DC INSTRUMENT, 3 ½ DIGITS, ALLOWS THE READING TO BE DISPLAYED IN ENGINEERING UNITS FOR ANY DC VOLTAGE INPUT LOWER THAN 2 Vdc.

SPECIFICATIONS

DISPLAYS . . . . . . . . . . . . . . . . . . . . . .

3½ digits, 7 segment, red LED

HEIGHT . . . . . . . . . . . . . . . . . . . . . . .

0.56" (14.2 mm.)

SYMBOLS . . . . . . . . . . . . . . . . . . . . . .

± 1.8.8.8

DECIMAL POINTS . . . . . . . . . . . . . . .

Selectable by jumpers

OVERRANGE INDICATION . . . . . . . .

Display flashes 1999

INPUT CONFIGURATION . . . . . . . . . Bipolar single ZERO . . . . . . . . . . . . . . . . . . . . . . . . . Automatic SPAN ADJUSTMENT . . . . . . . . . . . . . ± 5 %

CONVERTER . . . . . . . . . . . . . . . . . . . Dual-slope, average value POLARITY . . . . . . . . . . . . . . . . . . . . . Automatic ±

SIGNAL INTEGRATION PERIOD . . . 80 ms. READ RATE . . . . . . . . . . . . . . . . . . . . 3.12 / sec.

RANGES . . . . . . . . . . . . . . . . . . . . . . . See table selection

HOLD . . . . . . . . . . . . . . . . . . . . . . . . . Optional

NOISE REJECTION NMR . . . . . . . . . 50 dB. 50/60 Hz. ACCURACY . . . . . . . . . . . . . . . . . . . . 0.15 % ± 1 count WARMUP TO RATED ACCURACY . . 2 minutes

SPAN TEMPCO . . . . . . . . . . . . . . . . . 100 ppm.

ZERO TEMPCO . . . . . . . . . . . . . . . . . 2.5 µV/°C.

OPERATING TEMPERATURE . . . . . 0 to 50 °C (32 to 122 °F) STORAGE TEMPERATURE . . . . . . . -40 to 80 °C (-40 to 176 °F) WEIGHT . . . . . . . . . . . . . . . . . . . . . . . 310 gr. (0.68 lb)

CASE MATERIAL . . . . . . . . . . . . . . . . ABS, DIN 43700, black color STANDARD POWER . . . . . . . . . . . . . 115 Vac. ± 10 %, 50/60 Hz.

POWER CONSUMPTION . . . . . . . . . 5.5 VA for AC. ELECTRICAL CONNECTIONS . . . . . Push-in cable connectors BURN-IN . . . . . . . . . . . . . . . . . . . . . . . 24 h.

FIG. 1

FRONT VIEW

 

SPAN

OFFSET

SPAN : ADJUST THE MAXIMUM READING. OFFSET : NOT IN SERVICE

SPAN ADJUSTMENT IS ACCESSIBLE BEHIND THE LOW DOOR.

REAR VIEW

FIG. 2

Setpoint R2

Setpoint R1

 

(option)

(option)

Isolated digital output

 

 

(option)

 

 

 

 

D

 

 

SIGNAL

C

 

1

B 10

INPUT

A

 

 

ANALOG

OUTPUT

+

 

-

 

(OPTION)

 

 

 

 

 

HOLD, latch the reading

 

 

display, while these pins

 

POWER SUPPLY

are linked

 

 

see instrument label

 

 

 

FIG. 3

SIGNAL CONDITIONER

R4

 

C

SIGNAL INPUT

B

Vdc

A

 

THIS SIGNAL CONDITIONER ACCEPTS THE SIGNAL INPUT IN DC VOLTAGE, AND ALLOWS THE READING TO BE DISPLAYED IN ENGINEERING UNITS . IF THE ACTUAL READING IS NOT APPROPRIATE FOR YOUR REQUIREMENTS, USE THE FOLLOWING SYSTEM TO CALCULATE THE VALUE OF THE RESISTOR R4.

EXAMPLE : DISPLAY 124.8 WHEN SIGNAL INPUT IS 460 mVdc(DECIMALS MUST NOT BE CONSIDERED)

SIGNAL INPUT IN MILLIVOLTS

R4 VALUE IN OHMS

 

READING

 

1248

 

 

 

x 10.000) - 10.000 = R4

 

(

 

R4 = (

x 10.000) - 10.000 = 17.130

 

 

SIGNAL INPUT

 

460

 

INSTALL R4 ON THE SIGNAL CONDITIONER BOARD, PLUG-IN JUMPER IN POSITION "D1" (FIG. 5), ON THE DECIMAL POINT SELECTOR AND ADJUST SPAN POTENTIOMETER,PLACED ON THE FRONT PANEL, UNTIL THE DISPLAY READS 124.8