Honeywell ST9120U Installation Manual

5 (1)

ST9120B,U

Universal Electronic Fan Timers

INSTALLATION INSTRUCTIONS

APPLICATION

On/Off Delay Settings:

 

The ST9120B,U Universal Electronic Fan Timers integrate control of all combustion blower and circulating fan operations in a gas warm air appliance. This control is the central wiring point for most of the electrical components in the furnace. The basic purposes of the ST9120B,U are to monitor the thermostat for heat, cool and fan demands, run the induced draft blower motor and run a circulating fan (up to two speeds) as required. The ST9120B,U also monitors limit switch strings and energizes separate ignition control systems through pressure switches. The ST9120B,U can replace any ST9101, ST9120, ST9141 or ST9160 listed in Table 3 below. The ST9120B,U features a field-adjustable heat fan-on delay, a field-adjustable heat fan-off delay, a fieldadjustable cool fan-on delay and a field-adjustable cool fan-off delay.

Electronic air cleaner (EAC) and humidifier (HUM) convenience terminal connections and continuous low speed indoor air circulation are provided.

SPECIFICATIONS

Electrical Ratings:

Power Voltage Requirements: 18 to 30 VAC, 50/60 Hz.

Contact Ratings: Combustion Blower:

1.5A full load, 10A locked rotor at 115 VAC.

0.75A full load, 5A locked rotor at 230 VAC. (Reduce full load rating by humidifier [HUM] load.)

Circulating Fan: Heat-Cool speed:

15A full load, 30A locked rotor at 115 VAC.

7.5A full load, 15A locked rotor at 230 VAC.

(Reduce full load rating by electronic air cleaner [EAC] load.)

Continuous speed (optional):

8A full load, 16A locked rotor at 115 VAC.

4A full load, 8A locked rotor at 230 VAC. EAC and HUM:

0.8A maximum combined load at 115 VAC

0.4A maximum combined load at 230 VAC Thermostat W Load: 100mA at 24 VAC, plus ignition sys-

tem load.

Thermostat G, Y, Primary Limit, Burner Limit, Pressure Switch Load: 22mA at 24 VAC load/cleaning current.

NOTE: Timing is derived from 24 VAC supply frequency and is valid for 60Hz. At 50 Hz, the timings are lengthened 20%.

Heat Speed:

Delay On: Field-adjustable, 30 or 60 seconds. Delay timing starts when gas valve is energized.

Delay Off: Field-adjustable, 60, 120, 150 or 180 seconds. Delay timing starts when gas valve is deenergized.

Cool Speed:

Delay On: Field Adjustable, 4 or 30 seconds. Delay Off: Field Adjustable, 30 or 60 seconds.

Timing Tolerance: Larger of ±2% or ±2 seconds.

Post Purge Timing:

5 seconds.

Environmental Ratings:

Temperature: -40°F (-40°C) to +175°F (+79°C). Humidity: 5 to 95 percent, noncondensing.

Approvals:

Underwriters Laboratories Inc.

INSTALLATION

When Installing this Product...

1.Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.

2.Check the ratings and specifications given in the instructions and on the product to make sure the product is suitable for your application.

3.Installer must be a trained, experienced service technician.

4.After installation is complete, check out the product operation as provided in these instructions.

WARNING

Electrical Shock Hazard.

Can cause severe injury, death or property damage.

Disconnect power supply before wiring to prevent electrical shock or equipment damage. More than one disconnection can be required.

69-2252EF—07

ST9120B,U UNIVERSAL ELECTRONIC FAN TIMERS

Location and Mounting

Mount the ST9120B,U Electronic Fan Timer in the appliance wiring compartment using the two # 8 1/2-in. self-tapping screws.

Wiring

CAUTION

Explosion or fire hazard.

When installing the ST9120B,U, carefully check all appliance wires to make sure they are all connected to desired terminals at ST9120B,U. Incorrect wiring can lead to explosion hazard, fire, or equipment damage.

Make sure that all wiring complies with local codes and ordinances. Disconnect power before making wiring connections. Refer to Fig. 1–6 for standard wiring connections. Refer to Fig. 7–9 for schematic of provided wiring adapters.

Adjustable DIP Switch

The ST9120B,U control provides a wide variety of configurable heat on, heat off, cool on and cool off delays. Set the delay DIP switches as shown in Fig. 10 The heaton delay time starts when the main gas valve is energized at the start of a thermostat call for heat; the heat-off delay time starts when the main gas valve is deenergized at the end of a thermostat call for heat. The cool fan-on delay time starts when the compressor is energized at the start of a thermostat call for cool. The cool fan-off delay time starts when the compressor is deenergized at the end of thermostat call for cool.

Twinning

Twinning mode is used when two ST9120B,U controls operate in parallel. In this mode blower outputs (heat, cool and continuous speed) are activated or deactivated at both controls at the same time. Both ST9120B,U are synchronized through a communication bridge utilizing TWIN quick connect terminals, communication hardware and special software package.

To get into twinning mode both ST9120B,U must share common 24 VAC ground, both must be supplied off the same 24 VAC transformer or two identically-phased transformers and the TWIN terminals must be interconnected together. One or both ST9120B,U must be connected to the thermostat.

If two 24 VAC transformers are used (one for each ST9120B,U) then the transformers must be phased in (24 VAC HOT legs connected to X terminals at each ST9120B,U unit must be in the same phase relative to the 24 VAC common ground). If the transformers are phased out the twinning mode will not be achieved.

It is permissible to interconnect just two ST9120B,U to operate in the twinning mode. The ST9120B,U Twinning mode is not backwards compatible with legacy Electronic Fan Timers.

To operate in twinning mode:

1.Interconnect C quick connect terminals at both twinned ST9120B,U.

2.Interconnect TWIN quick connect terminals at both twinned ST9120B,U.

3.Use insulate wires of wire gauge at least AWG 24 for the interconnections. Wire lengths shall not exceed 5 m (15 ft.). Both C and TWIN wires shall lead in parallel to each other. Keep the wires out of wires under line voltage, ignition cable and other sources of electrical noise.

ST9120B,U Wiring Conversion

Instructions

1.Turn off power to appliance. Carefully remove each wire and connect directly to the corresponding location on the new ST9120B,U control board. Be careful to directly connect to the new terminal with the same labeled identity or label each wire prior to removing from the original board.

2.Identify the model number of the board being replaced and set the dip switches based on Table 3.

CAUTION

Explosion Hazard/Fire Hazard

ST9101 wiring harness adapter and ST9141 wiring harness adapter are very similar because both use identical connectors. Ensure proper harness is selected for the target system. Using the wrong wiring harness adapter leads to target system and/or ST9120B,U control damage.

ST9101 to ST9120B,U Wiring Conversion Instructions

1.Turn off power to appliance and carefully remove each wire and connect directly to the new ST9120B,U control board before removing the existing control. Use Table 1 to determine the proper ST9120B,U terminal for each corresponding ST9101 connection. Connect the wiring in accordance with schematic at Fig. 3. Be careful to directly connect to the new terminal or label each wire prior to removal from original board.

CAUTION

Electronic air cleaner use.

If electronic air cleaner is used in systems with continuous blower speed, connect the electronic air cleaner to line voltage input L1.

2.Unplug the 9-pin connector and plug existing wiring harness directly into the 9-pin connector found on the ST9101 wiring adapter 50011959. See Fig. 7 and Table 4 for further wire harness adapter description.

3.Plug the 6-pin connector found on the ST9101 wiring adapter directly to the open 6-pin connector on the new ST9120B,U control board.

4.Take the two remaining white wires on the ST9101 wiring adapter and connect to Neutral quick connect terminals on the ST9120B,U.

5.Take the black wire on the ST9101 wiring adapter and connect to the L1 quick connect terminal on the ST9120B,U.

6.Take the blue wire on the ST9101 wiring adapter and connect to the IND quick connect terminal on the ST9120B,U.

7.Identify the model number of the board being replaced and set the dip switches based on Table 3.

8.Check proper connection using Fig. 3.

69-2252EF—07

2

ST9120B,U UNIVERSAL ELECTRONIC FAN TIMERS

Table 1. ST9101 to ST9120B,U Wiring Conversions.

ST9101

ST9120

ST9141

ST9160

ST9120B,U

HEAT

HEAT

HEAT

HEAT

HEAT

COOL

COOL

COOL

COOL

COOL

 

CONT

CONT

CONT

CONT

ACC

---

---

---

* for systems with one

 

 

 

 

ON fan speed (see

 

 

 

 

note below)

 

DI

DI

---

IND

S

S1 to S3

S1 to S3

L1

L1

M1

UNUSED MOTOR LEADS

UNUSED MOTOR LEADS

M1

UNUSED

M2

UNUSED MOTOR LEADS

UNUSED MOTOR LEADS

M2

UNUSED

N

N

N

N

N

X

X

XI

24 VAC

X

C

C

C

COM

C

---

SPEED UP

SPEED UP

---

---

---

Z1

Z1

TWIN H

** TWIN (see note

 

 

 

 

below)

---

Z2

Z2

TWIN C

** TWIN (see note

 

 

 

 

below)

---

---

---

DATA

DATA

Thermostat

Terminals

 

 

 

R

R

R

R

R

Y

Y

Y

Y

Y

C

C

C

C

C

W

W

W

W

W

G

G

G

G

G

*ACC terminal is used in ST9101 systems, which use the same fan speed for both heating and cooling. In order to use the ST9120B,U to replace ST9101 devices in this type of system, the fan connection that originally was connected to

ACC on the ST9101 needs to be connected to both heat and cool connections on the ST9120B,U.

**TWIN terminal is used to interconnect two ST9120B,U units to operate blower outputs simultaneously. Twinning at new ST9120B,U control is not backwards compatible with legacy controls.

ST9141 to ST9120B,U Wiring Conversion Instructions

1.Turn off power to appliance and carefully remove each wire and connect directly to the new ST9120B,U control board before removing the existing control. Use Table 1 to determine the proper ST9120B,U terminal for each corresponding ST9141 connection. Be careful to directly connect the new terminal or label each wire prior to removal from original board.

2.Unplug the 9-pin connector and plug existing wiring harness directly into the 9-pin connector found on the ST9141 wiring adapter 50034962. See Fig. 8 and Table 5 for further wire harness adapter description.

3.Plug the 6-pin connector found on the ST9141 wiring adapter directly to the open 6-pin connector on the new ST9120B,U control board.

4.Take the gray wire on the ST9141 wiring adapter and connect to the LIM quick connect terminal on the ST9120B,U.

5.Take the brown wire on the ST9141 wiring adapter and connect to the PRSW quick connect terminal on the ST9120B,U.

6.Identify the model number of the board being replaced and set the dip switches based on Table 3.

7.Check proper connection using Fig. 4.

ST9160 to ST9120B,U Wiring Conversion Instructions

1.Turn off power to appliance and carefully remove each wire and connect directly to the new ST9120B,U control board before removing the existing control. Use Table 1 to determine the proper ST9120B,U terminal for each corresponding ST9160 connection.

2.Unplug the 6-pin connector and plug it into the J3 connector found on ST9120B,U.

3.Plug the jumper plug into the J1 connector at ST9120B,U.

4.Identify the model number of the board being replaced and set the dip switches based on Table 3.

5.Check proper connection using Fig. 5 or 6.

LED Diagnostic

The ST9120 control provides the following status information and diagnostic troubleshooting code sequence as shown in Table 2.

3

69-2252EF—07

ST9120B,U UNIVERSAL ELECTRONIC FAN TIMERS

 

 

Table 2. LED Diagnostic Troubleshooting Codes.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No. of flashes

 

Condition

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

dim/on (heartbeat)

Device works correctly.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

Limit switch (ST9120) or burner limit switch (ST9141) is open.

 

 

 

 

 

 

2

 

Primary limit switch (ST9141) is open.

 

 

 

 

 

 

 

 

 

 

 

 

3

 

Pressure switch is improperly closed or pressure switch open when inducer blower has been

 

running for >30 sec.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

Control is in lockout due to air not circulating (overheated).

 

 

 

 

 

 

5

 

Smart Valve II limit switch is open.

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

Twinning communication corrupted (check system transformers' phasing).

 

 

 

7

 

Wrong 24 VAC supply condition.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 3. Recommended Default Dip Switch Settings.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Legacy Timing

 

 

 

 

New ST9120B,U

 

 

 

Replaced

 

 

Heat

Heat

Cool

Cool

 

 

 

 

 

 

 

 

 

 

 

 

 

 

On

Off

On

Off

Heat On

 

Heat Off

Cool On

Cool Off

Control Model

Original OEM

 

Number

 

Appliance

sec

sec

sec

sec

1

sec

2

 

3

 

sec

4

 

sec

5

sec

ST9101A1006

Rheem

30

100

4

0

off

30

off

 

off

 

120

off

 

4

off

30

ST9101A1014

Rheem

30

100

4

0

off

30

off

 

off

 

120

off

 

4

off

30

ST9101A1022

Trade

30

100

4

0

off

30

off

 

off

 

120

off

 

4

off

30

ST9120A1006

Armstrong

30

100

4

0

off

30

off

 

off

 

120

off

 

4

off

30

ST9120A2004

Armstrong

30

140

4

0

on

30

off

 

on

 

150

off

 

4

off

30

ST9120B1005

Ducane

30

60

4

0

off

30

on

 

off

 

60

off

 

4

off

30

ST9120C1012

Snyder General

60

100

4

0

on

60

off

 

off

 

120

off

 

4

off

30

ST9120C1020

Nordyne

60

100

4

0

on

60

off

 

off

 

120

off

 

4

off

30

ST9120C2002

York

30

100

4

30

off

30

off

 

off

 

120

off

 

4

off

30

ST9120C2010

Ducane

30

100

4

30

off

30

off

 

off

 

120

off

 

4

off

30

ST9120C2028

Armstrong

30

100

4

60

off

30

off

 

off

 

120

off

 

4

on

60

ST9120C3000

ICP

30

140

30

30

off

30

off

 

on

 

150

on

 

30

off

30

ST9120C3018

Bard

60

100

4

60

on

60

off

 

off

 

120

off

 

4

on

60

ST9120C4008

ICP

30

140

30

30

off

30

off

 

on

 

150

on

 

30

off

30

ST9120C4016

ICP

30

140

30

30

off

30

off

 

on

 

150

on

 

30

off

30

ST9120C4040

ICP

30

140

30

30

off

30

off

 

on

 

150

on

 

30

off

30

ST9120C4057

ICP

30

140

30

30

off

30

off

 

on

 

150

on

 

30

off

30

*ST9120C5005

ICP

30

140

4

30

off

30

off

 

on

 

150

off

 

4

off

30

*ST9120C5013

ICP

30

140

4

30

off

30

off

 

on

 

150

off

 

4

off

30

*ST9120D3009

Goodman

30

140

4

60

off

30

off

 

on

 

150

off

 

4

on

60

ST9120G2008

ICP

60

100

30

0

on

60

off

 

off

 

120

on

 

30

off

30

ST9120G2016

ICP

30

100

30

30

off

30

off

 

off

 

120

on

 

30

off

30

ST9120G2024

Skymark

30

60

30

30

off

30

on

 

off

 

60

on

 

30

off

30

ST9120G2032

Skymark

30

60

4

100

off

30

on

 

off

 

60

off

 

4

on

60

ST9120G4004

ICP

30

140

30

30

off

30

off

 

on

 

150

on

 

30

off

30

ST9120G4012

ICP

30

140

30

30

off

30

off

 

on

 

150

on

 

30

off

30

ST9120G4038

Trade

30

140

30

30

off

30

off

 

on

 

150

on

 

30

off

30

ST9120U1003

Trade

30

140

4

30

off

30

off

 

on

 

150

off

 

4

off

30

ST9141A1002

Consolidated

30

140

6

60

off

30

off

 

on

 

150

off

 

4

on

60

Industries

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ST9141A1028

Consolidated

30

140

6

60

off

30

off

 

on

 

150

off

 

4

on

60

Industries

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ST9141B1001

Consolidated

75

180

6

60

on

60

on

 

on

 

180

off

 

4

on

60

Industries

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ST9150A1003

Consolidated

36

168

7

72

off

30

on

 

on

 

180

off

 

4

on

60

Industries

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Heat fan off delay setting may need adjustment based on performance. See Fig. 10 to adjust timings.

69-2252EF—07

4

ST9120B,U UNIVERSAL ELECTRONIC FAN TIMERS

Table 3. Recommended Default Dip Switch Settings. (Continued)

 

 

Legacy Timing

 

 

 

 

New ST9120B,U

 

 

 

Replaced

 

Heat

Heat

Cool

Cool

 

 

 

 

 

 

 

 

 

 

 

 

On

Off

On

Off

Heat On

 

Heat Off

Cool On

Cool Off

Control Model

Original OEM

 

Number

Appliance

sec

sec

sec

sec

1

sec

2

 

3

sec

4

 

sec

5

sec

ST9150B2000

 

36

144

7

0

off

30

off

 

on

150

off

 

4

off

30

ST9150B2018

ICP

30

140

30

30

off

30

off

 

on

150

on

 

30

off

30

ST9150B2026

Ducane

36

144

7

36

off

30

off

 

on

150

off

 

4

off

30

ST9150B2034

 

36

144

7

36

off

30

off

 

on

150

off

 

4

off

30

ST9160A1002

Armstrong

30

90

6

60

off

30

off

 

off

120

off

 

4

on

60

ST9160B1001

 

30

120

6

30

off

30

off

 

off

120

off

 

4

off

30

ST9160B1019

 

30

120

6

30

off

30

off

 

off

120

off

 

4

off

30

ST9160B1027

 

30

120

6

60

off

30

off

 

off

120

off

 

4

on

60

ST9160B1035

 

30

120

6

30

off

30

off

 

off

120

off

 

4

off

30

ST9160B1043

ICP

30

140

6

30

off

30

off

 

on

150

off

 

4

off

30

ST9160B1050

ICP

30

140

6

60

off

30

off

 

on

150

off

 

4

on

60

ST9160B1068

Armstrong

30

120

6

60

on

30

off

 

off

120

off

 

4

on

30

ST9160B1076

Ducane

30

120

6

30

off

30

off

 

off

120

off

 

4

off

30

ST9160B1084

ICP

30

140

6

90

off

30

off

 

on

150

off

 

4

on

60

ST9160C1000

 

30

140

30

30

off

30

off

 

on

150

on

 

30

off

30

ST9160C1018

 

30

140

30

30

off

30

off

 

on

150

on

 

30

off

30

*ST9120B,U Factory Default

 

 

 

 

off

30

off

 

off

120

off

 

4

off

30

Setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Heat fan off delay setting may need adjustment based on performance. See Fig. 10 to adjust timings. NOTE: Timings may not be exactly the same as the replaced control and adjustments may need to be made.

5

69-2252EF—07

ST9120B,U UNIVERSAL ELECTRONIC FAN TIMERS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HUMIDIFIER

 

INDUCER

 

 

AIR

 

 

 

 

 

 

 

 

 

 

 

 

 

CLEANER

 

 

 

TO 115/230 VAC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

POWER SUPPLY

FUSE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L1 (HOT)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L2 (N)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FAN

STARTING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CAP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

HI

 

 

 

 

 

NEUTRAL

UNUSED

HUM

IND

L1

 

CONT

EAC

COOL

HEAT

ML

 

 

 

 

 

 

MH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LO

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STATUS

 

 

 

DELAY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LIMIT

 

 

 

 

 

 

 

 

 

 

 

115/230 VAC

 

 

SWITCH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TWIN

TRANSFORMER

 

 

ROLLOUT

 

 

 

 

 

 

 

 

 

 

 

24 VAC

 

 

 

 

FUSE

 

 

 

 

 

 

 

 

 

 

 

 

SWITCH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J1

 

 

 

 

 

 

 

 

 

 

 

 

 

PRESSURE

C

X

LIM PRSW Y

C

C

G

Y

W

 

R

 

 

 

 

SWITCH

 

 

 

MV

MV/PV PV

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MV MV/PV PV BRN 24V 24V SPARK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GND

 

 

 

 

 

 

 

C G Y W R

 

 

 

 

 

S8600 IGNITION CONTROL

 

 

 

THERMOSTAT

 

 

 

 

 

 

 

 

 

GND

SENSE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PILOT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BURNER

 

 

 

 

1 CONNECT ONLY IF CONTINUOUS SPEED IS AVAILABLE AND USED.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DENOTES LINE VOLTAGE WIRING

 

2

CONNECT ONLY IF CONTINUOUS SPEED IS NOT USED.

 

 

 

 

 

 

 

 

DENOTES LOW VOLTAGE WIRING

 

 

M27704

 

 

 

 

 

 

 

 

 

 

Fig. 1. Typical ST9120B,U wiring connections in ST9120 system with S8600 Intermittent Pilot Ignition Control.

69-2252EF—07

6

ST9120B,U UNIVERSAL ELECTRONIC FAN TIMERS

HUMIDIFIER

INDUCER

AIR CLEANER

TO 115/230 VAC

POWER SUPPLY

FUSE

L1 (HOT)

L2 (N)

 

 

 

 

 

 

 

 

 

 

 

 

 

FAN

STARTING

 

 

 

 

 

 

 

 

 

 

 

 

 

CAP

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HI

 

 

 

NEUTRAL

 

 

 

 

 

 

 

 

 

 

ML

 

 

 

 

 

 

 

 

 

 

 

 

 

MH

 

 

 

 

UNUSED

HUM

IND

L1

 

CONT

EAC

COOL

HEAT

LO

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

24 VOLT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COMMON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24 VOLT

 

 

 

J3

 

 

 

 

 

 

 

 

 

 

HOT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EFT

 

 

 

 

 

STATUS

 

 

 

DELAY

 

 

OUTPUT

 

 

 

 

 

 

 

 

 

 

 

 

24 VOLT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

THERMOSTAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OR PRESSURE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SWITCH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TWIN

 

115/230 VAC

 

 

 

 

 

 

 

 

 

 

 

 

TRANSFORMER

 

 

FUSE

 

 

 

 

 

 

 

 

 

24 VAC

 

 

 

 

 

 

 

 

 

 

 

 

ROLLOUT

LIMIT

 

 

 

 

 

 

 

 

 

 

 

 

 

SWITCH

SWITCH

J1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C

X

LIM PRSW Y

C

C

G

Y

W

R

 

 

 

SV9500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HOT SURFACE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IGNITION CONTROL

C G Y W R

THERMOSTAT

PRESSURE SWITCH

1 CONNECT ONLY IF CONTINUOUS SPEED IS AVAILABLE AND USED.

DENOTES LINE VOLTAGE WIRING

DENOTES LOW VOLTAGE WIRING

2 CONNECT ONLY IF CONTINUOUS SPEED IS NOT USED.

M27705

Fig. 2. Typical ST9120B,U wiring connections in ST9120 system with SV9500/SV9501 SmartValve™ Control.

7

69-2252EF—07

Honeywell ST9120U Installation Manual

ST9120B,U UNIVERSAL ELECTRONIC FAN TIMERS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FAN

STARTING

 

 

MAIN

 

 

 

 

 

 

 

 

 

 

CAP

 

 

 

 

 

 

 

 

 

 

 

 

HI

 

 

 

LIMIT

 

NEUTRAL

UNUSED

HUM

IND

L1

 

CONT EAC COOL

HEAT

 

 

 

 

 

 

 

LO

 

 

 

ROLLOUT

 

 

 

 

 

 

 

 

 

HL

 

 

 

 

 

 

 

 

 

 

 

 

HH

 

 

 

VENT

 

 

 

 

 

 

 

 

 

 

 

 

 

AUX

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J3

 

 

 

 

 

 

 

 

TO 115/230 VAC

 

 

 

 

 

 

STATUS

 

DELAY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

POWER SUPPLY

 

 

 

 

 

 

 

 

 

 

 

 

 

L2 (N)

FUSE

 

 

 

 

 

 

 

 

 

 

 

 

L1 (HOT)

 

WIRE HARNESS ADAPTER

 

 

 

 

 

 

TWIN

115/230 VAC

 

 

1

L2 WHITE

 

 

 

 

 

 

 

TRANSFORMER

 

 

 

 

 

 

 

 

 

 

 

INDUCER

 

2

L2 WHITE

3

FUSE

 

 

 

 

 

 

24 VAC

 

3

PS/MV DRIVE ORANGE

 

 

 

 

 

 

 

 

 

 

 

 

4

LIMIT RED

6

J1

 

 

 

 

 

 

 

 

 

 

 

5

LIMIT RED

1

 

 

 

 

 

 

 

 

 

 

 

GAS

6 L1 BLACK

4 NC

 

 

 

 

 

 

 

 

 

 

 

VALVE

7

24V GND YELLOW

2

 

 

 

 

 

 

 

 

 

 

 

 

8

MV SENSE VIOLET

5

 

 

 

 

 

 

 

 

 

 

 

 

9

INDUCER BLUE

 

C

X LIM PRSW Y

C

C G Y W R

 

 

 

 

 

 

 

 

 

 

 

 

 

PRESSURE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SWITCH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DENOTES LINE VOLTAGE WIRING

 

 

 

 

C

G

Y W R

 

 

 

 

 

 

 

 

 

THERMOSTAT

 

 

 

 

 

DENOTES LOW VOLTAGE WIRING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M27777

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 3. Typical ST9120B,U wiring connections in ST9101 system.

 

 

 

 

 

 

 

 

 

INDUCER

 

 

AIR

 

 

 

 

 

 

 

 

 

HUMIDIFIER

 

CLEANER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TO 115/230 VAC

FUSE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

POWER SUPPLY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L1 (HOT)

 

 

 

 

 

 

 

 

 

 

 

 

 

24 VOLT

 

L2 (N)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STARTING

COMMON

 

 

 

 

 

 

 

 

 

 

 

 

 

FAN

 

 

 

 

 

 

 

 

 

 

 

 

 

CAP

 

24VOLT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HI

 

 

HOT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NEUTRAL

 

 

 

 

 

 

 

 

 

 

 

EFT

 

 

 

UNUSED

HUM

IND

 

 

CONT

EAC

COOL

HEAT

ML

 

SWITCH

 

 

 

 

 

MH

 

24 VOLT OUTPUT

 

 

 

 

 

 

 

 

 

 

 

 

 

LO

 

THERMOSTAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OR PRESSURE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

SV9500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HOT SURFACE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IGNITION CONTROL

 

J3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STATUS

 

 

 

DELAY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TWIN

115/230 VAC

N.O.

N.C.

 

 

 

 

 

 

 

 

 

 

 

TRANSFORMER

 

 

 

 

 

FUSE

 

 

 

 

 

 

 

 

24 VAC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PRESSURE

COM

ST9141 WIRE HARNESS ADAPTER

 

 

 

 

 

 

 

 

 

 

 

 

SWITCH

 

J1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24V RED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

24V GNDYELLOW

2

 

 

 

 

 

 

 

 

 

 

 

 

 

BURNER

3

WORANGE

3

 

 

 

 

 

 

 

 

 

 

 

 

 

4

24VRED

4

 

 

 

 

 

 

 

 

 

 

 

 

 

LIMIT

5

FTVIOLET

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BRN LIMGRAY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

PRSWBROWN

6

C

X LIM PRSW Y

C

C

G

Y

W

R

 

 

 

 

 

7

PRIM LIMRED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

N.C.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PRIMARY

 

 

 

 

 

 

 

C

G

Y

W

R

 

 

 

 

LIMIT

 

 

 

 

 

 

 

 

THERMOSTAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DENOTES LINE VOLTAGE WIRING

1

CONNECT ONLY IF CONTINUOUS SPEED IS AVAILABLE AND USED.

 

 

 

 

 

 

DENOTES LOW VOLTAGE WIRING

2

CONNECT ONLY IF CONTINUOUS SPEED IS NOT USED.

M27722

 

 

 

 

 

Fig. 4. Typical ST9120B,U wiring connections in ST9141 system with SV9500/SV9501 SmartValve™ Control.

69-2252EF—07

8

ST9120B,U UNIVERSAL ELECTRONIC FAN TIMERS

HUMIDIFIER

TO 115 VAC

POWER SUPPLY FUSE

L1 (HOT)

1 L2 (N)

2

115 VAC TRANSFORMER 24 VAC

LOAD

COMMON

NEUTRAL

UNUSED

HUM

IND

 

 

5

 

 

J3

 

 

J1

3

C

X

 

 

DENOTES LINE VOLTAGE WIRING

DENOTES LOW VOLTAGE WIRING

 

AIR CLEANER

 

 

 

 

 

 

 

 

 

STARTING

PRESSURE

 

 

4

 

FAN

CAP

INDUCER

SWITCH

 

 

 

HI

 

 

 

 

 

 

 

ML

 

 

 

 

L1

CONT EAC COOL

HEAT

MH

 

 

 

 

LO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NEUTRAL

HOT

LIMIT ROLLOUT

 

 

 

 

 

SWITCH SWITCH

 

 

 

 

 

SV9501;

 

 

 

 

 

 

 

SV9520

 

 

 

 

 

 

 

 

C1

 

 

 

 

 

C

 

 

 

 

 

 

 

R

 

 

 

 

 

 

 

DATA

 

 

 

 

 

 

 

NEUTRAL

C3

C2

 

 

 

 

 

 

 

 

 

 

 

 

L1

 

 

 

C G

Y W R

 

 

 

 

 

 

 

 

 

 

 

 

 

FLAME ROD

 

 

 

 

 

2

 

HOT

 

 

 

 

 

 

 

SURFACE

C G Y W R

 

 

 

 

 

IGNITER

 

 

 

 

 

 

THERMOSTAT

 

 

 

 

 

 

1THERE MUST BE 115 VAC CONNECTED TO L1 (HOT) ON ST9120U, ST9120B.

2APPLIANCE CHASSIS MUST HAVE RELIABLE CONNECTION TO EARTH GROUND.

3JUMPER PLUG MUST BE ATTACHED TO J1 CONNECTOR.

4CONNECT ONLY IF CONTINUOUS SPEED IS AVAILABLE AND USED.

5 CONNECT ONLY IF CONTINUOUS SPEED IS NOT USED

M16880

Fig. 5. Typical ST9120B,U wiring connections in ST9160 system with SV9510/SV9520 SmartValve™ Control.

9

69-2252EF—07

ST9120B,U UNIVERSAL ELECTRONIC FAN TIMERS

 

HUMIDIFIER

 

 

 

AIR

TO 115/230 VAC

 

 

CLEANER

POWER SUPPLY FUSE

1

L1 (HOT)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L2 (N)

 

 

 

 

 

 

 

 

 

 

 

PRESSURE

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STARTING

SWITCH

 

 

 

 

 

 

 

 

 

 

 

INDUCER

 

 

 

 

 

 

 

 

 

 

 

 

FAN

CAP

 

 

 

 

 

 

 

 

 

 

 

 

4

 

HI

 

 

 

 

 

115/230 VAC

 

NEUTRAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ML

 

 

 

 

 

 

TRANSFORMER

 

 

 

 

 

 

 

MH

 

 

 

 

 

 

24 VAC

 

 

HUM

IND

L1

CONT EAC COOL

HEAT

LO

 

 

 

 

 

 

COMMON

 

 

 

 

 

 

 

 

LOAD

 

 

 

 

HOT

LIMIT

ROLLOUT

 

5

 

 

NEUTRAL

SWITCH SWITCH

 

UNUSED

 

 

SV9540;

 

 

 

 

 

 

J3

 

 

 

 

 

 

 

SV9640

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C1

 

 

 

 

 

 

 

 

 

 

 

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24VAC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DATA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NEUTRAL

C3

 

C2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L1

 

 

 

 

 

 

 

3

C

J1

 

 

 

 

 

 

 

 

 

 

 

 

 

X

 

 

C G

Y W R

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

Q345

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IGNITER-

 

 

 

 

 

 

 

C G Y W R

 

 

 

 

 

 

SENSOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DENOTES LINE VOLTAGE WIRING

 

 

THERMOSTAT

 

 

 

 

 

 

 

DENOTES LOW VOLTAGE WIRING

 

 

 

 

 

 

 

 

 

 

 

1FOR 115 VAC / 50, 60 HZ INSTALLATIONS, THERE MUST BE 115 VAC CONNECTED TO L1 (HOT) ON ST9120U, ST9120B. FOR 230 VAC / 60 HZ INSTALLATIONS, THERE MUST BE 115 VAC BETWEEN L1 (HOT) AND APPLIANCE CHASSIS.

FOR 230 VAC / 50 HZ INSTALLATIONS, USE ONLY WITH SMART VALVE RATED FOR THE SAME LINE VOLTAGE PARAMETERS.

2APPLIANCE CHASSIS MUST HAVE RELIABLE CONNECTION TO EARTH GROUND.

3JUMPER PLUG MUST BE ATTACHED TO J1 CONNECTOR.

4CONNECT ONLY IF CONTINUOUS SPEED IS AVAILABLE AND USED.

5 CONNECT ONLY IF CONTINUOUS SPEED IS NOT USED

M27724A

Fig. 6. Typical ST9120B,U wiring connections in ST9160 system with SV9540/SV9640 SmartValve™ Control.

69-2252EF—07

10

Loading...
+ 22 hidden pages