tekmar 261 User Manual

4 (1)
tekmar 261 User Manual

- Data Brochure

D 261

Boiler Control 261

03/09

The Boiler Control 261 is designed to control two separate on / off boiler stages (or one low / high fire) in order to provide outdoor reset or setpoint operation. The control includes a Liquid Crystal Display (LCD) to view system status and operating information.

Additional functions include:

Quick Setup for simple installation and programming of control

User comfort adjustment to increase or decrease building space temperature

Advanced settings to fine-tune building requirements

Powered boiler pump output

Test sequence to ensure proper component operation

Setback input for energy savings

120 V (ac) power supply

CSA C US certified (approved to applicable UL standards)

BOIL

 

VIEW

 

°F

 

OCC

1 2

 

 

Terminal Unit

Setpoint

Boiler Demand

Fire Delay Setpoint Demand

Item

Note:

Boiler or setpoint demand must be powered with 20 to 260 V (ac) before the boiler is able to fire.

Input

Boiler Demand

Signal

Boiler Control 261

Two Stage Boiler & Setpoint

1

2

3

4

5

6

7

8

Boiler

Setpoint

Power

Boil

 

Demand

Demand

L

N

Pmp

N

Input

Setpoint Demand

Signal

Advanced RotateReturn

To increase or decrease the building temperature:

Press the Item,, buttons simultaneously for 1 sec. to enter the ADJUST menu

Use the , buttons to adjust the ROOM setting

Display defaults back to VIEW menu after 20 sec.

C US

158033

Installer

Off

Installer Instructions

ROOM - Set to desired room temp. OUTDR DSGN - Set to coldest (design) outdoor temp.

Terminal Unit

Set to

High Mass Radiant

1

Low Mass Radiant

2

Fan Coil

3

Convector

4

Radiator

5

Baseboard

6

Setpoint - Set to desired setpoint temp.

Refer to brochure for more information

Test

Made in Canada by

Meets Class B:

Canadian ICES

tekmar Control Systems Ltd.

FCC Part 15

tektra 910-02

V (ac) 10 A 1/3 hp

Code

Relays:

240

Power:

120

V 50/60 Hz 1300 VA

 

Demand:

20 to 260 V (ac) 2 VA

Date

 

 

 

9

10

11 12

Stage

Stage

1

1

2

2

Do not apply power

 

 

13 14 15 16 17

Signal wiring must be

H1108D

UnO Com Boil Out Com

rated at least 300V.

 

Sw

 

 

 

 

Input

 

 

Outdoor

 

 

Sensor Included

 

 

Input

 

 

Universal

 

 

Sensor Included

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input

Output

 

 

 

 

 

 

 

 

Input

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output

Output

120 V (ac) Power

Boiler System

tekmar Timer

 

Supply

Pump

Boiler

Boiler

Optional

1 of 20 Copyright © D 261 - 03/09

How To Use The Data Brochure

This brochure is organized into four main sections. They are: 1) Sequence of Operation, 2) Installation, 3) Control Settings, and 4) Troubleshooting. The Sequence of Operation section has three sub-sections. We recommend reading Section A: General Operation of the Sequence of Operation, as this contains important information on the overall operation of the control. Then read the sub-sections that apply to your installation. For quick installation and setup of the control refer to the Installation section, DIP Switch Settings section, followed by the Quick Setup section.

The Control Settings section (starting at DIP Switch Settings) of this brochure, describes the various items that are adjusted and displayed by the control. The control functions of each adjustable item are described in the Sequence of Operation.

Table of Contents

User Interface ................................................

pg 2

Quick Setup .................................................

pg 13

Description of Display Elements .................

pg 3

Control Settings ..........................................

pg 14

Sequence of Operation .................................

pg 4

View Menu ........................................

pg 14

Section A: General Operation ........

pg 4

Adjust Menu .....................................

pg 14

Section B: Boiler Reset ..................

pg 5

Testing and Troubleshooting .....................

pg 16

Section C: Setpoint.........................

pg 8

Error Messages ...............................

pg 18

Installation .....................................................

pg 9

Technical Data .............................................

pg 20

DIP Switch Settings ....................................

pg 12

Limited Warranty .........................................

pg 20

Reference Material: Essay E 003 “Characterized Heating Curve and Reset Ratio”

User Interface

The 261 uses a Liquid Crystal Display (LCD) as the method of supplying information. You use the LCD in order to set up and monitor the operation of your system. The 261 has three push buttons (Item, , ) for selecting, viewing, and adjusting settings. As you program your control, record your settings in the ADJUST menu table which is found in the second half of this brochure.

Item

The abbreviated name of the selected item will be displayed in the item field of the display. To view the next available item, press and release the Item button. Once you have reached the last available item, pressing and releasing the Item button will return the display to the first item.

Adjust

To make an adjustment to a setting in the control, press and hold simultaneously for 1 second, all 3 buttons. The display will then show the word ADJUST in the top right corner. Then select the desired item using the Item button. Finally, use the and / or button to make the adjustment.

Item

Item

To exit the ADJUST menu, either select the ESC item and press the or button, or leave the adjustment buttons alone for 20 seconds.

When the Item button is pressed and held in the VIEW menu, the display scrolls through all the adjust items in both access levels.

Additional information can be gained by observing the status field and pointers of the LCD. The status field will indicate which of the control’s outputs are currently active. Most symbols in the status field are only visible when the VIEW menu is selected.

Copyright © D 261 - 03/09

2 of 20

Display

Item Field

Number Field

Displays an

Displays the current value

abbreviated name of

of the selected item

the selected item

 

OUTDR DSGN

DIFF

VIEW

ADJUST

Menu Field

BOIL TARGET

 

 

°F

 

 

Displays the

MINMAX

 

 

°C

current menu

 

 

 

ROOM WWSD

 

 

min

 

 

 

1 2

 

INDR UNOCC

 

 

 

 

 

 

 

Terminal Unit

 

Setpoint

Boiler Demand

 

Fire Delay

Setpoint Demand

Status Field

 

 

Buttons

Displays the current

 

 

Selects Menus, Items and

 

 

{adjusts settings

status of the control’s

 

 

inputs, outputs and

Item

 

 

operation

 

 

Symbol Description

 

Pump

UNOCC

Unoccupied Schedule

 

Displays when the control is in unoccupied

 

Displays when the boiler pump is in operation.

 

 

 

(Night) mode.

 

 

 

 

 

 

 

1 2

Burner

°F, °C

°F, °C

Displays when the stage 1 and / or stage 2 relay

Displays the unit of measure that all of the

 

is turned on.

 

temperatures are to be displayed in the control.

 

 

 

 

OCC

Occupied Schedule

 

Pointer

Displays when the control is in occupied (Day)

 

Displays the control operation as indicated by

 

mode.

 

the text.

 

 

 

 

3 of 20

Copyright © D 261 - 03/09

Sequence of Operation

Section A

Section B

Section C

General Operation

Boiler Reset

Setpoint

Page 4

Page 5-8

Page 8

Section A — General Operation

POWERING UP THE CONTROL

When the Boiler Control 261 is powered up, the control displays the control type number in the LCD for 2 seconds. Next, the software version is displayed for 2 seconds. Finally, the control enters into the normal operating mode and the LCD defaults to displaying the current outdoor air temperature.

OPERATION

The 261 operates two on / off heat sources to control the supply water temperature to a hydronic system. The supply water temperature is based on either the current outdoor temperature, or a fixed setpoint.

Outdoor Reset

When a demand signal from the heating system is present, the 261 calculates a supply temperature based on the outdoor air temperature and Characterized Heating Curve settings.

Setpoint Control

When a demand signal from a setpoint system is present, the control operates the boiler(s) to maintain the supply water temperature at the Setpoint setting. Refer to section C.

Design Supply

 

Terminal Unit

Temperature

Indoor Design

Outdoor Design

Increasing Water

 

Decreasing Outdoor Temperature

SETBACK (UNOCCUPIED)

To provide greater energy savings, the 261 has a setback capability. With setback, the supply water temperature in the system is reduced when the building is unoccupied. By reducing the supply water temperature, air temperature in the space may be reduced even when thermostat(s) are not turned down. Any time the UnO Sw (13) and the Com (14) terminals are shorted together, the control operates in the unoccupied (Night) mode. When in the unoccupied (Night) mode, the UNOCC segment is displayed in the LCD. The 261 adjusts the supply water temperature based on the UNOCC settings made in the control. This feature has no effect when the control is used in setpoint operation.

ROTATION

13

14

UnO Com

Sw

 

Timer switch

The 261’s Equal Run Time Rotation function is fixed at 48 hours. The firing order of the boilers changes whenever one stage accumulates 48 hours more running time than the other stage. After each rotation, the stage with the least running hours is the first to fire, and the stage with the most running hours is the last to fire. This function ensures that both stages receive equal amounts of use. When the Rotate / Off DIP switch is set to the Off position, Stage 1 is always the first stage to fire.

EXERCISING

The 261 has a built-in exercising function. If the pump has not been operated at least once every 3 days, the control turns on the output for 10 seconds. This minimizes the possibility of the pump seizing during a long period of inactivity. While the control is exercising, the Test LED flashes.

Note: The exercising function does not work if power to the control or pump is disconnected.

FACTORY DEFAULTS

The control comes preset with several factory defaults. These defaults are based on the terminal unit selection (see section B2). To fine-tune building requirements, these defaults may be changed. If a factory default value for a terminal unit is changed, the terminal unit number will flash when selected in the ADJUST menu.

To reload the factory defaults listed in section B2, power down the control and wait for 10 seconds. Power up the control while simultaneously holding the Item and buttons. The terminal unit number should now be displayed constantly in the LCD rather than flashing.

Copyright © D 261 - 03/09

4 of 20

Section B: Boiler Reset

Section B1

Section B2

Section B3

General

Installer

Advanced

Section B1: General

BOILER DEMAND

A boiler demand is required in order for the 261 to provide heat to the heating system. A

boiler demand is generated by applying a voltage between 24 and 240 V (ac) across the Boiler Demand terminals (1 and 2). Once voltage is applied, the Boiler Demand pointer is displayed in the LCD. If the 261 is not in WWSD, the 261 closes the Boil Pmp contact. The

261 calculates a boiler target (BOIL TARGET) supply temperature based on the outdoor

24 to 240 V (ac)

air temperature and settings. The 261 then fires the boiler(s), if required, to maintain the target supply temperature.

1

2

Boiler

Demand

BOILER PUMP OPERATION (BOIL PMP)

The boiler pump contact (Boil Pmp, terminal 7) closes whenever there is a boiler demand and the 261 is not in WWSD. The boiler pump segment is displayed in the LCD. After the boiler demand has been satisfied, the 261 continues to operate the boiler pump for 20 seconds. This allows any excess heat to be purged out to the heating system. During WWSD, the boiler pump is operated based on the exercise function. For boiler pump contact operation during setpoint operation, refer to section C.

BOILER OPERATION

When the 261 determines that boiler operation is required, the boiler Stage contact(s) (9 and 10 and / or 11 and 12) close. While the boiler contact(s) is closed, the burner and stage segment in the LCD is displayed.

STAGING

The 261 controls up to two stages in order to supply the required target temperature. After the first stage is turned on in the firing sequence, the control waits a minimum amount of time before turning on the next stage. After the minimum time delay between stages has expired, the 261 examines the control error to determine when the next stage is to fire. The control error is determined using Proportional, Integral and Derivative (PID) logic.

Proportional - compares the actual supply temperature (BOIL) to the boiler target (BOIL TARGET) temperature. The colder the supply water temperature, the sooner the next stage is turned on.

Integral - compares the actual supply temperature (BOIL) to the boiler target (BOIL TARGET) temperature over a period of time.

Derivative - determines how fast or slow the supply water temperature is changing. If the supply temperature is increasing slowly, the next stage is turned on sooner. If the supply temperature is increasing quickly, the next stage is turned on later, if at all.

Each stage has a minimum on time, and a minimum off time.

CHARACTERIZED HEATING CURVE

The 261 varies the supply water temperature based on the outdoor air temperature. The control takes into account the type of terminal unit that the system is using. Since different types of terminal units transfer heat to a space using different proportions of radiation, convection and conduction, the supply water temperature must be controlled differently. Once the control is told what type of terminal unit is used, the control varies the supply water temperature according to the type of terminal unit. This improves the control of the air temperature in the building.

BOILER TARGET TEMPERATURE (BOIL TARGET)

The BOIL TARGET temperature is determined from the Characterized Heating Curve settings and the outdoor air temperature. The control displays the temperature that it is currently trying to maintain as the boiler supply temperature. If the control does not presently have a requirement for heat, it does not show a boiler target temperature. Instead, “- - -” is displayed in the LCD.

5 of 20

Copyright © D 261 - 03/09

Section B2: Installer

OUTDOOR DESIGN (OUTDR DSGN)

The OUTDR DSGN is the outdoor air temperature that is the typical coldest temperature of the year where the building is located. This temperature is used when doing the heat loss calculations for the building. If a cold outdoor design temperature is selected, the boiler supply temperature rises gradually as the outdoor temperature drops. If a warm outdoor design temperature is selected, the boiler supply temperature rises rapidly as the outdoor temperature drops.

 

BOIL DSGN

Temperature

cold

OUTDR

Water

DSGN

warm

 

Increasing

BOIL INDR

 

Decreasing Outdoor Temperature

ROOM OCC & UNOCC (ROOM)

The ROOM is the desired room temperature for the boiler zones, and it provides a parallel shift of the Characterized Heating Curve. The room temperature desired by the occupants is often different from the design indoor temperature (BOIL INDR). If the room temperature is not correct, adjusting the ROOM setting increases or decreases the amount of heat available to the building. A ROOM setting is available for both the occupied (Day) and unoccupied (Night) modes.

Increasing Water Temperature

 

.

 

 

p

 

 

m

 

 

e

 

 

T

 

 

l

 

 

a

 

 

tu

 

c

n

A

 

 

 

ig

 

s

 

e

 

 

D

 

 

l

 

 

a

 

 

rm

 

 

o

 

 

N

 

ROOM

BOIL INDR

Decreasing OutdoorTemperature

TERMINAL UNITS

When using a Characterized Heating Curve, the control requires the selection of a terminal unit. The terminal unit determines the shape of the Characterized Heating Curve according to how the terminal unit delivers heat into the building space (refer to Essay E 003). The 261 provides for selection between six different terminal unit types: two types of radiant floor heat, fancoil, fin-tube convector, radiator and baseboard. When a terminal unit is selected, the control automatically loads the design supply temperature (BOIL DSGN), maximum supply temperature (BOIL MAX), and minimum supply temperature (BOIL MIN). The factory defaults are listed below. To change defaults, refer to section B3. If a default has been changed, refer to section A to reload the factory defaults.

Terminal Unit

High Mass Radiant

Low Mass Radiant

Fancoil

Fin-tube Convector

Radiator

Baseboard

(1)

(2)

(3)

(4)

(5)

(6)

 

BOIL DSGN

120°F (49°C)

140°F (60°C)

190°F (88°C)

180°F (82°C)

160°F (71°C)

150°F (66°C)

BOIL MAX

140°F (60°C)

160°F (71°C)

210°F (99°C)

200°F (93°C)

180°F (82°C)

170°F(77°C)

BOIL MIN

OFF

OFF

140°F (60°C)

140°F (60°C)

140°F (60°C)

140°F (60°C)

High Mass Radiant (1)

This type of a hydronic radiant floor is embedded in either a thick concrete or gypsum pour. This heating system has a large thermal mass and is slow acting.

Default values: BOIL DSGN = 120°F (49°C), BOIL MAX = 140°F (60°C), BOIL MIN = OFF

Low Mass Radiant (2)

This type of radiant heating system is either attached to the bottom of a wood sub-floor, suspended in the joist space, or sandwiched between the sub-floor and the surface. This type of radiant system has a relatively low thermal mass and responds faster than a high mass system.

Default values: BOIL DSGN = 140°F (60°C), BOIL MAX = 160°F (71°C), BOIL MIN = OFF

Copyright © D 261 - 03/09

6 of 20

Loading...
+ 14 hidden pages