3 Nm Series Spring Return |
20 |
Direct Coupled Actuators |
|
|
|
MS7103, MS7503, MS3103 |
|
INSTALLATION INSTRUCTIONS |
MS7103, MS7503, MS3103 Spring Return Direct Coupled Actuators (DCA) are used within heating, ventilating, and air-conditioning (HVAC) systems. They can drive a variety of quarter-turn, final control elements requiring spring return fail-safe operation.
Applications include:
•Volume control dampers, mounted directly to the drive shaft or remotely (with the use of accessory hardware).
•Quarter-turn rotary valves, such as ball valves mounted directly to the drive shaft.
•Available with cable on all models
•Fast test mode
Models:
See Table 1.
Device Weight:
1.7lbs (0.78 kg)
Ambient Operating Temperature:
-40° to 150°F (-40° to 65°C)
Shipping and Storage Temperature:
-40° to +150°F (-40° to +65°C)
Table 1. Models.
|
|
|
|
|
|
|
|
|
|
|
Control Input / |
SPST |
1/2” |
|
|
|
Driving/ |
|
|
|
Output |
Aux |
360° |
Shaft |
|
|
Holding |
Drive |
|
Model Number |
Description |
Switches |
Conduit |
Adapter |
Torque |
Supply Voltage |
(VA) |
(sec) |
|
MS7103A1021 |
Modulating1 |
No |
|
|
|
|
4/2 |
90 |
|
MS7103A2021 |
Modulating1, |
|
SCSA |
|
|
4/2 |
90 |
||
|
|
|
|
||||||
MS7103A2221 |
Feedback |
Yes |
|
|
|
4/2 |
90 |
||
|
|
|
Yes |
|
|
|
|
|
|
MS7503A2021 |
Modulating2, |
No |
|
|
|
4/2 |
90 |
||
|
|
|
|
|
|
|
|
||
MS7503A2221 |
Yes |
|
|
|
|
4/2 |
90 |
||
|
Floating, 2 Pos, |
|
|
|
|
|
|
|
|
MS7503A2023 |
No |
|
|
|
|
4/2 |
90 |
||
Feedback |
|
|
|
|
|||||
|
|
|
|
|
|
|
|
||
MS7503A2223 |
|
Yes |
|
|
|
|
4/2 |
90 |
|
|
|
|
|
|
|
24 VAC +/-20% @ |
|
|
|
MS7103A2024 |
Modulating1, |
No |
No |
U-Bolt |
|
4/2 |
90 |
||
|
Feedback |
|
27 lb-in |
50/60 Hz Class 2 |
|
|
|||
MS7103A2224 |
Yes |
4/2 |
90 |
||||||
|
|
(3 N) |
Transformer, 24 VDC |
||||||
|
|
|
|
|
|
|
|||
MS3103J1023 |
|
No |
Yes |
|
|
+20%/-10% |
4.5/2 |
30-180 |
|
|
|
|
|
|
|
|
|
||
MS3103J1024 |
|
No |
|
|
|
4.5/2 |
30-180 |
||
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
MS3103J1221 |
|
|
Yes |
SCSA |
|
|
4.5/2 |
30-180 |
|
|
|
|
|
|
|
|
|
||
MS3103J1222 |
Sylk BUS |
Yes |
No |
|
|
4.5/2 |
30-180 |
||
|
|
|
|||||||
|
|
|
|
|
|
|
|||
MS3103J1223 |
Yes |
U-Bolt |
|
|
4.5/2 |
30-180 |
|||
|
|
|
|
||||||
|
|
|
|
|
|
|
|
||
MS3103J1224 |
|
|
No |
|
|
4.5/2 |
30-180 |
||
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
MS3103J1021 |
|
No |
Yes |
SCSA |
|
|
4.5/2 |
30-180 |
|
|
|
|
|
|
|
|
|||
MS3103J1022 |
|
No |
|
|
4.5/2 |
30-180 |
|||
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
12-10 VDC
20(2)-10 VDC, 10-0(2) VDC
31-00141M-06
https:// |
en-US/Pages/department.aspx?cat=HonECC%20Catalog&category=Commercial&catpath=1.1 |
3 NM SERIES SPRING RETURN DIRECT COUPLED ACTUATORS
Humidity Ratings:
5% to 95% R.H., Non-Condensing
Auxiliary Switches (Two SPST):
Fixed switches on 10 and 80 degrees
125 VAC, 1A, res. load
Mounting: Self-Centering Shaft Adapter (shaft coupling):
Round damper shafts: 3/8 to 5/8 in. (9 to 16 mm)
Square damper shafts: 1/4 to 1/2 in. (6 to 13 mm)
Nominal tightening torque for self-centering shaft adapter screw is 106 lb-in (12Nm).
Mounting: Non Self-Centering Shaft Adapter:
Round damper shafts: 1/4 to 3/4 in. (6 to 19 mm)
Square damper shafts: 1/4 to 1/2 in. (6 to 13 mm)
Nominal tightening torque for non self-centering shaft adapter screws is 62 lb-in (7 Nm)
Minimum Damper Shaft Length:
3.25 in. (83 mm) recommended for self-centering shaft adapter
3 in. (75 mm) recommended for non self-centering shaft adapter
Spring Return Timing (at rated load):
< 25 seconds @ -22°F to 150°F (-30°C to 65°C) < 60 seconds @ -40°F to -22°F (-40°C to -30°C)
Cable Specification:
Power Cable: Plenum Rated, 3 ft (0.914 m) length from end of access cover, 18 AWG
Switch Cable: Appliance Rated, 3 ft (0.914 m) length from end of access cover, 18 AWG
3-1/8 (78) |
A |
|
2-7/8 (72) |
||
|
||
B |
|
|
|
6-1/2 |
|
|
(164) |
|
5-3/8 |
|
|
(137) |
7 |
|
|
||
|
(179) |
|
3-17/64 (83) |
M37461 |
Fig. 1. Dimensional drawing of actuator in in. (mm). See Table 2 for A and B dimensions.
Table 2. Shaft Adapters.
|
|
|
|
Type of Shaft Adapter |
A |
B |
|
Self-Centering Adapter |
3.54 in. |
1.54 in. |
|
(90 mm) |
(39 mm) |
||
|
|||
|
|
|
|
Non Self-Centering Adapter |
3.11 in. |
1.57 in.1 |
|
(79 mm) |
(40 mm) |
||
|
|||
|
|
|
1 For 1/2” shaft.
3-1/8 (78) |
A |
|
2-7/8 (72) |
||
|
||
B |
|
|
|
6-1/2 |
|
|
(164) |
|
5-3/8 |
|
|
(137) |
|
|
3-17/64 (83) |
M37351 |
Fig. 2. Dimensional drawing of actuator without conduit in in. (mm). See Table 2 for A and B dimensions.
Stroke:
95° ±3°, mechanically limited.
Approvals:
UL60730
IEC 60730-1 and Part 2–14
UL1097 for Double Insulation
CE Certification Low Voltage Directive 2014/35/EU
CE EMC 2004/108/EC
Switch cables are UL certified only
Waste Electrical and Electronic Equipment (WEEE):
Correct disposal of this product (applicable in the European Union and other European countries with separate collection systems). This product should be disposed of, at the end of its useful life, as per applicable local laws, regulations, and procedures.
Enclosure Ratings:
IP54, depends on position according to “Determine Appropriate Mounting Orientation” on page 3.
NEMA 2
Flame Resistance UL94-5VA
UL2043, switch wiring dependent on conduit installation
Input Impedance:
95 kOhm minimum for analog modulating input.
Feedback Signal:
2-10 VDC, 1 mA source, 0.5 mA sink
31-00141M—06 |
2 |
Noise Rating at 1m Driving (Maximum at 90s drive speed):
Floating/Modulating/Sylk < 40 dB(A)
Spring Return: < 65 dB(A)
Accessories and Ordering Information:
Crank Arm Kit, OS-No. DIAM-CRK-01
Self Centering Shaft Adapter
Anti-Rotation Bracket
3 NM SERIES SPRING RETURN DIRECT COUPLED ACTUATORS
CAUTION
Electrical Shock or Equipment Damage Hazard. Low voltage can shock individuals or short equipment circuitry.
Disconnect power supply before installation.
IMPORTANT
All wiring must comply with applicable codes, ordinances and regulations.
Spring return actuators shall be direct coupled type requiring neither crankarm nor linkage and be capable of direct mounting to a jackshaft of up to 3/4 in. diameter. The actuator shall connect to the shaft using a removable output hub with a self-centering shaft coupling. This coupling shall provide concentric mounting and include an integral adjustable range-stop mechanism.
The actuator shall provide floating and proportional control. Proportional control refers to direct acceptance of 0-10 VDC, 2-10 VDC, or (with addition of a 500 ohm resistor) a 4- 20 mA input signal. Some proportional and floating control models shall provide a feedback signal. Floating actuators shall have a rotation direction control switch accessible on the cover.
All spring return actuators must be designed for either clockwise or counterclockwise fail-safe operation with a continuously engaged mechanical spring. This spring must return the valve or actuator to a fail-safe position within 25 seconds of power loss.
All actuators shall be designed for a minimum of 60,000 fullstroke cycles at rated torque and temperature, 60,000 spring return cycles and 1,500,000 repositions. Run time shall be constant and independent of: load, temperature, and supply voltage (within specifications). All actuators shall be UL60730 and cUL (CSA22.2) listed, have a five year warranty, and be manufactured under ISO 9001 International Quality Control Standards. Actuators shall be as manufactured by Honeywell.
Sylk™ Bus:
Sylk is a two-wire, polarity insensitive bus that provides communications between a Sylk-enabled actuator and a Sylkenabled controller. For wiring, the Sylk-enabled actuator may be mounted up to 200 ft. (61m) from the controller; twisted pair wire is recommended for wire runs longer than 100 ft. (30.5m). Using Sylk-enabled actuators saves I/O on the controller and is faster and cheaper to install since the bus is polarity insensitive.
1.Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.
2.Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3.Installer must be a trained, experienced service technician.
4.After installation is complete, check out product operation as provided in these instructions.
These actuators are designed to mount directly to a damper external drive shaft. The shaft coupling fastens to the drive shaft. The actuator housing includes slots which, along with an anti-rotation bracket, secure the actuator to the damper frame or duct work (see Fig. 10).
NOTES:
—When mounted correctly, these slots allow the actuator to float without rotating relative to the damper shaft.
—Using other brackets or linkages, the actuator can be foot-mounted or tandem-mounted.
CAUTION
Motor Damage Hazard.
Corrosive vapors and acid fumes can damage metal and plastic parts.
Install motor in areas free of acid fumes and other deteriorating vapors.
CAUTION
Equipment Damage Hazard.
Tightly securing actuator to damper housing can damage actuator.
Mount actuator to allow it to float along its vertical axis.
Before mounting the actuator onto the damper shaft, determine the:
—Damper/valve opening direction for correct spring return rotation. The actuator can be mounted to provide clockwise or counterclockwise spring return by flipping or turning the unit over.
—Damper shaft size (see the Specifications section).
Determine Appropriate Mounting
Orientation
The actuators are designed to open a damper by driving the damper shaft in either a clockwise or counterclockwise direction (see Fig. 3).
NOTES:
—Actuators are shipped in the fully closed (spring return) position.
—The groove on the adapter points to a location on the label to indicate the hub rotary position.
3 |
31-00141M—06 |
3 NM SERIES SPRING RETURN DIRECT COUPLED ACTUATORS
CCW TO CLOSE |
CW TO CLOSE |
(FAIL-SAFE POSITION) |
(FAIL-SAFE POSITION) |
CW TO OPEN |
CCW TO OPEN |
DAMPER BLADES
FRONT |
BACK |
M37462 |
Fig. 3. Spring Return DCA mounting orientation.
Measure Damper/Valve Shaft Length
If the shaft is less than 3.25 in. long for SCSA, the shaft coupling must be located between the damper/valve and actuator housing. If the shaft length is more than three inches, the shaft coupling may be located on either side of the actuator housing.
If the coupling must be moved from one side of the actuator to the other, reverse the spring return direction and flip the actuator. Follow these instructions (see Fig. 4):
1.Remove the retainer clip from the shaft coupling and set it aside for later use.
2.Remove shaft coupling from one side of the actuator.
3.Replace the shaft coupling on the opposite side of the actuator aligning it based on the stroke labeling.
4.Replace the retainer clip on the shaft coupling using the groove of the coupling.
To select the control signal simply turn the mode selection dial to the desired mode (as indicated on the device label) without exceeding range indicators.
|
|
MODE SELECT |
|
|
|
1 |
= 2... 10 VDC |
|
|
2 |
= 10... 2 VDC |
5 |
6 |
3 |
= 0... 10 VDC |
4 |
|
4 |
= 10... 0 VDC |
3 |
|
5 |
= FLOATING (FWD) |
2 |
1 |
6 |
= FLOATING (REV) |
|
|
||
|
|
|
M37464 |
Fig. 5. Dials for control signal.
For MS31XX models only
These actuators are available with Sylk address selection pot.
NOTE: There are 5 effective Sylk addresses that you can choose from. For example, to select Sylk address 11 move the range pot to 1.
|
|
ADDRESS SELECT |
|
|
|
1 |
= ADDRESS 11 |
|
|
2 |
= ADDRESS 12 |
5 |
6 |
3 |
= ADDRESS 13 |
4 |
|
4 |
= ADDRESS 14 |
3 |
|
5 |
= ADDRESS 15 |
2 |
1 |
6 |
= TEST |
|
|
Fig. 6. Address selection dial.
Fig. 4. Mounting shaft coupling to actuator opposite side.
Selecting Actuator Control Signal (For MS7503 models only)
Selections are made using a dial that appears on both the front and back of the actuator (see Fig. 5).
Mechanical Stroke Limit Reduction
For applications requiring a span less than 95 degrees, a simple adjustment can be made. When the rotational mounting of the shaft coupling is changed, the actuator drives less than the full 95 degrees stroke.
The stroke is adjustable in 7.5 degree increments. Once adjusted, the actuator drives until the shaft coupling reaches the mechanical stop (part of the housing). The stop causes the motor to discontinue driving and the shaft coupling drives no farther. When the actuator returns, it stops at the fail-safe position. Mechanical limitation of minimum position is prohibited. Use electronic or SW limitation if needed.
To limit the stroke range, proceed as follows:
1.Remove the retainer clip from the shaft coupling and set it aside for later use.
2.Remove shaft coupling from the actuator.
3.Rotate the coupling to the desired position, aligning it based on the stroke labeling. See Fig. 7.
NOTE: The shaft coupling location determines the travel span.
31-00141M—06 |
4 |
3 NM SERIES SPRING RETURN DIRECT COUPLED ACTUATORS
EXAMPLE: Setting shaft coupling to an approximate fail-safe position of 30 degrees (as indicated on the housing) limits stroke to 60 degrees. (See Fig. 7)
4.Install the shaft coupling at this position.
5.Replace the retainer clip on the shaft coupling using the groove of the coupling.
|
|
|
|
0 |
|
|
|
0 |
0 |
|
|
0 |
9 |
|
|
|
|
9 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
D |
45 |
|
45 |
|
|
SP |
|
|
RIVE |
|
|
|
|
|
|
|
|||
|
V |
|
RI |
|
|
|||
|
|
|
|
N |
G |
|
||
SP |
DRI |
E |
|
6 |
0 |
|
RETURN |
|
|
RN |
|
° ST |
|||||
|
|
|
||||||
|
RING RETU |
|
|
|
||||
90° STROKE |
|
|
|
|
|
ROKE |
||
|
|
|
|
|
M37465 |
|||
|
|
|
|
|
|
|
|
3.Remove actuator and mounting bracket.
4.Drill or center-punch holes for mounting screws (or use no.10 self-tapping sheet metal screws).
5.Turn damper blades to desired normal (closed) position.
6.Place actuator and mounting bracket back into position and secure bracket to damper box with sheet metal screws.
7.Using 10 mm wrench, tighten shaft coupling securely onto damper shaft using maximum 106 lbin. (12 Nm) torque.
NOTE: See Fig. 8 for proper mounting to a square damper shaft.
Fig. 7. Stroke reduction.
DAMPER SHAFT |
DAMPER SHAFT |
|
CAUTION
Device Malfunction Hazard.
Improper shaft coupling tightening causes device malfunction.
Tighten shaft coupling with proper torque to prevent damper shaft slippage.
Fig. 8. Proper mounting to square damper shaft.
To achieve ingress protection rating IP54, the actuator needs to be mounted according to Fig. 9. IP54 applies for all mounting positions except with cable-up position (crossed out) Fig. 9.
CAUTION
Actuator Damage Hazard.
Using actuator as shaft bearing causes device damage.
Use actuator only to supply rotational torque. Avoid any side loads to actuator output coupling bearings.
CAUTION
Equipment Damage Hazard.
Can damage the motor beyond repair.
Never turn the motor shaft by hand or with a wrench.
Forcibly turning the motor shaft can damage the gear train.
To mount the actuator to an external drive shaft of a damper, proceed as follows:
1.Place actuator over damper shaft; and hold mounting bracket in place. See Fig. 10.
2.Mark screw holes on damper housing.
CABLE-UP POSITION
IP50
REGULAR POSITIONS
IP54
M37467
Fig. 9. Mounting actuator for IP compliance.
5 |
31-00141M—06 |
3 NM SERIES SPRING RETURN DIRECT COUPLED ACTUATORS
Detail with U-Bolt
1
2
BRACKET
1ENSURE THAT MOUNTING ASSEMBLY PREVENTS ACTUATOR ROTATION AND ALLOWS ACTUATOR TO FLOAT ALONG INDICATED AXIS. WHEN TOO TIGHT, THE RESULTING BINDING CAN DAMAGE THE ACTUATOR OR REDUCE TORQUE OUTPUT.
2THE BRACKET CAN BE BENT TO ALLOW MOUNTING THE ACTUATOR PARALLEL TO THE MOUNTING SURFACE. M37466
Fig. 10. Mounting actuator to damper housing.
CAUTION
Electrical Shock or Equipment Damage Hazard. Disconnect all power supplies before installation.
Motors with auxiliary switches can have more than one disconnect.
IMPORTANT
All wiring must comply with local electrical codes, ordinances and regulations.
|
|
5(' |
|
|
%/$&. |
|
|
:+,7( 25 ə ə |
$&78$725 |
0$,1 |
%52:1 )(('%$&. 25 ə ə |
|
&$%/( |
|
6367 6:,7&+(6 |
|
|
|
|
%/8( |
|
|
%52:1 |
|
|
*5$< |
|
6:,7&+(6 |
%/$&. |
|
&$%/( |
|
Switch operation
Gray/Black = Normally Open. Closed in range 80 degrees to Fully Open.
Blue/Brown = Normally Closed. Open in range 10 degrees to Fully Open.
Table 3. Wiring Details.
|
|
|
|
|
|
|
|
|
|
Wire |
Floating |
Modulating |
Sylk |
||||||
RED |
power |
power |
power |
||||||
|
|
|
|
|
|
|
|
|
|
BLACK |
|
|
|
|
common |
common |
common |
||
|
|||||||||
|
|
|
|
|
|
|
|
|
|
WHITE2 |
0° - 90° |
control signal |
S-bus |
||||||
BROWN |
|
|
90° - 0° |
feedback1 |
S-bus |
||||
|
1Not available on all modulating models, see Table 1.
2Brown for MS3103.
Floating and Modulating Models
|
CLASS 2 |
ACTUATOR |
|
|
|
1 |
RED |
V |
24 VAC |
||
|
BLACK |
|
|
WHITE |
0°-90°/MODULATING |
|
BROWN 90°-0°/FEEDBACK |
|
|
SPDT |
|
|
|
|
|
|
|
|
|
|
|
|
2-10 VDC |
|
|
|
|
|
|
|
|
|
|
|
10-2 VDC |
|
|
|
|
|
|
|
|
|
|
|
|
1 |
LINE VOLTAGE POWER SUPPLY. |
2 |
|
|
|
|
|
|
|
0-10 VDC |
|
|
|
|
|
|
|
|
|||||
|
PROVIDE DISCONNECT MEANS AND |
|
|
|
|
|
|
|
|
|
10-0 VDC |
|
|
|
|
|
|
|
|
|
|
||
|
OVERLOAD PROTECTION AS REQUIRED. |
|
|
|
|
|
|
|
|
|
FLOATING, FWD |
|
|
|
|
|
|
|
|
|
|
||
2 |
SET SWITCH TO FLOATING. |
|
|
|
|
|
|
|
|
|
FLOATING, REV |
|
|
|
|
|
|
|
|
|
|
M37304
Fig. 12. Wiring for SPDT on/off control, MS75.
|
|
CLASS 2 |
|
|
|
|
|
|
|
|
|
|
|
|
ACTUATOR |
|||||||||||||
1 |
|
|
|
|
|
|
|
|
|
|
|
|
1 |
RED |
|
|||||||||||||
|
|
|
|
|
24 VAC |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
V |
||||||
|
|
|
|
|
|
|
|
|
|
|
2 |
BLACK |
|
|
|
|
||||||||||||
|
|
|
||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
3 |
WHITE |
0°-90°/MODULATING |
||||||||||||||||||
|
|
|
|
|||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
4 BROWN |
90°-0°/FEEDBACK |
|||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||
1 LINE VOLTAGE POWER SUPPLY. |
|
|
|
|||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
2-10 VDC |
|||||||||||||||
|
PROVIDE DISCONNECT MEANS AND |
|
|
|
|
|
|
|
|
|
|
|
|
|
10-2 VDC |
|||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||
|
OVERLOAD PROTECTION AS REQUIRED |
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
2 |
|
|
|
|
|
|
|
0-10 VDC |
|||||||||
2 SET SWITCH TO FLOATING. |
|
|
|
|
|
|
|
|
|
|
|
|
|
10-0 VDC |
||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||
|
|
|
|
|
|
|
|
|
FLOATING, FWD |
|||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
FLOATING, REV |
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
M37319 |
Fig. 13. Wiring for floating control, MS75.
Fig. 11. Cable installation details.
31-00141M—06 |
6 |
3 NM SERIES SPRING RETURN DIRECT COUPLED ACTUATORS
|
CLASS 2 |
|
|
ACTUATOR |
|
1 |
24 VAC |
1 RED |
|
||
2 |
|
V |
|||
|
|
2 |
BLACK |
|
|
0/2 TO 10 VDC |
3 |
WHITE |
0°-90°/MODULATING |
||
|
|
|
|||
PROPORTIONING |
4 |
BROWN |
90°-0°/FEEDBACK |
||
CONTROLLER |
|||||
|
|
|
|||
|
– |
|
|
|
+ |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2-10 VDC |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
10-2 VDC |
|
3 |
|
|
|
|
|
|
|
|
|
|
0-10 VDC |
|||||
FEEDBACK |
|
|
|
|
|
|
|
|
10-0 VDC |
|||||||
|
|
|
|
|
|
|
|
|
||||||||
|
|
|
|
|
|
|||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
FLOATING, FWD |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
FLOATING, REV |
1LINE VOLTAGE POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
224 VDC SUPPLY ACCEPTABLE.
3 SET SWITCH TO MODULATING IF AVAILABLE. |
M37320 |
Fig. 14. Wiring for modulating (0/2-10 VDC) proportioning control, MS75 (shown) and MS71.
|
CLASS 2 |
|
|
|
ACTUATOR |
|
1 |
24 VAC |
|
1 |
RED |
|
|
2 |
|
|
V |
|||
|
|
2 |
|
|||
|
|
BLACK |
|
|||
|
|
|
|
|||
4 TO 20 mA |
490 TO 510 |
3 |
WHITE |
0°-90°/MODULATING |
||
|
|
|
||||
PROPORTIONING |
4 |
BROWN |
|
|||
OHMS, |
90°-0°/FEEDBACK |
|||||
CONTROLLER |
||||||
1/2 W |
|
|
|
|||
|
|
|
|
|
||
|
– |
MINIMUM |
|
|
|
|
|
|
|
|
|
+ |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2-10 VDC |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
10-2 VDC |
|
3 |
|
|
|
|
|
|
|
|
|
|
0-10 VDC |
|||||
FEEDBACK |
|
|
|
|
|
|
|
|
|
|
10-0 VDC |
|||||
|
|
|
|
|
|
|||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
FLOATING, FWD |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
FLOATING, REV |
1LINE VOLTAGE POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
224 VDC SUPPLY ACCEPTABLE.
3 SET SWITCH TO MODULATING IF AVAILABLE. |
M37321 |
|
Fig. 15. Wiring for 4-20 mA proportioning controllers, MS75 (shown) and MS71.
CLASS 2
1 |
24 VAC 2 |
|
|
0/2 TO 10 VDC |
|
PROPORTIONING |
|
CONTROLLER |
|
|
– |
|
+ |
|
FEEDBACK |
1LINE VOLTAGE POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
224 VDC SUPPLY ACCEPTABLE.
3SET SWITCH TO MODULATING IF AVAILABLE.
|
|
ACTUATOR |
1 |
RED |
|
2 |
|
V |
BLACK |
|
|
3 |
WHITE |
0°-90°/MODULATING |
4 |
BROWN |
90°-0°/FEEDBACK |
|
|
|
|
|
|
|
2-10 VDC |
||||
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
10-2 VDC |
||||
3 |
|
|
|
|
|
0-10 VDC |
|||||
|
|
|
|
|
|||||||
|
|
|
|
|
10-0 VDC |
||||||
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
FLOATING, FWD |
||||
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
FLOATING, REV |
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ACTUATOR |
|
1 |
RED |
|
|
|
|
|||||
|
2 |
BLACK |
|
|
|
V |
|||||
|
|
|
|||||||||
|
|
|
|
|
|||||||
|
3 |
WHITE |
0°-90°/MODULATING |
||||||||
|
4 |
BROWN |
90°-0°/FEEDBACK |
||||||||
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
2-10 VDC |
||||
|
|
|
|
|
|
|
10-2 VDC |
||||
|
|
|
|
|
|
|
|||||
3 |
|
|
|
|
|
0-10 VDC |
|||||
|
|
|
|
|
|||||||
|
|
|
|
|
|
|
10-0 VDC |
||||
|
|
|
|
|
|
|
FLOATING, FWD
FLOATING, REV
M37322
Fig. 16. Wiring for modulating (0/2-10 VDC) proportioning control operating multiple actuators, MS75 (shown) and MS71.
CLASS 2 |
|
ACTUATOR |
|
|
|
||
24 VAC |
RED |
|
|
|
|
||
|
BLACK |
|
|
CONTROLLER |
BROWN |
S-BUS |
|
HOT |
BROWN |
S-BUS |
|
COM |
|||
|
|
||
S-BUS |
|
|
|
S-BUS |
ADDRESS 11 |
||
|
|||
1 LINE VOLTAGE POWER SUPPLY. |
ADDRESS 12 |
||
ADDRESS 13 |
|||
PROVIDE DISCONNECT MEANS |
|||
AND OVERLOAD |
ADDRESS 14 |
||
ADDRESS 15 |
|||
PROTECTION AS REQUIRED. |
|||
|
TEST |
224 VDC SUPPLY ACCEPTABLE.
3ADDRESS SELECTOR
Fig. 17. Wiring for SYLK BUS control, MS3103.
7 |
31-00141M—06 |
3 NM SERIES SPRING RETURN DIRECT COUPLED ACTUATORS
CLASS 2 |
|
ACTUATOR |
|
|
|
24 VAC |
RED |
|
|
|
|
|
BLACK |
|
CLASS 2 |
BROWN |
S-BUS |
24 VAC |
BROWN |
S-BUS |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ADDRESS 11 |
CONTROLLER |
|
|
|
|
|
|
|
|
|
|
ADDRESS 12 |
|||||
|
|
|
|
|
|
|
|
|
|
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ADDRESS 13 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
HOT |
|
|
|
|
|
|
|
|
|
|
|
|
ADDRESS 14 |
||
|
||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
COM |
|
|
|
|
|
|
|
|
|
|
|
|
|
ADDRESS 15 |
|
|
S-BUS |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
TEST |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
S-BUS |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1LINE VOLTAGE POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
224 VDC SUPPLY ACCEPTABLE.
3ADDRESS SELECTOR
CLASS 2 |
CLASS 2 |
TO ACTUATOR HOT |
TO ACTUATOR HOT |
|
|
|
24 VAC |
|
|
|
|
|
24 VAC |
|
|||||
|
|
|
|
|
|
|
|
|
|||||||
|
|
|
|
COMMON |
< 30 VAC |
|
|
|
|
|
COMMON |
> 30 VAC |
|||
CLASS 2 |
CLASS 2 |
||||||||||||||
|
|
|
|
|
|
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
24 VAC |
|
|
|
|
|
|
|
24 VAC |
|
|
|
|
|
|
|
TO CONTROLLER HOT |
|
|
|
|
TO CONTROLLER HOT |
NOTES: When using two transformers in the installation, make sure you connect the corresponding legs of the secondary windings as Common. Check voltage as shown in the picture and make sure it is lower than 30 VAC. If not, swap the legs of one secondary winding.
Fig. 18. Wiring for SYLK BUS control with separate transformers, MS3103.
The actuator is designed to be used in ventilating and air conditioning installations to operate valves, dampers, ventilation flaps and louvers. (For ratings, see the Specifications section.) If the power fails, the actuator will spring return to the fail safe position.
When using a proportional controller and actuator is set to (0)2 - 10 position, the actuator drives toward its fully open position when the input signal increases; the actuator drives toward the fully closed position when the input
signal decreases. The actuator stops when the input signal reaches the desired proportional control point. This operates in reverse when set to a 10-2(0) position.
IMPORTANT
The actuator is designed to respond to DDC Controller instantaneous contact closures. Take care not to short cycle the actuator. Unstable damper control can cause premature actuator failure.
Fast commissioning mode (modulating control mode and SYLK communication only)
When 24 VAC or 24 VDC signal is applied to the modulating input or on the SYLK communicating actuator the position 6 (TEST) is selected, the actuator will drive to the fully open position with higher speed corresponding to 30 sec timing. When the signal is disconnected, the actuator will drive to the fully closed position with normal operation timing.
CAUTION
Do not use fast test mode for permanent operation.
Lifetime will be reduced if this mode is used permanently. This mode is intended to be used only for initial commissioning/testing of the system after installation. Power consumption is not specified in this mode.
Some models include Auxiliary switches. For wiring details see Fig. 11.
To override the control signal (for freeze protection or similar applications):
1.Override to full open (fast commissioning, drive mode lower than 30 sec):
a.Disconnect the input signal (from terminal 3).
b.Apply 24 VAC to terminal 3.
c.See Fig. 19.
31-00141M—06 |
8 |
3 NM SERIES SPRING RETURN DIRECT COUPLED ACTUATORS
2.Return to full closed:
a.Disconnect the input signal (from terminal 3).
b.See Fig. 20.
|
CLASS 2 |
|
|
ACTUATOR |
|
1 |
24 VAC |
1 |
RED |
V |
|
2 |
|
||||
|
|
|
|||
|
|
2 |
BLACK |
|
|
0/2 TO 10 VDC |
3 |
WHITE |
0°-90°/MODULATING |
||
|
|
|
|||
PROPORTIONING |
4 BROWN 90°-0°/FEEDBACK |
||||
CONTROLLER |
|||||
|
|
|
|||
|
– |
|
|
|
|
|
+ |
|
|
2-10 VDC |
|
|
SPDT |
|
10-2 VDC |
||
|
|
|
0-10 VDC |
||
|
FEEDBACK |
3 |
|
||
|
|
|
10-0 VDC |
||
|
|
|
|
FLOATING, FWD |
|
|
|
|
|
FLOATING, REV |
1LINE VOLTAGE POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
224 VDC SUPPLY ACCEPTABLE.
3 SET SWITCH TO MODULATING IF AVAILABLE. |
M37323 |
Fig. 19. Override to open position.
CLASS 2 |
|
|
ACTUATOR |
|
1 |
24 VAC |
1 |
RED |
|
|
|
V |
||
|
2 |
2 |
|
|
|
BLACK |
|
||
|
|
|
||
0/2 TO 10 VDC |
|
3 |
WHITE |
0°-90°/MODULATING |
|
|
|
|
|
PROPORTIONING |
4 BROWN 90°-0°/FEEDBACK |
|||
CONTROLLER |
|
|||
|
|
|
|
|
– |
|
|
|
|
+ |
|
|
|
2-10 VDC |
SPST |
|
|
10-2 VDC |
|
FEEDBACK |
3 |
|
0-10 VDC |
|
|
|
|
10-0 VDC |
|
|
|
|
|
FLOATING, FWD |
|
|
|
|
FLOATING, REV |
1LINE VOLTAGE POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
224 VDC SUPPLY ACCEPTABLE.
3 SET SWITCH TO MODULATING. |
M37324 |
|
Fig. 20. Return to closed position.
4.Apply control signal for actuator full open or full closed position. (See Fig. 11 and Table 3.)
a.(0)2-10 VDC: apply 10 VDC signal to control wire (WHITE).
b.10-(0)2 VDC: apply (0)2 VDC signal to control wire (WHITE).
c.(0)4-20 mA: apply 20 mA signal to control wire (WHITE).
d.20-(0)4mA: apply (0)4 mA signal to control wire (WHITE).
e.Floating: apply 24 VAC to appropriate 0°-90° (WHITE) or 90°-0° (BROWN) wire.
5.Actuator drives to full open or full closed position.
6.Apply control signal for actuator 0% position. (See Fig. 11 and Table 3.)
a.(0)2-10 VDC: apply (0)2 VDC signal to control wire (WHITE).
b.10-(0)2 VDC: apply 10 VDC signal to control wire (WHITE).
c.(0)4-20 mA: apply (0)4 mA signal to control wire (WHITE).
d.20-(0)4mA: apply 20 mA signal to control wire (WHITE).
e.Floating: apply 24 VAC to appropriate 0°-90° (WHITE) or 90°-0° (BROWN) wire.
7.Actuator drives to full open or full closed position.
1.Mount actuator for required application (either
clockwise or counterclockwise rotation to open the damper or valve).
2.Connect power to power and common wire. (See Fig. 11 and Table 3.)
3.Set “Mode Select” dial to desired control signal. (See Fig. 5.)
4.Apply control signal for actuator 50% position.
a.VDC Input Signal: apply 5-6 VDC signal to control wire (WHITE). See Fig. 14.
b.mA Input Signal: apply 10-12 mA signal to control wire (WHITE). See Fig. 14.
c.Floating: apply 24 VAC to appropriate 0°-90° (3) or 90°-0° (4) wire until device reaches 50%.
5.Allow the actuator to drive to 50% position.
6.Disconnect power wire (RED).
7.Actuator spring returns to 0% position.
8.Re-connect power wire (RED), actuator drives back toward 50% position.
1.Mount actuator for required application (either
clockwise or counterclockwise rotation to open the damper).
2.Connect power to power and common wire. (See Fig. 11 and Table 3.)
3.Set “Mode Select” dial to desired control signal. (See Fig. 5.)
1.Connect a multi-meter, set for VDC, to common (BLACK) and feedback (BROWN) wire.
2.Apply the same signal as in step 4 of Modulating Operation.
3.The multi-meter reading increases to match the input signal as actuator drives towards full open or full closed position.
4.Apply the same signal as in step 6 of Modulating Operation.
5.The multi-meter reading decreases to match the input signal as actuator drives towards 0% position.
9 |
31-00141M—06 |
3 NM SERIES SPRING RETURN DIRECT COUPLED ACTUATORS
1.Mount actuator for required application (either
clockwise or counterclockwise rotation to open the damper or valve).
2.Check damper position and make sure that 24 VDC/VAC is present at the appropriate connections. (See Fig. 11.)
3.Apply control signal to the appropriate connections to move the damper to the opposite position. The actuator should drive the damper or valve.
4.If actuator does not run, verify that the actuator is
properly installed for either clockwise or counterclockwise rotation.
5.If actuator is correctly installed and still does not run, replace the actuator.
1.Mount actuator for required application (either
clockwise or counterclockwise rotation to open the damper).
2.Connect Sylk-enabled (S-BUS) controller to terminals 3 and 4.
3.Connect power to terminals 1 and 2.
4.Select the proper address on dial to correspond with the address you wish to use (as seen in the table next to the dial).
5.Apply S-BUS command via the connected Sylkenabled controller for actuator position.
6.Local test mode (fast commissioning mode) may be selected by selecting position 6 in the address selector dial. Remember to reset the dial to the appropriate settings for your address of choice after the test has been completed.
•Device complies with ISO/IEC 14443A.
•NFC can be utilized for communication between the actuator and NFC equipped device.
•The NFC access area location is shown in Fig. 21.
•If the NFC access point is facing the damper, limited access from the edge on the side of the power wires may be possible depending on installation and NFC device capabilities.
NFC
M37468
Fig. 21. NFC access area location.
Physical security control, such as a locked cabinet, equipment room or any other placement of the device that restricts physical access to it, is recommended to prevent device tampering and unauthorized manipulation of the parameters accessible via NFC connection and SYLK connection. Connection to the device via NFC is secured using a PIN. Each device is preset with a factory default PIN. The factory default PIN is 2586 and is the same for all devices of this product family. It is recommended that the default PIN is changed to a user unique PIN. The user unique PIN can be canceled using the factory default PIN at any time.
31-00141M—06 |
10 |
3 NM SERIES SPRING RETURN DIRECT COUPLED ACTUATORS
|
|
|
|
|
|
|
|
|
|
|
|
|
Hazardous Substances |
|
|
||
|
|
|
|
|
|
|
|
|
|
|
(Pb) |
(Hg |
(Cd) |
|
(Cr6+) |
(PBB) |
(PBDE) |
PCB |
|
X |
O |
O |
|
O |
O |
O |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Gears |
|
X |
O |
O |
|
O |
O |
O |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Terminal block |
|
X |
O |
O |
|
O |
O |
O |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Electric motor |
|
X |
O |
O |
|
O |
O |
O |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Spring |
|
X |
O |
O |
|
O |
O |
O |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
SJ/T 11364 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
O |
|
|
GB/T 26572 |
|
|
|
||
|
|
|
|
|
|
|
||
X |
|
|
GB/T 26572 |
|
|
|
||
|
|
|
|
|
|
|
|
|
"
All other components not listed in the table do not contain restricted substances above the threshold level.
11 |
31-00141M—06 |
3 NM SERIES SPRING RETURN DIRECT COUPLED ACTUATORS
By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages, including attorneys’ fees, arising out of, or resulting from, any modification to the literature by you.
Honeywell Building Technologies
In the U.S.:
® U.S. Registered Trademark
© 2020 Honeywell International Inc.
31-00141M—06 M.S. Rev. 03-20
Printed in United States
|
Moteurs de registre à ressort de |
20 |
rappel de série 3 Nm |
|
|
|
MS7103, MS7503, MS3103 |
|
INSTRUCTIONS D’INSTALLATION |
Les moteurs de registre a ressort de rappel MS7103, MS7503, MS3103 sont utilisés dans des systèmes de chauffage, ventilation et climatisation (HVAC). Ils peuvent commander une grande variété de vannes quart de tour et d’éléments de contrôle final qui requièrent une sécurité intégrée par ressort de rappel.
Usages :
•Volets à régulation de débit montés directement sur l’arbre d’entraînement ou à distance (avec la quincaillerie d’accessoires).
•Vannes quart de tour, comme les clapets à bille, montées directement sur l’arbre d’entraînement.
•Disponible avec câble sur tous les modèles.
•Mode d’essai rapide.
Modèles :
Voir le Tableau 1.
Poids de l’appareil :
0,78 kg (1,7 lb)
Température ambiante en fonctionnement :
-40 à 65 °C (-40 à 150 °F)
Température d’entreposage et de transport :
-40 à 65 °C (-40 à 150 °F)
Tableau 1. Modèles.
|
|
|
|
|
|
|
|
|
|
|
Description du mode |
Interrupteurs |
Conduit |
|
|
|
Actionnement |
|
|
|
de commande |
auxiliaires |
1/2 po |
Adaptateur |
|
Tension |
/ maintien |
Actionne |
|
Numéro de modèle |
d’entrée/sortie |
SPST |
360° |
d’arbre |
Couple |
d’alimentation |
(VA) |
ment (s) |
|
MS7103A1021 |
Modulation1 |
Non |
|
|
|
|
4/2 |
90 |
|
MS7103A2021 |
1 |
|
|
|
|
4/2 |
90 |
||
|
|
|
|
|
|||||
|
Modulation , |
|
|
SCSA |
|
|
|
|
|
MS7103A2221 |
rétroaction |
Oui |
|
|
|
4/2 |
90 |
||
|
|
|
Oui |
|
|
|
|
|
|
MS7503A2021 |
|
Non |
|
|
|
4/2 |
90 |
||
|
|
|
|
|
|
|
|
|
|
MS7503A2221 |
Modulant2, Flottant, |
Oui |
|
|
|
|
4/2 |
90 |
|
MS7503A2023 |
2 pos, Retour |
Non |
|
|
|
|
4/2 |
90 |
|
|
|
|
|
|
|
|
|
|
|
MS7503A2223 |
|
Oui |
|
|
|
|
4/2 |
90 |
|
|
|
|
|
|
|
Transformateur 24 V |
|
|
|
MS7103A2024 |
Modulation1, |
Non |
Non |
Étrier |
|
4/2 |
90 |
||
|
rétroaction |
|
3 N.m |
c.a. ±20% classe 2 à |
|
|
|||
MS7103A2224 |
Oui |
4/2 |
90 |
||||||
|
|
(27 lb-pi) |
50/60 Hz, 24 V c.c. |
||||||
|
|
|
|
|
|
|
|||
MS3103J1023 |
|
Non |
Oui |
|
|
+20%/-10 % |
4.5/2 |
30-180 |
|
|
|
|
|
|
|
|
|
||
MS3103J1024 |
|
Non |
|
|
|
4.5/2 |
30-180 |
||
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
MS3103J1221 |
|
|
Oui |
SCSA |
|
|
4.5/2 |
30-180 |
|
|
|
|
|
|
|
|
|
||
MS3103J1222 |
BUS Sylk |
Oui |
Non |
|
|
4.5/2 |
30-180 |
||
|
|
|
|||||||
|
|
|
|
|
|
|
|||
MS3103J1223 |
Oui |
Étrier |
|
|
4.5/2 |
30-180 |
|||
|
|
|
|
||||||
|
|
|
|
|
|
|
|
||
MS3103J1224 |
|
|
Non |
|
|
4.5/2 |
30-180 |
||
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
MS3103J1021 |
|
Non |
Oui |
SCSA |
|
|
4.5/2 |
30-180 |
|
|
|
|
|
|
|
|
|||
MS3103J1022 |
|
Non |
|
|
4.5/2 |
30-180 |
|||
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
12 à 10 V CC
20(2) à 10 V CC, 10 à 0(2) V CC
https:// |
en-US/Pages/department.aspx?cat=HonECC%20Catalog&category=Commercial&catpath=1.1 |
MOTEURS DE REGISTRE À RESSORT DE RAPPEL DE SÉRIE 3 NM
Valeurs nominales d’humidité :
5 % à 95 % HR, sans condensation
Interrupteurs auxiliaires (deux SPST) :
Interrupteurs fixes à 10 et 80 degrés
125 V CA, 1 A, charge résiduelle
Montage : Adaptateur d’arbre à centrage automatique (accouplement d’arbre) :
Arbres de volet ronds : 9 à 16 mm (3/8 à 5/8 po)
Arbres de volet carrés : 6 à 13 mm (1/4 à 1/2 po)
Couple de serrage nominal de la vis de l’adaptateur d’arbre à centrage automatique : 12 Nm (106 lb-pi).
Montage : Adaptateur d’arbre sans centrage automatique :
Arbres amortisseur ronds : 1/4 à 3/4 po (6 à 19 mm)
Arbres amortisseur carrés : 1/4 à 1/2 po (6 à 13 mm)
Le couple nominal de serrage pour les vis de l’adaptateur de l’arbre sans centrage automatique est 62 lb po (7 Nm)
Longueur minimale de l’arbre de volet :
3,25 po (83 mm) recommandée pour l’adaptateur de l’arbre avec centrage automatique.
3 po (75 mm) recommandée pour l’adaptateur de l’arbre sans centrage automatique.
Durée du retour de ressort (à charge nominale) :
< 25 secondes à -30 à 65 °C (-22 à 150 °F) < 60 secondes à -40 à -30 °C (-40 à -22 °F)
Spécification du câble :
Câble d'alimentation : pour plénum, longueur de 0,914 m (3 pi) depuis l'extrémité du couvercle d'accès, calibre 18 AWG
Câble des interrupteurs : pour appareils, longueur de 0,914 m (3 pi) depuis l'extrémité du couvercle d'accès, calibre 18 AWG
78 (3-1/8) |
A |
|
72 (2-7/8) |
||
|
||
B |
|
|
|
164 |
|
|
(6-1/2) |
|
137 |
|
|
(5-3/8) |
179 |
|
|
||
|
(7) |
|
83 (3-17/64) |
MG37461 |
Fig. 1. Plan dimensionnel de l’actionneur en mm (po). Voir le Tableau 2 pour les dimensions A et B.
Tableau 2. Adaptateurs d’arbre.
|
|
|
Type d’adaptateur d’arbre |
A |
B |
Adaptateur à centrage |
90 mm |
39 mm |
automatique |
(3,54 po) |
(1,54 po) |
|
|
|
Adaptateur sans centrage |
3,11 po |
1,57 in.1 |
automatique |
(79 mm) |
(40 mm) |
|
|
|
1 Pour 1/2 arbre.
78 (3-1/8) |
90 (3-1/2) |
|
72 (2-7/8) |
||
|
||
37 |
|
|
(1-1/2) |
|
|
|
164 |
|
|
(6-1/2) |
|
137 |
|
|
(5-3/8) |
|
|
83 (3-17/64) |
MG37351 |
Fig. 2. Plan dimensionnel de l’actionneur sans conduit en mm (po). Voir le Tableau 2 pour les dimensions A et B.
Course :
95° ±3°, limite mécanique.
Homologation :
UL60730
IEC 60730-1 et partie 2–14
UL1097 pour isolation double
Certification CE Low Voltage Directive (2014/35/EU)
CE EMC 2004/108/EC
Les câbles des interrupteurs sont homologués en vertu de la norme UL uniquement.
Déchet d’équipements électriques et électroniques (DEEE) (Waste Electrical and Electronic Equipment, WEEE) :
Élimination appropriée de ce produit (applicable en Union européenne et dans les autres pays européens dotés de systèmes de collecte distincts). À la fin de sa durée de vie utile, ce produit doit être éliminé conformément aux lois, aux règlements et aux procédures applicables de la région.
Spécifications du boîtier :
IP54, dépend de la position, selon « Déterminer l’orientation de montage adéquate » à la page 4.
NEMA 2
Résistance aux flammes UL94-5VA
UL2043, le câblage de l'interrupteur dépend de l'installation de la conduite
31-00141M—06 |
2 |
MOTEURS DE REGISTRE À RESSORT DE RAPPEL DE SÉRIE 3 NM
Impédance d’entrée :
95 kOhms minimum pour l’entrée modulante analogique.
Signal de rétroaction :
2 à 10 V CC, source 1mA, chute 0,5 mA
Caractéristiques bruit à 1 m de l’entraînement (maximum à une vitesse d’entraînement de 90 s) :
Flottant/modulant/Sylk < 40 dB(A)
Rappel par ressort : < 65 dB(A)
Accessoires et références de commande :
Kit manivelle, n° OS DIAM-CRK-01
Adaptateur à centrage automatique
Support antirotation
Les moteurs de registre doivent être de type à accouplement direct. Ils doivent se monter directement sur un arbre de renvoi d’un diamètre allant jusqu’à 19 mm (3/4 po), sans nécessiter une manivelle ou une bielle. L’actionneur doit se monter sur l’arbre au moyen d’un moyeu de sortie doté d’un accouplement d’arbre à centrage automatique. Le montage de l’accouplement doit être concentrique et l’ensemble doit comporter un mécanisme de butée réglable intégré.
L’actionneur doit comporter deux positions de commande, soit par action proportionnelle ou flottante. La commande proportionnelle utilise directement un signal d’entrée de 0 à 10 V c.c., de 2 à 10 V c.c., ou de 4 à 20 mA (avec résistance shunt de 500 ohms). Certains modèles d’actionneur à régulation proportionnelle et flottante fournissent un signal de rétroaction. Les actionneurs à régulation flottante doivent être munis d’un interrupteur de commande de sens de rotation accessible, situé sur le couvercle.
Tous les actionneurs à ressort de rappel doivent être Installes pour l’une ou l’autre des positions de sécurité (sens horaire ou antihoraire) avec un ressort de rappel mécanique toujours engagé. Ce ressort doit ramener la vanne ou l’actionneur en position de sécurité dans les 25 secondes qui suivent une coupure de courant.
Tous les actionneurs doivent être conçus pour un niveau de rendement minimal de 60 000 courses complètes au couple nominal et à la température spécifiés, de 60 000 cycles de retour de ressort et de 1 500 000 repositionnements. Le temps de fonctionnement doit être constant et indépendant de la charge, de la température et du niveau de tension, selon les spécifications. Tous les actionneurs doivent être conformes aux normes UL60730 et cUL (CSA22.2) indiquées, comporter une garantie de cinq ans et être fabriqués conformément aux normes internationales de contrôle de la qualité ISO 9001. Les actionneurs doivent être tels que fabriqués par Honeywell.
Bus Sylk™ :
Le bus Sylk est un bus à deux fils à polarité indifférente qui fournit une communication entre un actionneur adapté Sylk et un contrôleur Sylk. Pour le câblage, l’actionneur adapté Sylk peut être monté à une distance maximale de 61 m (200 pi) du contrôleur ; il est recommandé d'utiliser un câble à paire torsadée pour un câblage supérieur à 30,5 m (100 pi). L’utilisation des actionneurs Sylk permet d’enregistrer les E/S sur le contrôleur et l'installation est plus rapide et moins coûteuse, le bus n'étant pas sensible à la polarité.
1.Lisez ces instructions attentivement. Le non-respect de ces consignes peut entraîner l’endommagement du produit ou causer une condition dangereuse.
2.Vérifiez les caractéristiques nominales indiquées dans les instructions et sur le produit pour vous assurer qu’il convient à l’utilisation prévue.
3.L’installateur doit être un technicien en entretien formé et expérimenté.
4.Une fois l’installation terminée, vérifiez le fonctionnement du produit de la manière décrite dans ces instructions.
MISE EN GARDE
Les tensions faibles peuvent électrocuter les personnes ou provoquer un court-circuit de l’équipement.
Débranchez l’alimentation avant de commencer l’installation.
IMPORTANT
Tout le câblage doit être conforme aux codes, aux ordonnances et aux réglementations électriques en vigueur.
Ces actionneurs sont conçus pour être montés directement à un arbre d’entraînement de volet externe. L’accouplement d’arbre se fixe à l’arbre d’entraînement. Le boîtier de l’actionneur comprend des fentes qui, avec le support antirotation, fixe l’actionneur au cadre du volet ou au conduit (voir la Fig. 10).
REMARQUES :
—Avec un montage conforme, ces fentes permettent à l’actionneur de flotter sans pivoter par rapport à l’arbre du volet.
—En utilisant d’autres supports ou bielles, l’actionneur peut être monté au pied ou en tandem.
MISE EN GARDE
Risque d’endommagement du moteur. Les vapeurs corrosives et d’acides peuvent endommager les pièces métalliques et plastiques.
Installez le moteur à un endroit non exposé aux vapeurs d’acides ou à d’autres vapeurs destructrices.
MISE EN GARDE
Risque d’endommagement de l’équipement. Serrer l’actionneur trop fermement au boîtier du volet peut endommager l’actionneur.
Montez l’actionneur de manière à lui permettre de flotter sur son axe vertical.
3 |
31-00141M—06 |
MOTEURS DE REGISTRE À RESSORT DE RAPPEL DE SÉRIE 3 NM
Avant de monter l’actionneur sur l’arbre du volet, déterminez :
—Le sens d’ouverture du volet ou de la vanne afin de connaître le sens de pivotement du ressort de rappel. L’actionneur peut être monté pour fournir un retour de ressort en sens horaire ou antihoraire en inversant la position de l’unité.
—Diamètre de l’arbre de volet (voir la section Spécifications).
Déterminer l’orientation de montage adéquat
Les actionneurs sont conçus pour ouvrir un volet en actionnant l’arbre de ce dernier en sens horaire ou antihoraire (voir la Fig. 3).
REMARQUES :
—Les actionneurs sont expédiés en position complètement fermée (ressort de rappel).
—La rainure sur l’adaptateur pointe vers un emplacement sur l’étiquette pour indiquer la position rotative du moyeu.
ANTIHORAIRE POUR FERMER |
HORAIRE POUR FERMER |
(POSITION DE SÉCURITÉ) |
(POSITION DE SÉCURITÉ) |
HORAIRE POUR OUVRIR |
ANTIHORAIRE POUR OUVRIR |
LAMES DU VOLET
AVANT |
ARRIÈRE |
MF37462 |
Fig. 3. Orientation de montage DCA du ressort de rappel.
Mesurer la longueur de l’arbre de volet/vanne
Si l’arbre mesure moins de 83 mm (3,25 po) pour le SCSA, l’accouplement de l’arbre doit se situer entre le volet/vanne et le boîtier de l’actionneur. Si l’arbre mesure plus de 76 mm (3 po), l’accouplement d’arbre peut être placé d’un côté ou l’autre du boîtier d’actionneur.
Si vous devez déplacer l’accouplement d’un côté de l’actionneur à l’autre, inversez le sens du ressort de rappel et inversez l’actionneur. Veuillez suivre ces directives (Fig. 4) :
1.Retirez l’agrafe de l’accouplement d’arbre, puis mettez-la de côté pour une utilisation ultérieure.
2.Retirez l’accouplement d’arbre d’un côté de l’actionneur.
3.Replacez l’accouplement d’arbre de l’autre côté de l’actionneur en l’alignant selon son étiquette de course.
4.Reposez l’agrafe de l’accouplement sur l’arbre à l’aide de la rainure de l’accouplement.
Fig. 4. Montage de l’accouplement de l’autre côté de l’actionneur.
Sélection du signal de commande de l’actionneur (modèles MS7503 seulement)
On effectue les sélections au moyen du cadran qui apparaît sur le devant et l’arrière de l’actionneur (voir la Fig. 5).
Pour sélectionner un signal de commande, tournez simplement le cadran au mode souhaité (comme indiqué sur l’étiquette de l’appareil) sans dépasser les indicateurs de plage.
|
|
SÉLECTION DE MODE |
|
|
|
1 |
= 2... 10 V CC |
|
|
2 |
= 10... 2 V CC |
5 |
6 |
3 |
= 0... 10 V CC |
4 |
|
4 |
= 10... 0 V CC |
3 |
|
5 |
= FLOTTANT (MARCHE AVANT) |
2 |
1 |
6 |
= FLOTTANT (MARCHE ARRIÈRE) |
|
|
||
|
|
|
MF37464 |
Fig. 5. Cadran de signal de commande.
Pour les modèles MS31XX uniquement
Ces actionneurs sont disponibles avec le pot de sélection d’adresse Sylk.
REMARQUE : Vous pouvez choisir parmi 5 adresses Sylk effectives. Par exemple, pour sélectionner l’adresse Sylk 11, déplacez le pot de la plage sur 1.
31-00141M—06 |
4 |
MOTEURS DE REGISTRE À RESSORT DE RAPPEL DE SÉRIE 3 NM
|
|
SÉLECTION D'ADRESSE |
|
|
|
1 |
= ADRESSE 11 |
|
|
2 |
= ADRESSE 12 |
5 |
6 |
3 |
= ADRESSE 13 |
4 |
|
4 |
= ADRESSE 14 |
3 |
|
5 |
= ADRESSE 15 |
2 |
1 |
6 |
= TEST |
|
|
Fig. 6. Cadran de sélection d’adresse.
Réduction de la course mécanique
Pour les utilisations nécessitant une plage de moins de 95°, un simple réglage suffit. Lorsque le montage rotationnel de l’accouplement d’arbre est modifié, l’actionneur n’utilise pas la course complète de 95°.
Vous pouvez régler la course par incréments de 7,5°. Une fois la course réglée, l’actionneur s’arrête lorsque l’accouplement d’arbre atteint la butée mécanique (qui fait partie du boîtier). Cette butée arrête la force appliquée par le moteur et ainsi l’accouplement d’arbre. Lorsque l’actionneur revient à la position, il arrête à la position de sécurité. Il est interdit de limiter mécaniquement la position minimale. Au besoin, utilisez une limitation électronique ou logicielle.
Suivez ces directives pour limiter la course :
1.Retirez l’agrafe de l’accouplement d’arbre, puis mettez-la de côté pour une utilisation ultérieure.
2.Retirez l’accouplement d’arbre de l’actionneur.
3.Faites pivoter l’accouplement à la position voulue, en l’alignant selon son étiquette de course. Voir la Fig. 7.
REMARQUE : L’emplacement de l’accouplement d’arbre détermine la course.
EXEMPLE : Le fait de régler l’accouplement d’arbre
àune position de sécurité approximative de 30° (comme indiqué sur le boîtier) limite la course à 60°. (Voir la Fig. 7)
4.Posez l’accouplement d’arbre à cette position.
5.Reposez l’agrafe de l’accouplement sur l’arbre à l’aide de la rainure de l’accouplement.
MISE EN GARDE
Risque de dysfonctionnement de l’appareil.
Un serrage inadéquat de l’accouplement d’arbre entraînera un dysfonctionnement de l’appareil.
Serrez l’accouplement d’arbre au bon couple pour empêcher le glissement de l’arbre du volet.
MISE EN GARDE
Risque d’endommagement de l’actionneur. Utiliser l’actionneur comme support d’arbre endommagera l’appareil.
Utilisez seulement l’actionneur pour fournir un couple rotatif. Évitez les charges latérales sur les roulements d’accouplement de sortie de l’actionneur.
MISE EN GARDE
Risque d’endommagement de l’équipement. Peut endommager le moteur de manière permanente.
Ne tournez jamais l’arbre du moteur à la main ou à l’aide d’une clé.
Vous pourriez endommager le train d’engrenages si vous forcez l’arbre du moteur.
Pour monter l’actionneur à l’arbre d’entraînement externe d’un volet, suivez ces directives :
1.Placez l’actionneur sur l’arbre du volet, puis maintenez le support de montage en place. Voir la Fig. 10.
2.Marquez les trous de vis sur le boîtier du volet.
3.Déposez l’actionneur et le support de montage.
4.Percez ou poinçonnez des trous pour les vis de fixation (ou utilisez des vis à tôle autotaraudeuses nº 10).
5.Tournez les lames du volet à la position normale (fermée) voulue.
6.Remettez l’actionneur et le support de montage en place, puis fixez le support de montage au boîtier du volet à l’aide de vis à tôle.
7.À l’aide d’une clé de 10 mm, serrez fermement l’accouplement d’arbre sur l’arbre du volet à un couple maximal de 12 Nm (106 lb-po).
REMARQUE : Voir la Fig. 8 pour le montage à un arbre de volet carré.
|
|
|
|
|
|
|
9 |
|
|
|
|
|
|
0 |
|
|
|
|
0 |
|
0 |
|
|
|
|
|
|
9 |
|
|
|
|
|
|
|
E |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
45 |
||
|
|
|
|
|
|
R |
|
|
NTR |
AÎ |
|
||
|
|
|
45 |
|
|
AP |
PEL |
|
NEMENT |
||||
|
EN |
NT |
|
|
|
|
PAR |
|
|
||||
R |
AP |
|
TRAÎNEME |
T |
|
|
C |
O |
|
RESSORT |
|||
|
|
|
|
|
|
|
|
|
|||||
|
|
OR |
|
|
|
UR |
|
|
|
||||
|
|
PEL PAR RESS |
|
|
|
|
|
|
|
|
|||
|
|
|
° |
|
|
|
|
|
|
SE |
DE 6 |
0° |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
COURSE DE 90 |
|
|
|
|
|
|
|
|
|
|
Fig. 7. Réduction de la course.
0
MF37465
ARBRE |
ARBRE |
|
D’AMORTISSEUR |
||
D’AMORTISSEUR |
||
|
Fig. 8. Montage adéquat à un arbre de volet carré.
5 |
31-00141M—06 |
MOTEURS DE REGISTRE À RESSORT DE RAPPEL DE SÉRIE 3 NM
Pour respecter la norme de résistance aux infiltrations IP54, l’actionneur doit être monté conformément à la Fig. 9. La norme IP54 s’applique à toutes les positions de montage à l’exception de la position avec câble vers le haut (rayé) Fig. 9.
Détails avec étrier
CÂBLE VERS LE HAUT
IP50
POSITIONS STANDARD |
1 |
IP54 |
|
|
2 |
MF37467 |
|
Fig. 9. Montage de l’actionneur conforme à la norme IP. |
|
|
SUPPORT |
|
1 S’ASSURER QUE L’ENSEMBLE DE MONTAGE EMPÊCHE LA |
|
ROTATION DE L’ACTIONNEUR ET PERMET À L’ACTIONNEUR |
|
DE FLOTTER LE LONG DE L’AXE INDIQUÉ. QUAND IL EST |
|
TROP SERRÉ, LA LIAISON RÉSULTANTE PEUT ENDOMMAGER |
|
L’ACTIONNEUR OU RÉDUIRE LE COUPLE DE SORTIE. |
|
2 LE SUPPORT PEUT ÊTRE COURBÉ POUR PERMETTRE LE |
|
MONTAGE DE L’ACTIONNEUR PARALLÈLEMENT À LA |
|
SURFACE DE MONTAGE. |
Fig. 10. Montage de l’actionneur au boîtier de volet.
MISE EN GARDE
Risque d’électrocution ou de dégât matériel. Débranchez toutes les sources d’alimentation avant de commencer l’installation.
Les moteurs munis d’interrupteurs auxiliaires peuvent comprendre plus d’un sectionneur.
IMPORTANT
Tout le câblage doit être conforme aux codes, aux ordonnances et aux réglementations électriques locaux.
31-00141M—06 |
6 |
|
MOTEURS DE REGISTRE À RESSORT DE RAPPEL DE SÉRIE 3 NM |
|||
|
528*( |
CLASSE 2 |
|
ACTIONNEUR |
|
|
|
||
|
12,5 |
1 |
ROUGE |
|
|
1 |
24 V CA |
|
V |
|
|
2 NOIR |
||
|
%/$1& 28 r r |
|
||
$&7,211(85 |
& %/( 0$5521 5(7285 28 r r |
|
||
|
35,1&,3$/ |
3 |
BLANC |
0°-90°/MODULATION |
,17(55837(856 6367 |
|
|||
|
|
4 |
BRUN |
90°-0°/RÉTROACTION |
|
%/(8 |
|
|
|
0$5521 |
|
|
|
|
|
|
|
|
|
|
||
|
|
|
1 |
TENSION D’ALIMENTATION. |
|
|
|
|
|
|
|
2-10 V CC |
|
|
|
|
|
|
|
|
|
|
|||
|
|
*5,6 |
|
AU BESOIN, PLACEZ UN DISPOSITIF |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
& %/(6'( 12,5 |
|
DE COUPURE ET UNE PROTECTION |
|
|
|
|
|
|
|
10-2 V CC |
||
/,17(55837(85 |
|
CONTRE LES SURCHARGES. |
2 |
|
|
|
|
|
|
0-10 V CC |
||
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
10-0 V CC |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Fig. 11. Détails de l’installation du câble. |
2 |
RÉGLEZ LE COMMUTATEUR AU |
|
|
|
|
|
|
|
FLOTTANT, MARCHE AVANT |
||
|
|
|
|
|
|
|
||||||
|
MODE « FLOTTANT ». |
|
|
|
|
|
|
|
FLOTTANT, MARCHE ARRIÈRE |
MF37319
Fonctionnement de l’interrupteur
Gris/noir = normalement ouvert. Fermé dans la plage 80 degrés à entièrement ouvert.
Bleu/marron = normalement fermé. Ouvert dans la plage 10 degrés à entièrement ouvert.
Tableau 3. Détails de câblage.
|
|
|
|
|
|
|
|
|
|
|
|
|
Câble |
Flottant |
Modulation |
Sylk |
|||
ROUGE |
alimentation |
alimentation |
alimentation |
||||||
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
NOIR |
neutre |
neutre |
commun |
||||||
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
BLANC2 |
0° - 90° |
signal de |
S-bus |
||||||
commande |
|||||||||
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
BRUN |
90° - 0° |
rétroaction1 |
S-bus |
||||||
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
1Non disponible sur tous les modèles à modulation, voir le Tableau 1.
2Marron pour MS3103.
Modèles flottants et à modulation
|
CLASSE 2 |
ACTIONNEUR |
1 |
ROUGE |
|
24 V CA |
V |
|
|
NOIR |
|
|
BLANC |
0°-90°/MODULATION |
|
BRUN |
90°-0°/RÉTROACTION |
|
SPDT |
|
|
|
|
|
|
|
|
|
|
2-10 V CC |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
10-2 V CC |
|
|
|
|
|
|
|
|
|
|
1 TENSION D’ALIMENTATION. |
2 |
|
|
|
|
|
|
0-10 V CC |
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
10-0 V CC |
|||
AU BESOIN, PLACEZ UN DISPOSITIF |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
FLOTTANT, MARCHE AVANT |
|
DE COUPURE ET UNE PROTECTION |
|
|
|
|
|
|
|
|
|
CONTRE LES SURCHARGES. |
|
|
|
|
|
|
|
|
FLOTTANT, MARCHE ARRIÈRE |
2 RÉGLEZ LE COMMUTATEUR AU |
|
|
|
|
|
|
|
|
|
MODE « FLOTTANT ». |
|
|
|
|
|
|
|
|
MF37304 |
Fig. 13. Câblage pour commande flottante, MS75.
|
CLASSE 2 |
|
ACTIONNEUR |
1 |
24 V CA |
1 |
ROUGE |
2 |
V |
||
|
|
2 |
NOIR |
0/2 À 10 V CC |
|
|
|
3 BLANC |
|
0°-90°/MODULATION |
||||||||||||
RÉGULATEUR À |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
COMMANDE |
|
|
|
|
|
4 BRUN |
|
90°-0°/RÉTROACTION |
||||||||||
PROPORTIONNELLE |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
– |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2-10 V CC |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
+ |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
10-2 V CC |
||
RÉTROACTION |
|
|
|
|
3 |
|
|
|
|
|
|
|
|
0-10 V CC |
||||
|
|
|
|
|
|
|
|
|
|
|
|
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
10-0 V CC |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
FLOTTANT, MARCHE AVANT |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
FLOTTANT, MARCHE ARRIÈRE |
1TENSION D’ALIMENTATION. AU BESOIN, PLACEZ UN DISPOSITIF DE COUPURE ET UNE PROTECTION CONTRE LES SURCHARGES.
2ALIMENTATION 24 V CC ACCEPTÉE.
3 RÉGLEZ LE COMMUTATEUR À MODULATION, SI POSSIBLE. |
MF37320 |
Fig. 14. Câblage à commande modulante (0/2-10 V CC) |
||||||
proportionnelle, MS75 (montrée) et MS71 |
||||||
CLASSE 2 |
|
|
|
ACTIONNEUR |
||
1 |
24 V CA |
|
1 |
ROUGE |
||
2 |
|
|
V |
|||
|
|
2 |
|
|||
|
|
NOIR |
|
|||
|
|
|
|
|||
0/2 À 10 V CC |
|
3 |
BLANC |
0°-90°/MODULATION |
||
RÉGULATEUR À |
490 À 510 |
|||||
|
|
|
||||
COMMANDE |
|
4 |
BRUN |
90°-0°/RÉTROACTION |
||
|
OHMS, |
|||||
PROPORTIONNELLE |
1/2 W |
|
|
|
||
|
|
|
|
|
||
|
– |
MINIMUM |
|
|
|
|
|
|
|
|
|
||
|
+ |
|
|
|
2-10 V CC |
|
|
|
|
|
10-2 V CC |
||
RÉTROACTION |
|
3 |
|
0-10 V CC |
||
|
|
|
10-0 V CC |
|||
|
|
|
|
|
FLOTTANT, MARCHE AVANT |
|
|
|
|
|
|
FLOTTANT, MARCHE ARRIÈRE |
1TENSION D’ALIMENTATION. AU BESOIN, PLACEZ UN DISPOSITIF DE
COUPURE ET UNE PROTECTION CONTRE LES SURCHARGES.
2ALIMENTATION 24 V CC ACCEPTÉE.
3 RÉGLEZ LE COMMUTATEUR À MODULATION, SI POSSIBLE. |
MF37321 |
Fig. 15. Câblage à commande proportionnelle 4-20 mA, Fig. 12. Câblage pour commande de marche/arrêt SPDT, MS75 (montrée) et MS71.
MS75.
7 |
31-00141M—06 |
MOTEURS DE REGISTRE À RESSORT DE RAPPEL DE SÉRIE 3 NM
CLASSE 2 |
|
ACTIONNEUR |
1 |
24 V CA |
1 |
ROUGE |
V |
2 |
NOIR |
|||
|
|
2 |
|
|
RÉGULATEUR À |
3 |
BLANC |
0°-90°/MODULATION |
|
COMMANDE |
|
|||
|
|
|
|
|
PROPORTIONNELLE |
4 |
BRUN |
90°-0°/RÉTROACTION |
|
0/2 À 10 V CC |
|
|
|
– |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2-10 V CC |
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
+ |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
10-2 V CC |
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||
RÉTROACTION |
|
|
|
|
|
|
3 |
|
|
|
|
|
|
|
|
|
0-10 V CC |
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
10-0 V CC |
|||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
FLOTTANT, MARCHE AVANT |
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
FLOTTANT, MARCHE ARRIÈRE |
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ACTIONNEUR |
||
|
|
|
|
|
|
|
|
|
|
1 ROUGE |
|
|
|
V |
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||
|
|
|
|
|
|
|
|
|
|
2 |
|
NOIR |
|
|
|
|||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||
|
|
|
|
|
|
|
|
|
|
3 BLANC |
0°-90°/MODULATION |
|||||||||||||
|
|
|
|
|
|
|
|
|
||||||||||||||||
|
|
|
|
|
|
|
|
4 |
|
BRUN |
90°-0°/RÉTROACTION |
|||||||||||||
1 TENSION D’ALIMENTATION. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||
AU BESOIN, PLACEZ UN |
|
|
|
|
|
|
|
|
|
|
|
|
|
2-10 V CC |
||||||||||
DISPOSITIF DE COUPURE ET |
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||
UNE PROTECTION CONTRE |
|
|
|
|
|
|
|
|
|
|
|
|
|
10-2 V CC |
||||||||||
LES SURCHARGES. |
3 |
|
|
|
|
|
|
|
|
|
0-10 V CC |
|||||||||||||
|
|
|
|
|
|
|
|
|
||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
10-0 V CC |
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||
2 ALIMENTATION 24 V CC |
|
|
|
|
|
|
|
|
|
|
|
|
|
FLOTTANT, MARCHE AVANT |
||||||||||
ACCEPTÉE. |
|
|
|
|
|
|
|
|
|
|
|
|
FLOTTANT, MARCHE ARRIÈRE |
|||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
3 RÉGLEZ LE COMMUTATEUR À
MODULATION, SI POSSIBLE. |
MF37322 |
|
Fig. 16. Câblage à commande modulante (0/2-10 V CC) proportionnelle actionnant plusieurs actionneurs, MS75 (montrée) et MS71.
CLASSE 2 |
|
ACTIONNEUR |
|
|
|
||
24 V CA |
ROUGE |
||
|
|
||
|
NOIR |
|
|
CONTRÔLEUR |
BRUN |
S-BUS |
|
CHAUD |
BRUN |
S-BUS |
|
COM |
|||
|
|
||
S-BUS |
|
|
|
S-BUS |
|
ADRESSE 11 |
|
|
|
||
1 ALIMENTATION DE TENSION DE |
|
ADRESSE 12 |
|
|
ADRESSE 13 |
||
LIGNE. FOURNIR DES MOYENS |
|
||
DE DÉCONNEXION ET UNE |
|
ADRESSE 14 |
|
|
ADRESSE 15 |
||
PROTECTION CONTRE LES |
|
||
SURCHARGES, SI NÉCESSAIRE. |
|
TEST |
|
2 ALIMENTATION 24 V CC ACCEPTÉE. |
|
|
3 SÉLECTEUR D'ADRESSE
Fig. 17. Câblage pour le contrôle du BUS SYLK, MS3103.
CLASSE 2 |
ACTIONNEUR |
24 V CA |
ROUGE |
|
|
|
NOIR |
CLASSE 2 |
BRUN |
24 V CA |
BRUN |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ADRESSE 11 |
CONTRÔLEUR |
|
|
|
|
|
|
|
|
|
ADRESSE 12 |
|||||
|
|
|
|
|
|
|
|
|
|||||||
|
|
|
|
|
|
|
|
|
ADRESSE 13 |
||||||
|
CHAUD |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ADRESSE 14 |
|||
|
|||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
COM |
|
|
|
|
|
|
|
|
|
|
|
|
ADRESSE 15 |
|
|
S-BUS |
|
|
|
|
|
|
|
|
|
|
|
|
|
TEST |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
S-BUS |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1ALIMENTATION DE TENSION DE LIGNE. FOURNIR DES MOYENS DE DÉCONNEXION ET UNE PROTECTION CONTRE LES SURCHARGES, SI NÉCESSAIRE.
2ALIMENTATION 24 V CC ACCEPTÉE.
3SÉLECTEUR D'ADRESSE
CLASSE 2 |
CLASSE 2 |
VERS L'ACTIVATEUR CHAUD |
VERS L'ACTIVATEUR CHAUD |
24 V CA |
24 V CA |
|
COMMUN |
> 30 V C.A. |
|
COMMUN |
> 30 V C.A. |
||
CLASSE 2 |
|
|
|
CLASSE 2 |
|
|
|
24 V CA |
24 V CA |
VERS LE CONTRÔLEUR CHAUD |
|
|
|
|
|
VERS LE CONTRÔLEUR CHAUD |
REMARQUES : Lors de l'utilisation de deux transformateurs dans l’installation, assurez-vous de connecter les pattes correspondantes des enroulements secondaires comme étant communes. Vérifiez la tension comme indiqué sur l’image et assurez-vous qu’elle est inférieure à 30 V c.a. Si tel n’est pas le cas, remplacez les pattes d’un enroulement secondaire.
Fig. 18. Câblage pour le contrôle du BUS SYLK avec des transformateurs distincts, MS3103.
L’actionneur est conçu pour être utilisé dans les installations de ventilation et de climatisation pour actionner les vannes, les volets et les persiennes. (Voir la section Spécifications pour les valeurs nominales.) En cas de panne de courant, l’actionneur rappelle le ressort à la position de sécurité.
Lorsque vous utilisez un régulateur à commande proportionnelle et que l’actionneur est réglé à la position (0)2-10, l’actionneur passe en position complètement ouverte lorsque le signal d’entrée augmente; l’actionneur passe en position complètement fermée lorsque le signal d’entrée diminue. L’actionneur s’arrête lorsque le signal d’entrée atteint le point de commande proportionnelle souhaitée. Cette opération est inversée au réglage à la position 10-2(0).
IMPORTANT
L’actionneur est conçu pour répondre aux fermetures instantanées des contacts du contrôleur RND. Prenez garde de ne pas raccourcir le cycle de l’actionneur. La régulation instable du volet pourrait entraîner une panne précoce de l’actionneur.
31-00141M—06 |
8 |
MOTEURS DE REGISTRE À RESSORT DE RAPPEL DE SÉRIE 3 NM
Mode de mise en service rapide (mode de contrôle de modulation et communication SYLK uniquement)
Lorsque le signal 24 V c.a. ou 24 V c.c. est appliqué à l’entrée de modulation ou sur l’actionneur communicant SYLK, la position 6 (TEST) est sélectionnée, l’actionneur se dirige vers la position entièrement ouverte avec une vitesse supérieure correspondant à une temporisation de 30 secondes. Lorsque le signal est déconnecté, l’actionneur entraîne à la position entièrement fermée avec une temporisation de fonctionnement normal.
MISE EN GARDE
N’utilisez pas le mode d’essai rapide pour le fonctionnement permanent.
La durée de vie sera réduite si ce mode est utilisé de manière permanente. Ce mode est uniquement conçu pour être utilisé lorsque de la mise en service/mise à l’essai initial après l’installation. La consommation énergétique n’est pas précisée pour ce mode.
CLASSE 2 |
|
|
ACTIONNEUR |
|
1 |
24 V CA |
1 ROUGE |
V |
|
|
|
|||
|
2 |
2 NOIR |
||
|
|
|||
|
|
|
||
RÉGULATEUR À |
3 |
BLANC |
0°-90°/MODULATION |
|
COMMANDE |
|
|||
|
|
|
|
|
PROPORTIONNELLE |
4 |
BRUN |
90°-0°/RÉTROACTION |
|
0/2 À 10 V CC |
|
|||
|
|
|
|
|
|
– |
|
|
|
|
+ |
|
|
2-10 V CC |
|
|
|
10-2 V CC |
|
|
SPST |
3 |
|
0-10 V CC |
RÉTROACTION |
|
|
10-0 V CC |
|
|
|
|
|
FLOTTANT, MARCHE AVANT |
|
|
|
|
FLOTTANT, MARCHE ARRIÈRE |
1TENSION D’ALIMENTATION. AU BESOIN, PLACEZ UN DISPOSITIF
DE COUPURE ET UNE PROTECTION CONTRE LES SURCHARGES.
2ALIMENTATION 24 V CC ACCEPTÉE.
3RÉGLEZ LE COMMUTATEUR À
MODULATION, SI POSSIBLE. |
MF37324 |
Fig. 20. Retour en position complètement fermée.
Certains modèles comprennent des interrupteurs auxiliaires. Voir la Fig. 11 pour les détails de câblage.
Pour neutraliser le signal de commande (pour la protection contre le gel ou applications semblables) :
1.Neutralisation en position complètement ouverte (mise en service rapide, mode d’entraînement inférieur à 30 s) :
a.Débranchez le signal d’entrée (de la borne 3).
b.Appliquez une tension de 24 V CA à la borne 3.
c.Voir la Fig. 19.
2.Retour en position complètement fermée :
a.Débranchez le signal d’entrée (de la borne 3).
b.Voir la Fig. 20.
|
CLASSE 2 |
|
|
ACTIONNEUR |
|
1 |
24 V CA 2 |
1 |
ROUGE |
V |
|
|
|
||||
|
2 |
NOIR |
|||
|
|
|
|||
RÉGULATEUR À |
3 BLANC 0°-90°/MODULATION |
||||
COMMANDE |
|||||
|
|
|
|||
PROPORTIONNELLE |
4 |
BRUN |
90°-0°/RÉTROACTION |
||
0/2 À 10 V CC |
|
|
|
||
|
– |
|
|
|
|
|
+ |
|
|
2-10 V CC |
|
|
SPDT |
|
10-2 V CC |
||
|
|
|
0-10 V CC |
||
RÉTROACTION |
3 |
|
|||
|
|
10-0 V CC |
|||
|
|
|
|
FLOTTANT, MARCHE AVANT |
|
|
|
|
|
FLOTTANT, MARCHE ARRIÈRE |
1TENSION D’ALIMENTATION. AU BESOIN, PLACEZ UN DISPOSITIF
DE COUPURE ET UNE PROTECTION CONTRE LES SURCHARGES.
2ALIMENTATION 24 V CC ACCEPTÉE.
3RÉGLEZ LE COMMUTATEUR À
MODULATION, SI POSSIBLE. |
MF37323 |
|
Fig. 19. Neutraliser à la position ouverte.
1.Montez l’actionneur en fonction de l’usage prévu
(rotation horaire ou antihoraire pour ouvrir le volet).
2.Branchez l’alimentation aux fils d’alimentation et neutre. (Voir la Fig. 11 et le Tableau 3.)
3.Réglez le cadran « Sélection de mode » au signal de commande souhaité. (Voir la Fig. 5.)
4.Envoyez le signal de commande d’ouverture ou de fermeture complète de l’actionneur. (Voir la Fig. 11 et le Tableau 3.)
a.(0)2-10 V CC : envoyez un signal de 10 V CC au fil de commande (BLANC).
b.10-(0)2 V CC : envoyez un signal de 0(2) V CC au fil de commande (BLANC).
c.(0)4-20 mA : envoyez un signal de 20 mA au fil de commande (BLANC).
d.20-(0)4 mA : envoyez un signal de 0(4) mA au fil de commande (BLANC).
e.Flottant : envoyez un signal 24 V CA au fil 0°-90° (BLANC) ou 90°-0° (BRUN) approprié.
5.L’actionneur passe en position complètement ouverte ou complètement fermée.
6.Envoyez le signal de commande de position 0 % de l’actionneur. (Voir la Fig. 11 et le Tableau 3.)
a.(0)2-10 V CC : envoyez un signal de 0(2) V CC au fil de commande (BLANC).
b.10-(0)2 V CC : envoyez un signal de 10 V CC au fil de commande (BLANC).
c.(0)4-20 mA : envoyez un signal de 0(4) mA au fil de commande (BLANC).
d.20-(0)4 mA : envoyez un signal de 20 mA au fil de commande (BLANC).
e.Flottant : envoyez un signal 24 V CA au fil 0°-90° (BLANC) ou 90°-0° (BRUN) approprié.
7.L’actionneur passe en position complètement ouverte ou complètement fermée.
9 |
31-00141M—06 |
MOTEURS DE REGISTRE À RESSORT DE RAPPEL DE SÉRIE 3 NM
1.Montez l’actionneur en fonction de l’usage prévu
(rotation horaire ou antihoraire pour ouvrir le volet ou la vanne).
2.Branchez l’alimentation aux fils d’alimentation et neutre. (Voir la Fig. 11 et le Tableau 3.)
3.Réglez le cadran « Sélection de mode » au signal de commande souhaité. (Voir la Fig. 5.)
4.Envoyez le signal de commande de position 50 % de l’actionneur.
a.Signal d’entrée V CC : envoyez un signal de 5-6 V CC au fil de commande (BLANC). Voir la Fig. 14.
b.Signal d’entrée mA : envoyez un signal de 10-12 mA au fil de commande (BLANC). Voir la Fig. 14.
c.Flottant : envoyez un signal 24 V CA au fil 0°-90°
(3) ou 90°-0° (4) jusqu’à ce que l’appareil atteigne 50 %.
5.Laissez l’actionneur se rendre à la position 50 %.
6.Débranchez le fil d’alimentation (ROUGE).
7.Le ressort de l’actionneur revient à la position 0 %.
8.Rebranchez le fil d’alimentation (ROUGE), l’actionneur revient à la position 50 %.
1.Montez l’actionneur pour l’application requise en le tournant (dans le sens des aiguilles d'une montre
ou dans le sens inverse pour ouvrir le clapet).
2.Connectez le contrôleur adapté Sylk (S-BUS) aux bornes 3 et 4.
3.Connectez l’alimentation aux bornes 1 et 2.
4.Sélectionnez l’adresse appropriée sur le cadran afin de correspondre à l’adresse que vous souhaitez utiliser (comme illustré dans le tableau à côté du cadran).
5.Appliquez la commande S-BUS via le contrôleur connecté adapté Sylk pour la position de l’actionneur.
6.Le mode de test local (mode de mise en service rapide) peut être sélectionné en sélectionnant la position 6 dans le cadran de sélection d’adresse. N’oubliez pas de réinitialiser le cadran avec les paramètres appropriés pour l'adresse de votre choix une fois le test terminé.
1.Branchez un multimètre, réglé à VCC, au fil neutre (NOIR) et au fil de rétroaction (BRUN).
2.Envoyez le même signal qu’à l’étape 4 du fonctionnement par modulation.
3.La valeur du multimètre augmente pour correspondre au signal d’entrée alors que l’actionneur passe en position complètement ouverte ou complètement fermée.
4.Envoyez le même signal qu’à l’étape 6 du fonctionnement par modulation.
5.La valeur du multimètre diminue pour correspondre au signal d’entrée alors que l’actionneur passe à la position 0 %.
1.Montez l’actionneur en fonction de l’usage prévu
(rotation horaire ou antihoraire pour ouvrir le volet ou la vanne).
2.Vérifiez la position de l’actionneur et assurez-vous de la présence de tensions 24 V CC/CA aux raccordements appropriés. (Voir la Fig. 11.)
3.Envoyez le signal de commande aux raccordements appropriés pour déplacer le volet à la position opposée. L’actionneur devrait entraîner le volet ou la vanne.
4.Si l’actionneur ne s’active pas, assurez-vous qu’il est
bien installé pour une rotation horaire ou antihoraire .
5.Si l’actionneur est bien installé, mais ne fonctionne toujours pas, remplacez-le.
•Appareil conforme aux normes ISO/IEC 14443A.
•LE NFC peut être utilisée pour la communication entre l’actionneur et un appareil prenant en charge LE NFC.
•La zone d’accès NFC est indiquée à la Fig. 21.
•Si le point d’accès NFC est orienté vers le volet, l’accès du côté des fils d’alimentation pourrait être limité selon l’installation ou les capacités NFC de l’appareil.
NFC
M37468
Fig. 21. Zone d’accès NFC.
31-00141M—06 |
10 |