Product Catalog
Packaged Rooftop Air Conditioners
Voyager™ Commercial with ReliaTel™Controls
27½ to 50 Tons - 60 Hz
22.9 to 41.7 Tons (81-148 kW) - 50 Hz
May 2014 |
RT-PRC033F-EN |
Packaged Rooftop Air Conditioners
Through the years, Trane has designed and developed the most complete line of Packaged Rooftop products available in the market today. Trane was the first to introduce the Micro—microelectronic unit controls—and has continued to improve and revolutionize this design concept.
The ReliaTel™ control platform offers the same great features and functionality as the original Micro, with additional benefits for greater application flexibility.
The Voyager™ Commercial line offers 27½ to 50 ton, 60 Hz and 23 to 42 ton 50 Hz models. Both 50 and 60 Hz models come in a choice of five sizes to meet the changing demands of the commercial rooftop market.
Trane customers demand products that provide exceptional reliability, meet stringent performance requirements, and are competitively priced. Trane delivers with Voyager Commercial.
Voyager Commercial features cutting edge technologies: reliable 3-D™ Scroll compressors, eStage for premium efficiency, Trane engineered ReliaTel controls, computer-aided run testing, and Integrated Comfort™ Systems.
So, whether you’re a contractor, the engineer, or an owner you can be certain Voyager Commercial Products are built to meet your needs.
It’s Hard To Stop A Trane.®
Revision Summary
RT-PRC033F-EN (05 May 2014)
•Added Low Leak Damper option, eStage, Ultra Low Leak Power Exhaust, Touchscreen Human Interface.
•Updated Features and Benefits, General Data, Model Number Description, Performance Data, Controls, Dimensional Data, Electrical Data, Mechanical Specifications.
© 2014 Trane All rights reserved |
RT-PRC033F-EN |
Table of Contents
Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Standard Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Optional Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Quality and Reliability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Easy to Install, Service and Maintain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Rigorous Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
ReliaTel™ Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Human Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Conversionless Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Drum and Tube Heat Exchanger (Gas Heat Only) . . . . . . . . . . . . . . . . . . . 9
Low Ambient Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Microchannel Condenser Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Phase Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Pressure Cutouts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Single Point Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Sloped Drain Pans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Temperature Discharge Limit (TDL) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Outstanding Optional Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
11 |
Variable Frequency Drives (VFD) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
11 |
Single Zone VAV – An Ideal Energy Saving Solution for Yesterday’s “Con- |
|
stant Volume” Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
11 |
Delivered VAV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
11 |
VariTrac™ Changeover-Bypass VAV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
12 |
Power Exhaust Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
12 |
Fresh Air Tracking Power Exhaust Option . . . . . . . . . . . . . . . . . . . . . . . . |
12 |
Statitrac™ Direct Space Building Pressurization Control . . . . . . . . . . . . |
12 |
Downflow and Horizontal Economizers . . . . . . . . . . . . . . . . . . . . . . . . . . |
12 |
Trane Air Quality (Traq™) Outside Air Measurement System . . . . . . . . |
13 |
Interoperability with BACnet (BCI-R) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
13 |
Interoperability with LonTalk® (LCI-R) . . . . . . . . . . . . . . . . . . . . . . . . . . . |
13 |
Trane Communication Interface (TCI) . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
13 |
Trane Wireless Comm Interface (WCI) . . . . . . . . . . . . . . . . . . . . . . . . . . . |
13 |
Modulating Hot Gas Reheat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
13 |
Tool-Less Condenser Hail Guards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
14 |
Trane Factory Built Roof Curbs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
14 |
Motor Shaft Grounding Ring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
14 |
Condensate Overflow Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
14 |
eStage - High Efficiency Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
14 |
One of Our Finest Assets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
14 |
Application Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
15 |
60/50 Hz Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Exhaust Air Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Application Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Altitude Corrections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
RT-PRC033F-EN |
3 |
Acoustical Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Clearance Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Duct Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
60 Hz Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Cooling Capacity Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Heating Capacity Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Air Delivery Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Unit Electrical Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Unit Designation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
50 Hz Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Cooling Capacity Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Heating Capacity Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Air Delivery Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Unit Electrical Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Unit Designation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Model Number Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
60 Hz Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
50 Hz Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
General Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Performance Adjustment Factors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Performance Data (60 Hz Units) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Performance Data (50 Hz Units) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
VAV Units Only—Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Supply Air Pressure Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Supply Air Temperature Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Zone Temperature Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
CV Units Only—Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Occupied Zone Temperature Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Single Zone VAV Units Only (SZ VAV)—Sequence of Operation . . . . . . . . . 93 Zone Temperature Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Control Sequences of Operation Common to CV, VAV, and SZ VAV . . . . . 95
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Electrical Service Sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Fresh Air, Power Exhaust Hoods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Field Installed Sensors—Variable Air Volume VAV . . . . . . . . . . . . . . . . . . . 109
4 |
RT-PRC033F-EN |
Field Installed Sensors—Constant Volume CV or Single Zone Variable Air Volume SZ VAV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Integrated Comfort™ System Sensors—CV, VAV, and SZ VAV . . . . . . . . . 110
Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Mechanical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
115 |
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
115 |
Control Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
117 |
Outside Air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
118 |
Exhaust Air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
118 |
Unit Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
119 |
RT-PRC033F-EN |
5 |
•R-410A refrigerant
•Factory installed and commissioned ReliaTel™ controls
•Compressor lead-lag
•Crankcase heaters
•Emergency stop input
•Frostat™ coil frost protection on all units
•Occupied-Unoccupied switching
•Phase monitor
•Temperature discharge limit (TDL)
•Timed override activation
•FC supply fans
•Supply airflow proving
•Supply air overpressurization protection on VAV units
•Dedicated downflow, horizontal, or mixed airflow configurations
•Trane 3-D™ Scroll compressors
•Two inch standard efficiency filters
•Sloped condensate drain pan
•Cleanable, IAQ-enhancing, foil faced insulation on all interior surfaces exposed to the unit air stream
•cULus listing on standard options
•CV, VAV, or SZ VAV Control
•Variable frequency drives on VAV and SZ VAV units (with or without bypass)
•Motors with Internal Shaft Grounding Ring
•Discharge air temperature sensor (CV only)
•High efficiency through eStage
•50% fresh air tracking power exhaust
•100% fresh air tracking power exhaust
•50% power exhaust
•100% power exhaust
•Ultra low leak power exhaust
•Barometric relief
•Statitrac™ direct space pressure control
•Trane Air Quality TRAQ™ (outside air measurement)
•BACnet Communication Interface (BCI-R)
•LonTalk® Communication Interface (LCI-R)
•Trane Communication Interface (TCI)
•Wireless Comm Interface (WCI)
6 |
RT-PRC033F-EN |
Features and Benefits
•Touchscreen Human Interface
•Natural gas heat with single stage, two stage and modulating options
•Two stage LP gas heat (kit only)
•Stainless steel heat exchanger (gas heat only)
•Electric heat
•Economizer with differential (comparative) enthalpy control
•Economizer with dry bulb control
•Economizer with reference enthalpy control
•Ultra low leak economizer
•Manual fresh air damper
•CO2 sensors for space comfort control (SCC) or discharge air control (DAC)
•Ventilation override
•Corrosion protected condenser coil
•Factory installed condenser coil guards
•Factory installed tool-less condenser hail guards
•Hinged service access
•Factory mounted disconnect with external handle (non-fused)
•Factory powered or field powered 15A GFI convenience outlet
•MERV 8 high efficiency 2” or 4” throwaway filters
•MERV 14 high efficiency 4” filters
•Clogged filter switch
•Condensate Overflow Switch
•High Fault SCCR
•Modulating hot gas reheat
•Remote potentiometer
•Service valves
•Sloped stainless steel evaporator coil drain pans
•Through-the-base electrical provision
Because today’s owners are very cost-conscious when it comes to service and maintenance, the Trane Voyager was designed with direct input from service contractors. This valuable information helped to design a product that would get the service technician off the job quicker and save the owner money.
All of Voyager’s designs were rigorously rain tested at the factory to ensure water integrity. Actual shipping tests are performed to determine packaging requirements. Units are test shipped around the country. Factory shake and drop tested as part of the package design process to help assure that the unit will arrive at your job site in top condition.
RT-PRC033F-EN |
7 |
Features and Benefits
Rigging tests include lifting a unit into the air and letting it drop one foot, assuring that the lifting lugs and rails hold up under stress. 100% coil leak test is performed at the factory. The evaporator coil is pressure tested to 450 psig and the condenser coil at 650 psig.
All parts are inspected at the point of final assembly. Sub-standard parts are identified and rejected immediately. Every unit receives a 100% unit run test before leaving the production line to make sure it lives up to rigorous Trane requirements.
ReliaTel controls provide unit control for heating, cooling and ventilating utilizing input from sensors that measure outdoor and indoor temperature.
Quality and Reliability are enhanced through ReliaTel control and logic:
•Prevents the unit from short cycling, considerably improving compressor life.
•Ensures that the compressor will run for a specific amount of time which allows oil to return for better lubrication, enhancing the reliability of the commercial compressor.
Voyager with ReliaTel reduces the number of components required to operate the unit, thereby reducing possibilities for component failure.
ReliaTel Makes Installing and Servicing Easy
ReliaTel eliminates the need for field installed anti-shortcycle timer and time delay relays. ReliaTel controls provide these functions as an integral part of the unit. The contractor no longer has to purchase these controls as options and pay to install them.
The wiring of the low voltage connections to the unit and the zone sensors is as easy as 1-1, 2-2, and 3-3. This simplified system makes it easier for the installer to wire.
ReliaTel Makes Testing Easy
ReliaTel requires no special tools to run the Voyager unit through its paces. Simply place a jumper between Test 1 and Test 2 terminals on the Low Voltage Terminal Board and the unit will walk through its operational steps automatically.
Note: The unit automatically returns control to the zone sensor after stepping through the test mode a single time, even if the jumper is left on the unit.
As long as the unit has power and the “system on” LED is lit, ReliaTel is operational. The light indicates that the controls are functioning properly. ReliaTel features expanded diagnostic capabilities when utilized with Trane Integrated Comfort™ Systems. Some zone sensor options have central control panel lights which indicate the mode the unit is in and possible diagnostic information (dirty filters for example).
Other ReliaTel Benefits
The ReliaTel’s built-in anti-shortcycle timer, time delay relay and minimum “on” time control functions are factory tested to assure proper operation. ReliaTel softens electrical “spikes” by staging on fans, compressors and heaters. Intelligent Fallback is a benefit to the building occupant. If a component goes astray, the unit will continue to operate at predetermined temperature setpoint.
Intelligent Anticipation is a standard ReliaTel feature. It functions continuously as ReliaTel and zone sensor(s) work together in harmony to provide much tighter comfort control than conventional electro-mechanical thermostats.
8 |
RT-PRC033F-EN |
Features and Benefits
The 5 Inch Color Touchscreen Human Interface provides an intuitive user interface to the rooftop unit that speeds up unit commissioning, shortens unit troubleshooting times, and enhances preventative maintenance measures. The human interface includes several features such as:
•Data trending capabilities by means of time series graphs
•Historical alarm messages
•Real-time sensor measurements
•On board system setpoints
•USB port that enables the downloading of component runtime information as well as trended historical sensor data
•Customized reports
Note: For more information, refer to Tracer™ TD-5 literature, RT-SVX49*-EN.
The dedicated downflow, horizontal or mixed airflow configurations require no panel removal or alteration time to convert in the field — a major cost savings during installation.
Forced Combustion Blower
Negative Pressure
Gas Valve
Hot Surface Ignitor
The drum and tube heat exchanger is designed for increased efficiency and reliability and utilizes the same technology that has been incorporated into large commercial roof top units for over 20 years.
The heat exchanger is manufactured using optional stainless, or standard aluminized, steel with stainless steel components for maximum durability. The requirement for cycle testing of heat exchangers is 10,000 cycles by ANSI Z21.47. This is the standard required by both cULus and AGA for cycle test requirements. Trane requires the design to be tested to 2½ times this current standard. The drum and tube design has been tested and passed over 150,000 cycles which is over 15 times the current ANSI cycling requirements.
The regulated gas valve will not allow gas flow unless the combustion blower is operating. This is one of the unique safety features of Voyager Commercial. The forced combustion blower
RT-PRC033F-EN |
9 |
Features and Benefits
supplies pre-mixed fuel through a single stainless steel burner screen into a sealed drum where ignition takes place. It is more reliable to operate and maintain than a multiple burner system.
The hot surface ignitor is a gas ignition device which doubles as a safety device utilizing a continuous test to prove the flame. The design is cycle tested at the factory for quality and reliability.
All the gas/electric rooftops exceed all California seasonal efficiency requirements. They also perform better than required to meet the California NOx emission requirements.
All Voyager Commercial units have cooling capabilities down to 0°F as standard.
Due to flat streamlined tubes with small ports, and metallurgical tube-to-fin bond, microchannel coil has better heat transfer performance.
Microchannel condenser coil can reduce system refrigerant charge by up to 50% because of smaller internal volume, which leads to better compressor reliability. Compact all-aluminum microchannel coils also help to reduce the unit weight.
All-aluminum construction improves recyclability. Galvanic corrosion is also minimized due to all-aluminum construction. Strong aluminum brazed structure provides better fin protection. In addition, flat streamlined tubes also make microchannel coils more dust resistant and easier to clean.
Voyager features a three-phase line monitor module that protects against phase loss, phase reversal and phase unbalance. It is intended to protect compressors from reverse rotation. It has an operating input voltage range of 190–600 Vac, and LED indicators for ON and FAULT. There are no field adjustments and the module will automatically reset from a fault condition.
Low and high pressure cutouts are standard on all models.
A single electrical connection powers the unit.
Every unit has a non-corrosive, sloped drain pan made of pre-painted steel and standard on all units.
A bi-metal element discharge line thermostats is installed as a standard feature on the discharge line of each system. This standard option provides extra protection to the compressors against high discharge temperatures in case of loss of charge, extremely high ambient and other conditions which could drive the discharge temperature higher.
10 |
RT-PRC033F-EN |
Features and Benefits
Variable Frequency Drives are factory installed and tested to provide supply fan motor speed modulation, as well as modulating gas heat. VFD’s on the supply fan, as compared to inlet guide vanes or discharge dampers, are quieter, more efficient, and are eligible for utility rebates. The VFD’s are available with or without a bypass option. Bypass control will simply provide full nominal airflow in the event of drive failure.
Modulating gas heat models with VFD's allow tighter space temperature control with less temperature swing.
Single zone VAV is designed for use in single zone applications like gymnasiums, auditoriums, manufacturing facilities, retail box stores, and any large open spaces, where there is a lot of diversity in the load profile. Single Zone VAV (SZ VAV) is an ideal replacement to “yesterday’s” constant volume (CV) systems, by reducing operating costs while improving occupant comfort.
SZ VAV systems combine Trane application, control and system integration knowledge to exactly match fan speed with cooling and heating loads, regardless of the operating condition. Trane algorithms meet/exceed ASHRAE 90.1- 2010, SZ VAV energy-saving recommendations, and those of CA Title 24. The result is an optimized balance between zone temperature control and system energy savings. Depending on your specific application, energy savings can be as much as 20+%.
Note: Building system modeling in energy simulation software like TRACE is recommended to evaluate performance improvements for your application.
SZ VAV is fully integrated into the ReliaTel Control system and is available today. It provides the simplest and fastest commissioning in the industry through proven factory-installed, wired, and tested system controllers. All control modules, logic and sensors are factory installed, and tested to assure the highest quality and most reliable system available. This means no special programming of algorithms, or hunting at the jobsite for sensors, boards, etc. that need to be installed in the field. Single zone VAV is a quick and simple solution for many applications and is available from your most trusted rooftop VAV system solution providerTrane.
Trane provides true pressure independent variable air volume with Voyager Commercial delivered VAV. The system is auto-configured to reduce programming and set-up time on the job. Generally available only on sophisticated larger models, this Voyager Commercial system can economically handle comfort requirements for any zone in the facility.
The system consists of:
•Voyager™ Commercial VAV packaged rooftops
•Up to 32 VariTrane™ VAV boxes with DDC (direct digital controls)
•VariTrac™ Central Control Panel (CCP) with Operator Display (OD)
The VariTrac Central Control Panel acts as a communications hub by coordinating the actions of the VAV rooftop and the VAV boxes. Single duct or fan powered VAV boxes are available, along with an option for factory-installed local heat. For more details, see VAV-SLM003-EN.
RT-PRC033F-EN |
11 |
Features and Benefits
For large commercial applications, Trane offers constant volume (CV) Voyager Commercial models with a changeover-bypass VAV system. For the most advanced comfort management systems, count on Trane.
Provides exhaust of the return air when using an economizer to maintain proper building pressurization. Great for relieving most building overpressurization problems.
Provides exhaust of the return air to maintain proper building pressurization by proportionally controlling the exhaust air to the economizer dampers; in other words, the exhaust damper “tracks” the outside air damper position.
Trane's Statitrac™ control is a highly accurate and efficient method of maintaining building pressure control with a large rooftop air conditioner. Statitrac space pressure control turns the exhaust fans on and modulates exhaust dampers to maintain space pressure within the space pressure deadband. Proper building pressurization eliminates annoying door whistling, doors standing open, and odors from other zones.
The economizers come with three control options: dry bulb, enthalpy and differential enthalpy. The photo shows the three fresh air hoods on the horizontal discharge configuration.
12 |
RT-PRC033F-EN |
Features and Benefits
Trane Air Quality (Traq) outside air measurement system uses velocity pressure sensing rings to measure airflow in the outside air opening from 40 cfm/ton to maximum airflow. Measurement accuracy is at least ±15%, meeting requirements of LEED IE Q Credit 1.
The Trane BACnet Control Interface (BCI-R) for Voyager Commercial offers a building automation control system with outstanding interoperability benefits. BACnet, which is an industry standard, is an open, secure and reliable network communication protocol for controls, created by American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (ASHRAE).
Interoperability allows application or project engineers to specify the best products of a given type, rather than one individual supplier's entire system. It reduces product training and installation costs by standardizing communications across products. Interoperable systems allow building managers to monitor and control IntelliPak equipment with Tracer SC controls or a 3rd party building automation system. It enables integration with many different building controls such as access/intrusion monitoring, lighting, fire and smoke devices, energy management, and a wide variety of sensors (temperature, pressure, light, humidity, occupancy, CO2 and air velocity).
The LonTalk Communication (LCI-R) for Voyager Commercial offers a building automation control system with outstanding interoperability benefits. LonTalk, which is an industry standard, is an open, secure and reliable network communication protocol for controls, created by Echelon Corporation and adopted by the LonMark Interoperability Association. It has been adopted by several standards, such as: EIA-709.1, the Electronic Industries Alliance (EIA) Control Network Protocol Specification and ANSI/ASHRAE 135, part of the American Society of Heating, Refrigeration, and Air-Conditioning Engineer’s BACnet control standard for buildings.
Interoperability allows application or project engineers to specify the best products of a given type, rather than one individual supplier’s entire system. It reduces product training and installation costs by standardizing communications across products.
Interoperable systems allow building managers to monitor and control Voyager Commercial equipment with a Trane Tracer Summit™ or a 3rd party building automation system.
It enables integration with many different building controls such as access/intrusion monitoring, lighting, fire and smoke devices, energy management, and a wide variety of sensors for temperature, pressure, humidity and occupancy CO2. For additional information visit LonMark, www.lonmark.org or Echelon, www.echelon.com.
The TCI is available factory or field installed. When applied with ReliaTel, this module easily interfaces with the Trane Integrated Comfort™ System.
The Trane® Wireless Comm Interface (WCI) is the perfect alternative to Trane’s BACnet™ wired communication links (for example, Comm links between a Tracer™ SC and a Tracer UC400). Minimizing communication wire use between terminal products, zone sensors, and system controllers has substantial benefits. Installation time and associated risks are reduced. Projects are completed with fewer disruptions. Future re-configurations, expansions, and upgrades are easier and more cost effective.
This option allows for increased outdoor air ventilation. It reduces humidity levels while increasing comfort level in the air space. Cooling can operate without a demand for dehumidification. The hot gas reheat coil and modulating valve are designed to deliver maximum reheat temperatures and
RT-PRC033F-EN |
13 |
Features and Benefits
increase unit efficiency. This energy efficiency helps to meet local energy codes and ASHRAE Standard 90.1 compliance.
Figure 1. Modulating hot gas reheat option
Tool-less condenser hail guards are available as a factory installed option to protect the unit condenser coil from hail, debris damage and vandalism.
Available for all units.
Motors with internal Shaft grounding rings can be used with VFDs to provide a conductive discharge path away from the motor bearings to ground.
A condensate overflow switch is available to shut the unit down in the event that the condensate drain becomes clogged. This option protects the unit from water overflowing from the drain pan and entering the base of the unit.
Through compressor staging on a single circuit, this option allows units to have a maximum 25% load at the first stage allowing the unit to meet Title 24, along with providing increased full load and part load unit efficiency.
Trane Commercial Sales Engineers are a support group that can assist you with:
• |
Product |
• |
Special Applications |
• |
Application |
• |
Specifications |
• |
Service |
• Computer Programs and more |
•Training
14 |
RT-PRC033F-EN |
When is it necessary to provide building exhaust?
Whenever an outdoor air economizer is used, a building generally requires an exhaust system. The purpose of the exhaust system is to exhaust the proper amount of air to prevent over or underpressurization of the building.
A building may have all or part of its exhaust system in the rooftop unit. Often, a building provides exhaust external to the air conditioning equipment. This external exhaust must be considered when selecting the rooftop exhaust system.
Voyager™ Commercial rooftop units offer four types of exhaust systems:
1.50% or 100% Power exhaust fan
2.50% or 100% Fresh Air Tracking Power Exhaust Fan(s)
3.100% Power Exhaust with Statitrac™ Building Pressure Control
4.Barometric relief dampers
Power Exhaust Fan (with or without Fresh Air Tracking)
The exhaust fan option is either a single fan for exhausting approximately half of the air-moving capabilities of the supply fan system or dual fans for 100% exhaust. Either exhaust capability arrangement is configured as an on/off non-modulating exhaust or an on/off exhaust with an actuator controlled damper to track the position of the fresh air damper.
For non-100% air applications, the 50% non-tracking power exhaust fan generally should not be selected for more than 40 to 50% of design supply airflow. Since it is an on/off non-modulating fan, it does not vary exhaust cfm with the amount of outside air entering the building. Therefore, if selected for more than 40 to 50% of supply airflow, the building may become under pressurized when economizer operation is allowing lesser amounts of outdoor air into the building. If, however, building pressure is not of a critical nature, the non-modulating exhaust fan may be sized for more than 50% of design supply airflow. Consult Table 28, p. 59 and Table 29, p. 59 (60Hz) or Table 60, p. 87 and Table 61, p. 88 (50Hz) for specific exhaust fan capabilities with Voyager Commercial units.
100% Power Exhaust with Statitrac™ Building Pressure Control
This control is available only with 100% power exhaust. The exhaust dampers are modulated in response to building pressure. Statitrac, a differential pressure control system, uses a differential pressure transducer to compare indoor building pressure to atmospheric pressure. The exhaust fans are turned on when required to lower building static pressure to setpoint. The Statitrac control system then modulates the exhaust dampers to control the building pressure to within the adjustable, specified deadband that is set at the RTVM board. Economizer and return air dampers are modulated independent of the exhaust dampers based on ventilation control and economizer cooling requests.
Statitrac can only lower building pressure; it cannot raise it. To lower building pressure, Statitrac exhausts air from the space using the power exhaust. To raise building pressure, more air must be supplied to the space, as with economizer operation. Additional relief, such as a bathroom exhaust fan or relief fan, as well as other units serving the space, will affect building pressure and must be taken into account.
Barometric Relief Dampers
Barometric relief dampers consist of gravity dampers which open with increased building pressure. As the building pressure increases, the pressure in the unit return section also increases,
RT-PRC033F-EN |
15 |
Application Considerations
opening the dampers and relieving air. Barometric relief may be used to provide relief for single story buildings with no return ductwork and exhaust requirements less than 25%.
The rooftop performance tables and curves of this catalog are based on standard air (.075 lbs/ft). If the rooftop airflow requirements are at other than standard conditions (sea level), an air density correction is needed to project accurate unit performance.
Figure 3, p. 42 shows the air density ratio at various temperatures and elevations. Trane rooftops are designed to operate between 40° and 90°F leaving air temperature.
The procedure to use when selecting a supply or exhaust fan on a rooftop for elevations and temperatures other than standard is as follows:
1.First, determine the air density ratio using Figure 3, p. 42.
2.Divide the static pressure at the nonstandard condition by the air density ratio to obtain the corrected static pressure.
3.Use the actual cfm and the corrected static pressure to determine the fan rpm and bhp from the rooftop performance tables or curves.
4.The fan rpm is correct as selected.
5.Bhp must be multiplied by the air density ratio to obtain the actual operating bhp.
In order to better illustrate this procedure, the following examples are used:
60 Hz
Consider a 30 ton rooftop unit that is to deliver 11,000 actual cfm at 1.50 inches total static pressure (tsp), 55°F leaving air temperature, at an elevation of 5,000 ft.
1.From Figure 3, p. 42, the air density ratio is 0.86.
2.Tsp=1.50 inches/0.86=1.74 inches tsp.
3.From the performance tables: a 30 ton rooftop will deliver 11,000 cfm at 1.74 inches tsp at 632 rpm and 6.2 bhp.
4.The rpm is correct as selected — 632 rpm.
5.Bhp = 6.2 x 0.86 = 5.33.
Compressor MBh, SHR, and kW should be calculated at standard and then converted to actual using the correction factors in Table 9, p. 42. Apply these factors to the capacities selected at standard cfm so as to correct for the reduced mass flow rate across the condenser.
Heat selections other than gas heat will not be affected by altitude. Nominal gas capacity (output) should be multiplied by the factors given in Table 10, p. 42 before calculating the heating supply air temperature.
50 Hz
Consider a 29 ton (105 kW) rooftop unit that is to deliver 9,160 actual cfm (4323 L/s) at 1.50 inches total static pressure (tsp) (38 mm, 373 Pa), 55°F (12.8°C) leaving air temperature, at an elevation of 5,000 ft (1524 m).
1.From Figure 3, p. 42, the air density ratio is 0.86.
2.Tsp = 1.50 inches/0.86 = 1.74 inches tsp. 374/.86 = 434 Pa.
3.From the performance tables: a 29-ton (105 kW) rooftop will deliver 9,160 cfm at 1.74 inches tsp (4323 L/s at 434 Pa) at 618 rpm and 4.96 bhp (3.7 kW).
4.The rpm is correct as selected – 618 rpm.
5.Bhp = 4.96 x 0.86 = 4.27 bhp actual. kW = 3.7 x 0.86 = 3.18 kW
16 |
RT-PRC033F-EN |
Application Considerations
Compressor MBh, SHR, and kW should be calculated at standard and then converted to actual using the correction factors in Table 9, p. 42. Apply these factors to the capacities selected at standard cfm so as to correct for the reduced mass flow rate across the condenser.
Heat selections other than gas heat will not be affected by altitude. Nominal gas capacity (output) should be multiplied by the factors given in Table 10, p. 42 before calculating the heating supply air temperature.
Proper placement of rooftops is critical to reducing transmitted sound levels to the building. The ideal time to make provisions to reduce sound transmissions is during the design phase. The most economical means of avoiding an acoustical problem is to place the rooftop(s) away from acoustically critical areas. If possible, rooftops should not be located directly above areas such as: offices, conference rooms, executive office areas and classrooms. Instead, ideal locations might be over corridors, utility rooms, toilets or other areas where higher sound levels directly below the unit(s) are acceptable.
Several basic guidelines for unit placement should be followed to minimize sound transmission through the building structure:
1.Never cantilever the compressor end of the unit. A structural cross member must support this end of the unit.
2.Locate the unit center of gravity which is close to, or over, a column or main support beam.
3.If the roof structure is very light, roof joists must be replaced by a structural shape in the critical areas described above.
4.If several units are to be placed on one span, they should be staggered to reduce deflection over that span.
It is impossible to totally quantify the effect of building structure on sound transmission, since this depends on the response of the roof and building members to the sound and vibration of the unit components. However, the guidelines listed above are experienceproven guidelines which will help reduce sound transmissions.
The recommended clearances identified with unit dimensions should be maintained to assure adequate serviceability, maximum capacity and peak operating efficiency. A reduction in unit clearance could result in condenser coil starvation or warm condenser air recirculation. If the clearances shown are not possible on a particular job, consider the following:
Do the clearances available allow for major service work such as changing compressors or coils?
Do the clearances available allow for proper outside air intake, exhaust air removal and condenser airflow?
If screening around the unit is being used, is there a possibility of air recirculation from the exhaust to the outside air intake or from condenser exhaust to condenser intake?
Actual clearances which appear inadequate should be reviewed with a local Trane sales engineer.
When two or more units are to be placed side by side, the distance between the units should be increased to 150% of the recommended single unit clearance. The units should also be staggered for two reasons:
1.To reduce span deflection if more than one unit is placed on a single span. Reducing deflection discourages sound transmission.
2.To assure proper diffusion of exhaust air before contact with the outside air intake of adjacent unit.
RT-PRC033F-EN |
17 |
Application Considerations
It is important to note that the rated capacities of the rooftop can be met only if the rooftop is properly installed in the field. A well designed duct system is essential in meeting these capacities.
The satisfactory distribution of air throughout the system requires that there be an unrestricted and uniform airflow from the rooftop discharge duct. This discharge section should be straight for at least several duct diameters to allow the conversion of fan energy from velocity pressure to static pressure.
When job conditions dictate elbows be installed near the rooftop outlet, the loss of capacity and static pressure may be reduced through proper direction of the bend in the elbow. The high velocity side of the rooftop outlet should be directed at the outside radius of the elbow rather than the inside.
18 |
RT-PRC033F-EN |
Five Basic Areas
1.Cooling capacity
2.Heating capacity
3.Air delivery
4.Unit electrical requirements
5.Unit designation
1.Summer design conditions — 95 DB/76 WB, 95°F entering air to condenser.
2.Summer room design conditions — 76 DB/66 WB.
3.Total peak cooling load — 321 MBh (26.75 tons).
4.Total peak supply cfm — 12000 cfm.
5.External static pressure — 1.2 inches.
6.Return air temperatures — 80 DB/66 WB.
7.Return air cfm — 10800 cfm.
8.Outside air ventilation cfm and load — 1200 cfm and 18.23 MBh (1.52 tons).
9.Unit accessories include:
a.Aluminized heat exchanger — high heat module.
b.2” Hi-efficiency throwaway filters.
c.Economizer.
Step 1. A summation of the peak cooling load and the outside air ventilation load shows: 26.75 tons + 1.52 tons = 28.27 required unit capacity. From Table 13, p. 45, 30-ton unit capacity at
80 DB/67 WB, 95°F entering the condenser and 12,000 total peak supply cfm, is 353 MBh (29.4 tons). Thus, a nominal 30 ton unit is selected.
Step 2. Having selected a nominal 30 ton unit, the supply fan and exhaust fan motor bhp must be determined.
Supply Air Fan
Determine unit static pressure at design supply cfm (see Table 26, p. 57):
External static pressure = 1.20 inches
Heat exchanger = High Heat: 0.14 inches
High efficiency filter 2”= 0.23 inches
Indoor coil = 0.34 inches
Economizer = 0.07 inches
Unit total static pressure = 1.98 inches
Using total cfm of 12000 and total static pressure of 1.98 inches, Table 24, p. 54 shows 7.78 bhp with 676 rpm.
Step 3. Determine evaporator coil entering air conditions. Mixed air dry bulb temperature determination.
Using the minimum percent of OA (1,200 cfm ÷ 12,000 cfm = 10 percent), determine the mixture dry bulb to the evaporator. RADB +%OA (OADB - RADB) = 80 + (0.10) (95 - 80) = 80 + 1.5 = 81.5°F
RT-PRC033F-EN |
19 |
Selection Procedure
Approximate Wet Bulb Mixture Temperature
RAWB + OA (OAWB - RAWB) = 66 + (0.10) (76-66) = 68 + 1 = 67°F. A psychrometric chart can be used to more accurately determine the mixture temperature to the evaporator coil.
Step 4.
Determine Total Required Unit Cooling Capacity
Required capacity = total peak load + O.A. load + supply air fan motor heat. From Figure 2, p. 22, the supply air fan motor heat for 7.78 bhp = 22.1 MBh. Capacity = 321 + 18.23 + 22.1 = 361.3 MBh (30.1 tons)
Step 5.
Determine Unit Capacity
From Table 13, p. 45 unit capacity at 81.5 DB. 67 WB entering the evaporator, 12000 supply air cfm, 95°F entering the condenser is 355 MBh (29.6 tons) 290 sensible MBh.
Step 6.
Determine Leaving Air Temperature
Unit sensible heat capacity, corrected for supply air fan motor heat 290 - 22.1 = 267.9 MBh.
Supply air dry bulb temperature difference = 267.9 MBh ÷ (1.085 x 12,000 cfm) = 20.6°F.
Supply air dry bulb: 81.5 - 20.6 = 60.9.
Unit enthalpy difference = 355 ÷ (4.5 x 12,000) = 6.57 Btu/lb.
Btu/lb leaving enthalpy = h (ent WB) = 31.62 Btu/lb.
Leaving enthalpy = 31.62 Btu/lb - 6.57 Btu/lb = 25.1 Btu/lb.
From Table 8, p. 41, the leaving air wet bulb temperature corresponding to an enthalpy of 25.1 Btu/lb = 58°F.
Leaving air temperatures = 60.9°F/58°F
1.Winter outdoor design conditions—0°F.
2.Total return air temperature — 72°F.
3.Winter outside air minimum ventilation load and cfm — 1,200 cfm and 87.2 MBh.
4.Peak heating load 225 MBh.
Utilizing Unit selection in the Cooling Capacity Procedure
Mixed air temperature = RADB +%O.A. (OADB - RADB) = 72 + (0.10) (0-72) = 64.8°F.
Supply air fan motor heat temperature rise = 20,600 BTU ÷ (1.085 x 12,000) cfm = 1.6°F.
Mixed air temperature entering heat module = 64.8 + 1.6 = 66.4°F.
Total winter heating load = peak heating + ventilation load - total fan motor heat = 225 + 87.2 - 22.1 = 290.1 MBh.
Electric Heating System
Unit operating on 480/60/3 power supply. From Table 22, p. 53, kw may be selected for a nominal 30-ton unit operating on 480-volt power. The high heat module — 90 KW or 307 MBh will satisfy the winter heating load of 290.1 MBh.
Table 22, p. 53 also shows an air temperature rise of 23.6°F for 12,000 cfm through the 90 kw heat module.
20 |
RT-PRC033F-EN |
Selection Procedure
Unit supply temperature at design heating conditions = mixed air temperature + air temperature rise = 66.4 + 23.6 = 90°F.
Natural Gas Heating System
Assume natural gas supply — 1000 Btu/ft3. From Table 23, p. 53 select the high heat module (486 MBh output) to satisfy 290.1 at unit cfm.
Table 23, p. 53 also shows air temperature rise of 37.3°F for 12,000 cfm through heating module.
Unit supply temperature design heating conditions = mixed air temperature + air temperature rise = 66.4 + 37.3 = 103.7°F.
Hot Gas Reheat Dehumidification Selection
The hot gas reheat option allows for increased outdoor air ventilation. It reduces humidity levels while increasing comfort level in the air space.
Note: Please note that hot gas reheat operation will not be allowed when there is a call for cooling or heating.
Utilize the Trane TOPSS™selection program or contact a local Trane sales office to calculate leaving unit air temperature, latent capacity, reheat sensible capacity, leaving unit dew point, and moisture removal when the unit is in hot gas reheat operation.
The hot gas reheat TOPSS selection requires the following customer input values: supply fan airflow, ambient air temperatures, entering air temperatures, and a desired reheat set point temperature. If the conditions provided are not within the reheat operating envelope an error will be generated in the TOPSS program. If the reheat set point is not obtainable at the provided conditions the customer will be required to make adjustments to the conditions or change the reheat set point value.
Supply air fan bhp and rpm selection. Unit supply air fan performance shown in Table 24, p. 54 includes pressure drops for dampers and casing losses. Static pressure drops of accessory components such as heating systems, and filters if used, must be added to external unit static pressure for total static pressure determination.
The supply air fan motor selected in the previous cooling capacity determination example was 7.78 bhp with 676 rpm. Thus, the supply fan motor selected is 7.5 hp.
To select the drive, enter Table 27, p. 58 for a 30-ton unit. Select the appropriate drive for the applicable rpm range. Drive selection letter C with a range of 650 rpm, is required for 676 rpm. Where altitude is significantly above sea level, use Table 9, p. 42, Table 10, p. 42 and Figure 3, p. 42 for applicable correction factors.
Selection procedures for electrical requirements for wire sizing amps, maximum fuse sizing and dual element fuses are given in the electrical service selection of this catalog.
After determining specific unit characteristics utilizing the selection procedure and additional job information, the complete unit model number can be developed using the model number nomenclature page.
RT-PRC033F-EN |
21 |
Selection Procedure
Figure 2. Fan motor heat
STANDARDB MOTOR
HIGH EFFICIENCY MOTOR
C
|
120 |
|
|
|
|
|
|
|
|
|
110 |
|
|
|
|
|
|
|
|
MBH |
100 |
|
|
|
|
|
|
|
|
90 |
|
|
|
|
|
|
|
|
|
- |
|
|
|
|
|
|
|
|
|
HEAT |
80 |
|
|
|
|
|
|
|
|
70 |
|
|
|
|
|
|
|
|
|
MOTOR |
60 |
|
|
|
|
|
|
|
|
50 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
FAN |
40 |
|
|
|
|
|
|
|
|
30 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
20 |
|
|
|
|
|
|
|
|
|
10 |
|
|
|
|
|
|
|
|
|
0 |
|
|
|
|
|
|
|
|
|
0 |
5 |
10 |
15 |
20 |
25 |
30 |
35 |
40 |
MOTOR BRAKE HORSE POWER
Five basic areas
1.Cooling capacity
2.Heating capacity
3.Air delivery
4.Unit electrical requirements
5.Unit designation
1.Summer design conditions – 95 DB/76 WB (35/24.4°C), 95°F (35°C) entering air to condenser.
2.Summer room design conditions – 76 DB/66 WB (24.4/18.9°C).
3.Total peak cooling load – 270 MBh (79 kW) (22.5 tons).
4.Total peak supply cfm – 10,000 cfm (4720 L/s).
5.External static pressure – 1.24 inches wc (310 Pa).
6.Return air temperatures – 80 DB/66°F WB (26.7/18.9°C).
7.Return air cfm – 3540 cfm (1671 L/s).
8.Outside air ventilation cfm and load – 1000 cfm and 15.19 MBh (1.27 tons or 4.45 kW) 472 L/s.
9.Unit accessories include:
a.Aluminized heat exchanger – high heat module.
b.2” Hi-efficiency throwaway filters.
c.Exhaust fan.
d.Economizer cycle.
22 |
RT-PRC033F-EN |
Selection Procedure
Step 1.
A summation of the peak cooling load and the outside air ventilation load shows: 22.5 tons + 1.27 tons = 23.77 (79 kW + 4.45 kW = 83.45) required unit capacity. From Table 34, p. 64, 25.4 ton (89 kW) unit capacity at 80 DB/67 WB (27/19°C), 95°F entering the condenser and 10,000 total peak supply cfm (4720 L/s) is 297 MBh (24.75 tons).
Step 2.
Having selected the correct unit, the supply fan and exhaust fan motor bhp must be determined.
Supply Air Fan
Using Table 58, p. 86, determine unit static pressure at design supply cfm:
External static pressure = 1.24 inches (310 Pa)
Heat exchanger = 0.12 inches (30 Pa)
High efficiency filter 2” (50 mm) = 0.18 inches (45 Pa)
Economizer = 0.07 inches (17 Pa)
Unit total static pressure = 1.61 inches (402 Pa)
Using total cfm of 10,000 (4720 L/s) and total static pressure of 1.61 inches (41 mm), enter Table 55, p. 83. Table 55 shows 5.11 bhp (3.8 kW) with 601 rpm.
Step 3.
Determine evaporator coil entering air conditions. Mixed air dry bulb temperature determination.
Using the minimum percent of OA (1,000 cfm ÷ 10,000 cfm = 10 percent), determine the mixture dry bulb to the evaporator. RADB +% OA
(OADB - RADB) = 80 + (0.10) (95 - 80) = 80 + 1.5 = 81.5°F [26.7 + 1.5 = 28°C).
Approximate Wet Bulb Mixture Temperature
RAWB + OA (OAWB - RAWB) = 66 + (0.10) (76-66) = 68 + 1 = 67°F.
A psychrometric chart can be used to more accurately determine the mixture temperature to the evaporator coil.
Step 4.
Determine Total Required Unit Cooling Capacity
Required capacity = total peak load + O.A. load + supply air fan motor heat. From Figure 2, p. 22, the supply air fan motor heat for 5.11 bhp = 14 MBh. Capacity = 270 + 15 + 14 = 299 MBh (89 kW)
Step 5.
Determine Unit Capacity
From Table 34, p. 64 unit capacity at 81.5 DB/67 WB entering the evaporator, 10,000 supply air cfm, 95°F (35°C) entering the condenser about 298 MBh (87 kW) with 243 MBh (71.1 kW) sensible.
Step 6.
Determine Leaving Air Temperature
Unit sensible heat capacity, corrected for supply air fan motor heat 243 - 14 = 229 MBh (67 kW).
Supply air dry bulb temperature difference = 229 MBh ÷ (1.085 x 10,000 cfm) = 21.1°F (-6.1°C)
Supply air dry bulb: 81.5-21.1 = 60.4 (15.8°C)
Unit enthalpy difference = 298 ÷ (4.5 x 10,000) = 6.62
Btu/lb leaving enthalpy = h (ent WB) = 31.62
Leaving enthalpy = 31.62 Btu/lb - 6.62 Btu/lb = 25 Btu/lb.
RT-PRC033F-EN |
23 |
Selection Procedure
From Table 8, p. 41, the leaving air wet bulb temperature corresponding to an enthalpy of 25 Btu/ lb = 57.8ºF (14.3ºC).
Leaving air temperatures = 60.4 DB/57.8 WB (15.8/14.3°C).
1.Winter outdoor design conditions – 0°F (-17.8°C).
2.Total return air temperature – 72°F (22.2°C).
3.Winter outside air minimum ventilation load and cfm – 1,000 cfm and 87.2 MBh.
4.Peak heating load 150 MBh.
Utilizing unit selection in the cooling capacity procedure.
Mixed air temperature = RADB +% O.A. (OADB - RADB) = 72 + (0.10) (0-72) = 64.8°F.
Supply air fan motor heat temperature rise = 20,600 Btu ÷ (1.085 x 10,000) cfm= 1.9°F.
Mixed air temperature entering heat module = 64.8 + 1.9 = 66.7°F.
Total winter heating load = peak heating + ventilation load - total fan motor heat = 150 + 87.2 - 14 = 223.2 MBh.
Electric Heating System
Unit operating on 415 power supply. From Table 50, p. 80, kW may be selected for TC*305 unit to satisfy the winter heating load. The 67 kW module will do the job.
Table 50, p. 80 also shows an air temperature rise of 21.2°F for 10,000 cfm through the 67 kW heat module.
Unit supply temperature at design heating conditions = mixed air temperature + air temperature rise = 66.7 + 21.2 = 87.9°F.
Natural Gas Heating System
Assume natural gas supply – 1000 Btu/ft3. From Table 53, p. 80, select the low heat module (243 MBh output) to satisfy 223 at unit cfm.
Table 53, p. 80 also shows air temperature rise of 37.3°F for 10,000 cfm through heating module.
Unit supply temperature design heating conditions = mixed air temperature + air temperature rise = 66.7 + 37.3 = 104.0°F.
Hot Gas Reheat Dehumidification Selection
The hot gas reheat option allows for increased outdoor air ventilation. It reduces humidity levels while increasing comfort level in the air space.
Note: Please note that hot gas reheat operation will not be allowed when there is a call for cooling or heating.
Utilize the Trane TOPSS™selection program or contact a local Trane sales office to calculate leaving unit air temperature, latent capacity, reheat sensible capacity, leaving unit dew point, and moisture removal when the unit is in hot gas reheat operation.
The hot gas reheat TOPSS selection requires the following customer input values: supply fan airflow, ambient air temperatures, entering air temperatures, and a desired reheat set point temperature. If the conditions provided are not within the reheat operating envelope an error will be generated in the TOPSS program. If the reheat set point is not obtainable at the provided conditions the customer will be required to make adjustments to the conditions or change the reheat set point value.
24 |
RT-PRC033F-EN |
Selection Procedure
Supply air fan bhp and rpm selection. Unit supply air fan performance shown in Table 54, p. 81, Table 55, p. 83, Table 56, p. 84, and Table 57, p. 85 includes pressure drops for dampers and casing losses. Static pressure drops of accessory components such as heating systems, and filters if used, must be added to external unit static pressure for total static pressure determination.
The supply air fan motor selected in the previous cooling capacity determination example was 5.11 bhp with 601 rpm. Thus, the supply fan motor selected is 7.5 hp.
To select the drive, enter Table 59, p. 87 for a 25.4 unit. Select the appropriate drive for the applicable rpm range. Drive selection letter D with a range of 583 rpm, is required for 601 rpm. Where altitude is significantly above sea level, use Table 9, p. 42, Table 10, p. 42 and Figure 3, p. 42 for applicable correction factors.
Selection procedures for electrical requirements for wire sizing amps, maximum fuse sizing and dual element fuses are given in the electrical service selection of this catalog.
After determining specific unit characteristics utilizing the selection procedure and additional job information, the complete unit model number can be developed using the model number nomenclature page.
RT-PRC033F-EN |
25 |
Y |
C |
D |
3 |
3 |
0 |
|
B |
|
E |
|
L |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
Digit 1, 2 — Unit Function
TC = |
DX Cooling, No Heat |
TE = |
DX Cooling, Electric Heat |
YC = |
DX Cooling, Natural Gas Heat |
Digit 3 — Unit Airflow Design
Note: When second digit is “E” for Electric Heat, the following values apply in the ninth digit.
A= 36 kW (27 kW for 208v)
B= 54 kW (41 kW for 208v)
C= 72 kW
D= 90 kW
E= 108 kW
D |
= |
Downflow Supply and Return |
H |
= |
Horizontal Supply and Return |
F= Horizontal Supply and Upflow Return
R= Downflow Supply and Horizontal Return
Digit 4, 5, 6 — Nominal Cooling
Capacity
330 = |
27½ Tons |
360 = |
30 Tons |
420 = |
35 Tons |
480 = |
40 Tons |
600 = |
50 Tons |
Digit 7 — Major Development
Sequence
B = R-410A Refrigerant
Digit 8 — Power Supply1
E |
= |
208/60/3 |
F |
= |
230/60/3 |
4 |
= |
460/60/3 |
5 |
= |
575/60/3 |
Digit 9 — Heating Capacity4
0 |
= |
No Heat (TC only) |
L |
= |
Low Heat (YC only) |
H |
= |
High Heat (YC only) |
J= Low Heat-Stainless Steel Gas Heat Exchanger (YC only)
K= High Heat-Stainless Steel Gas Heat Exchangers (YC only)
M |
= |
Low Heat-Stainless Steel Gas |
|
|
Heat Exchanger w/ |
|
|
Modulating control |
|
|
(27.5-35 ton YC only) |
P |
= |
High Heat-Stainless Steel Gas |
|
|
Heat Exchangers w/ |
|
|
Modulating control |
|
|
(27.5-35 ton YC only) |
R= Low Heat-Stainless Steel Gas Heat Exchanger w/
Modulating control (40-50 ton YC only)
T= High Heat-Stainless Steel Gas Heat Exchangers w/ Modulating control
(40-50 ton YC only)
Digit 10 — Design Sequence
A = First
Digit 11 — Exhaust6
0 = None
1= Barometric Relief (Available w/ Economizer only)
2= 100% Power Exhaust Fan (Available w/ Economizer only)
3= 50% Power Exhaust Fan (Available w/ Economizer only)
4= 100% Fresh Air Tracking Power Exhaust Fan (Available
w/ Economizer only)
5= 50% Fresh Air Tracking Power Exhaust Fan (Available
w/ Economizer only)
6= 100% Power Exhaust w/ Statitrac™
7= 100% Fresh Air Tracking Power Exhaust Fan w/ Ultra Low Leak Exhaust Damper (Available w/ Economizer only)
8= 50% Fresh Air Tracking Power Exhaust Fan w/ Ultra Low Leak Exhaust Damper (Available w/ Economizer only)
9= 100% Power Exhaust w/ Ultra Low Leak Exhaust Damper w/ Statitrac™
Digit 12 — Filter
A= 2” MERV 4, Std Eff, Throwaway Filters
B= 2” MERV 8, High Eff, Throwaway Filters
C= 4” MERV 8, High Eff, Throwaway Filters
D= 4” MERV 14, High Eff, Throwaway Filters
Digit 13 — Supply Fan Motor, HP
1= 7.5 Hp
2= 10 Hp
3= 15 Hp
4= 20 Hp
A |
0 |
|
A |
1 |
|
|
|
|
|
|
|
10 |
11 |
12 |
13 |
Digit 14 — Supply Air Fan Drive
Selections3
A= 550 RPM
B= 600 RPM
C= 650 RPM
D= 700 RPM
E= 750 RPM
F= 790 RPM
G= 800 RPM
H = 500 RPM
J= 525 RPM
K= 575 RPM
L= 625 RPM
M= 675 RPM
N= 725 RPM
Digit 15 — Fresh Air Selection
A= No Fresh Air
B= 0-25% Manual Damper
C= 0-100% Economizer, Dry Bulb Control
D= 0-100% Economizer, Reference Enthalpy Control
E= 0-100% Economizer, Differential Enthalpy Control
F= “C” Option and Low Leak Fresh Air Damper
G= “D” Option and Low Leak Fresh Air Damper
H= “E” Option and Low Leak
Fresh Air Damper
J= “C” Option and Ultra Low Leak Outside Air Damper
K= “D” Option and Ultra Low Leak Outside Air Damper
L= E Option and Ultra Low Leak Outside Air Damper
1= Option “C” with Traq
2= Option “D” with Traq
3= Option “E” with Traq
4= Option “F” with Traq
5= Option “G” with Traq
6= Option “H” with Traq
7= Option “C” with Traq w/ Ultra Low Leak Outside Air Damper
8= Option “D” with Traq w/ Ultra Low Leak Outside Air Damper
9= Option “E” with Traq w/ Ultra Low Leak Outside Air Damper
Digit 16 — System Control
1= Constant Volume w/Zone Temperature Control
2= Constant Volume w/ Discharge Air Control
4= VAV Supply Air Temperature Control w/Variable Frequency Drive w/o Bypass
5= VAV Supply Air Temperature Control w/Variable Frequency Drive and Bypass
6= Single Zone VAV w/VFD w/o Bypass
7= Single Zone VAV w/VFD w/ Bypass
26 |
RT-PRC033F-EN |
Model Number Descriptions
A= VAV Supply Air Temperature Control w/VFD w/o Bypass w/ Motor Shaft Grounding Ring
B= VAV Supply Air Temperature Control w/VFD w/Bypass w/Motor Shaft Grounding Ring
C= Single Zone VAV w/VFD w/o Bypass w/ Motor Shaft Grounding Ring
D= Single Zone VAV w/VFD w/ Bypass w/Motor Shaft Grounding Ring
Note: Zone sensors are not included with option and must be ordered as a separate accessory.
Miscellaneous Options
Digit 17
A = Service Valves2
Digit 18
B= Through the Base Electrical Provision
Digit 19
C= Non-Fused Disconnect Switch w/External Handle
Digit 20
D= Factory-Powered 15A GFI Convenience Outlet and Non-Fused Disconnect Switch w/External Handle
Digit 21
E= Field-Powered 15A GFI Convenience Outlet
Digit 22
F= Trane Communication Interface (TCI)
Digit 23
G = Ventilation Override
Digit 24
H = Hinged Service Access
Digit 25
H |
= |
Tool-less Condenser Hail Guards |
J |
= |
Condenser Coil Guards |
Digit 26
K = LCI (LonTalk)
B= BACnet Communications Interface (BCI)
Digit 27
0 = 5kA SCCR
D= 65kA SCCR Disconnect7
E= 65kA SCCR Disconnect w/ Powered Convenience Outlet7
Digit 28
0 |
= |
Standard Drain Pan |
M |
= |
Stainless Steel Drain Pan |
1= Standard Drain Pan w/ Condensate Overflow Switch
RT-PRC033F-EN
2= Stainless Steel Drain Pan w/ Condensate Overflow Switch
Digit 29 — Efficiency/ Condenser
Coil Options
0 = Standard Efficiency Unit
J= Standard efficiency unit w/ Corrosion Protected Condenser Coil
K= High efficiency unit (eStage)
L= High efficiency unit (eStage) w/ Corrosion Protected Condenser Coil
Digit 30-31 — Miscellaneous
Options
P |
= |
Discharge Temperature |
|
|
Sensor |
R |
= |
Clogged Filter Switch |
Digit 32 |
— Dehumidification |
||
Option |
|
||
T |
= |
Modulating Hot Gas Reheat |
|
Digit 33 |
— Human Interface |
||
5 |
= |
Touchscreen Human Interface, 5" |
Model Number Notes
1.All voltages are across the line starting only.
2.Option includes Liquid, Discharge, Suction Valves.
3.Supply air fan drives A thru G are used with 27½-35 ton units only and drives H thru N are used with 40 & 50 ton units only.
4.Electric Heat KW ratings are based upon voltage ratings of 208/240/480/ 600 V. For a 240 V heater derated to 208 V, the resulting kW rating decreases from 36 kW to 27 kW, and from 54 kW to 41 kW. Voltage offerings are as follows (see Table 22, p. 53 for additional information):
|
Electric |
|
|
KW |
|
|
|
Heater |
|
|
|
|
|
|
|
|
|
|
|
|
|
Rated |
27/ 41/ |
|
|
|
|
Tons Voltage |
36 |
54 |
72 |
90 |
108 |
|
|
|
|
|
|
|
|
|
208 |
x |
x |
|
|
|
27½ |
240 |
x |
x |
|
|
|
to 35 |
480 |
x |
x |
x |
x |
|
|
600 |
|
x |
x |
x |
|
|
|
|
|
|
|
|
|
208 |
|
x |
|
|
|
40 |
240 |
|
x |
|
|
|
and |
480 |
|
x |
x |
x |
x |
50 |
|
|||||
|
600 |
|
x |
x |
x |
x |
|
|
|
|
|
|
|
5.The service digit for each model number contains 32 digits; all 32 digits must be referenced.
6.Ventilation override exhaust mode is not available for the exhaust fan with
fresh air tracking power exhaust. VOM is available for the exhaust fan without fresh air tracking power exhaust.
7.575 VAC option is 25kA.
27
Model Number Descriptions
Y |
C |
D |
2 |
7 |
5 |
|
B |
|
C |
|
L |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
Digits 1, 2 – Unit Function
TC = |
DX Cooling, No Heat |
TE = |
DX Cooling, Electric Heat |
YC = |
DX Cooling, Natural Gas Heat |
Digit 3 – Unit Airflow Design
D |
= |
Downflow Supply and Return |
H |
= |
Horizontal Supply and Return |
F |
= |
Horizontal Supply and Upflow |
|
|
Return |
R= Downflow Supply and Horizontal Return
Digits 4, 5, 6 – Nominal Cooling Capacity
275 = 22.9 Tons (82 kW)
305 = 25.4 Tons (89 kW)
350 = 29.2 Tons (105 kW)
400 = 33.3 Tons (120 kW)
500 = 41.7 Tons (148 kW)
Digit 7 – Major Development
Sequence
B = R-410A Refrigerant
Digit 8 – Power Supply1
C |
= |
380/50/3 |
D |
= |
415/50/3 |
Digit 9 – Heating Capacity4
0 |
= |
No Heat (TC only) |
L |
= |
Low Heat (YC only) |
H |
= |
High Heat (YC only) |
Note: |
When second digit is “E” for |
|
|
|
Electric Heat, the following values |
|
|
apply in the ninth digit. |
7= 100% Fresh Air Tracking Power Exhaust Fan w/ Ultra Low Leak Exhaust Damper (Available w/ Economizer only)
8= 50% Fresh Air Tracking Power Exhaust Fan w/ Ultra Low Leak Exhaust Damper (Available w/ Economizer only)
9= 100% Power Exhaust w/ Ultra Low Leak Exhaust Damper w/ Statitrac™
Digit 12 – Filter
A= 2” (51 MM) MERV 4, Std Eff, Throwaway Filters
B= 2” (51 MM) MERV 8, High Eff, Throwaway Filters
C= 4” (102 MM) MERV 8, High Eff, Throwaway Filters
D= 4” (102 MM) MERV 14, High Eff, Throwaway Filters
Digit 13 – Supply Fan Motor, HP
1= 7.5 Hp (5.6 kW)
2= 10 Hp (7.5 kW)
3= 15 Hp (10 kW)
4= 20 Hp (15 kW)
Digit 14 – Supply Air Fan Drive
Selections3
A= 458 RPM
B= 500 RPM
C= 541 RPM
D= 583 RPM
E= 625 RPM
F= 658 RPM
G= 664 RPM
H = 417 RPM
J= 437 RPM
K= 479 RPM
L= 521 RPM
M= 562 RPM
N= 604 RPM
380V / 415V
A= 23 kW / 27 kW
B= 34 kW / 40 kW
C= 45 kW / 54 kW
D= 56 kW / 67 kW
E= 68 kW / 81 kW
Digit 10 – Design Sequence
A = First
Digit 11 – Exhaust6
0 = None
1= Barometric Relief (Available w/Economizer only)
2= 100% Power Exhaust Fan (Available w/ Economizer only)
3= 50% Power Exhaust Fan (Available w/ Economizer only)
4= 100% Fresh Air Tracking Power Exhaust Fan (Available w/Economizer only)
5= 50% Fresh Air Tracking Power Exhaust Fan (Available
w/ Economizer only)
6= 100% Power Exhaust w/ Statitrac™
28
Digit 15 – Fresh Air Selection
A= No Fresh Air
B= 0-25% Manual Damper
C= 0-100% Economizer, Dry Bulb Control
D= 0-100% Economizer, Reference Enthalpy Control
E= 0-100% Economizer, Differential Enthalpy Control
F= “C” Option and Low Leak Fresh Air Damper
G= “D” Option and Low Leak Fresh Air Damper
H= “E” Option and Low Leak Fresh Air Damper
J= “C” Option and Ultra Low Leak Outside Air Damper
K= “D” Option and Ultra Low Leak Outside Air Damper
L= E Option and Ultra Low Leak Outside Air Damper
1= Option “C” with Traq
2= Option “D” with Traq
3= Option “E” with Traq
4= Option “F” with Traq
A |
0 |
|
A |
1 |
|
|
|
|
|
|
|
10 |
11 |
12 |
13 |
5= Option “G” with Traq
6= Option “H” with Traq
7= Option “C” with Traq w/ Ultra Low Leak Outside Air Damper
8= Option “D” with Traq w/ Ultra Low Leak Outside Air Damper
9= Option “E” with Traq w/ Ultra Low Leak Outside Air Damper
Digit 16 – System Control
1= Constant Volume w/ Zone Temperature Control
2= Constant Volume w/ Discharge Air Control
4= VAV Supply Air Temperature Control w/Variable Frequency Drive w/o Bypass
5= VAV Supply Air Temperature Control w/Variable Frequency Drive and Bypass
6= Single Zone VAV w/VFD w/o Bypass
7= Single Zone VAV w/VFD w/ Bypass
A= VAV Supply Air Temperature Control w/VFD w/o Bypass w/ Motor Shaft Grounding Ring
B= VAV Supply Air Temperature Control w/VFD w/Bypass w/Motor Shaft Grounding Ring
C= Single Zone VAV w/VFD w/o Bypass w/ Motor Shaft Grounding Ring
D= Single Zone VAV w/VFD w/ Bypass w/Motor Shaft Grounding Ring
Note: Zone sensors are not included with option and must be ordered as a separate accessory.
Miscellaneous Options
Digit 17
A = Service Valves2
Digit 18
B= Through the Base Electrical Provision
Digit 19
C= Non-Fused Disconnect Switch with External Handle
Digit 20
*= Unused Digit
Digit 21
*= Unused Digit
Digit 22
F= Trane Communication Interface (TCI)
Digit 23
G = Ventilation Override
RT-PRC033F-EN
Model Number Descriptions
Digit 24
H = Hinged Service Access
Digit 25
H |
= |
Tool-less Condenser Hail Guards |
J |
= |
Condenser Coil Guards |
Digit 26
K = LCI (LonTalk)
B= BACnet Communications Interface (BCI)
Digit 27
0 |
= |
5kA SCCR |
D |
= |
65kA SCCR Disconnect |
Digit 28
0 |
= |
Standard Drain Pan |
M |
= |
Stainless Steel Drain Pan |
1= Pre-Painted Steel Drain Pan w/ Condensate Overflow Switch
2= Stainless Steel Drain Pan w/ Condensate Overflow Switch
Digit 29 — Efficiency/ Condenser
Coil Options
0 = Standard Efficiency Unit
J= Standard efficiency unit w/ Corrosion Protected Condenser Coil
K= High efficiency unit (eStage)
L= High efficiency unit (eStage) w/ Corrosion Protected Condenser Coil
Digit 30-31 — Miscellaneous
Options
P |
= |
Discharge Temperature Sensor |
R |
= |
Clogged Filter Switch |
Digit 32 |
— Dehumidification |
||
Option |
|
||
T |
= |
Modulating Hot Gas Reheat |
|
Digit 33 |
— Human Interface |
||
5 |
= |
Touchscreen Human Interface, 5" |
Model Number Notes
1.All voltages are across-the-line starting only.
2.Option includes Liquid, Discharge, Suction Valves.
3.Supply air fan drives A thru G are used with 22.9-29.2 ton (82-105 kW) units only and drives H through N are used with 33.3 and 41.7 ton (120-148 kW) units only.
4.Electric Heat kW ratings are based upon voltage ratings of 380/415 V. Heaters A, B, C, D are used with 22.9-
29.2ton (82-105 kW) units only and heaters B, C, D, E are used with 33.3-
41.7ton (120-148 kW) units only.
5.The service digit for each model number contains 32 digits; all 32 digits must be referenced.
6.Ventilation override exhaust mode is not available for the exhaust fan with fresh air tracking power exhaust. VOM is available for the exhaust fan without fresh air tracking power exhaust.
RT-PRC033F-EN |
29 |
Table 1. General data - 27½ - 30 tons (60 Hz)
|
|
27½ Ton |
|
|
30 Ton |
|
|||
Cooling Performance1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
Nominal Gross Capacity - Std Efficiency |
|
323,000 |
|
|
353,000 |
|
|||
Nominal Gross Capacity - High Efficiency |
|
342,000 |
|
|
360,000 |
|
|||
|
|
|
|
|
|||||
|
Two Stage |
Modulating |
Two Stage |
Modulating |
|||||
Natural Gas Heat2,6 |
Low |
High |
Low |
High |
Low |
High |
Low |
High |
|
Heating Input (BTUH) |
350,000 |
600,000 |
350,000 |
600,000 |
350,000 |
600,000 |
350,000 |
600,000 |
|
First Stage/Low Fire |
250,000 |
425,000 |
140,000 |
140,000 |
250,000 |
425,000 |
140,000 |
140,000 |
|
Heating Output (BTUH) |
283,500 |
486,000 |
283,500 |
486,000 |
283,500 |
486,000 |
283,500 |
486,000 |
|
First Stage/Low Fire |
202,500 |
344,500 |
113,400 |
113,400 |
202,500 |
344,500 |
113,400 |
113,400 |
|
Steady State Efficiency (%)3 |
81.00 |
81.00 |
81.00 |
81.00 |
81.00 |
81.00 |
81.00 |
81.00 |
|
No. Burners |
1 |
2 |
1 |
2 |
1 |
2 |
1 |
1 |
|
No. Stages/Turn down rate |
2 |
2 |
2.5:1 |
5:1 |
2 |
2 |
2.5:1 |
5:1 |
|
Gas Supply Pressure (in. w.c.) |
|
|
|
|
|
|
|
|
|
Natural or LP (Two Stage only) |
2.5/14.0 |
2.5/14.0 |
2.5/14.0 |
2.5/14.0 |
2.5/14.0 |
2.5/14.0 |
2.5/14.0 |
2.5/14.0 |
|
(min/max) 2.5/14.0 |
|||||||||
|
|
|
|
|
|
|
|
||
Gas Connection Pipe Size (in.) |
3/4 |
1 |
3/4 |
1 |
3/4 |
1 |
3/4 |
1 |
|
|
|
|
|
|
|
|
|
|
|
Electric Heat |
|
|
|
|
|
|
|
|
|
kW Range4 |
|
27-90 |
|
|
27-90 |
|
|||
Capacity Steps |
|
|
2 |
|
|
2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
Compressor - Std Efficiency |
|
|
|
|
|
|
|
|
|
Number/Type/Refrigerant |
|
2/Scroll/R-410A |
|
|
2/Scroll/R-410A |
|
|||
Size (Nominal) |
|
12/13 |
|
|
13 |
|
|
||
Unit Capacity Steps (%) |
|
100/48 |
|
|
100/50 |
|
|||
Compressor - High Efficiency |
|
|
|
|
|
|
|
|
|
Number/Type/Refrigerant |
|
3/Scroll/R-410A |
|
|
3/Scroll/R-410A |
|
|||
|
|
|
|
||||||
Size (Nominal) |
|
6/9/9 |
|
|
6/10/10 |
|
|||
Unit Capacity Steps (%) |
|
100/75/63/37/25 |
|
|
100/76/62/38/24 |
|
|||
|
|
|
|
|
|
|
|
|
|
Outdoor Coil - Std Efficiency |
|
|
|
|
|
|
|
|
|
Type |
|
Microchannel |
|
|
Microchannel |
|
|||
Face Area (sq. ft.) |
|
|
43.6 |
|
|
49.9 |
|
||
Rows |
|
|
1 |
|
|
1 |
|
|
|
Outdoor Coil - High Efficiency |
|
|
|
|
|
|
|
|
|
Type |
|
Microchannel |
|
|
Microchannel |
|
|||
|
|
|
|
||||||
Face Area (sq. ft.) |
|
|
49.9 |
|
|
49.9 |
|
||
Rows |
|
|
1 |
|
|
1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
Indoor Coil - Std Efficiency |
|
|
|
|
|
|
|
|
|
Tube Size (in.) OD |
|
|
3/8 |
|
|
3/8 |
|
|
|
Face Area (sq. ft.) |
|
|
31.7 |
|
|
31.7 |
|
||
Rows/Fins Per Foot |
|
3/180 |
|
|
3/180 |
|
|||
Refrigerant Control |
|
|
TXV |
|
|
TXV |
|
||
No. of Circuits |
|
|
1 |
|
|
1 |
|
|
|
Drain Connection No./Size (in) |
|
1/1.25 |
|
|
1/1.25 |
|
|||
Type |
|
|
PVC |
|
|
PVC |
|
||
|
|
|
|
|
|
|
|
|
30 |
RT-PRC033F-EN |