Honeywell T7460C, T7460A, T7460D, T7460B, T7460F Manual

...
0 (0)
® U.S. Registered Trademark
Copyright © 2005 Honeywell Inc. All Rights Reserved 74-3083-2
T7460A,B,C,D,E,F
WALL MODULES
HONEYWELL EXCEL 5000 OPEN SYSTEM
SPECIFICATION DATA
FEATURES
directly on a wall.
Models with setpoint adjustment.
Models with bypass (override) button and LED.
Models with 3-position (auto/0/1) or 5-position
(auto/0/1/2/3 speed) fan switch.
Setpoint dials with Celsius relative or Celsius absolute
scale.
Locking cover on all models.
Operating range 43…104°F (6…40°C).
CE-approved.
IP 30 housing.
GENERAL
The T7460A,B,C,D,E,F are a family of direct-wired wall
modules for use with Honeywell Excel 10 W7750, W7751,
W7752, W7753, W7761, W7762, W7763, and Excel 600,
500, 100, 50, 20 Controllers. All models have a space
temperature sensor; some models have setpoint adjustment,
bypass button and LED, and fan switch.
DESCRIPTION
The T7460A,B,C,D,E,F packages include two setpoint dials.
By default, the “Celsius Relative” type (-5 … +5) is mounted,
but can be easily replaced with the “Celsius Absolute” type
(12…30°C).
T7460A,B,C,D,E,F WALL MODULES
74-3083-2 2
SPECIFICATIONS
Table 1. T7460 Wall Module models
type no. setpoint adjustment
bypass
(override)
button and
LED
fan switch
3- or 5-
position
compatible with
T7460A -- -- --
W7750A,B, W7751B,D,F,H, W7752D,E,F,G, W7753A, W7761A,
W7762A,B, W7763C,D,E, and
Excel 600, 500, 100, 50, 20
T7460B -- --
W7750A,B, W7751B,D,F,H, W7752D,E,F,G, W7753A, W7762B,
W7763E, and
Excel 600, 500, 100, 50, 20
T7460C 3 --
W7750A,B, W7751B,D,F,H, W7752D,E,F,G, W7753A,
W7762A,B, W7763D,E, and
Excel 600, 500, 100, 50, 20
T7460D -- 5
W7752D,E,F,G, W7753A, and
Excel 600, 500, 100, 50, 20
T7460E 3 3
W7750A,B, W7752D,E,F,G, W7753A, and Excel 600, 500, 100,
50, 20
T7460F
12…30 °C (absolute)
± 5 K (relative)
3 5
W7752D,E,F,G, W7753A, and
Excel 600, 500, 100, 50, 20
NOTE: Not all of the T7460 Wall Modules are compatible with W7751A,C,E,G (VAV1) and W7752D1 (FCU1) controllers.
NOTE: Refer to T7460A,B,C,D,E,F Installation Instructions (product literature no.: EN1B-0291GE51) for wall module settings
and wiring diagrams.
Construction:
Two-piece construction: cover and internally wired subbase.
Field wiring 16 to 22 AWG (1.5 to 0.34 mm
2
) connects to a
terminal block on the PCB.
Temperature Sensor Operating Range:
43…104°F (6…40°C).
T7460A,B,C,D,E,F 20k Sensor:
All T7460 models are furnished with a 20k NTC temperature
sensor following a specific temperature-resistance curve. See
Fig. 1. Honeywell controllers used with the T7460 employ an
algorithm that provides readings close to the actual
temperature. Table 2 summarizes the T7460 sensor accuracy
for normal operating temperatures. Throughout the range of
43…104°F (6…40°C), the accuracy is better than ±0.75°F
(±0.42°C).
Table 2. Temperature sensor accuracy
ambient temp.
°F (°C)
max. error
°F (°C)
nom. resistance
()
60 (15.5) ±0.52 (±0.29) 31543
65 (18.3) ±0.49 (±0.27) 27511
70 (21.1) ±0.48 (±0.27) 24047
80 (26.7) ±0.49 (±0.27) 18490
85 (29.5) ±0.52 (±0.29) 16264
80 K
70 K
60 K
50 K
40 K
30 K
20 K
10 K
30
0 10 20 30 40
40 50 60 70 80 90 100 110
°
F
°C
temperature (degrees)
elec
t
r
ical
r
e
s
i
s
t
ance (
o
hm
s
)
Fig. 1. Temperature vs. resistance for 20k sensor
T7460B,C,D,E,F Setpoint Adjustment:
In the case of wall modules equipped with setpoint adjust-
ment, depending on the type of setpoint dial in use, the con-
troller must be set for either the relative or the absolute scale.
The relation between setpoint and resistance is given in Table
3. Accuracy of resistance is:
±5% in middle position, e.g. 5225 to 5775 ;
±10% in end position, e.g. 9450 to 11550 .