1⁄16 DIN MICROMEGA® Autotune PID
Temperature/Process Controllers
CN77000 Series
Shown actual size.
Panel Punches
Available, Visit
omega.com/
panelpunches
UHigh Accuracy: ±0.5°C (0.9°F), 0.03% Rdg
UHigh Quality Backed by 5-Year Warranty
UUniversal Inputs— Process Voltage/Current, Thermocouple, RTD
UDual 4-Digit LED Display and Indicators for Output and Alarm Status
UOptional RS232 or RS485, OMEGA® Protocol
URelay, SSR, DC Pulse,
0 to 10 V, and 0 to 20 mA Output Types
URamp-to-Setpoint Feature
UUniversal Power Supply, 90 to 250 Vac or Vdc
UDual Output and Dual Alarm Capability
UIsolated Analog Output or Remote Setpoint Selection
CN77533 NEMA 4 square cutout.
The high-accuracy, high-quality MICROMEGA® controllers offer unparalleled flexibility in process control. Each unit allows the user to select the input type, from
10 thermocouple Types (J, K, T, E, R, S, B, C, N, and J DIN), Pt RTDs (100, 500, or 1000 Ω, with either 385 or 392 curve), or analog voltage or current input. The voltage/ current inputs are fully scalable to engineering units, with a selectable decimal point, perfect for use with
pressure, flow, or other process inputs.
The MICROMEGA® controller features a large, dual LED display, front-panel configuration, selectable temperature/ process inputs, and universal power supply that accepts 90 to 250 Vac or Vdc. Available in singleand dualoutput configurations, the CN77000
|
|
|
Put |
aSquare |
|
|
Controller |
|
|
inaRound |
|
|
|
Hole! |
CN77000 R300 and R500 controllers shown with model RHS-43 hole saw for easy-to-drill round holes. See last page for ordering information.
CN77333-A2 NEMA 12 style square cutout.
Series is available with relay, SSR, DC pulse, or analog voltage or current outputs. A single alarm is standard. Options include a second alarm, RS232, RS485, analog output, and remote setpoint selection.
The “300” Series controllers offer many features of larger, 1⁄4 DIN controllers in a compact, 1⁄16 DIN size. These controllers feature a 1⁄16 DIN cutout and bezel with a NEMA 12 (IP54) rating, and dual LED displays, which show different colors for the process and setpoint values. Individual indicators provide output and
alarm status.
The “500” features a 1⁄16 DIN cutout, 53.3 mm (2.1") square face with NEMA 4 (IP65) rating, large dual LED display, front-panel configuration, and selectable temperature/process inputs. Available in singleand dual-output configurations, the
CN77500 is available with relay, SSR, DC pulse, or analog voltage or current outputs. A single alarm is standard.
The R300 and R500 controllers feature a detachable display and adaptor to allow mounting in a round, 44 mm (1.75") cutout. This feature allows users to prepare the panel with a standard round hole saw as well as the conventional 1⁄16 DIN cutout.The 2 piece design snaps together, for quick, easy installation.
P-37
Specifications
Accuracy: ±0.5°C (0.9°F) temp; 0.03% rdg process
Resolution: 1°/0.1°; 10 µV process
Temperature Stability:
0.08°C/°C; 50 ppm/°C process
Thermocouple Cold-End Tracking:
0.05°C/°C
NMRR: 60 dB CMRR: 120 dB
Common-Mode Voltage: 1500 V peak test, 350 V per IEC spacing
A/D Conversion: Dual slope Reading Rate: 3 samples/s Digital Filter: Programmable
Display: Dual 4-digit, 7-segment LED, 9.2 mm (0.36"); red process variable, green setpoint; indicators for output and alarm status; 7.6 mm (0.3") for NEMA 12 (IP54) units
Warm-Up to Rated Accuracy: 30 min
Input
Input Types: Thermocouple, RTD, analog voltage, analog current
Thermocouple Lead Resistance:
100 Ω maximum
RTD Input: 2-, 3- or 4-wire; 100, 500 and 1000 Ω; 0.00385 or 0.00392 Pt curve
Voltage Input:
0 to 100 mV, 0 to 1V, 0 to 10 Vdc Current Input: 0 to 20 mA, 4 to 20 mA
Configuration: Single-ended Polarity: Unipolar
Step Response: 0.7 s for 99.9% Decimal Selection: None, 0.1 or 0.01
Span Adjustment:
0.001 to 9999 counts
Offset Adjustment: -9999 to 9999
Control
Action: Reverse (heat) or direct (cool) Modes: Time proportioning and proportional control modes; selectable preset tune, autotune, PID, proportional, proportional with integral, proportional with derivative with anti-reset
windup, on/off Rate: 0 to 999.9 s
Reset: 0 to 99 minutes, 59 seconds Cycle Time: 1 to 199 seconds;
set to 0 for on/off operation Gain: 0.5 to 100% of span; setpoints 1 or 2
Damping: 1 to 8 in unit steps Soak: 00.00 to 99.59 (HH.MM)
Ramp to Setpoint:
00.00 to 99.59 (HH.MM) Autotune: For heating only
Break Protection:
Programmable upor down-scale
Control Output
Relay: 5 A @ 120 Vac, 3 A @ 240 Vac; configurable for on/off, PID or ramp and soak; output 1: SPDT type; output 2:
SPST type
SSR: Rated 0.5 A @ 120/240 Vac, continuous
DC Pulse: Non-isolated; 10 Vdc @ 20 mA
Analog Output: Non-isolated 0 to
10 Vdc or 0 to 20 mA; 500 Ω maximum
Options
Remote Setpoint Selection:
Up to 4 setpoints stored in memory; contact closure selection
Analog Output: Isolated 0 to 10 Vdc or 0 to 20 mA, programmable
Communications
RS232 or RS485: OMEGA® protocol 300 to 19.2 Kb; complete programmable setup capability; program to transmit current display, alarm status, min/max, actual measured input value and status
RS485: Addressable from 0 to 199 Connection: Screw terminals
Alarms
Type: SPST relay, 5 A @ 120 Vac, 3 A @ 240 Vac
Operation: High/low, latching/ non latching and process/deviation; front-panel configuration
Insulation
Power to Input or Output:
2500 Vac/Vdc, except
2 option has only 1500 between inputs 500
General
Power: 90 to 250 Vac/Vdc, 50 to 400 Hz
Operating Ambient: 0 to 55°C
(32 to 131°F), 90% RH non condensing
Power Consumption:
6 VA maximum @ 120 Vac
Panel Cutout
CN77R000 Series:
44.5 mm (1.75") diameter round cutout
CN77300 and CN77500 Series:
45 mm (1.772") square, 1⁄16 DIN
Dimensions: CN77R000 Series:
48 H x 48 W x 135 mm D
(1.89 x 1.89 x 5.32")
CN77300 Series:
48 H x 48 W x 123.3 mm D
(1.89 x 1.89 x 4.85")
CN77500 Series:
53 H x 53 W x 123.3 mm D
(2.1 x 2.1 x 4.85") Weight: 227 g (0.5 lb)
Trim plates for mounting 1⁄16 controller in existing 1⁄4 DIN or 1⁄8 DIN cutouts.
TP4.
SPC116-S splashproof |
TP6. |
|
|
cover for 1⁄16 DIN |
|
controller. |
|
|
|
|
Input Type |
Range |
Accuracy |
|
|
|
|
|
Iron- |
-210 to 760°C/-346 to 1400°F |
0.4°C/0.7°F |
|
|
|
|
|
Constantan |
|
|
||
|
|
|
|
|
|
|
|
|
|
|
CHROMEGA®- |
-270 to -160°C/-160 to 1372°C |
1.0°C/0.4°C |
|
|
|
|
|
ALOMEGA® |
-454 to -256°F/-256 to 2502°F |
1.8°F/0.7°F |
|
|
|
|
|
Copper- |
-270 to -190°C/-190 to 400°C |
1.0°C/0.4°C |
|
|
|
|
|
Constantan |
-454 to -310°F/-310 to 752°F |
1.8°F/0.7°F |
|
|
|
|
|
|
|
|
|
|
|
|
|
CHROMEGA®- |
-270 to -220°C/-220 to 1000°C |
1.0°C/0.4°C |
|
|
|
|
|
Constantan |
-454 to -364°F/-364 to 1832°F |
1.8°F/0.7°F |
|
|
|
|
|
|
P |
|||
|
|
|
|
|
|
|
|
|
|
|
Pt/13%Rh-Pt |
-50 to 40°C/40 to 1768°C |
1.0°C/0.5°C |
|
|
|
|
|
-58 to 104°F/104 to 3214°F |
1.8°F/0.9°F |
|
||
|
|
|
Pt/10%Rh-Pt |
-50 to 100°C/100 to 1768°C |
1.0°C/0.5°C |
|
|
|
|
|
-58 to 212°F/212 to 3214°F |
1.8°F/0.9°F |
|
|
|
|
|
|
|
|
|
||
|
|
|
30%Rh-Pt/6%Rh-Pt |
100 to 640°C/640 to 1820°C |
1.0°C/0.5°C |
|
|
|
|
|
212 to 1184°F/1184 to 3308°F |
1.8°F/0.9°F |
|
|
|
|
|
|
|
|
|
||
|
|
|
5%Re-W/26%Re-W |
200 to 2320°C/400 to 4208°F |
0.4°C/0.7°F |
|
|
|
|
|
|
|
|
|
|
|
|
|
Nicrosil-Nisil |
-250 to -100°C/-100 to 1300°C |
1.0°C/0.4°C |
|
|
|
|
|
-418 to -148°F/-148 to 2372°F |
1.8°F/0.7°F |
|
|
|
|
|
|
|
|
|
||
L |
J DIN |
-200 to 900°C/-328 to 1652°F |
0.4°C/0.7°F |
|
|
||
|
|
|
Pt, 0.00385, 100Ω, 500Ω, 1000Ω |
-200 to 900°C/-328 to 1652°F |
0.4°C/0.7°F |
|
|
|
|
|
|
|
|||
|
|
|
|
|
|||
|
|
|
Pt, 0.00392, 100Ω, 500Ω, 1000Ω |
-200 to 850°C/-328 to 1562°F |
0.4°C/0.7°F |
|
|
|
|
|
|
|
|||
|
|
|
Process voltage |
0 to 100 mV, 0 to 1 V, 0 to 10 Vdc |
0.03% rdg |
|
|
|
|
|
Process current |
0 to 20 mA, 4 to 20 mA |
0.03% rdg |
|
|
|
|
|
P-38 |
|
|
|
|
|
|
|
|
|
|
|
|