULATION ON

 

 

THE INSULATORS

 

 

 

 

— DAMAGED CONTACTS ON

 

 

THE TERMINAL BOARD AT

 

 

THE END OF THE CELL

 

 

 

 

 

YES

NO

 

 

 

REPLACE OR

 

REPAIR CELLS.

 

 

 

 

 

 

 

WITH AN OHMMETER, CHECK

FOR SHORT BETWEEN:

CELL FRAME AND IONIZER WIRES

CELL FRAME AND COLLECTOR BLADES

 

 

 

 

 

 

 

SHORT

 

 

NO

 

 

DETECTED

 

 

SHORT

 

 

 

 

 

 

 

 

 

 

REPLACE

 

CELLS OK.

 

CELLS.

 

REPLACE AIR

 

 

 

 

CLEANER

 

 

 

 

 

 

 

 

POWER SUPPLY.

REMOVE THE CELLS (LEAVE THE

PREFILTERS IN PLACE). CLOSE THE

ACCESS DOOR AND TURN ON THE

AIR CLEANER POWER SWITCH.

CHECK THE SYSTEM LIGHT

ON THE AIR CLEANER.

OFF

WARNING

THIS STEP EXPOSES

DANGEROUSLY HIGH VOLTAGE.

ONLY A QUALIFIED SERVICE

TECHNICIAN SHOULD ATTEMPT

THIS STEP.

CHECK FOR CORRECT INPUT

VOLTAGE ACROSS P1 AND P2 NO FIX WIRING. TERMINALS ON POWER

SUPPLY BOARD.

YES

REPLACE AIR CLEANER

POWER SUPPLY.

THIS AIR CLEANER PRODUCES A TRACE LEVEL OF OZONE AS A BY-PRODUCT OF NORMAL OPERATION, WHICH IS WELL UNDER THE LIMIT PRESCRIBED BY THE U.S. F.D.A. PLEASE REFER TO YOUR OWNERS MANUAL FOR FURTHER INFORMATION. FOR A REPLACEMENT OWNERS MANUAL, CALL 1-800-468-1502 OR VISIT http://yourhome.honeywell.com

WARNING

INCORRECT CONVERSION TO MEDIA AIR CLEANER CAN CAUSE FIRE HAZARD.

WHEN CONVERTING AN ELECTRONIC AIR CLEANER TO A MEDIA AIR CLEANER THE POWER SUPPLY MUST BE REMOVED OR PERMANENTLY DISABLED.

M13656

69-2673EFS—01

6

PS1201A00, PS1202A00 AND PS2401A00 REPLACEMENT POWER SUPPLIES

Use an ohmmeter to check the electronic cells for short circuits.

COLLECTOR

TERMINAL

IONIZER

TERMINAL

COLLECTOR

TERMINAL

M6155A

Modification to Reduce Ozone Odor

CAUTION

Electric Shock Hazard. Can cause personal injury.

Always disconnect power and open access door before opening power supply cover.

The electronic air cleaner generates a small amount of ozone in normal operation. During the first week or two of operation, the amount may be higher because of sharp edges on some of the new high voltage metal parts. Normal use quickly dulls these edges.

If desired, the ozone generated by the air cleaner can be reduced in one of two ways:

1.Install an activated carbon filter downstream from the air cleaner. Make sure particles from the air filter cannot fall into the air cleaner.

2.Move J8 shorting bar. This will reduce ozone production about 20 to 25 percent and reduce efficiency about seven to ten percent, depending on actual airflow delivered by the furnace blower.

a.Unplug or disconnect power supply to the air cleaner.

b.Open the access door.

c.Remove the power box cover.

d.Move J8 shorting bar. See figure below.

7

69-2673EFS—01

PS1201A00, PS1202A00 AND PS2401A00 REPLACEMENT POWER SUPPLIES

P3

J8 SHUNT

J8

P4

IN OZONE

 

REDUCTION

 

POSITION

 

 

J4

J8 IN

NORMAL

POSITION

J3

J1

P2

P1

M32906

Automation and Control Solutions

Honeywell International Inc. 1985 Douglas Drive North Golden Valley, MN 55422 customer.honeywell.com

® U.S. Registered Trademark

© 2013 Honeywell International Inc.

69-2673EFS—01 M.S. 09-13

Printed in United States

Loading...
+ 16 hidden pages