Installation & Operation Manual |
654_D |
Snow Melting Control 654 |
06/13 |
Snow Melting |
Replaces: New |
Introduction
The Snow Melting Control 654 is designed to operate electric or hydronic equipment to melt snow or ice from any surface including driveways, walkways, patios, business entrances, parking ramps, loading docks, hospital entrances, helipads or car wash bays. The surface temperature for snow melting is controlled automatically to reduce operating energy costs. The 654 has an automatic start and stop function when used with the Snow/Ice Sensor 090 or 094. Automatic start with a timed stop is available when used with the Snow Sensor 095. The 654 can operate a dedicated hydronic boiler or a mixing device. Isolation relays are required to operate line voltage pumps. Electric systems require a separate GFCI and electrical relay contactor.
Features
• Automatic Snow / Ice Detection
• Supports Both Inslab & Retrofit Aerial Sensors
• Manual Start With Timer
• Programmable Schedule
• tekmarNet® Communication Compatible
• Warm Weather Shut Down
• Cold Weather Cut Out
• Idling
• Snow Melt Zoning With Priority
• Tandem Snow / Ice Detection
• Slab Protection
• Storm
• EconoMelt
• Manual Override
• Snow Melt Zone Tracking
• Scenes
• Away Key
• Exercising
• Alert Output
1 of 44 |
© 2013 |
654_D - 06/13 |
Table of Contents
Important Safety Information............................................. |
3 |
Installation ......................................................................... |
4 |
Preparation .................................................................... |
4 |
Physical Dimensions ..................................................... |
4 |
Installation Location....................................................... |
4 |
Rough-In Wiring............................................................. |
4 |
Sizing the Transformer .................................................. |
5 |
Control Wiring................................................................ |
5 |
Sensor Wiring ................................................................ |
7 |
Testing the Sensor Wiring ............................................. |
8 |
Testing the Control Wiring ............................................. |
8 |
Manual Override - Maximum Heat ................................ |
9 |
Manual Override - Test .................................................. |
9 |
Manual Override - Purge ............................................... |
9 |
Manual Override - Off.................................................... |
9 |
Switch Settings.................................................................. |
9 |
User Interface................................................................... |
10 |
Display .......................................................................... |
10 |
Operation Field ............................................................. |
10 |
Status Field................................................................... |
10 |
Symbols ........................................................................ |
10 |
Programmable Settings.................................................... |
11 |
Programming Menus .................................................... |
11 |
Access Levels and Access Level Lock ........................ |
11 |
View Menu .................................................................... |
12 |
Set Temp Menu ............................................................ |
14 |
Time Menu.................................................................... |
15 |
Schedule Menu ............................................................ |
16 |
Display Menu................................................................ |
17 |
Scene Menu ................................................................. |
17 |
Monitor Menu................................................................ |
18 |
Toolbox Menu ............................................................... |
19 |
Override Menu.............................................................. |
20 |
System Menu................................................................ |
21 |
Boiler Menu .................................................................. |
22 |
Mix Menu ...................................................................... |
23 |
tekmarNet® Menu ......................................................... |
24 |
Sequence of Operation .................................................... |
25 |
Snow Melting Overview................................................ |
25 |
Slab Temperature Control ............................................ |
25 |
Melt Operation .............................................................. |
25 |
Melt - Manual Start and Timed Stop ............................ |
26 |
Melt - Automatic Start and Stop ................................... |
26 |
Melt - EconoMelt........................................................... |
27 |
Melt - Automatic Start and Timed Stop ........................ |
27 |
Melt - Tracked Start and Stop ...................................... |
28 |
Melt - Scheduled Start and Stop .................................. |
28 |
Additional Melting Time ................................................ |
29 |
Idle Operation ............................................................... |
29 |
Storm Operation ........................................................... |
29 |
Warm Weather Shut Down........................................... |
30 |
Cold Weather Cut Out .................................................. |
30 |
Away Scene.................................................................. |
30 |
Programmable Schedules............................................ |
31 |
Time Clock.................................................................... |
31 |
Snow Melt Zones and Priority ...................................... |
31 |
Slab Protection ............................................................. |
33 |
Application Modes ........................................................ |
33 |
Electric Operation......................................................... |
33 |
Pulse Width Modulation Operation .............................. |
33 |
Boiler Operation ........................................................... |
33 |
Mixing Operation .......................................................... |
35 |
Tandem Snow / Ice Detection ...................................... |
36 |
Exercising ..................................................................... |
36 |
Alert Relay .................................................................... |
36 |
Pump Post Purge.......................................................... |
36 |
Melt and Storm Groups ................................................ |
37 |
User Switch Setup ........................................................ |
37 |
Troubleshooting............................................................... |
38 |
Error Messages ............................................................ |
38 |
Frequently Asked Questions ........................................ |
42 |
Job Record ....................................................................... |
42 |
Technical Data................................................................. |
44 |
Limited Warranty and Product Return Procedure ........... |
44 |
Getting Started
Congratulations on the purchase of your new Snow Melting Control!
This manual covers the complete installation, programming and sequence of operation for this control. You will also find instruction on testing, commissioning, and troubleshooting the control and system that it operates.
© 2013 |
654_D - 06/13 |
2 of 44 |
Important Safety Information
It is your responsibility to ensure that this control is safely installed according to all applicable codes and standards. tekmar is not responsible for damages resulting from improper installation and/or maintenance.
To avoid serious personal injury and damage to the equipment:
•Read Manual and all product labels BEFORE using the equipment. Do not use unless you know the safe and proper operation of this equipment.
•Keep this Manual available for easy access by all users.
•Replacement Manuals are available at tekmarControls.com
•Disconnect all power before opening the control.
•It is the installers responsibility to ensure that this control is safely installed according to all applicable codes and standards.
•Improper installation and operation of this control could result in damage to the equipment and possibly even personal injury or death.
•This electronic control is not intended for use as a primary limit control. Other controls that are intended and certified as safety limits must be placed into the control circuit.
•Do not attempt to service the control. There are no user serviceable parts inside the control. Attempting to do so voids warranty.
Radio Frequency Interference
The installer must ensure that this control and its wiring are isolated and/or shielded from strong sources of electromagnetic noise. Conversely, this Class B digital apparatus complies with Part 15 of the FCC Rules and meets all requirements of the Canadian Interference-Causing Equipment Regulations. However, if this control does cause harmful interference to radio or television reception, which is determined by turning
the control off and on, the user is encouraged to try to correct the interference by re-orientating or relocating the receiving antenna, relocating the receiver with respect to this control, and/or connecting the control to a different circuit from that to which the receiver is connected.
Cet appareil numérique de la classe B respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.
3 of 44 |
© 2013 |
654_D - 06/13 |
Installation
Preparation
Tools Required -----------------------------------------------------------------------------------------
• |
tekmar or jeweller screwdriver |
• |
Needle-nose Pliers |
• |
Phillips head screwdriver |
• |
Wire Stripper |
Materials Required -------------------------------------------------------------------------------------
• 18 AWG LVT Solid Wire (Low Voltage Connections) • tekmar 24 V (ac) Transformer 009
Physical Dimensions
Front View |
Side View |
Mounting Base |
|
|
29/32" |
|
|
|
|
|
(23 mm) |
|
|
|
|
9/16" |
|
|
|
13/16" |
|
|
(14 mm) |
|
|
|
|
|
|
|
|
CL |
(20 mm) |
|
|
|
|
CL |
|
||
|
|
1-7/8" |
|
|
||
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
(47 mm) |
|
2-1/2" |
|
|
|
|
|
|
|
||
|
|
|
|
(64 mm) |
|
|
5" |
|
4" |
3/4" |
|
3-1/4" |
|
(127 mm) |
|
(19 mm) |
|
(83 mm) |
||
|
(102 mm) |
|
||||
|
|
|
|
|
|
|
|
|
|
|
654 |
No Power |
|
|
|
|
Aux Ht R C |
tN4 Mod Brn Yel Blu Red Blk Out/ Sup |
|
|
|
|
|
Com |
+ Slab |
Com Bret |
|
|
|
|
|
CL |
|
|
3-1/4" |
15/16" |
|
|
|
1-1/2" |
|
(82 mm) |
(23 mm) |
|
|
|
|
|
|
|
|
(38 mm) |
|
||
|
|
|
|
|
|
Installation Location
When choosing the location for the control, consider the following:
•Interior Wall.
•Keep dry. Avoid potential leakage onto the control.
•Relative Humidity less than 90%. Non-condensing environment.
•No exposure to extreme temperatures beyond -4 to 122°F (-20 to 50°C).
•No draft, direct sun, or other cause for inaccurate temperature readings.
•Away from equipment, appliances, or other sources of electrical interference.
•Easy access for wiring, viewing, and adjusting the display screen.
•Approximately 5 feet (1.5 m) off the finished floor.
•The maximum length of wire is 500 feet (150 m).
•Strip wire to 3/8" (10 mm) for all terminal connections.
•Use standard 8 conductor, 18 AWG wire.
Rough-In Wiring
Low Voltage Wiring-------------------------------------------------------------------------------------
Each cable must be pulled from the equipment to the control’s plastic enclosure. All low voltage wiring connections enter the enclosure through the square knockout on the rear. It is recommended to label each cable for easy identification. All low voltage wires are to be stripped to a length of 3/8" (9 mm) to ensure proper connection to the control.
Pull four conductor 18 AWG LVT cable, up to 500 feet (150 m) for the following equipment:
• Snow Sensor 095
Pull five conductor 18 AWG LVT cable, up to 500 feet (150 m) for the following equipment:
• Snow / Ice Sensor 090 or 094
Pull two conductor 18 AWG LVT cable, up to 500 feet (150 m) for the following equipment:
•24 V (ac) power from transformer
•Outdoor temperature sensor
•Supply sensor (if applicable)
•On/off boiler (if applicable)
•Modulating boiler 0-10 V (dc) or 4-20 mA (if applicable)
•Mixing valve or mixing injection pump 0-10 V (dc) or 4-20 mA (if applicable)
•Boiler return temperature sensor (if applicable)
•Alert output (if applicable)
•tekmarNet®4 communication to other devices
© 2013 |
654_D - 06/13 |
4 of 44 |
Sizing the Transformer
The control requires an external transformer. A tekmar Transformer 009 can supply up to 40 VA, and includes an in-line fuse to protect the transformer and control.
The total power capacity of the power supply should be larger than the total load of all the devices connected to the control. This total load must not exceed 100 VA.
Control Wiring |
|
See Application Brochure 654_A for specific application wiring diagrams. |
|
Snow / Ice Sensor ------------------------------- |
Snow and Slab Sensor -------------------------- |
Snow / Ice Sensor |
Snow Sensor |
090 or 094 |
095 |
|
Slab Sensor |
|
072 or 073 |
|
Snow |
|
Sensor |
|
095 |
|
tN4 Mod Brn Yel |
No Power |
Aux Ht R C |
Blu Red Blk Out/Sup |
|
– |
+ Slab |
Com Bret |
|
tN4 Mod Brn Yel |
No Power |
Aux Ht R C |
Blu Red Blk Out/Sup |
|
– |
+ Slab |
Com Bret |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
------Outdoor, Supply and Boiler Return Sensor |
-----Modulating Output and tN4 Communication |
Modulating Boiler
Mixing Valve or
Mixing Injection Pump
0-10 V (dc) Signal
– +
|
|
No Power |
|
|
|
|
No Power |
Aux Ht R C |
tN4 Mod Brn Yel |
Blu Red Blk Out/Sup |
|
tN4 C |
Aux Ht R C |
tN4 Mod Brn Yel |
Blu Red Blk Out/Sup |
– |
+ Slab |
Com Bret |
|
tekmarNet®4 |
– |
+ Slab |
Com Bret |
|
|
Supply |
Outdoor |
|
|
|
|
|
|
Communication |
|
|
|
||
|
|
Sensor |
Sensor |
|
|
|
|
|
|
|
|
|
|
082070 or
Boiler
Return
Sensor
082
5 of 44 |
© 2013 |
654_D - 06/13 |
tN4 Wiring Center or Zone Manager ------------- |
Alert Relay Output ------------------------------ |
|
|
|
No Power |
|
|
No Power |
Aux Ht R |
C |
tN4 Mod Brn Yel Blu Red Blk Out/Sup |
Aux Ht R C |
tN4 Mod Brn Yel Blu Red Blk Out/Sup |
||
tN4 C R W tN4 C R W |
– |
+ Slab |
Com Bret |
– |
+ Slab |
Com Bret |
Zone 1 Zone 2 |
|
|
|
|
|
|
tN4 Wiring Center |
|
|
|
Alert |
|
|
or Zone Manager |
|
|
|
|
|
|
|
|
|
Equipment |
|
|
|
|
|
|
|
|
|
Transformer and Relays --------------------------------------------------------------------------------
Transformer 009
L |
R |
N |
C |
|
|
|
|
tN4 Mod Brn Yel |
No Power |
Relay 003 |
Relay 003 |
Aux Ht R |
C |
Blu Red Blk Out/Sup |
|
|
– |
+ Slab |
Com Bret |
|
3 |
2 |
3 |
2 |
|
4 |
1 |
4 |
1 |
|
5 |
8 |
5 |
8 |
|
6 |
7 |
6 |
7 |
T |
T |
|
|
System |
|
|
|
|
|
|
|
|
|
Pump |
|
|
G |
N |
L |
On/Off Boiler |
115 V (ac) |
© 2013 |
654_D - 06/13 |
6 of 44 |
Sensor Wiring
Mounting the Outdoor Sensor --------------------------------------------------------------------------
Notice: The temperature sensor (thermistor) is built into the sensor enclosure.
•Remove the screw and pull the front cover off the sensor enclosure.
•The outdoor sensor can either be mounted directly onto a wall or a 2" x 4" electrical box. When the outdoor sensor is wall mounted, the wiring should enter through the back or bottom of the enclosure. Do not mount the outdoor sensor with the conduit knockout facing upwards as rain could enter the enclosure and damage the sensor.
•In order to prevent heat transmitted through the wall from affecting the sensor reading, it may be necessary to install an insulating barrier behind the enclosure.
•The outdoor sensor should be mounted on a wall which best represents the heat load on the building (a northern wall for most buildings and a southern facing wall for buildings with large south facing glass areas). The outdoor sensor should not be exposed to heat sources such as ventilation or window openings.
•The outdoor sensor should be installed at an elevation above the ground that will prevent accidental damage or tampering.
Sensor with rear |
Sensor with bottom |
Sensor mounted |
entry wiring |
entry wiring |
onto 2" x 4" |
|
|
electrical box |
Wiring the Outdoor Sensor -----------------------------------------------------------------------------
•Connect 18 AWG or similar wire to the two terminals provided in the enclosure and run the wires from the outdoor sensor to the control. Do not run the wires parallel to telephone or power cables. If the sensor wires are located in an area with strong sources of electromagnetic interference (EMI), shielded cable or twisted pair should be used or the wires can be run in a grounded metal conduit. If using shielded cable, the shield wire should be connected to the Com or Com Sen terminal on the control and not to earth ground.
•Follow the sensor testing instructions in this brochure and connect the wires to the control.
•Replace the front cover of the sensor enclosure.
Wires from outdoor sensor to control’s outdoor sensor and sensor common terminals
Sensor is built into the enclosure
Mounting the Universal Sensor-------------------------------------------------------------------------
NOTICE: These sensors are designed to mount on a pipe or in a temperature immersion well.
The Universal Sensor should be placed downstream of a pump or after an elbow or similar fitting. This is especially important if large diameter pipes are used as the thermal stratification within the pipe can result in erroneous sensor readings. Proper sensor location requires that the fluid is thoroughly mixed within the pipe before it reaches the sensor.
Strapped to Pipe
The Universal Sensor can be strapped directly to the pipe using the cable tie provided. Insulation should be placed around the sensor to reduce the effect of air currents on the sensor measurement.
7 of 44 |
© 2013 |
654_D - 06/13 |
Immersion Well
If a Universal Sensor is mounted onto 1" (25 mm) diameter L type copper pipe, there is approximately an 8 second delay between a sudden change in water temperature and the time the sensor measures the temperature change. This delay increases considerably when mild steel (black iron) pipe is used. In general, it is recommended that a temperature well be used for steel pipe of diameter greater than 1-1/4" (32 mm). Temperature wells are also recommended when large diameter pipes are used and fluid stratification is present.
Conduit Connection
The Universal Sensor and Universal Sensor Enclosure 080 (sold separately) are specifically designed to mount onto a 3/8" (10 mm) ID temperature well that is supplied with an end groove. To install the well, plumb a ‘T’ into the pipe and fix the well into the ‘T’. The 080 enclosure has a 7/8" (22 mm) back knockout that must be removed and fitted over the temperature well. The universal sensor is then inserted into the well and the retaining clip supplied with the enclosure is snapped onto the well end groove. If the well has a threaded end, the installer must supply a standard threaded conduit retaining ring. The two wires from the sensor are connected to the terminal block provided in the enclosure. The other side of the terminal block is used to connect wires from the control.
Retaining
Clip
Universal
Sensor
Sensor Well
Bottom of
Enclosure 080
Universal Cable Tie
Sensor
Testing the Sensor Wiring
A good quality test meter capable of measuring up to 5,000 kΩ (1 kΩ = 1000 Ω) is required to measure the sensor resistance. In addition to this, the actual temperature must be measured with either a good quality digital thermometer, or if a thermometer is not available, a second sensor can be placed alongside the one to be tested and the readings compared.
First measure the temperature using the thermometer and then measure the resistance of the sensor at the control. The wires from the sensor must not be connected to the control while the test is performed. Using the chart below, estimate
the temperature measured by the sensor. The sensor and thermometer readings should be close. If the test meter reads a very high resistance, there may be a broken wire, a poor wiring connection or a defective sensor. If the resistance is very low, the wiring may be shorted, there may be moisture in the sensor or the sensor may be defective. To test for a defective sensor, measure the resistance directly at the sensor location.
Do not apply voltage to a sensor at any time as damage to the sensor may result.
Temperature |
Resistance |
Temperature |
Resistance |
Temperature |
Resistance |
Temperature |
Resistance |
||||
°F |
°C |
|
°F |
°C |
|
°F |
°C |
|
°F |
°C |
|
-50 |
-46 |
490,813 |
20 |
-7 |
46,218 |
90 |
32 |
7,334 |
160 |
71 |
1,689 |
-45 |
-43 |
405,710 |
25 |
-4 |
39,913 |
95 |
35 |
6,532 |
165 |
74 |
1,538 |
-40 |
-40 |
336,606 |
30 |
-1 |
34,558 |
100 |
38 |
5,828 |
170 |
77 |
1,403 |
-35 |
-37 |
280,279 |
35 |
2 |
29,996 |
105 |
41 |
5,210 |
175 |
79 |
1,281 |
-30 |
-34 |
234,196 |
40 |
4 |
26,099 |
110 |
43 |
4,665 |
180 |
82 |
1,172 |
-25 |
-32 |
196,358 |
45 |
7 |
22,763 |
115 |
46 |
4,184 |
185 |
85 |
1,073 |
-20 |
-29 |
165,180 |
50 |
10 |
19,900 |
120 |
49 |
3,760 |
190 |
88 |
983 |
-15 |
-26 |
139,403 |
55 |
13 |
17,436 |
125 |
52 |
3,383 |
195 |
91 |
903 |
-10 |
-23 |
118,018 |
60 |
16 |
15,311 |
130 |
54 |
3,050 |
200 |
93 |
829 |
-5 |
-21 |
100,221 |
65 |
18 |
13,474 |
135 |
57 |
2,754 |
205 |
96 |
763 |
0 |
-18 |
85,362 |
70 |
21 |
11,883 |
140 |
60 |
2,490 |
210 |
99 |
703 |
5 |
-15 |
72,918 |
75 |
24 |
10,501 |
145 |
63 |
2,255 |
215 |
102 |
648 |
10 |
-12 |
62,465 |
80 |
27 |
9,299 |
150 |
66 |
2,045 |
220 |
104 |
598 |
15 |
-9 |
53,658 |
85 |
29 |
8,250 |
155 |
68 |
1,857 |
225 |
107 |
553 |
Testing the Control Wiring
Testing the Power --------------------------------------------------------------------------------------
1.Remove the front cover from the control.
2.Use an electrical test meter to measure (ac) voltage between the R and C terminals. The reading should be 24 V (ac) +/– 10%.
3.Install the front cover.
© 2013 |
654_D - 06/13 |
8 of 44 |
Testing the Relay Outputs -----------------------
The control includes an Override menu to check if the control’s relays are operating and that the control is wired correctly to the snow melting equipment.
Step 1: Press and hold the Home button for 3 seconds. Step 2: Press NEXT to navigate to the Override menu. Step 3: Press ENTER to enter the Override menu.
Step 4: Select Manual Override to Hand.
Step 5: For hydronic systems, set System Pump to On. The system pump should now be operating.
Step 6: Set Heat Relay to On. The boiler or electric heating cables should start heating.
Step 7: For modulating boilers change the Boiler Percent from 0 to 100%. The boiler should be firing.
Step 8: For a mixing valve or mixing injection pump, change the Mix Percent from 0 to 100%. The mixing valve should open or the mixing injection pump should increase speed.
Step 9: Select the Override Time after which the control resumes normal operation.
Step 10: Exit the Manual Override by selecting Auto.
Manual Override - Maximum Heat
In hydronic application modes, the control includes a Maximum Heat operation where the control operates the snow melting system to maintain the maximum allowed heating setpoints. This allows testing of the snow melting system during warm weather.
Step 1: Press and hold the Home button for 3 seconds. Step 2: Press NEXT to navigate to the Override menu. Step 3: Press ENTER to enter the Override menu.
Step 4: Select Manual Override to Max.
Step 5: Select the Maximum Heat Time after which the control resumes normal operation.
Step 6: Exit the Manual Override by selecting Auto.
Manual Override - Test
When operating an electric snow melting system, the control includes a Test operation where the electrical heating cables can be energized for 10 minutes after which the control resumes normal operation. This allows testing of the electric snow melting system during warm weather.
Step 1: Press and hold the Home button for 3 seconds. Step 2: Press NEXT to navigate to the Override menu. Step 3: Press ENTER to enter the Override menu.
Step 4: Select Manual Override to Test.
Step 5: Exit the Manual Override by selecting Auto.
Manual Override - Purge
When operating a hydronic snow melting system, it is necessary to purge and bleed all air out of the system. The control includes a Purge operation where the System Pump as well as pumps operated by the tekmarNet® system are all turned on to assist in purging air from the system.
Step 1: Press and hold the Home button for 3 seconds. Step 2: Press NEXT to navigate to the Override menu. Step 3: Press ENTER to enter the Override menu.
Step 4: Select Manual Override to Purge.
Step 5: Select the Maximum Purge Time after which the control resumes normal operation.
Step 6: Exit the Manual Override by selecting Auto.
Manual Override - Off
The snow melting system can be manually turned off and the |
Step 1: |
Press and hold the Home button for 3 seconds. |
|||||||
control remains off until manually changed back to Auto. This |
Step 2: |
Press NEXT to navigate to the Override menu. |
|||||||
allows the installer or end user to permanently disable the snow |
Step 3: |
Press ENTER to enter the Override menu. |
|||||||
melting system without removing power from the control. |
Step 4: |
Select Manual Override to Off. |
|||||||
Switch Settings |
|
|
|
|
Step 5: Exit the Manual Override by selecting Auto. |
||||
|
|
|
|
|
|
||||
Switch |
Position |
Action |
|
|
|||||
|
|
|
|
|
|
||||
1058-01 |
Lock |
|
|
|
|
|
|
|
|
|
Snow Melting Control 654 |
|
|
|
LOCK ACCESS LEVEL |
||||
|
|
|
|
|
|||||
|
|
|
|
|
|
||||
Switch Settings |
ON |
|
|
ON |
The control is locally locked and the access level cannot be changed. |
||||
|
|
tekmarNet Electric or Hydronic Boiler/Mixing |
|
|
|||||
1 2 |
|
www.tekmarControls.com |
|
|
|
Set to Lock when installation has been completed. |
|||
|
Unlock Unused |
|
Power: 24 V (ac) ±10%, 60 Hz, Class 2, |
|
|
|
|
|
|
|
|
|
|
UNLOCK ACCESS LEVEL |
|||||
|
|
Relays: 24 V (ac) 2 A, 3.5 A combined |
|
|
|
||||
|
|
|
16 VA standby, 100 VA fully loaded |
|
|
|
|
|
|
|
|
|
Designed and assembled in Canada |
1 |
|
The control is unlocked and the access level may be changed. Go to |
|||
H1220A |
|
|
Meets Class B: ICES & FCC Part 15 |
|
the Toolbox menu to change the access level. Set to Unlock during |
||||
|
|
|
|
|
|||||
|
|
Back of Control |
|
|
OFF |
the installation process. |
|||
|
|
|
|
Note: tekmarNet® system controls include a Global Lock that locks all |
|||||
|
|
|
|
|
|||||
|
|
|
|
|
|
|
connected snow melt controls, and thermostats. Set the tekmarNet® |
||
|
|
|
|
|
|
|
system control to unlock to allow access level adjustment on all |
||
|
|
|
|
|
|
|
connected devices. |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2 |
ON |
Not used |
|
||
|
|
|
|
|
|
|
|
||
|
|
|
|
OFF |
Not used |
|
|||
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
9 of 44 |
© 2013 |
654_D - 06/13 |
User Interface
Display
Status Field
Operation Field
Touch to turn system off while away
Touch to
Melt or Stop
Touch to adjust settings
Touch to display Run Time,
Outdoor & Slab Temperature
Touch to quickly enter the View menu
ENTER
Home
Button
Touch to go to the next setting
Home Button
Return to the Home Screen
Press and hold for 3 seconds to access the programming menus.
Operation Field
MELT |
System is melting snow or ice. |
IDLE |
System is idling. |
STRM |
System is in storm operation. |
OFF |
System is off. |
Status Field
WWSD
Warm Weather Shut Down. The slab is naturally warm enough to melt snow or ice.
CWCO Cold Weather Cut Out. Too cold to melt.
TIMED
Timed melting operation. System operates until time has elapsed.
WARM Slab is warming up to the melting temperature.
AWAY
Away scene. No melting until the away scene is exited.
PEND
Pending. The system has detected water but it is too cold to operate or the schedule is in Idle or Off.
WAIT
Zone priority in effect. Zone must wait until higher priority zone finishes melting.
SENSOR Tandem 090 sensor.
TRACK This zone tracks the melting operation of zone 1.
Symbols
HEAT ON
Heat is turned on.
tekmarNet®
Communication is present.
WARNING SYMBOL
Indicates an error is present.
ARROWS
Adjust the displayed setting.
© 2013 |
654_D - 06/13 |
10 of 44 |
Programmable Settings
Programming Menus
Press and hold the Home button for 3 seconds to enter the programming menus. The control returns to the last programming menu previously used.
Press and hold for 3 seconds to access the programming menus.
Select a Programming Menu --------------------
•Touch “NEXT” to advance (clockwise in above illustration) to the next menu.
•Touch “BACK” to go backwards (counterclockwise in above illustration) through the menus.
•Touch “ENTER” to enter a menu.
Setting Items ------------------------------------
•Touch or arrow to adjust the setting if required.
•Touch “NEXT ITEM” to advance to the next item within the menu.
•Touch “BACK ITEM” to go backwards to the previous item within the menu.
•To return to the parent menu after changing a setting, press and release the Home button.
•To return to the Home screen, press and release the Home button twice or wait 30 seconds to automatically return to the Home screen.
Access Levels and Access Level Lock
The control is shipped pre-programmed with common settings. The control has an “Installer” access level that allows full access to all settings and a “User” access level that restricts the number of settings available. The control defaults to the “User” access level after 12 hours of operation.
Notice: tekmarNet® system controls include a Global Lock that locks all connected snow melting controls and thermostats. Set the tekmarNet® system control to unlock to allow access level adjustment on all connected devices.
To change to the “Installer” access level:
•In the Toolbox menu, locate Access
•Adjust the access level to “Installer” by pressing the up or down button. This will permit setting changes to the control.
11 of 44 |
© 2013 |
654_D - 06/13 |
View Menu (1 of 2)
The View menu items display the current operating temperatures and status information of the system.
|
Item Field |
Range |
Access |
Description |
Set to |
|
|
|
User |
SNOW ZONE |
|
|
|
1 to 12 |
The snow melt zone number on the tekmarNet® |
|
|
|
|
Installer |
system. |
|
|
|
|
|
|
||
|
|
|
|
Conditions: tekmarNet® communication available. |
|
|
|
|
|
OUTDOOR |
|
|
|
– – –, -76 to |
|
Current outdoor air temperature as measured by the local |
|
|
|
User |
or remote outdoor sensor. The outdoor air temperature is |
|
|
|
|
149°F |
shared to all devices in the tekmarNet® system. “– – –” is |
|
|
|
|
(-60 to 65°C) |
Installer |
displayed when no outdoor sensor is available. |
|
|
|
|
|
Conditions: Application Mode is set to PWM, Boil, Mix or |
|
|
|
|
|
Elec. |
|
|
|
– – –, -76 to |
|
SLAB TARGET |
|
|
|
Installer |
The calculated slab target of the snow melting system. |
|
|
|
|
149°F |
“– – –” is displayed when the snow melt control is off. |
|
|
|
|
(-60 to 65°C) |
|
Conditions: Application Mode is set to PWM, Boil, Mix or Elec |
|
|
|
|
|
and a snow/ice sensor or slab sensor is installed. |
|
|
|
-76 to 149°F |
User |
SLAB |
|
|
|
Current slab temperature as measured by the control. |
|
||
|
|
(-60 to 65°C) |
Installer |
Conditions: Application Mode is set to PWM, Boil, Mix or Elec |
|
|
|
|
|
and a snow/ice sensor or slab sensor is installed. |
|
|
|
|
User |
WATER SENSOR |
|
|
|
DRY or WET |
Current status of the water detection sensor. |
|
|
|
|
Installer |
|
||
|
|
|
Conditions: A snow/ice sensor or snow sensor is installed. |
|
|
|
|
|
|
|
|
|
|
|
|
BOILER TARGET |
|
|
|
---, 70 to 200°F |
|
The calculated boiler target of the snow melt system. |
|
|
|
Installer |
“– – –” is displayed when the snow melt control is not operating |
|
|
|
|
(21.0 to 93.5°C) |
|
||
|
|
|
the boiler. |
|
|
|
|
|
|
|
|
|
|
|
|
Conditions: Application Mode is set to Boil. |
|
|
|
|
|
MIX TARGET |
|
|
|
---, 70 to 200°F |
|
The calculated mix target of the snow melt system. “– – –” |
|
|
|
Installer |
is displayed when the snow melt control is not operating the |
|
|
|
|
(21.0 to 93.5°C) |
|
||
|
|
|
mixing valve or mixing injection pump. |
|
|
|
|
|
|
|
|
|
|
|
|
Conditions: Application Mode is set to Mix. |
|
|
|
-58 to 212°F |
|
SUPPLY |
|
|
|
Installer |
Current system supply temperature as measured by the |
|
|
|
|
(50.0 to 100.5°C) |
control. |
|
|
|
|
|
|
||
|
|
|
|
Conditions: Application Mode is set to PWM, Boil or Mix. |
|
|
|
|
|
BOILER RETURN |
|
|
|
-58 to 212°F |
|
Current boiler return temperature as measured by the |
|
|
|
Installer |
control. |
|
|
|
|
(50.0 to 100.5°C) |
|
||
|
|
|
Conditions: Application Mode is set to PWM, Boil or Mix and |
|
|
|
|
|
|
|
|
|
|
|
|
Out/Bret Sensor is set to Bret (boiler return sensor). |
|
|
|
|
|
MIX RATE |
|
|
|
0 to 100% |
Installer |
Current position of the mixing valve or mixing injection |
|
|
|
pump speed. |
|
||
|
|
|
|
|
|
|
|
|
|
Conditions: Application Mode is set to Mix. |
|
|
|
|
|
BOILER RATE |
|
|
|
0 to 100% |
Installer |
Current firing rate of the modulating boiler. |
|
|
|
Conditions: Application Mode is set to Boil and Boiler Type |
|
||
|
|
|
|
|
|
|
|
|
|
is set to Mod (modulating boiler). |
|
© 2013 |
654_D - 06/13 |
|
12 of 44 |
|
View Menu (2 of 2)
Item Field |
Range |
Access |
Description |
Set to |
|
|
|
HEAT RELAY |
|
|
|
User |
Current status of the heat relay. The boiler, pump or |
|
|
OFF or ON |
electric cable is on when ON is displayed. The boiler, |
|
|
|
Installer |
pump or electric cable is off when OFF is displayed. |
|
|
|
|
|
||
|
|
|
Conditions: Application Mode is set to PWM, Boil, Mix, or |
|
|
|
|
Elec. |
|
|
|
|
PWM RATE |
|
|
|
|
Current duty cycle rate of the zone or boiler for each 20 |
|
|
0 to 100% |
Installer |
minute cycle. |
|
|
|
|
Conditions: Application Mode is set to PWM or Elec. Not |
|
|
|
|
visible when Manual Override is not Auto. |
|
|
|
User |
SYSTEM PUMP RELAY |
|
|
OFF or ON |
Current status of the system pump relay. |
|
|
|
Installer |
Conditions: Application Mode is set to PWM, Boil or Mix and |
|
|
|
|
|
||
|
|
|
Auxiliary Relay is set to SYS (system pump). |
|
|
|
|
ALERT RELAY |
|
|
OFF or ON |
User |
Current status of the alert relay. |
|
|
Conditions: Application Mode is set to PWM, Boil or Mix and |
|
||
|
Installer |
|
||
|
|
Auxiliary Relay is set to ALRT (alert) or Application Mode is |
|
|
|
|
|
|
|
|
|
|
set to Elec. |
|
|
|
|
MANUAL MELT TIME |
|
|
00:00 to 24:00 |
User |
When manually started, the display shows the remaining |
|
|
run time before shutting off. |
|
||
|
hours |
Installer |
|
|
|
Conditions: Application Mode is set to PWM, Boil, Mix or |
|
||
|
|
|
|
|
|
|
|
Elec. |
|
|
|
|
ADDITIONAL MELT TIME |
|
|
00:00 to 6:00 |
User |
When automatically started by a Snow/Ice Sensor 090 |
|
|
or 094, the display shows the remaining run time before |
|
||
|
hours |
Installer |
shutting off. |
|
|
|
|
Conditions: Application Mode is set to PWM, Boil, Mix or Elec |
|
|
|
|
and a snow / ice sensor 090 or 094 is installed. |
|
13 of 44 |
© 2013 |
654_D - 06/13 |
Set Temp Menu
The Set Temp menu items select the operating temperatures of the snow melt system.
Item Field |
Range |
Access |
Description |
Set to |
|
|
|
32 to 95°F |
|
MELTING |
|
|
|
|
Select the desired surface temperature of the snow melt |
|
|
|
|
(0.0 to 35.0°C) |
User |
|
|
|
|
Default = 36°F |
Installer |
surface when melting. |
|
|
|
Conditions: Application Mode is set to PWM, Boil, Mix |
|
||
|
|
(2.0°C) |
|
|
|
|
|
|
or Elec. |
|
|
|
|
|
|
|
|
|
|
|
|
IDLING |
|
|
|
|
|
Select the desired surface temperature of the snow melt |
|
|
|
OFF, 20 to 95°F |
|
surface when idling. Idling pre-heats the slab when the |
|
|
|
(-6.5 to 35.0°C) |
Installer |
slab is dry but cold and allows faster reaction time to reach |
|
|
|
the melting temperature. Recommended for commercial |
|
||
|
|
Default = OFF |
|
|
|
|
|
|
use only. |
|
|
|
|
|
|
|
|
|
|
|
|
Conditions: Application Mode is set to PWM, Boil, Mix |
|
|
|
|
|
or Elec. |
|
|
|
|
|
STORM |
|
|
|
OFF, 20 to 95°F |
|
Select the desired surface temperature of the snow melt |
|
|
|
(-6.5 to 35.0°C) |
Installer |
surface while operating in the storm operation. Storm |
|
|
|
Default = 28°F |
operation temporarily pre-heats the slab to allow faster |
|
|
|
|
|
reaction time to reach the melting temperature. |
|
|
|
|
(-2.0°C) |
|
|
|
|
|
|
Conditions: Application Mode is set to PWM, Boil, Mix |
|
|
|
|
|
|
or Elec. |
|
|
|
0:30 to 24:00 |
|
MANUAL MELT RUN TIME |
|
|
|
|
Select the amount of running time when manually starting |
|
|
|
|
hours |
User |
|
|
|
|
Default = 4:00 |
Installer |
the system. |
|
|
|
Conditions: Application Mode is set to PWM, Boil, Mix |
|
||
|
|
hours |
|
|
|
|
|
|
or Elec. |
|
|
|
|
|
|
|
|
|
|
|
|
ADDITIONAL MELT TIME |
|
|
|
0:00 to 6:00 |
|
Select the amount of additional melting time after the |
|
|
|
|
Snow / Ice Sensor 090 or 094 is dry. This allows low |
|
|
|
|
hours |
|
|
|
|
|
Installer |
spots on the slab to fully dry before the snow melting |
|
|
|
|
Default = 0:00 |
system is shut off. |
|
|
|
|
|
|
||
|
|
hours |
|
Conditions: Conditions: Application Mode is set to PWM, |
|
|
|
|
|
Boil, Mix or Elec and a Snow / Ice Sensor is installed or |
|
|
|
|
|
Track Zone is set to On. |
|
|
|
0:30 to 24:00 |
|
STORM RUN TIME |
|
|
|
|
Select the amount of storm run time to pre-heat the slab |
|
|
|
|
hours |
Installer |
|
|
|
|
Default = 8:00 |
when advised of a winter storm warning. |
|
|
|
|
|
Conditions: Application Mode is set to PWM, Boil, Mix or Elec |
|
|
|
|
hours |
|
|
|
|
|
|
and Storm is set to a temperature. |
|
|
|
|
|
|
|
|
|
|
AUTO, MIN, -2, |
|
WATER SENSITIVITY |
|
|
|
-1, MID, +1, +2, |
Installer |
Select how sensitive the Snow / Ice Sensor 090 or 094, |
|
|
|
MAX |
or the Snow Sensor 095 is to water detection. |
|
|
|
|
|
|
||
|
|
Default = AUTO |
|
Conditions: Snow / Ice Sensor is set to 090 or 095. |
|
|
|
AUTO, 32 to |
|
WARM WEATHER SHUT DOWN |
|
|
|
|
Select the temperature at which to shut down the snow |
|
|
|
|
95°F |
|
|
|
|
|
Installer |
melting system during warm weather. This allows the |
|
|
|
|
(0.0 to 35.0°C) |
snow or ice to melt off the slab naturally. |
|
|
|
|
|
|
||
|
|
Default = AUTO |
|
Conditions: Application Mode is set to PWM, Boil, Mix |
|
|
|
|
|
or Elec. |
|
|
|
OFF, -30 to 50°F |
|
COLD WEATHER CUT OUT |
|
|
|
|
Select the temperature at which to shut down the snow |
|
|
|
|
(-34.5 to 10.0°C) |
Installer |
|
|
|
|
Default = 10°F |
melting system during extremely cold weather. Below |
|
|
|
|
|
this temperature, the heat loss of the slab exceeds the |
|
|
|
|
(-12.0°C) |
|
|
|
|
|
|
capacity of the boiler or heating appliance. |
|
|
|
|
|
|
|
|
© 2013 |
654_D - 06/13 |
|
14 of 44 |
|