tekmar 356 User Manual

0 (0)

- Data Brochure

D 356

Mixing Control 356

09/08

The Mixing Control 356 is designed to control the supply water temperature to a hydronic system in order to provide outdoor reset or setpoint operation. The control uses a variable speed injection pump to regulate the supply water temperature, while protecting the boiler against flue gas condensation. The control has a Liquid Crystal Display (LCD) to view system status and operating information.

Additional functions include:

Quick Setup for easy installation and programming of control

User comfort adjustment to increase or decrease building space temperature

Advanced settings to fine-tune building requirements

Boiler Control for improved energy savings

Test sequence to ensure proper component operation

CSA C US certified (approved to applicable UL standards)

Input

Supply Sensor

Included

Input

Outdoor Sensor

Included

Press & Hold

Power:

24 V ±10% 50/60 Hz 3 VA

Item, to view settings

Var. Pmp:120 V (ac) 2.4 A 1/6 hp

, to test

Relay:

120 V (ac) 5 A 1/6 hp

Press & Release

 

 

Meets Class B:

Item + + , to adjust menu

 

 

 

 

Canadian ICES

tektra 911-02

 

 

 

 

FCC Part 15

 

 

 

 

 

 

 

 

 

H1193C

 

 

 

 

 

VIEW

 

 

 

 

MIX

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Terminal Unit

 

 

10 30 50 70 90

Mixing

 

Return

 

Supply

% Out

 

 

Demand

Item

 

Miixiing Conttroll 356

 

 

 

 

 

 

 

 

 

Code

 

 

 

 

 

 

 

 

 

 

Date

Inst/Adv

Variiablle Speed

 

 

 

 

 

 

C

US

Do not apply power

Made in Canada

 

 

 

 

 

 

 

 

 

 

 

 

1 2

3

4

Signal wiring

5 6 7

8

9

 

Com Sup

Out

Boil

must be rated

 

 

 

 

 

 

 

 

Power

 

 

 

Boiler

 

 

 

 

at least 300 V

 

 

 

 

 

 

T

 

R+

C-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output

Boiler Sensor

 

 

 

 

 

Included

 

 

 

 

Boiler

Output

Variable Speed

Injection Pump

(through back

of control)

Input

24 V (ac)

Power Supply

Input

Mixing Demand

Signal

Note:

Mix demand must have an electrical closure between terminals 7 and 9 before the mix injection pump is able to operate and the boiler

is able to fire.

1 of 16

Copyright © D 356 -09/08

How To Use The Data Brochure

This brochure is organized into four main sections. They are: 1) Sequence of Operation, 2) Installation, 3) Control Settings, and 4) Troubleshooting. The Sequence of Operation section has three sub-sections. We recommend reading Section A: General Operation of the Sequence of Operation, as this contains important information on the overall operation of the control. Then read the sub-sections that apply to your installation. For quick installation and setup of the control, refer to the Installation section, DIP Switch Setting section, followed by the Quick Setup section.

The Control Settings section (starting at DIP Switch Setting) of this brochure, describes the various items that are adjusted and displayed by the control. The control functions of each adjustable item are described in the Sequence of Operation.

Table of Contents

User Interface ....................................................

Pg 2

Quick Setup .....................................................

Pg 11

Description of Display Elements .....................

Pg 3

Control Settings ..............................................

Pg 12

Sequence of Operation .....................................

Pg 3

View Menu ...........................................

Pg 12

Section A: General Operation ..............

Pg 3

Adjust Menu ........................................

Pg 12

Section B: Mixing ..................................

Pg 4

Testing and Troubleshooting .........................

Pg 14

Section C: Boiler Operation .................

Pg 7

Error Messages ..................................

Pg 15

Installation .........................................................

Pg 8

Technical Data .................................................

Pg 16

DIP Switch Setting ..........................................

Pg 10

Limited Warranty .............................................

Pg 16

Reference Material: Essay E 003 “Characterized Heating Curve and Reset Ratio”

Essay E 021 “Mixing Methods and Sizing of Variable Speed Injection Pumps”

User Interface

The 356 uses a Liquid Crystal Display (LCD) as the method of supplying information. You use the LCD in order to set up and monitor the operation of your system. The 356 has three push buttons (Item, , ) for selecting, viewing, and adjusting settings. As you program your control, record your settings in the ADJUST menu table which is found in the second half of this brochure.

Item

The abbreviated name of the selected item will be displayed in the item field of the display. To view the next available item, press and release the Item button. Once you have reached the last available item, pressing and releasing the Item button will return the display to the first item.

Adjust

To make an adjustment to a setting in the control, press and hold simultaneously for 1 second, all 3 buttons. The display will then show the word ADJUST in the top right corner. Then select the desired item using the Item button. Finally, use the and / or button to make the adjustment.

Item

Item

To exit the ADJUST menu, either select the ESC item and press the or button, or leave the adjustment buttons alone for 20 seconds.

When the Item button is pressed and held in the VIEW menu, the display scrolls through all the control adjust items in both access levels.

Additional information can be gained by observing the status field and pointers of the LCD. The status field will indicate which of the control’s outputs are currently active. Most symbols in the status field are only visible when the VIEW menu is selected.

Copyright © D 356 -09/08

2 of 16

tekmar 356 User Manual

Display

Item Field

Displays an abbreviated name of the selected item

Status Field

Displays the current status of the control’s inputs, outputs and operation

 

 

 

 

Number Field

 

 

 

 

 

Displays the current value

 

 

 

 

of the selected item

OUTDR DSGN

DIFF

VIEW

ADJUST

Menu Field

BOIL TARGET

 

 

°F

 

 

Displays the

MIX

MINMAX

 

 

°C

current menu

 

 

 

ROOM WWSD

 

 

 

 

INDR

 

 

 

 

 

Terminal Unit

 

10

30 50 70 90

Mixing

Return

 

Supply

% Out

Demand

{Buttons

Selects Menus, Items and adjusts settings

Item

Symbol Description

 

Burner

Pointer

 

Displays the control operation as indicated by

 

Displays when the boiler relay is turned on.

 

the text.

 

 

 

 

 

°F, °C

°F, °C

 

Displays the unit of measure that all of the

 

 

temperatures are to be displayed in the control.

 

 

 

 

Sequence of Operation

Section A

Section B

Section C

General Operation

Mixing

Boiler Operation

Page 3-4

Page 4-6

Page 7

Section A — General Operation

POWERING UP THE CONTROL

When the Mixing Control 356 is powered up, the control displays the control type number in the LCD for 2 seconds. Next, the software version is displayed for 2 seconds. Finally, the control enters into the normal operating mode and the LCD defaults to displaying the current outdoor air temperature.

3 of 16

Copyright © D 356 -09/08

OPERATION

The 356 uses a variable speed injection pump to control the supply water temperature to a hydronic system. The supply water temperature is based on either the current outdoor temperature, or a fixed setpoint.

Outdoor Reset

When the outdoor design (OUTDR DSGN) setting is not set to OFF, the 356 calculates a mixing supply temperature based on the current outdoor air temperature and the Characterized Heating Curve settings.

Setpoint Control

When the outdoor design (OUTDR DSGN) setting is set to OFF, the 356 supplies a fixed mixing supply temperature equal to the MIX TARGET setting. An outdoor sensor is not required during this mode of operation.

VARIABLE SPEED INJECTION

A standard wet rotor circulator is connected to the 356 at the back of the control. The 356 increases or decreases the power output to the circulator when there is a mixing demand. The circulator speed varies to maintain the correct mixed supply water temperature at the mix sensor. For correct sizing and piping of the variable speed injection driven circulator, refer to essay E 021. A visual indication of the current variable speed output is displayed in the LCD in the form of a horizontal bar graph.

BOILER PROTECTION (BOIL MIN)

The 356 is capable of providing boiler protection from cold mixing sys-

 

Mixing

 

 

sensor

 

tem return water temperatures. If the boiler sensor temperature is cooler

 

 

 

 

 

 

 

 

 

 

than the BOIL MIN setting while the boiler is firing, the 356 reduces the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

output to the variable speed injection pump. This limits the amount of

 

 

 

 

 

 

 

 

cool return water to the boiler, and allows the boiler temperature to re-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

cover. This feature can only be used if a boiler sensor is installed.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Design Supply

 

Terminal Unit

Temperature

Indoor Design

Outdoor Design

Increasing Water

 

Decreasing Outdoor Temperature

Current output of variable

speed injection pump

10 30 50 70 90

% Out

Boiler supply

sensor

or

Boiler return

sensor

EXERCISING

The 356 has a built-in exercising function. If the pump has not been operated at least once every 3 days, the control turns on the output for 10 seconds. This minimizes the possibility of the pump seizing during a long period of inactivity.

Note: The exercising function does not work if power to the control or pump is disconnected.

FACTORY DEFAULTS

The control comes preset with several factory defaults. These defaults are based on the terminal unit selection (see section B2). To fine-tune building requirements, these defaults may be changed. If a factory default value for a terminal unit is changed, the terminal unit number will flash when selected in the ADJUST menu.

To reload the factory defaults listed in section B2, power down the control and wait for 10 seconds. Power up the control while simultaneously holding the Item and buttons. The terminal unit number should now be displayed constantly in the LCD rather than flashing.

Section B: Mixing

Section B1

Section B2

Section B3

General

Installer

Advanced

Section B1: General

To control

MIXING DEMAND

A mixing demand is required in order for the 356 to provide heat. A mixing demand is generated by connecting terminal T(7) to terminal C-(9) through a switching device. Once the switching device closes, the Mixing Demand pointer is displayed in the LCD. The 356 calculates a MIX TARGET supply temperature based on the outdoor air temperature and settings. If required, the 356 operates the boiler in order to provide heat to the variable speed injection pump.

C R

Zone Valve Motor

End Switches

M

M

Copyright © D 356 -09/08

4 of 16

CHARACTERIZED HEATING CURVE

When used as a mixing reset control, the 356 varies the supply water temperature based on the outdoor air temperature. The control takes into account the type of terminal unit that the system is using. Since different types of terminal units transfer heat to a space using different proportions of radiation, convection and conduction, the supply water temperature must be controlled differently. Once the control is told what type of terminal unit is used, the control loads the factory defaults and varies the supply water temperature according to the type of terminal unit. This improves the control of the air temperature in the building.

MIXING TARGET TEMPERATURE (MIX TARGET)

When used as a mixing reset control, the MIX TARGET temperature is determined from the Characterized Heating Curve settings and outdoor air temperature. When used as a setpoint control, the installer will set the MIX TARGET temperature. The control displays the temperature that it is currently trying to maintain as the mixing supply temperature. If the control does not have a mixing demand, “- - -” is displayed as the MIX TARGET.

Section B2: Installer

OUTDOOR DESIGN (OUTDR DSGN)

The OUTDR DSGN is the outdoor air temperature that is the typical coldest temperature of the year where the building is located. This temperature is used when doing the heat loss calculations for the building. If a cold outdoor design temperature is selected, the mixing supply temperature rises gradually as the outdoor temperature drops. If a warm outdoor design temperature is selected, the mixing supply temperature rises rapidly as the outdoor temperature drops.

SETPOINT OPERATION (MIX TARGET)

For setpoint operation, set the OUTDR DSGN to OFF. The MIX TARGET becomes the setpoint supply temperature that the control is to maintain. The MIX TARGET temperature is set by the installer in the ADJUST menu. An outdoor sensor is not required during this mode of operation.

ROOM (ROOM)

The ROOM is the desired room temperature for the mixing zones, and it provides a parallel shift of the Characterized Heating Curve. The room temperature desired by the occupants is often different from the design indoor temperature (MIX INDR). If the room temperature is not correct, adjusting the ROOM setting increases or decreases the amount of heat available to the building.

 

MIX DSGN

Temperature

cold

OUTDR

Water

DSGN

warm

 

Increasing

MIX INDR

 

Decreasing Outdoor Temperature

 

 

.

 

 

 

p

 

 

 

m

 

 

 

e

 

 

 

T

 

 

 

l

 

 

 

a

 

TemperatureWater

 

tu

 

c

 

A

 

n

 

 

 

ig

 

 

s

 

 

e

 

 

 

D

 

 

 

l

 

 

 

a

 

 

 

rm

 

 

 

o

 

 

 

N

 

Increasing

 

ROOM

 

 

MIX INDR

 

 

 

 

Decreasing Outdoor Temperature

TERMINAL UNITS

When using a Characterized Heating Curve, the control requires the selection of a terminal unit. The terminal unit determines the shape of the Characterized Heating Curve according to how the terminal unit delivers heat into the building space (refer to Essay E 003). The 356 provides for selection between six different terminal unit types: two types of radiant floor heat, fancoil, fin-tube convector, radiator and baseboard. When a terminal unit is selected, the control automatically loads the design supply temperature (MIX DSGN) and maximum supply temperature (MIX MAX). The factory defaults are listed below. To change defaults, refer to section B3. If a default has been changed, refer to section A to reload the factory defaults.

Terminal Unit

High Mass Radiant

Low Mass Radiant

Fancoil

Fin-tube Convector

Radiator

Baseboard

(1)

(2)

(3)

(4)

(5)

(6)

 

MIX DSGN

120°F (49°C)

140°F (60°C)

190°F (88°C)

180°F (82°C)

160°F (71°C)

150°F (66°C)

MIX MAX

140°F (60°C)

160°F (71°C)

210°F (99°C)

200°F (93°C)

180°F (82°C)

170°F (77°C)

5 of 16

Copyright © D 356 -09/08

Loading...
+ 11 hidden pages