Trane Voyager 12.5 to 25 Tons Installation and Maintenance Manual

4.5 (2)

Installation, Operation,

and Maintenance

Packaged Rooftop Air Conditioners

Voyager™ Heat Pump

12½ – 20 Ton, 60/50 Hz

Model Numbers

WS*150-240

SAFETY WARNING

Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and airconditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.

May 2014

RT-SVX33E-EN

Warnings, Cautions and Notices

Warnings, Cautions and Notices. Note that warnings, cautions and notices appear at appropriate intervals throughout this manual. Warnings are provide to alert installing contractors to potential hazards that could result in personal injury or death. Cautions are designed to alert personnel to hazardous situations that could result in personal injury, while notices indicate a situation that may result in equipment or property-damage-only accidents.

Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.

ATTENTION: Warnings, Cautions and Notices appear at appropriate sections throughout this literature. Read these carefully:

WARNING

CAUTIONs

NOTICE:

Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.

Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.

Indicates a situation that could result in equipment or property-damage only

Important

Environmental Concerns!

Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants-including industry replacements for CFCs such as HCFCs and HFCs.

Responsible Refrigerant Practices!

Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified. The Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.

WARNING

Personal Protective Equipment (PPE)

Required!

Installing/servicing this unit could result in exposure to electrical, mechanical and chemical hazards.

Before installing/servicing this unit, technicians MUST put on all PPE required for the work being undertaken (Examples; cut resistant gloves/sleeves, butyl gloves, safety glasses, hard hat/bump cap, fall protection, electrical PPE and arc flash clothing). ALWAYS refer to appropriate Material Safety Data Sheets (MSDS)/Safety Data Sheets (SDS) and OSHA guidelines for proper PPE.

When working with or around hazardous chemicals, ALWAYS refer to the appropriate MSDS/SDS and OSHA/GHS (Global Harmonized System of Classification and Labelling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection and handling instructions.

If there is a risk of energized electrical contact, arc, or flash, technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other country-specific requirements for arc flash protection, PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASH CLOTHING. ENSURE ELECTRICAL METERS AND EQUIPMENT ARE PROPERLY RATED FOR INTENDED VOLTAGE.

Failure to follow instructions could result in death or serious injury.

WARNING

Proper Field Wiring and Grounding

Required!

All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury.

© 2014 Trane All rights reserved

RT-SVX33E-EN

Warnings, Cautions and Notices

Overview of Manual

Note: One copy of this document ships inside the control panel of each unit and is customer property. It must be retained by the unit’s maintenance personnel.

This booklet describes proper installation, operation, and maintenance procedures for air cooled systems.

By carefully reviewing the information within this manual and following the instructions, the risk of improper operation and/or component damage will be minimized.

It is important that periodic maintenance be performed to help assure trouble free operation. A maintenance schedule is provided at the end of this manual.

Should equipment failure occur, contact a qualified service organization with qualified, experienced HVAC technicians to properly diagnose and repair this equipment.

Revision Summary

RT-SVX33E-EN (27 May 2014)

New Low Leak Economizer & Fault Detection Diagnostics (FDD) Options

Updated Model Number Description Section

Added back Warranty Section

RT-SVX33E-EN

3

Table of Contents

Model Number Description . . . . . . . . . . . . . . . 5

General Information . . . . . . . . . . . . . . . . . . . . . 7

Unit Inspection . . . . . . . . . . . . . . . . . . . . . . . . 7

Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Unit Clearances . . . . . . . . . . . . . . . . . . . . . . . 7

Unit Description . . . . . . . . . . . . . . . . . . . . . . . 7

ReliaTel™ Control . . . . . . . . . . . . . . . . . . . . . 8

System Input Devices & Functions . . . . . . . 8

Zone Sensors . . . . . . . . . . . . . . . . . . . . . . . . 10

Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . 11

Unit Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

Factory-Mounted Unit Options . . . . . . . . . . . 26

Circuit Breaker (FIYUCB) & Unit Disconnect

(FIYUDC) . . . . . . . . . . . . . . . . . . . . . . . . . . . .

26

Powered/Unpowered Convenience Outlet 27

Return Air Smoke Detector . . . . . . . . . . . . .

28

Pre-Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

31

Start Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

33

Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . .

35

Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . .

38

ReliaTel Controls . . . . . . . . . . . . . . . . . . . . .

38

System Status Checkout Procedure . . . . .

38

Resetting Cooling and Heating Lockouts . 39

Zone Temperature Sensor (ZTS) Service Indi-

cator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

40

Clogged Filter Switch . . . . . . . . . . . . . . . . .

40

Fan Failure Switch . . . . . . . . . . . . . . . . . . . .

40

Condensate Overflow Switch . . . . . . . . . . .

40

Zone Temperature Sensor (ZTS) Tests . .

40

Programmable & Digital Zone Sensor Test 41

Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . .

43

Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

44

Heat Pump . . . . . . . . . . . . . . . . . . . . . . . . . . .

44

4

RT-SVX33E-EN

Model Number Description

W

S

D

1

5

0

 

E

3

 

R

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

3

4

5

6

7

8

9

Digit 1 — Unit Type

W = Packaged Cooling, Electric Heat

Digit 2 — Efficiency

S = Standard Efficiency

Digit 3 — Airflow Configuration

D

=

Downflow

H

=

Horizontal

Digit 4, 5, 6 — Nominal Gross

Cooling Capacity (MBh)

150 = 12½ Tons, 60Hz

155 = 15 Tons, 50Hz

180 = 15 Tons, 60Hz

200 = 20 Ton, 50Hz

240 = 20 Tons, 60Hz

Digit 7 — Major Design

Sequence

E = R-410A Refrigerant

Digit 15 — Supply Fan/Drive

Type/Motor

0= Standard Motor

1= Oversized Motor2

3 = High Efficiency Motor2

6= Single Zone Variable Air Volume Standard Motor

7= Multi-Speed Standard Motor

8= Single Zone Variable Air Volume Oversized Motor

9= Multi-Speed Oversized Motor

A= Single Zone Variable Air Volume Standard Motor w/ Shaft Ground Ring

B= Multi-Speed Standard Motor w/ Shaft Ground Ring

C= Single Zone Variable Air Volume Oversized Motor w/ Shaft Ground Ring

D= Multi-Speed Oversized Motor w/ Shaft Ground Ring

Digit 8 — Voltage Selection

3

=

208-230/60/3

4

=

460/60/3

W

=

575/60/3

T

=

200/50/1

D

=

380-415/50/3

Digit 9 — Unit Controls

R = Reliatel

Digit 10 — Heating Capacity

Note:

(Applicable to Digit 1 W models

 

 

only)

0

=

No Heat

G

=

18 kW Electric Heat

N

=

36 kW Electric Heat

P

=

54 kW Electric Heat

R

=

72 kW Electric Heat

Digit 11 — Minor Design

Sequence

Digit 12, 13 — Service Sequence

Digit 14 — Fresh Air Selection

0 = No Fresh Air

D= Econ Dry Bulb w/ Barometric Relief1

F= Econ Reference Enthaply w/ Barometric Relief1

H= Econ Comparative Enthaply w/ Barometric Relief1

K= Low Leak Econ w/ Barometric Relief1

M= Low Leak Econ Reference Enthalpy w/ Barometric Relief1

P= Low Leak Econ Comparative Enthalpy w/ Barometric Relief1

Digit 16 — Hinged Service

Access / Filters

0= Standard Panels/Standard Filters13

A= Hinged Access/Standard Filters13

B= Standard Panels / 2" MERV 8 Filters2

C= Hinged Access / 2" MERV 8 Filters2

D= Standard Panels / MERV 13 Filters2

E= Hinged Access / MERV 13 Filters2

Digit 17 — Condenser Coil

Protection

0= Standard Coil

1= Standard Coil With Hail Guard

2= Black Epoxy Pre-Coated Coil

3= Black Epoxy Pre-Coated Coil with Hail Guard

Digit 18 — Through The Base

Provisions

0

=

No Through The Base Provisions

A

=

Through The Base Electric3

D

=

Through The Base Utilities Access

Digit 19 — Disconnect Switch/

Circuit Breaker4

0= No Disconnect/circuit break

1= Unit Mounted Non-Fused Disconnect Switch

2= Unit Mounted Circuit Breaker

Digit 20 — Convenience Outlet

Option

0 = Without Convenience Outlet

A= Unpowered Convenience Outlet5

B= Powered Convenience Outlet5

G

 

B

*

*

 

 

 

 

 

 

10

11

12

13

Digit 21 — Communications

Options

0= Without Communications Options

1= Trane Communications Interface

2= Lontalk Communications Interface

6= Building Automation Control Network Communications Interface

Digit 22 — Refrigeration System Option

0 = Standard refrigeration system

Digit 23 — Refrigeration

Controls

0= Without Refrigeration Controls

1= Frostat6

Digit 24 — Smoke Detector7, 8

0 = Without Smoke Detector

A= Return Air Smoke Detector

B= Supply Air Smoke Detector

C= Return/Supply Air Smoke Detector

D= Plenum Smoke Detector9

Digit 25 — System Monitoring

Controls6

0= No Monitoring Controls

1= Clogged Filter Switch

2= Fan Failure Switch

3= Discharge Air Sensing

4= Clogged Filter Switch and Fan Failure

5= Clogged Switch and Discharge Air Sensing

6= Fan Failure Switch and Discharge Air Sensing

7= Clogged Filter Switch, Fan Failure Switch and Discharge Air Sensing

A= Condensate Drain Pan Overflow Switch

B= Clogged Filter Switch and Condensate Drain Pan Overflow Switch

C= Fan Failure Switch and Condensate Drain Pan Overflow Switch

D= Discharge Air Sensing and Condensate Drain Pan Overflow Switch

E= Clogged Filter Switch, Fan Failure Switch and Condensate Drain Pan Overflow Switch

F= Clogged Filter Switch, Discharge Air Sensing Tube and Condensate Drain Pan Overflow Switch

G= Fan Failure Switch, Discharge Air Sensing Tube and Condensate Drain Pan Overflow Switch

RT-SVX33E-EN

5

Model Number Description

H= Clogged Filter Switch, Fan Failure Switch, Discharge Air Sensing and Condensate Drain Pan Overflow Switch

Digit 26 - System Monitoring

Controls

0 = No Monitoring Controls

A= Demand Control Ventilation (CO2)10

B= FDD (Fault Detection and Diagnostics)

C= FDD (Fault Detection Diagnostics)

&Demand Control Ventilation (CO2)10

Digit 27 - Unit Hardware

Enhancements

0= No Enhancements

1= Stainless Steel Drain Pan

Digit 28 - Short Circuit Current

Rating

0

=

Standard SCCR

A

=

65kA SCCR Option11, 12

Digit 31 - Advanced Unit

Controls

0= Standard Unit Controls

1= Human Interface14

Note: Most Factory Installed Options available for Downflow Air Discharge units only. Please verify with ordering system for availability.

Model Number Notes

1.Some field set up required.

2.Available factory installed on downflow AND horizontal units. Verify with ordering system.

3.Through-the-base electrical option or Horizontal-Side Access must be ordered with either unit mounted disconnect or circuit breaker.

4.Unit mounted disconnect and circuit breakers are mutually exclusive of each other.

5.Must be ordered with Through- the-Base Electrical option or Horizontal-Side Access and either Unit Mounted Disconnect or Circuit Breaker.

6.ReliaTel Options Module is required when ordering the following accessories: Clogged Filter Switch, Fan Fail Switch,

Condensate Overflow Switch,

Discharge Air Sensing Kit, Frostat,

Ventilation Override, Smoke

Detector, Dehumidification and

Modulating Gas Heat Furnace.

7.Requires ReliaTel Options Module.

8.Option cannot be ordered in conjunction with field installed economizer on downflow units. Must be factory installed. The return air smoke detector may not fit up or work properly on the Voyager units when used in conjunction with 3rd party accessories (such as bolt on heat wheels, economizers, and power exhaust). Do not order the return air smoke detectors when using this type of accessory.

9.Supply and/or return smoke detector may not be used with the plenum smoke detector.

10.Demand Control Ventilation Option includes wiring only. The C02 sensor is a field-installed only option.

11.Only available where MOP is above 60A.

12.575 VAC option is 25kA.

13.Standard filters are not available with Low Leak Economizers.

14.Human Interface is standard with FDD (Fault Detection Diagnostics).

6

RT-SVX33E-EN

General Information

Unit Inspection

As soon as the unit arrives at the job site:

Verify that the nameplate data matches the data on the sales order and bill of lading (including electrical data).

Verify that the power supply complies with the unit nameplate specifications.

Visually inspect the exterior of the unit, including the roof, for signs of shipping damage.

Visually inspect the internal components for shipping damage as soon as possible after delivery and before it is stored. Do not walk on the sheet metal base pans.

If concealed damage is discovered, notify the carrier’s terminal of damage immediately by phone and by mail. Concealed damage must be reported within 15 days.

Request an immediate joint inspection of the damage by the carrier and the consignee. Do not remove damaged material from the receiving location. Take photos of the damage, if possible. The owner must provide reasonable evidence that the damage did not occur after delivery.

Notify the appropriate sales representative before installing or repairing a damaged unit.

WARNING

Fiberglass Wool!

Product contains fiberglass wool. Disturbing the insulation in this product during installation, maintenance or repair will expose you to airborne particles of glass wool fibers and ceramic fibers known to the state of California to cause cancer through inhalation. You MUST wear all necessary Personal Protective Equipment (PPE) including gloves, eye protection, mask, long sleeves and pants when working with products containing fiberglass wool. Exposition to glass wool fibers without all necessary PPE equipment could result in cancer, respiratory, skin or eye irritation, which could result in death or serious injury.

Precautionary Measures

Avoid breathing fiberglass dust.

Use a NIOSH approved dust/mist respirator.

Avoid contact with the skin or eyes. Wear long-sleeved, loose-fitting clothing, gloves, and eye protection.

Wash clothes separately from other clothing: rinse washer thoroughly.

Operations such as sawing, blowing, tear-out, and spraying may generate fiber concentrations requiring additional respiratory protection. Use the appropriate NIOSH approved respiration in these situations.

First Aid Measures

Eye Contact - Flush eyes with water to remove dust. If symptoms persist, seek medical attention.

Skin Contact - Wash affected areas gently with soap and warm water after handling.

Storage

Take precautions to prevent condensate from forming inside the unit’s electrical compartments and motors if:

15.The unit is stored before it is installed; or,

16.The unit is set on the roof curb, and temporary heat is provided in the building. Isolate all side panel service entrances and base pan openings (e.g., conduit holes, S/A and R/A openings, and flue openings) from the ambient air until the unit is ready for start-up.

Note: Do not use the unit’s heater for temporary heat without first completing the start-up procedure detailed under “Start Up,” p. 33.

The manufacturer will not assume any responsibility for equipment damage resulting from condensate accumulation on the unit’s electrical and/or mechanical components.

Unit Clearances

Figure 1, p. 11 illustrates the minimum operating and service clearances for either a single or multiple unit installation. These clearances are the minimum distances necessary to assure adequate serviceability, cataloged unit capacity, and peak operating efficiency.

Providing less than the recommended clearances may result in condenser coil starvation, “short-circuiting” of exhaust and economizer airflows, or recirculation of hot condenser air.

Unit Description

Before shipment, each unit is leak tested, dehydrated, charged with refrigerant and compressor oil, and run tested for proper control operation.

The condenser coils are aluminum fin, mechanically bonded to copper tubing.

Direct-drive, vertical discharge condenser fans are provided with built-in thermal overload protection.

The ReliaTel™ Control Module is a microelectronic control system that is referred to as “Refrigeration Module” (RTRM). The acronym RTRM is used extensively throughout this document when referring to the control system network.

This module through Proportional/Integral control algorithms perform specific unit functions that governs unit operation in response to; zone temperature, supply air

RT-SVX33E-EN

7

General Information

temperature, and/or humidity conditions depending on the application. The stages of capacity control for these units are achieved by starting and stopping the compressors.

The RTRM is mounted in the control panel and is factory wired to the respective internal components. The RTRM receives and interprets information from other unit modules, sensors, remote panels, and customer binary contacts to satisfy the applicable request for cooling.

ReliaTel™ Control

Economizer Control Actuator

The ECA monitors the mixed air temperature, return air temperature, minimum position setpoint (local or remote), power exhaust setpoint, CO2 setpoint, CO2, and ambient dry bulb/enthalpy sensor or comparative humidity (return air humidity against ambient humidity) sensors, if selected, to control dampers to an accuracy of +/- 5% of stroke. The actuator is spring returned to the closed position any time that power is lost to the unit. It is capable of delivering up to 25 inch pounds of torque and is powered by 24 Vac.

RTCI – ReliaTel™ Trane Communication

Interface (Optional)

This module is used when the application calls for an ICS™ building management type control system. It allows the control and monitoring of the system through an ICS panel. The module can be ordered from the factory or ordered as a kit to be field installed. Follow the installation instruction that ships with each kit when field installation is necessary.

RLCI – ReliaTel™ LonTalk Communication

Interface (Optional)

This module is used when the application calls for an ICS™ building management type control system that is LonTalk. It allows the control and monitoring of the system through an ICS panel. The module can be ordered from the factory or ordered as a kit to be field installed. Follow the installation instruction that ships with each kit when field installation is necessary.

RTOM – ReliaTel™ Options Module (Optional)

The RTOM monitors the supply fan proving, clogged filter, supply air temperature, exhaust fan setpoint, supply air tempering, Frostat™ and smoke detector. Refer to system input devices and functions for operation.

System Input Devices &

Functions

The RTRM must have a zone sensor or thermostat input in order to operate the unit. The flexibility of having several mode capabilities depends upon the type of zone sensor or thermostat selected to interface with the RTRM.

The descriptions of the following basic Input Devices used within the RTRM network are to acquaint the operator with their function as they interface with the various modules. Refer to the unit’s electrical schematics for the specific module connections.

The following Controls are Available from the Factory for Field Installation:

Supply Fan Failure Input (Optional)

The Fan Failure Switch can be connected to sense indoor fan operation:

FFS (Fan Failure Switch) If air flow through the unit is not proven by the differential pressure switch connected to the RTOM (factory set point 0.07 “ w.c.) within 40 seconds nominally, the RTRM will shut off all mechanical operations, lock the system out, send a diagnostic to ICS, and the SERVICE output will flash. The system will remain locked out until a reset is initiated either manually or through ICS.

Drain Pan Condensate Overflow Switch (Optional)

This input incorporates the Condensate Overflow Switch (COF) mounted on the drain pan and the ReliaTel Options Module (RTOM). When the condensate level reaches the trip point for 6 continuous seconds, the RTOM will shut down all unit function until the overflow condition has cleared. The unit will return to normal operation after 6 continuous seconds with the COF in a non-tripped condition. If the condensate level causes the unit to shutdown more than 2 times in a 3 day period, the unit will be locked-out of operation. A manual reset of the diagnostic system through the Zone Sensor or Building Automation System (BAS) will be required. Cycling unit power will also clear the fault."

Clogged Filter Switch (Optional)

The unit mounted clogged filter switch monitors the pressure differential across the return air filters. It is mounted in the filter section and is connected to the RTOM. A diagnostic SERVICE signal is sent to the remote panel if the pressure differential across the filters is at least 0.5" w.c. The contacts will automatically open when the pressure differential across the filters decreases to approximately 0.4" w.c. The clogged filter output is energized when the supply fan is operating and the clogged filter switch has been closed for at least 2 minutes.

8

RT-SVX33E-EN

General Information

The system will continue to operate regardless of the status of the filter switch.

Please note that on units equipped with factory installed MERV 13 filters, a clogged filter switch with different pressure settings will be installed. This switch will close when the differential pressure is approximately 0.8' w.c. and open when the differential falls to 0.7" w.c.

Compressor Disable (CPR1/2)

This input incorporates the low pressure control (LPC) of each refrigeration circuit and can be activated by opening a field supplied contact installed on the LTB.

If this circuit is open before the compressor is started, the compressor will not be allowed to operate. Anytime this circuit is opened for 1 continuous second during compressor operation, the compressor for that circuit is immediately turned “Off”. The compressor will not be allowed to restart for a minimum of 3 minutes should the contacts close.

If four consecutive open conditions occur during the first three minutes of operation, the compressor for that circuit will be locked out, a diagnostic communicated to the remote panel (if installed), and a manual reset will be required to restart the compressor.

Low Pressure Control

ReliaTel Control

When the LPC is opened for 1 continuous second, the compressor for that circuit is turned off immediately. The compressor will not be allowed to restart for a minimum of 3 minutes.

If four consecutive open conditions occur during the first three minutes of operation, the compressor will be locked out, a diagnostic communicated to ICS™ if applicable, and a manual reset will be required to restart the compressor.

High Pressure Control (Optional)

ReliaTel Control

The high pressure controls are wired in series between the compressor outputs on the RTRM and the compressor contactor coils. If the high pressure control switch opens, the RTRM senses a lack of current while calling for cooling and locks the compressor out.

On dual circuit units, if the high pressure control opens, the compressor on the affected circuit is locked out. A manual reset for the affected circuit is required.

Power Exhaust Control (Optional)

The power exhaust fan is started whenever the position of the economizer dampers meets or exceed the power exhaust setpoint when the indoor fan is on.

The setpoint panel is located in the return air section and is factory set at 25%.

Lead/Lag Control (Dual Circuit Only)

Lead/Lag is a selectable input located on the RTRM. The RTRM is configured from the factory with the Lead/Lag control disabled. To activate the Lead/Lag function, simply cut the wire connected to J3-8 at the RTRM. When it is activated, each time the designated lead compressor is shut off due to the load being satisfied, the lead compressor or refrigeration circuit switches. When the RTRM is powered up, i.e. after a power failure, the control will default to the number one circuit compressor.

Evaporator Frost Control

This input incorporates the Frostat™ control (FOS) mounted in the indoor coil and can be activated by closing a field supplied contact installed in parallel with the FOS.

If this circuit is closed before the compressor is started, the compressor will not be allowed to operate. Anytime this circuit is closed for 1 continuous second during compressor operation, the compressor for that circuit is immediately turned “Off”. The compressor will not be allowed to restart for a minimum of 3 minutes should the FOS open.

Smoke Detector Sensor (Optional)

This sensor is only applicable on units equipped with a RTOM. It provides high limit “shutdown” of the unit and requires a manual reset. The sensor is used to detect smoke due to fire in the air conditioning or ventilation ducts.

The supply and return air smoke detectors are designed to shut off the unit if smoke is sensed in the supply air stream or return air stream. This function is performed by sampling the airflow entering the unit at the return air opening. Follow the instructions provided below to assure that the airflow through the unit is sufficient for adequate sampling. Failure to follow these instructions will prevent the smoke detectors from performing it's design function.

Important: Airflow through the unit is affected by the amount of dirt and debris accumulated on the indoor coil and filters. To insure that airflow through the unit is adequate for proper sampling by the return air smoke detector, complete adherence to the maintenance procedures, including recommended intervals between filter changes, and coil cleaning is required.

Periodic checks and maintenance procedures must be performed on the smoke detector to insure that it will function properly. For detailed instructions concerning these checks and procedures, refer to the appropriate section(s) of the smoke detector Installation and Maintenance Instructions provided with the literature package for this unit.

In order for the supply air smoke detector or return air smoke detector to properly sense smoke in the supply air

RT-SVX33E-EN

9

General Information

stream or return air stream, the air velocity entering the smoke detector unit must be between 500 and 4000 feet per minute. Equipment covered in this manual will develop an airflow velocity that falls within these limits over the entire airflow range specified in the evaporator fan performance tables.

Zone Sensors

Note: Zone sensor required for units configured for Single Zone VAV indoor fan system control to enable Single Zone VAV functionality.

Zone Sensor Module (ZSM) (BAYSENS107*)

This electronic sensor features three system switch settings (Heat, Cool, and Off) and two fan settings (On and Auto). It is a manual changeover control with single setpoint. (Cooling Setpoint Only)

Zone Sensor (BAYSENS109*)

This electronic sensor features four system switch settings (Heat, Cool, Auto, and Off) and two fan settings (On and Auto) with four system status LED’s. It is a manual or auto changeover control with dual setpoint capability. It can be used with a remote zone temperature sensor BAYSENS075*.

Programmable Zone Sensor (BAYSENS119*)

Programmable Night Setback: Auto or manual changeover with seven-day programming. Keyboard selection of Heat, Cool, Fan, Auto, or On. All programmable sensors have System On, Heat, Cool, Service LED/indicators as standard. Night Setback Sensors have one (1) Occupied, one (1) Un-occupied, and one (1) Override program per day.

Remote Zone Sensor (BAYSENS073*)

This electronic sensor features remote zone sensing and timed override with override cancellation. It is used with a Trane Integrated Comfort™ building management system.

Remote Zone Sensor (BAYSENS074*)

This electronic sensor features single setpoint capability and timed override with override cancellation. It is used with a Trane Integrated Comfort™ building management system.

Remote Zone Sensor (BAYSENS016*)

This bullet type temperature sensor can be used for; outside air (ambient) sensing, return air temperature sensing, supply air temperature sensing, remote temperature sensing (uncovered). Wiring procedures vary according to the particular application and equipment

involved. Refer to the unit’s wiring diagrams for proper connections.

Remote Zone Sensor (BAYSENS075*)

This electronic sensor can be used with BAYSENS106*, 108*, 110*, 109* Remote Panels. When this sensor is wired to a BAYSENS109* Remote Panel, wiring must be 18 AWG Shielded Twisted Pair (Belden 8760 or equivalent). Refer to the specific Remote Panel for wiring details.

Wireless Zone Sensor (BAYSENS050)

This electronic sensor features five system settings (Auto, Off, Cool, Heat, and Emergency Heat) and with On and Auto fan settings. It is a manual or auto changeover control with dual setpoint capability. Other features include a timed override function, lockable system settings, and Fahrenheit or Celsius temperature display. Included with the wireless zone sensor will be a receiver that is to be mounted inside the unit, a mounting bracket, and a wire harness.

Thermostat (BAYSTAT150)

This thermostat is a multi-stage 3 heat/2 cool, autochangeover digital display thermostat. It is a programmable thermostat, and a 7-day programmable stat with night setback shall be available. In addition, it is wall mounted.

Thermostat (BAYSTAT151)

This thermostat is a single-stage 1 heat/1 cool, autochangeover digital display thermostat. It is a nonprogrammable, wall-mounted thermostat.

Thermostat (BAYSTAT155)

This thermostat is a multi-stage 3 heat/2 cool, auto changeover digital display thermostat. It is a nonprogrammable, wall-mounted thermostat, and it can be used for Economizer Operation.

Human Interface - 5 Inch Color

Touchscreen (Optional)

The 5 inch Color Touchscreen Human Interface provides an intuitive user interface to the rooftop unit that speeds up unit commissioning, shortens unit troubleshooting times, and enhances preventative maintenance measures. The human interface includes several features including:

Data trending capabilities by means of time series graphs

Historical alarm messages

Real-time sensor measurements

On board system setpoints

USB port that enables the downloading of component runtime information as well as trended historical sensor data

Customized reports

10

RT-SVX33E-EN

Unit Dimensions

Figure 1. Typical installation clearances for single & multiple unit applications

WITHOUT ECONOMIZER 5' 8" WITH ECONOMIZER

5' 0"

RT-SVX33E-EN

11

Unit Dimensions

Figure 2.

Heat pump models - 12½ - 15 tons

 

 

85 5/16"

 

 

2167MM

 

 

122 5/16"

 

 

3107MM

 

 

13/16"

 

 

20MM

FILTER

 

 

ACCESS DOOR

 

 

HORIZONTAL

 

 

 

 

54"

 

 

1372MM

 

 

1"

 

 

25.4MM

 

 

6 7/16"

DOWNFLOW CONDENSATE

163.51MM

DRAIN CONN 1" (25.4MM) NPT

 

48 1/2"

 

 

 

1231.90MM

33 3/16"

 

 

 

843MM

 

 

56"

 

 

 

1422MM

 

 

7/8" (22.23MM) DIA. HOLE

6 13/16"

 

 

(UNIT CONTROL WIRE)

173MM

 

 

 

 

 

SINGLE POINT

8 15/16"

 

 

POWER ENTRY

227MM

 

 

121 11/16"

 

 

SERVICE GAUGE

3091MM

 

84 3/16"

 

2 11/16"

2154MM

PORT ACCESS

 

68.26MM

 

 

 

 

3" (76MM) DIA HOLE

 

 

 

(UNIT POWER WIRE)

 

* All dimensions are in inches/millimeters.

Figure 3. Heat pump models - 12½ - 15 tons

* All dimensions are in inches/millimeters.

12

RT-SVX33E-EN

Trane Voyager 12.5 to 25 Tons Installation and Maintenance Manual

Unit Dimensions

Figure 4. Heat pump models - 12½ - 15 tons

Figure 5. Heat pump models - 12½ - 15 tons

9

1”

25.4 MM CURB FLANGE LONG SIDES

SHORT SIDES

* All dimensions are in inches/millimeters.

* Duct flanges mount 7-7/16" down inside the curb on the 1-1½ curb flanges.

Roofcurb is intended for downflow use only. * All dimensions are in inches/millimeters.

Figure 6. Heat pump models - 12½ - 15 tons

* All dimensions are in inches/millimeters.

RT-SVX33E-EN

13

Unit Dimensions

Figure 7.

Heat pump models - 20 tons

 

 

85 5/16"

 

 

2167MM

 

 

122 5/16"

 

 

3107MM

 

 

13/16"

 

 

20MM

FILTER

 

 

ACCESS DOOR

 

 

HORIZONTAL

 

 

 

 

64 1/8"

 

 

1629MM

 

 

1"

 

 

25.4MM

 

 

6 7/16"

DOWNFLOW CONDENSATE

163.51MM

DRAIN CONN 1" (25.4MM) NPT

 

48 1/2"

 

 

 

1231.90MM

33 3/16"

 

 

 

843MM

 

 

56"

 

 

 

1422MM

 

 

7/8" (22.23MM) DIA. HOLE

6 13/16"

 

 

(UNIT CONTROL WIRE)

173MM

 

 

 

 

 

SINGLE POINT

8 15/16"

 

 

POWER ENTRY

227MM

 

 

121 11/16"

 

 

SERVICE GAUGE

3091MM

 

84 3/16"

 

2 11/16"

2154MM

PORT ACCESS

 

68.26MM

 

 

 

 

3" (76MM) DIA HOLE

 

 

 

(UNIT POWER WIRE)

 

* All dimensions are in inches/millimeters.

Figure 8. Heat pump models - 20 tons

* All dimensions are in inches/millimeters.

14

RT-SVX33E-EN

Loading...
+ 30 hidden pages