Introduction
The Zone Manager 335 is designed to simplify the wiring between tN4 thermostats and zone valves. The 335 has an internal transformer that supplies power to the tekmarNet®4 (tN4) thermostats and connected zone valves.
Features:
• |
tN4 Compatible |
• |
Simple Wiring |
• |
Internal Transformer |
• Time Delay for Thermal Motor Zone Valves |
|
• Six Powered Zone Valve Outputs |
• |
CSA C US Certified for use in USA and Canada |
|
• Powered Zone Group Pump Output |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
tN4 |
|
C |
Pmp |
tN4 |
|
C |
|
R |
|
W |
tN4 |
|
C |
|
R |
|
W |
tN4 |
|
C |
|
R |
|
W |
tN4 |
|
C |
|
R |
|
W |
tN4 |
|
C |
|
R |
|
W |
tN4 |
|
C |
|
R |
|
W |
|
|
Zn Grp A |
A |
tNt |
|
|
|
Zone A1 |
|
tNt |
|
|
|
Zone A2 |
|
|
tNt |
|
|
Zone A3 |
|
tNt |
|
|
|
Zone A4 |
|
tNt |
|
|
|
Zone |
A5 |
|
tNt |
|
|
Zone |
A6 |
|
||||||||
|
1 |
2 |
3 |
4 |
5 |
6 |
|
7 |
8 |
9 |
10 |
|
11 |
12 |
13 |
14 |
|
15 |
16 |
17 |
18 |
|
19 |
20 |
21 |
22 |
|
23 |
24 |
25 |
26 |
|
27 |
||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Limited power available, see wiring brochure |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
tN4 |
|
|
|
|
|
|
Zone Manager 335 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
Power |
|
|
Zone A1 |
|
|
|
24 V (ac) Fuse: T2.5 A 250 V |
|
||||||||
|
|
|
|
|
|
|
|
|
|
|
|
Zone Group Pump A |
|
|
Zone A2 |
|
|
|
|
|
|
On/Off |
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
A1 |
|
|
|
|
|
|||||
|
|
|
|
|
tektra 996-01 |
|
|
|
|
|
|
|
|
Zone A3 |
|
Zone Group |
A2 |
|
|
|
|
|
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
A3 |
|
|
|
|
|
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Zone A4 |
|
|
Pump A |
A4 |
|
|
|
|
|
|||
|
|
|
For product literature: |
|
|
|
|
|
|
|
|
Zone A5 |
|
|
|
|
|
A5 |
|
|
|
|
|
||||||
|
|
|
www.tekmarcontrols.com |
|
|
|
|
|
|
|
|
|
|
|
|
|
A6 |
|
|
|
|
|
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Zone A6 |
|
|
|
|
|
A1 |
|
|
|
|
|
|
|
|
For product instructions, see brochure |
|
|
|
|
|
|
|
Zone Group |
A2 |
|
|
|
|
|
|||||||||||||
|
|
|
|
|
|
|
|
|
|
|
A3 |
|
|
|
|
|
|||||||||||||
|
|
Input Power: 115 V (ac) ±10% 60 Hz 12 A |
|
|
|
|
|
|
|
|
|
Pump A Delay |
A4 |
|
|
|
|
|
|||||||||||
|
|
Relay Rating: 115 V (ac) 5 A |
|
|
|
|
|
|
Caution! Disconnect All |
|
|
|
|
|
A5 |
|
|
|
|
|
|||||||||
|
|
All Loads Using Input Power: 11.5 A |
|
|
|
|
Power before Opening |
|
|
|
|
|
A6 |
|
|
|
|
|
|||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Made in Canada |
|
|
|
|
|
|
|
|
Supply/signal wires 90°C min. |
H7003B |
|
|||||||
|
|
|
Input Power |
Zone Group |
Meets Class B: |
|
Zone A1 |
Zone A2 |
Zone A3 |
Zone A4 |
|
Zone A5 |
Zone A6 |
|
|||||||||||||||
|
|
28 |
|
29 |
30 |
|
31 |
|
|
32 |
33 |
34 |
35 |
36 |
37 |
38 |
39 |
40 |
41 |
42 |
43 |
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
Canadian ICES & |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
FCC Part 15 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
L |
|
N |
Pmp A |
|
N |
|
|
|
C |
Vlv |
C |
Vlv |
C |
Vlv |
C |
Vlv |
|
C |
Vlv |
C |
Vlv |
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1 of 4 |
© 2005 |
D 335 - 06/05 |
Sequence of Operation
24 V (ac) Powered Outputs
The 335 has an internal transformer that provides powered outputs for up to six 24 V (ac) zone valves and six thermostats.
The internal transformer has limited power available. Refer to the Job Records to determine the load on the transformer. If the load is too large for the transformer, refer to the Wiring Brochure to add additional power to the system.
115 V (ac) Powered Outputs
The 335 has an internal relay that provides a powered output for a zone group pump.
Refer to the Job Records to determine the allowable loads for this relay.
Sequence of Operation
When a thermostat calls for heat, the Zone LED turns on and power is supplied to the zone valve.
•If the Zone Group Pump DIP switch is set to On and the Zone Group Pump Delay DIP switch is set to Off, the Zone Group Pump LED and relay turn on.
•If the Zone Group Pump DIP switch is set to On and the Zone Group Pump Delay DIP switch is set to On, the Zone Group Pump LED and relay turn on three minutes after the zone valve is powered.
•If the Zone Group Pump DIP switch is set to Off, the Zone Group Pump LED and relay are not turned on.
Pump A Demand
To operate the Zone Group Pump A relay externally, a powered signal must be sent to the Pmp A terminal on the 335. Refer to the Wiring Brochure for the proper wiring.
24 V (ac) R & C |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
tN4 Bus A |
C |
Pmp |
tN4 |
C |
R |
W |
tN4 |
C |
R |
W |
tN4 |
C |
R |
W |
tN4 |
C |
R |
W |
tN4 |
C |
R |
W |
tN4 |
C |
R |
W |
tN4 |
||||||||||||||||||||||||||
Zn Grp A |
A |
tNt |
|
Zone A1 |
|
tNt |
|
Zone A2 |
|
tNt |
|
Zone A3 |
|
tNt |
|
Zone A4 |
|
tNt |
|
Zone A5 |
|
tNt |
|
Zone A6 |
|
|
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
10 |
11 |
12 |
13 |
14 |
15 |
16 |
17 |
18 |
19 |
20 |
21 |
22 |
23 |
24 |
25 |
26 |
27 |
Limited power available, see wiring brochure
tN4
tektra 996-01
For product literature:
www.tekmarcontrols.com
For product instructions, see brochure Input Power: 115 V (ac) ±10% 60 Hz 12 A Relay Rating: 115 V (ac) 5 A
All Loads Using Input Power: 11.5 A
28 |
29 |
30 |
31 |
Input Power |
Zone Group |
||
L |
N |
Pmp A |
N |
Zone Manager 335
|
|
Power |
|
|
|
|
Zone A1 |
|||
|
Zone Group Pump A |
|
|
|
|
Zone A2 |
||||
|
|
|
|
|
|
|
|
Zone A3 |
||
|
|
|
|
|
|
|
|
Zone A4 |
||
|
|
|
|
|
|
|
|
Zone A5 |
||
|
|
|
|
|
|
|
|
Zone A6 |
||
|
|
|
|
|
Caution! Disconnect All |
|||||
|
|
|
|
|
Power before Opening |
|||||
Made in Canada |
|
|
|
|
|
|
|
|
|
|
Meets Class B: |
|
32 |
33 |
|
34 |
35 |
|
36 |
37 |
|
Canadian ICES & |
|
|
|
|||||||
Zone A1 |
|
Zone A2 |
|
Zone A3 |
|
|||||
FCC Part 15 |
|
|
|
|
||||||
|
C |
Vlv |
|
C |
Vlv |
|
C |
Vlv |
|
|
|
|
|
|
|
24 V (ac) Fuse: T2.5 A 250 V
|
|
|
|
|
|
|
On/Off |
|
|||
|
|
|
|
|
|
A1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
Zone Group |
|
A2 |
|
|
|
|
|
|||
|
|
A3 |
|
|
|
|
|
||||
|
|
Pump A |
|
A4 |
|
|
|
|
|
||
|
|
|
|
|
|
A5 |
|
|
|
|
|
|
|
|
|
|
|
A6 |
|
|
|
|
|
|
|
|
|
|
|
A1 |
|
|
|
|
|
|
Zone Group |
|
A2 |
|
|
|
|
|
|||
|
|
A3 |
|
|
|
|
|
||||
|
Pump A Delay |
|
A4 |
|
|
|
|
|
|||
|
|
|
|
|
|
A5 |
|
|
|
|
|
|
|
|
|
|
|
A6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Supply/signal wires 90°C min. |
H7003B |
|||||||||
38 |
39 |
|
40 |
41 |
|
42 |
43 |
|
|
||
|
|
|
|
|
|||||||
Zone A4 |
|
Zone A5 |
|
Zone A6 |
|
|
|||||
C |
Vlv |
|
C |
Vlv |
|
C |
Vlv |
|
|
115 V (ac) L & N
© 2005 |
D 335 - 06/05 |
2 of 4 |