Trane TCONT803AS32DA, TCONT802AS32DA User Manual

4.5 (2)

TCONT802AS32DA Touch Screen and TCONT803AS32DA Touch Screen with Dehumidification Control Comfort Controls

18-HD25D19-3

INSTALLATION INSTRUCTIONS

APPLICATION

The TCONT802AS32DA and TCONT803AS32DA Touch Screen Comfort Controls provide electronic control of 24 Vac heating and cooling systems. See Table 1 for a general description.

Table 1. TCONT802AS32DA and TCONT803AS32DA Comfort Control Description.

 

 

 

 

 

Power Method

Changeover

System Selection

Fan Selection

Comments

 

 

 

 

 

 

 

 

 

 

24 Vac common

Automatic or

Heat-Off-Cool-

On-Auto-Circ

System and Fan selection

wire

manual selectable

Auto (Em. Heat

 

vary based on system type

 

 

for heat pumps)

 

 

 

 

 

System and Fan selection

 

 

 

 

 

 

 

 

vary based on System type.

 

 

 

 

Humidity sensor to control

 

 

 

 

dehumidification.

 

 

 

 

 

MERCURY NOTICE

If this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash. Dispose of properly.

Contact your local waste management authority for instructions regarding recycling and the proper disposal of the old control.

INSTALLATION

When Installing this Product...

1.Read these instructions carefully. Failure to follow the instructions can damage the product or cause a hazardous condition.

2.Installer must be a trained, experienced service technician.

3.After completing installation, use these instructions to check out the product operation.

Selecting Location

Install the comfort control about 5 ft. (1.5m) above the floor in an area with good air circulation at average temperature. See Fig. 1.

NO

 

YES

 

NO

NO

5 FEET

[1.5 METERS]

M19925

Fig. 1. Selecting comfort control location.

U.S. Pat. No. 6595430, D509151, and Other Patents Pending

69-1790-3

TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION

Do not install the comfort control where it can be affected by:

Drafts or dead spots behind doors and in corners.

Hot or cold air from ducts.

Radiant heat from sun or appliances.

Concealed pipes and chimneys.

Unheated (uncooled) areas such as an outside wall behind the comfort control.

Installing Wallplate

CAUTION

Electrical Hazard.

Can cause electrical shock or equipment damage.

Disconnect power before wiring.

The comfort control can be mounted horizontally on the wall or on a 4 in. x 2 in. (101.6 mm x 50.8 mm) wiring box.

1.Position and level the wallplate (for appearance only).

2.Use a pencil to mark the mounting holes.

WALL

WIRES THROUGH WALL

AND WIRE SLOT

WALL ANCHORS (2)

MOUNTING

HOLES

MOUNTING

SCREWS (2)

M19916

Fig. 2. Mounting wallplate.

3.Remove the wallplate from the wall and, if drywall, drill two 3/16-in. holes in the wall, as marked. For firmer material such as plaster, drill two 7/32-in. holes. Gently tap anchors (provided) into the drilled holes until flush with the wall.

4.Position the wallplate over the holes, pulling wires through the wiring opening. See Fig. 2.

5.Insert mounting screws into the holes and tighten.

3.Securely tighten each screw.

4.Push excess wire back into the hole.

5.Plug the hole with nonflammable insulation to prevent drafts from affecting the comfort control.

HEAT PUMP

HEAT/COOL

Y2

Y2

RC

RC

F

 

R

R

X2

 

W1

O

W1

W2

Y

Y

S1

S1

G

G

S2

S2

B

B

 

SCREW TERMINALS

M22636

Fig. 3. Selecting terminal identifications for system type.

Table 2. Selecting Terminal Identifications for System Type.

 

 

 

 

Wallplate

Wiring

System Type

Terminal

Diagram

Identifications

Reference

 

 

 

Standard Heat/Cool

Heat/Cool

Fig. 5,

 

 

Fig. 6

 

 

 

Standard Multistage

Heat/Cool

Fig. 7,

up to 2 Heat/2 Cool

 

Fig. 8

 

 

 

Heat Pump with

Heat Pump

Fig. 9,

Electric Auxiliary

 

Fig. 10,

(Backup) Heat

 

Fig. 11

 

 

 

Heat Pump with

Heat Pump

Fig. 12,

Fossil Fuel Auxiliary

 

Fig. 13,

(Dual Fuel) Heat

 

Fig. 14,

 

 

Fig. 15

 

 

 

NOTE: The factory default setting is configured for a 1 Heat/1 Cool System with a gas furnace.

WIRING (FIG. 5-15)

All wiring must comply with local electrical codes and ordinances.

1.Select set of terminal identifications (Table 2) that corresponds with system type (heat/cool or heat pump in Fig. 3).

2.Loosen the screws for the appropriate system type selected; see Table 2. Insert wires in the terminal block under the loosened screw. See Fig. 4.

M19917

Fig. 4. Inserting wires in terminal block.

IMPORTANT

Use 18 gauge comfort control wire.

Pub. No. 18-HD25D19-3

 

69-1790—3

2

Trane TCONT803AS32DA, TCONT802AS32DA User Manual

TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION

 

 

HEAT/COOL

Y2

1

RC

 

 

R

 

 

W1

W2

 

Y

S1

 

G

S2

 

B

 

T

 

 

2

 

R

 

Y

 

G

 

 

 

W2

 

W3

 

B/C

AIR

 

 

 

W1

 

 

 

 

 

 

 

 

 

HANDLER

INDOOR

OUTDOOR

 

ODT

 

COOLING UNIT

Y

B

O.D. SECTION

 

(SINGLE STAGE)

 

 

 

TO POWER SUPPLY

(3 PH

 

PER LOCAL CODES

ONLY)

 

 

 

1FACTORY INSTALLED JUMPER.

OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE

2ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE

FROM THE THERMOSTAT CABLE.

M22637

 

 

 

HEAT/COOL

Y2

1

RC

 

 

R

 

 

W1

W2

 

Y

S1

 

G

S2

 

B

2

T

 

 

 

R

BK

O

YLO

Y

G

W1

W2

B/C

INDOOR

OUTDOOR

VARIABLE SPEED

TWO-STAGE

FURNACE/VARIABLE SPEED AIR HANDLER

Y1 Y2

B

COOLING UNIT

O.D. SECTION

 

 

(TWO STAGE)

TO POWER SUPPLY

(3 PH

 

PER LOCAL CODES

ONLY)

 

 

 

1FACTORY INSTALLED JUMPER.

2OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE

FROM THE THERMOSTAT CABLE.

M22640

 

Fig. 5. Typical hookup of single-stage heat and cool system with single transformer (1H/1C).

 

HEAT/COOL

Y2

RC

 

R

 

W1

W2

Y

S1

G

S2

B

 

T

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OIL

R

 

Y

 

G

T

 

T

W

B/C

 

 

FURNACE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OIL BURNER PRIMARY

 

 

 

 

 

 

 

 

 

 

INDOOR

 

 

 

 

 

 

 

 

 

 

 

 

 

OUTDOOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COOLING UNIT

 

 

Y

 

 

 

 

B

 

 

O.D. SECTION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(SINGLE STAGE)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TO POWER SUPPLY

 

(3 PH

 

 

 

 

 

 

PER LOCAL CODES

 

ONLY)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE

FROM THE THERMOSTAT CABLE.

M22638

Fig. 6. Typical hookup of single-stage heat and cool system with two transformers (1H/1C).

Fig. 7. Typical hookup of two-stage indoor and two-stage cooling unit in a single transformer system (2H/2C or 2H/1C or 1H/2C).

 

 

 

 

 

 

HEAT/COOL

 

Y2

 

 

 

 

1

 

RC

 

 

 

 

 

 

 

 

R

 

 

 

 

 

 

 

 

 

W1

 

W2

 

 

 

 

 

 

Y

 

 

S1

 

 

 

 

 

 

G

 

 

S2

 

 

 

 

 

 

B

 

 

2

 

T

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

R

BK

O

YLO

Y

G

W1

W2

B/C

VARIABLE SPEED

TWO STAGE

 

 

 

 

 

 

 

 

 

FURNACE

 

 

 

 

 

 

 

 

 

INDOOR

 

 

 

 

 

 

 

 

 

OUTDOOR

 

 

 

 

 

 

 

 

 

16 SEER

 

Y2

Y1

 

 

 

 

 

B

COOLING UNIT

 

 

 

 

 

 

O.D. SECTION

 

 

 

 

 

 

 

 

 

(TWO STEP)

TO POWER SUPPLY

(3 PH

 

PER LOCAL CODES

ONLY)

 

 

1 FACTORY INSTALLED JUMPER.

2OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE.

3 THE INSTALLER MUST JUMPER AT THE LVTB “R” TO “O”. M24231

Fig. 8. Typical hookup of two-stage indoor and two-step scroll cooling unit in a single transformer system (2H/2C or 2H/1C or 1H/2C).

 

Pub. No. 18-HD25D19-3

3

69-1790—3

TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION

HEAT PUMP

Y2

1

RC

 

F

 

R

 

X2

 

O

 

W1

 

Y

 

S1

 

G

 

S2

 

B

 

2

T

 

 

 

 

 

 

 

I-PF

PM-A

 

 

 

 

SUPPL. HTR.

 

R

Y

O

G W1 W2

W3 CONTROL BOX

B/C T

 

 

 

 

REQ.

 

 

 

 

ODT-1

FOR

 

 

 

 

TO POWER 3 PH

 

 

 

 

 

 

 

 

 

ODT-2

SUPPLY PER

 

 

 

 

LOCAL

 

 

 

 

 

CODES AND

 

 

 

 

 

AS DEFINED

 

 

 

 

 

IN FIELD

 

 

 

 

INDOOR

WIRING TABLE

 

 

 

 

OUTDOOR

 

 

R

Y

O

X2/BK

BR(T)

B

 

 

 

 

TO POWER SUPPLY

(3 PH

 

 

 

 

PER LOCAL CODES

ONLY)

 

 

 

 

 

1FACTORY INSTALLED JUMPER.

2OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE.

AIR

HANDLER

HEAT PUMP

O.D. SECTION (SINGLE STAGE)

M22641

Fig. 9. Typical hookup of single-stage heat pump with auxiliary/backup heat (2H/1C heat pump).

HEAT PUMP

Y2

1

RC

 

F

 

R

 

X2

 

O

 

W1

 

Y

 

S1

 

G

 

S2

 

B

 

2

T

 

 

 

 

 

 

 

I-PF

PM-A

 

 

 

 

 

 

 

 

 

SUPPL. HTR.

 

R

BK

Y

YLO

O

G

W1

W2

W3

CONTROL BOX

 

 

 

 

 

 

 

 

 

 

 

 

 

REQ.

 

 

 

 

 

 

ODT-1

 

 

FOR

 

 

 

 

 

 

 

TO POWER

3 PH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ODT-2

 

SUPPLY PER

 

 

 

 

 

 

 

LOCAL

 

 

 

 

 

 

 

 

 

 

CODES AND

 

 

 

 

 

 

 

 

 

 

AS DEFINED

 

 

 

 

 

 

 

 

 

 

IN FIELD

 

 

 

 

 

 

INDOOR

 

 

WIRING TABLE

 

 

 

 

 

OUTDOOR

 

 

 

 

B/C T VARIABLE SPEED AIR HANDLER

R

Y2

Y1

O

X2/BK

BR(T)

F

B

 

 

 

 

 

 

 

 

 

TO POWER SUPPLY

(3 PH

 

 

ONLY)

 

PER LOCAL CODES

 

 

 

 

 

 

 

 

HEAT PUMP O.D. SECTION (TWO STAGE)

1FACTORY INSTALLED JUMPER.

2OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS.

WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE.

M22642

Fig. 10. Typical hookup of multistage heat pump with auxiliary/backup heat (3H/2C heat pump).

Pub. No. 18-HD25D19-3

 

69-1790—3

4

TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION

HEAT PUMP

Y2

 

 

 

 

1

 

RC

F

 

 

 

 

 

 

R

 

X2

 

 

 

 

 

 

O

 

W1

 

 

 

 

 

 

Y

 

S1

 

 

 

 

 

 

G

 

S2

 

 

 

 

 

 

B

 

2

 

T

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

R

BK

O

G

YLO

Y

W1

W2

B/C

VARIABLE SPEED AIR HANDLER

 

 

INDOOR

 

 

OUTDOOR

 

 

16 SEER

R Y2 Y1 O X2/BK BR(T)

B

HEAT PUMP

O.D. SECTION

 

 

(TWO STEP)

TO POWER SUPPLY

(3 PH

 

PER LOCAL CODES

ONLY)

 

 

 

1 FACTORY INSTALLED JUMPER.

2OUTDOOR REMOTE SENSOR. WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE.

3

THE INSTALLER MUST JUMPER AT THE LVTB “R” TO “O”.

M24230

 

 

Fig. 11. Typical hookup of multistage two-step scroll heat pump with auxiliary/backup heat (3H/2C heat pump).

HEAT PUMP

 

Y2

RC

 

 

1

 

F

R

 

X2

O

 

W1

Y

2

S1

G

 

 

T

S2

B

 

 

 

 

 

 

 

 

NON-V.S.

R

G

Y

W1

W2

B/C

ONE OR TWO

 

 

 

 

 

 

STAGE GAS

 

 

 

 

 

 

FURNACE

 

 

 

INDOOR

 

 

 

 

 

OUTDOOR

 

 

 

1

2

R

Y

O

X2/BK

BR(T)

 

B

 

 

 

 

HEAT PUMP

 

 

 

 

 

O.D. SECTION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(SINGLE STAGE)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TO POWER SUPPLY

(3 PH

 

 

 

 

 

 

 

FACTORY INSTALLED JUMPER.

PER LOCAL CODES

ONLY)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUTDOOR REMOTE SENSOR. WIRES MUST HAVE A

CABLE SEPARATE FROM THE THERMOSTAT CABLE.

M24200

Fig. 12. Typical hookup of singe-stage heat pump with non-variable speed gas furnace.

 

Pub. No. 18-HD25D19-3

5

69-1790—3

TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION

 

 

 

 

 

HEAT PUMP

 

 

 

 

 

 

Y2

 

 

 

1

 

RC

 

 

 

F

 

 

 

 

R

 

 

 

 

 

 

 

 

 

 

 

X2

 

 

 

 

 

O

 

 

 

W1

 

 

 

 

 

Y

 

 

2

S1

 

 

 

 

 

G

 

 

 

 

 

 

 

 

 

 

 

T

S2

 

 

 

 

 

B

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VARIABLE

R

BK

O

G

YLO

Y

W1

W2

B/C

SPEED

TWO STAGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FURNACE

INDOOR

OUTDOOR

1

2

R

Y

O

BR/X2

BR(T)

 

B

 

 

 

HEAT PUMP

 

 

 

 

O.D. SECTION

 

 

 

OR BK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(SINGLE STAGE)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TO POWER SUPPLY

(3 PH

 

 

 

 

 

 

FACTORY INSTALLED JUMPER.

PER LOCAL CODES

ONLY)

 

 

 

 

 

 

 

 

 

 

 

 

OUTDOOR REMOTE SENSOR. WIRES MUST HAVE A

CABLE SEPARATE FROM THE THERMOSTAT CABLE.

M24201

Fig. 13. Typical hookup of single-stage heat pump with two stage variable speed gas furnace (2H/1C heat pump).

Pub. No. 18-HD25D19-3

 

69-1790—3

6

Loading...
+ 14 hidden pages