tekmar 662 User Manual

0 (0)
tekmar 662 User Manual

- Data Brochure

D 662

Snow Detector & Melting Control 662

07/99

 

OUTSIDE

Power

 

 

F C

Remote

 

 

 

WWCO

CWCO

 

 

Melting

Idling

 

 

Water

Maximum

Supply

Target T

T

Return

Actual T

Maximum

Minimum

Slab

% Output

Supply

Return

Boiler Return

 

To change between

 

Pump 1

Pump 2

°F and °C, press and

 

hold for 1 sec.

 

Opening

Closing

Item

 

Boiler

 

 

 

 

 

 

Warning

 

Snow Detector & Melting Control 662

 

LR 58223

 

 

 

 

Mixing Operation

N

R LT / C

 

The tekmar Snow Detector & Melting Control 662 is a microprocessor-based control which, together with the Snow/Ice Sensor 090, activates and controls the rate of heat delivery to a snow melt system. This versatile control has three modulating outputs to control the heat delivery for most pump and/or valve arrangements. Protection of both the snow melt slab and the boiler is achieved through several safety features. Faster pick up times are also ensured through a viscosity compensation function which optimizes the rate of heat delivery to the slab during start up. The 662 combines all the necessary features to make snow melting safe and trouble free.

 

 

 

 

 

Sequence of Operation

 

 

pg. 2

 

Testing . . . . . . . . . . . . .

pg. 9

 

 

 

 

 

Installation . . . . . . . . . .

 

 

pg. 3

 

Error Messages . . . . . .

pg. 10

 

 

 

 

 

Settings . . . . . . . . . . . .

 

 

pg. 7

 

Technical Data . . . . . . .

pg. 12

 

 

 

 

 

Display Operation . . . .

 

 

pg. 8

 

Limited Warranty . . . . .

pg. 12

Relative Energy

Water is detected

 

 

Slab is warm enough,

 

 

 

120 Vac power

 

 

Weather is too cold,

 

Control is limiting heat

 

usage in T x Hours

by the sensor

 

no snow melting is required

 

 

supply is on

 

 

 

snow melting is off

 

output to Max T setting

 

Boiler return

Current % Heat

 

 

Snow detected:

 

Remote Enable

 

Control is limiting supply

 

Control is in

 

Control is maintaining

temperature

Output to slab

 

 

control is in

 

 

Signal present

 

 

temperature to Max.

 

 

Idling mode

 

Min. boiler return temperature

 

 

 

 

 

Melting mode

 

 

 

 

 

 

 

 

 

Supply setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Desired slab surface

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

temperature during

Target slab T

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

melting mode

Actual slab T

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power

 

120 V ac 50/60 Hz 300 VA

 

 

 

Desired slab surface

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

System Pumps

120 V ac 6 A 1/3 hp, pilot duty 240 VA 2 A

 

temperature during

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Variable Pump

120 V ac 50/60 Hz 2.2 A 1/6 hp, internally fused

Supply temperature to slab

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power

 

 

Mix Relays

24 V ac 10 A, pilot duty 48 VA 2 A

 

idling mode

 

 

 

 

 

 

 

 

OUTSIDE

 

 

 

 

 

 

Other Relays

120 V ac 10 A 1/3 hp, pilot duty 240 VA 2 A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Enclosed

Energy

Management Equipment

 

 

Sensor Sensitivity to

Slab surface temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F C

 

 

 

 

Remote

 

 

Manufactured

 

 

 

2094

Date

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

water

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1234567

S/N

 

Boiler pump is on

 

 

 

 

 

 

 

 

 

 

 

 

 

WWCO

 

CWCO

in Canada by

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

39°F

 

 

29°F

 

50 %

 

Test button to initiate

System pump is on

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Melting

 

Idling

 

 

 

 

 

 

 

 

 

test sequence

Valve is

 

 

Slab

 

 

 

 

 

 

% Output

 

 

 

Water

 

Maximum

 

 

 

 

 

 

 

 

Maximum Supply

 

 

 

 

 

 

 

 

 

 

 

 

T

 

 

 

 

24

 

 

 

 

opening/closing

 

 

Supply

 

 

 

 

Usage (T x hrs)

 

 

 

Maximum

Minimum

34

 

44

Off

35

20

 

80

temperature

 

 

 

Actual T

 

 

 

 

 

Boiler Return

 

 

 

Supply

 

Return

 

Melting

Surface

Idling

Sensitivity

Min. Boiler Return

LCD display

 

 

Target T

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

150°F

 

100°F

 

item select

 

 

 

 

 

 

 

To change between

 

 

 

Pump 1

 

Pump 2

 

 

 

 

 

 

 

 

 

temperature

 

 

 

 

 

 

 

 

°F and °C, press and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Boiler operating

 

 

 

 

 

 

 

hold for 1 sec.

 

 

 

 

Opening

Closing

 

 

 

 

 

60

 

 

Max. Temperature

 

 

 

 

 

Item

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Test

 

100

200

Off

150

drop across slab

Fault warning

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Boiler

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Max. Supply Min. Boil Return

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cold Weather Cut-off

 

The Snow/Ice Sensor is installed in a hostile environment.

 

 

 

 

Warning

 

 

30°F

 

 

0°F

 

130 sec

 

Output:

It should be cleaned and checked on a regular basis.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Melt relay is closed

Snow Detector & Melting Control 662

 

 

 

R

LR 58223

 

 

 

 

 

-20

 

 

 

tekmar

Motor Speed setting

when control is

 

 

 

 

 

 

 

 

 

 

 

 

 

motor

 

 

 

 

 

 

 

10

 

 

50

Off

25

30

 

230

 

 

in melting mode.

Floating / Variable Speed / 4-20 mA

 

 

 

 

 

 

N R T L / C

 

 

 

 

 

 

Terminal Plugs

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

∆T Max.

CWCO

Motor Speed /

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Use Nº 20 AWG or larger copper conductors rated for at least 75°C / 300V

1000Ω

 

 

 

 

 

 

 

 

 

Pump Response

 

 

 

 

 

 

 

Do not apply power here

 

 

 

 

 

Warning relay is

1

2

3

4

5

6

7

8

9

10

11

12 13 14

15

16 17

18 19 20 21 22 23 24 25 26 27 28 29

H11002

 

 

Melt

Warning

N

L

Pmp

Pmp

Pmp Pmp

Boiler

+

Mix

Mix

Mix

Sen Sen

Sen

Sen

Sen Sen En

Sen Sen Sen

Sen

Sen

 

 

Output:

 

 

 

 

Power

Com

P1

P2

Var

 

 

4-20 4-20 Com

Opn

Cls

Red Blk

Blu

Yel

Brn Com Rem

Bret Com Ret

Sup

Out

 

 

 

activated if sensor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

fault is detected

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input: Outdoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sensor 070

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Included)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input: System Supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sensor 071(Included)

Output: Turn on

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

system pump P1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input: System Return

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sensor 071(Included)

 

 

 

 

Input: Boiler Return

Output: Turn on

 

 

 

Sensor 071(Included)

boiler pump P2

 

 

 

 

120 Vac

 

OR

 

Input: Remote Enable

Power Supply

 

 

Signal. (Optional)

 

 

M

M

OR

 

 

 

 

 

 

 

 

Input: Slab Sensor 072 (Included)

Output:

 

 

 

Detects slab temperature

 

 

 

only. Does not detect Snow/Ice.

operate pump at

 

 

 

Output:

Output: control

Output: control

Input: Snow/Ice Sensor 090 installed with Sensor Socket 091. (Optional)

varying speeds

 

Turn on boiler

4-20 mA device

Floating Action

Both of these components must be ordered separately.

In order for this control to operate effectively, it must be installed in a well designed melting system. The Application Brochures A 662 provide a series of schematics which can be used with this control. Any deviations from these drawings must be discussed with a tekmar factory representative to ensure that system performance is not compromised. The application drawings are not final designs - each component within the system must be correctly sized for the control to operate effectively. It is important that the sequence of operation and the application drawings for this control are fully understood to ensure that the control selected is compatible with its intended use.

Sequence of Operation

Powering up the control

After the Snow Detector & Melting Control 662 is powered up, the red status lights and the LCD segments are turned on for 7 seconds. The control then displays the “Outdoor” temperature.

Melting Mode

Operation using a Snow/ Ice Sensor 090 - The control continually monitors the Snow/Ice Sensor 090. When water is detected, the “Water” light turns on and if the control is not in WWCO or CWCO (see page 3 for an explanation of these terms), melting mode begins.

Operation using a Remote Enable - Melting mode can also be initiated if a remote enable signal is present (terminals Com Sen and Rem Sen shorted together) and the control is not in WWCO or CWCO. The remote enable is typically used with multiple Snow Melting Controls and Snow/ Ice Sensors. It can be also be used to manually turn the melting system on by wiring a switch between the remote terminals. A remote enable switch must be installed when a Slab Sensor 072 is used as this sensor cannot detect water.

Opening light is on if the melting system requires more heat

If a remote signal is Power present, the Remote

light turns on

Remote

 

WWCO

 

CWCO

 

Melting

 

Idling

 

 

 

Water

 

Maximum

 

 

T

 

Maximum

 

 

 

Minimum

 

Supply

 

Return

 

 

 

Pump 1

 

Pump 2

 

 

 

Opening

 

Closing

 

 

 

Boiler

Closing light is on

 

if the melting

 

Warning

system requires

 

less heat

Once the control is in melting mode, the Melting relay and boiler pump (relay P2 Pmp) are turned

on. After a 4 second delay, the system pump (relay P1 Pmp) is turned on and after 8 seconds, heat is applied to the snow melt system through either a variable speed pump, a floating action mixing valve or a 4-20 mA device. The opening and closing lights indicate whether the control is increasing or decreasing the heat applied to the snow melt system. Essay E 021 compares the use of these devices for controlling the system temperature and also discusses the sizing and operation of the variable speed pump. Information on floating action can be found in Essay E 000. The 4-20 mA, variable speed pump and mixing valve outputs operate simultaneously. The 4-20 mA output can therefore be used to provide a remote readout of the pump or valve operation. The control remains in melting mode until no water is detected for at least 30 seconds and the slab is up to temperature for at least 30 minutes. Cold Weather or Warm Weather Cut Off can also terminate melting mode. When the control exits melting mode the boiler and system pumps are operated for an additional 90 seconds to purge the boiler. If the control switches from melting to idling mode, the boiler is not purged.

Idling Mode

 

 

 

 

 

 

 

 

 

 

When the melting system starts off from a cold temperature, the time required for the slab to reach

 

Power

 

 

 

 

 

 

 

“Melting” temperature can be excessive. To decrease this start up time, the slab can be maintained

 

Remote

 

at an “Idling” temperature until melting is required. The idling feature is also useful for preventing

 

WWCO

 

CWCO

 

 

 

Melting

 

Idling

frost and light ice formation. When the control is in idling mode, control operation is similar to melting

 

 

 

Water

 

Maximum

mode except the “Melting” and “Water” lights are off and the “Idling” light is on.

 

 

T

 

Maximum

 

 

 

Minimum

 

 

 

 

 

 

Supply

 

Return

 

 

Opening light is

 

Pump 1

 

Pump 2

 

 

 

 

 

 

on if the melting

 

Opening

 

Closing

 

 

system requires

 

 

 

 

more heat

 

Boiler

Closing light is on

 

 

 

 

if the melting

 

 

 

 

Warning

system requires

Snow melt system protection features

 

 

less heat

 

 

 

 

 

 

 

 

 

 

The 662 control has several features for protection of the snow melt system:

 

 

 

 

-to protect the slab from cracking due to thermal stresses, the control limits the rate of heat applied to the slab through a “T Max” setting. The T represents the difference between the slab supply and return fluid temperatures which are measured by the control. If this temperature difference approaches the “T Max” setting, the “Maximum T” light turns on and the control operates the valve or pump to maintain the T at the “T Max” setting.

-to protect the piping and other components in the system, the control limits the supply temperature to a “Max. Supply” setting. When the melt system supply temperature approaches the maximum supply setting, the “Maximum Supply” light turns on and the control operates the valve or pump to reduce the supply temperature.

-to prevent the flue gases in the boiler from condensing, the control limits the boiler return temperature to a “Min. Boil. Return” setting. When the boiler return temperature approaches this setting, the “Minimum Return” light turns on and the control operates the valve or pump to increase the boiler return temperature.

T compensation for changes in fluid viscosity

Glycol solutions used in snow melt systems have widely varying viscosities between high and low temperatures. As the glycol solution temperature drops, viscosity increases causing a reduction in flow rate. This reduction in flow rate reduces the rate of heat output if the fluid temperature drop across the slab (T) remains constant. To compensate for this, the control increases the Maximum T. This compensation is only applied when the fluid temperature is below 30°F, which is the temperature at which the viscosity of a typical 40% ethylene glycol / 60% water solution starts to increase significantly. The compensation feature is designed for fluids containing 40% ethylene glycol or 30 % propylene glycol; however, if the glycol percentage in the solution is lower than these values, the quality of heat regulation is not significantly affected. When the control is compensating for viscosity changes, the “Maximum T” light flashes.

Ramping the T during melting system start up

When the control turns on the melting system, the “Target T” is slowly ramped up to the maximum T to prevent thermal shock of the slab. If the temperature of the fluid returning to the boiler (source) is sufficient, the ramping time is less than 17 minutes. If the heat source is not dedicated to snow melting and there are other heat demands on the source, the ramping time may be longer.

2

Boiler Warning
Maximum Minimum Supply Return
Pump 1 Pump 2 Opening Closing
Water
Melting
WWCO
Closing light is on to turn off the melting system
Idling
Maximum
T
CWCO
If water is detected the Water light turns on
If a remote signal is present, the Remote light turns on

Warm Weather Cut Off (WWCO)

If the “Slab” and “Outdoor” temperatures rise above the “Melting” temperature, heating the slab is no longer required. The control therefore shuts down the melting system and enters WWCO. During WWCO the “Closing” light remains on continuously and the heat supplied through the valve or variable speed pump is reduced to zero. When the “Outdoor” or “Slab” temperature drops below the “Melting” temperature, the control exits WWCO and continues with normal operation.

Cold Weather Cut Off (CWCO)

 

 

 

Note:

 

Power

 

In Cold Weather Cut

 

 

Off, the CWCO light is

 

 

 

on and the WWCO

 

Remote

 

light is off

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maintaining the slab at a “Melting” or “Idling” temperature in extremely cold weather can be expensive and may even be impossible. When it does snow at these colder temperatures, the snow

is usually dry, light and less slippery. The control therefore turns the melting system off when the “Outdoor” temperature drops below the “CWCO” setting. During CWCO the “Closing” light remains

on continuously and the heat supplied through the valve or pump is reduced to zero. The heater

in the Snow/ Ice Sensor 090 is kept on during CWCO until the control detects snow. If snow is detected, the heater is turned off but the control retains the snow detected information. When the outdoor temperature rises above the “CWCO” temperature, the control exits CWCO and if the Snow/Ice Sensor 090 detected snow during CWCO, the control initiates melting mode.

Warning Light and Relay

If a sensor fault occurs, the Warning relay and light are turned on and an error message is given. The look-up table provided on pages 10 and 11 can be used to determine which sensor has the fault.

Pump 1 Pump 2

Opening Closing

Boiler

Warning

Exercising of the Pumps and Valves

To prevent the pumps or valves from seizing after long inactive periods, the pumps and valves are operated after every 3 days of no operation. The Pump P1 and Pump P2 relays are turned on for 20 seconds and the mixing valve or variable speed pump output is run fully open and/or fully closed. During exercising, the LCD screen alternates between two special characters as illustrated in the diagram.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Slab

 

 

 

 

 

 

 

 

 

 

 

 

% Output

Slab

 

 

 

 

 

 

 

 

 

 

 

 

% Output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Supply

 

 

 

 

 

 

 

 

Usage (T x hrs)

Supply

 

 

 

 

 

 

 

 

 

Usage (T x hrs)

Actual T

 

 

 

 

 

 

 

 

 

Boiler Return

Actual T

 

 

 

 

 

 

 

 

 

 

Boiler Return

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Target T

 

 

 

 

 

 

 

 

 

 

 

 

Target T

 

 

 

 

 

 

 

 

 

 

 

 

Installation

Caution

Improper installation and operation of this control could result in damage to equipment and possibly even personal injury. It is your responsibility to ensure that this control is safely installed according to all applicable codes and standards. This electronic control is not intended for use as a primary limit control. Other controls that are intended and certified as safety limits must be placed into the control circuit.

Step One

 

Getting ready

 

 

Check the contents of this package. If any of the contents listed are missing or damaged, please refer to the Limited Warranty and Product Return Procedure on the back of this brochure and contact your wholesaler or tekmar sales agent for assistance.

Type 662 includes: One Snow Detector & Melting control 662 • One Outdoor Sensor 070

Three Universal Sensors 071 • One Slab Sensor 072

One Data Brochure D 662 • Application Brochures A 662 • One Data Brochure D 001

Other information available: • Essay E 021 • Essay E 000 • Essay E 600

Read Brochures A 662 and select the correct Application for your job.

Note: This control can be installed with EITHER a Snow/Ice Sensor 090 and Sensor Socket 091 OR a Slab Sensor 072. The Snow/Ice Sensor 090 and Sensor Socket 091 are not included with the type 662 and must be ordered separately.

Carefully read the details of the Sequence of Operation sections in all applicable brochures to ensure that you have chosen the proper control and understand its functions within the operational requirements of your system.

Step Two

 

Mounting of the base

 

 

The control should be removed from its base by pressing down on the release clip in the wiring chamber and sliding upwards on the control. The base is then mounted in accordance with the instructions in the Data Brochure D 001.

Step Three

 

Rough-in Wiring

 

 

All electrical wiring terminates in the control base wiring chamber. It has standard 7/8" (22mm) knock-outs that accept all common wiring hardware and conduit fittings. Before breaking out the knock-outs, check the wiring diagram and select those sections of the chamber with common voltages. Do not allow the wiring to cross over sections as safety dividers, installed later, prevent this.

Power should not be applied to any of the wires during the rough-in wiring stage.

EITHER: Install the Snow/Ice Sensor 090 according to the instructions in Data Brochure D 090 and run the wiring back to the base. See Data Brochure 090 for very important details on sensor location and installation.

OR: Install the Slab Sensor 072 according to the instructions in the Data Brochure D 001 and run the wiring back to the base.

See page 5 for very important details on sensor location and installation.

Run the wiring from the other system components to the base.

Run 120 V ac to the power terminals on the control. Use a clean 120 V ac power source to ensure proper operation.

Multi-strand 16 AWG wire is recommended for the 120 V ac wiring due to its superior flexibility and ease of installation into the terminal.

3

Step Four

 

 

 

 

 

 

Electrical connections to the control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power and output connections

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The installer should test to confirm no voltage is present at any of the wires.

 

 

5

6

7

 

 

8

9

 

10

 

 

Install the control back into the base by sliding it down until it snaps in firmly.

 

 

Power

Com

 

P1

 

P2

 

Var

 

 

Connect the 120 V ac power supply to terminals Power N — L (5 and 6).

 

 

N

L

 

Pmp

 

Pmp

 

Pmp

Pmp

 

 

Melt Output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Connect the melting device to terminals Melt (1 and 2). These terminals lead to an unpowered

 

 

 

 

1

 

2

3

 

4

 

 

 

(dry) relay contact inside the control which closes when the control enters melting mode. The

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Melt

 

Warning

 

 

 

most common devices to be enabled by the 662 are pumps, heating devices or other controls.

 

 

 

 

 

 

 

 

Warning

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

If desired, connect a warning device to terminals Warning (3 and 4). These terminals lead to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

a dry relay contact inside the control which closes when there is a sensor or wiring fault.

 

 

 

 

1

 

2

3

 

4

 

 

Caution: The 662 is an operating control and is not certified as a safety device. If safety

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Melt

Warning

 

 

 

 

 

considerations are critical, a separate alarm system must be installed.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pump Power Supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Terminal Com Pmp (7) is the common power supply terminal for both terminals P1 Pmp (8)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and P2 Pmp (9).

 

 

5

6

 

7

 

 

8

 

9

 

 

10

 

 

If the pumps P1 and P2 are operated from the same 120 V ac power supply as the control,

 

 

Po

wer

 

Com

P1

 

P2

 

Var

 

 

connect the terminal Power L (6) to the terminal Com Pmp (7).

 

 

N

L

 

Pmp

Pmp

Pmp

Pmp

 

• If a separate power supply is required for P1 and/or P2, contact tekmar for details.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

System Pump P1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

6

 

7

 

 

 

 

9

 

 

10

 

 

Connect the System Pump to terminals Power N — P1 Pmp (5 and 8). These terminals lead

 

 

 

 

 

8

 

 

 

 

 

 

 

Po

wer

 

Com

 

P1

 

P2

 

Var

 

 

to a dry relay contact which closes when the control requires System Pump operation.

 

 

 

 

 

 

 

Boiler Pump P2

 

 

 

 

 

 

 

 

N

L

 

Pmp

 

Pmp

 

Pmp

 

Pmp

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Connect the Boiler Pump to terminals Power N — P2 Pmp (5 and 9). These terminals lead

 

5

6

7

 

 

8

 

9

 

10

 

 

 

 

Po

wer

 

Com

 

P1

 

P2

 

Var

 

 

to a dry relay contact which closes when the control requires Boiler Pump operation.

 

 

 

 

 

 

 

Variable Speed

 

 

 

 

 

 

 

 

 

N

L

 

Pmp

 

Pmp

 

Pmp

 

Pmp

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Connect the variable speed pump to terminals Power N Var Pmp (5 and 10). Pumps

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

6

 

7

 

 

8

9

 

 

10

 

 

 

operated by this circuit must be permanent capacitor, impedance protected with a locked rotor

 

 

 

 

 

 

 

 

 

 

 

Po

wer

 

Com

 

P1

 

P2

 

Var

 

 

 

current less than 2.2 amps. The Snow Detector & Melting Control 662 has an internal 2.5 amp

 

 

 

 

 

 

 

 

 

 

 

N

L

 

Pmp

 

Pmp

Pmp

 

Pmp

 

 

 

fuse for overload protection. This fuse is not field replaceable. Contact tekmar for details on

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

return and repair procedures if this fuse is blown.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Boiler

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Connect the boiler or the boiler control to the terminals Boiler (11 and 12). These terminals

11

12

13

14

 

15

16

 

17

 

 

 

lead to a dry relay contact which closes when the control requires boiler operation.

 

 

 

4-20

 

 

4 - 20

Com

Opn

Cls

 

 

 

Boiler

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+

 

 

 

Mix

Mix

Mix

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4-20 mA Device

Connect the positive 4 - 20 mA lead to terminal 4-20 + (13) and the negative 4 - 20 mA lead to terminal 4 - 20 – (14). Maximum resistance allowed in the 4 - 20 mA circuit is 1000 Ω. The 4 - 20 mA output can be converted to a voltage output by connecting a resistor between terminals 13 and 14.

13

14

1

13

14

1

13

14

1

4-20 4-20 C

4-20 4-20 C

4-20 4-20 C

+

M

+

M

+

M

 

 

 

 

 

500 Ω resistor

 

 

66.5 Ω resistor

 

 

 

 

 

4-20 mA converted

 

 

 

 

 

 

 

to 2-10 Vdc output

 

 

 

 

 

 

 

 

OR

 

 

 

 

 

 

 

 

250 Ω resistor

 

 

237 Ω resistor

 

 

 

 

 

4-20 mA converted

 

 

 

 

 

 

 

to 1-5 Vdc output

 

 

 

+

4 - 20 mA Actuating Motor

Connection to Operate a 4 - 20 mA Device

+

1-5 or 2-10 Vdc Actuating Motor

Converting the 4 - 20 mA Output to Operate a 1 - 5 Vdc or 2 - 10 Vdc Device

W B R

0 - 135"Slidewire"

Actuating Motor

Converting the 4 - 20 mA Output to Operate a 0 - 135Actuating Motor

Floating Action Mixing Valve

Connect one side (R) of a 24 V ac transformer to terminal Com Mix (15).

Connect the (C) side of the transformer to terminal N/C on the tekmar 010 Actuating Motor.

For other makes of actuating motors, refer to the manufacturers' installation instructions.

Connect the OPEN terminal of the Actuating Motor (CCW) to the terminal Opn Mix (16) on the control. This terminal leads to a relay contact which closes to provide 24 V ac to open the valve.

Connect the CLOSE terminal of the Actuating Motor (CW) to the terminal Cls Mix (17) on the control. This terminal leads to a relay contact which closes to provide 24 V ac to close the valve.

11

12

13

14

15

16

17

 

 

4-20

4-20

Com

Opn

Cls

Boiler

+

 

Mix

Mix

Mix

 

 

 

 

 

 

 

 

 

 

Separate Class II

 

N

1

2

 

Transformer

 

C

 

 

 

 

 

 

 

 

 

L

24Vac

R

 

 

 

N

 

C

M

type 010

4

Loading...
+ 8 hidden pages