Honeywell R8182D, R8182E, R8182F, R8182H, R8182J User Manual

0 (0)

R8182D,E,F,H,J Combination

Protectorelay™ Primary Control and

Aquastat® Controller

INSTALLATION INSTRUCTIONS

APPLICATION

The R8182 combines a Protectorelay™ primary control and immersion type Aquastat® controller in one unit for use in oil-fired, hydronic heating systems.

KNOCKOUTS FOR 1/2 IN. (13 MM) CONDUIT (5)

The Protectorelay™ primary control provides control of a line voltage, intermittent ignition oil burner when used with a C554A Cadmium Sulfide Flame Detector and a 24V thermostat.

The R8182 models provide switching as follows:

Model

Switching

 

 

R8182D

High limit, spst;

 

Low limit/circulator, spdt

 

 

R8182E

High limit, spst

 

 

R8182F

High limit, spst

 

Circulator, spst

 

 

R8182H (with remote bulb)

High limit, spst

 

Low limit/circulator, spdt

 

 

R8182J (with remote bulb)

High limit, spst

 

 

The auxiliary ZC and ZR terminals on the R8182D,E,H,J provide zone control through an R845A Switching Relay.

All models are capable of zone control using zone valves. Each additional zone requires a separate 24V thermostat and a V8043 or V8044 Zone Valve.

The R8182D,E,F models mount directly on the boiler. The R8182H,J models mount directly on a 4 by 4 inch junction box and have a 5 foot (1.5 meter) armored capillary for remote sensor location.

To order an immersion well, use form 68-0040 Wells and Fittings for Temperature Controllers, for part numbers and descriptions.

Refer to Fig. 1 through 3 for installation dimensions.

Refer to Fig. 4 through 8 for internal views of the R8182D,E,F,G,J.

2-7/16

 

 

(62)

 

 

1-5/16

 

 

(33)

 

1

 

 

VERTICAL

7-1/8

 

MOUNT

 

ONLY

(181)

 

 

 

3-9/16

HORIZONTIAL

MOUNT ONLY

(91)

 

 

3/16

5-1/4

(133)

(5)

 

 

1 VERTICAL MOUNT SHOWN.

3-1/4 (83)

M4517

Fig. 1. R8182D,E,F installation dimensions in inches (millimeters).

Copyright © 1995 Honeywell Inc. • All Rights Reserved

X-XX UL

69-0600-1

Honeywell R8182D, R8182E, R8182F, R8182H, R8182J User Manual

R8182D,E,F,H,J COMBINATION PROTECTORELAY™ PRIMARY CONTROL AND AQUASTAT® CONTROLLER

1/2 (13)

3-3/8 (86)

7/8

 

(22)

 

3-7/16

 

(87)

 

7-1/8

 

(181)

 

5-1/4

(133)

KNOCKOUTS

FOR 1/2 IN. (13 MM) CONDUIT (5)

1

3-7/16 (87)

 

SAFETY SWITCH

GROUNDING SCREW

RESET BUTTON

TRANSFORMER

FOR THERMOSTAT

CIRCUIT

DIFFERENTIAL

SETTING

CIRCULATOR

RELAY (1K)

BURNER MOTOR

AND IGNITION

RELAY (2K)

LOW LIMIT

SETTING

VOLTAGE BARRIER

HIGH LIMIT

TRANSFORMER FOR

SETTING

CAD CELL CIRCUIT

 

M4525

Fig. 4. Internal view of R8182D.

 

SAFETY SWITCH

GROUNDING SCREW

RESET BUTTON

 

1 SIDE MOUNTED HINGE SHOWN.

 

 

 

TRANSFORMER

 

 

 

 

 

 

 

 

 

 

 

M4518

 

FOR THERMOSTAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CIRCUIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AQUASTAT SWITCH

Fig. 2. R8182H,J installation dimensions in inches

 

 

 

 

 

 

(millimeters).

 

CIRCULATOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RELAY (1K)

 

R8182D,E,F

 

 

 

BURNER MOTOR

 

 

 

 

AND IGNITION

 

 

CONTROL MOUNT

FITS BOILER TAPPED HOLE

 

RELAY (2K)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1/2 OR 3/4 NPT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VOLTAGE BARRIER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INSERTION LENGTH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INSULATION LENGTH

 

 

 

 

HIGH LIMIT

TRANSFORMER FOR

 

 

1-1/2 OR 3 IN.

3-3/8 IN. (86 MM)

M4532

 

(38 OR 76 MM)

 

 

SETTING

CAD CELL CIRCUIT

 

 

 

 

 

 

R8182H,J

SETSCREW

 

 

FITS BOILER TAPPED HOLE

 

 

 

 

 

 

 

 

1/2 OR 3/4 NPT

 

 

 

 

 

 

 

 

INSERTION LENGTH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INSULATION LENGTH

 

 

 

 

 

 

1-1/2 IN. (38 MM)

 

 

3-3/8 IN. (86 MM)

 

 

 

 

 

 

 

 

M4530

Fig. 3. Immersion well dimensions in inches (millimeters).

Fig. 5. Internal view of R8182E.

GROUNDING SCREW

SAFETY SWITCH

RESET BUTTON

HIGH LIMIT

SETTING

BURNER MOTOR

AND IGNITION

RELAY (2K)

LOW LIMIT

SETTING

TRANSFORMER FOR

CAD CELL CIRCUIT

VOLTAGE BARRIER

M4515

Fig. 6. Internal view of R8182F.

69-0600—1

2

R8182D,E,F,H,J COMBINATION PROTECTORELAY™ PRIMARY CONTROL AND AQUASTAT® CONTROLLER

SAFETY SWITCH

RESET BUTTON

 

 

TRANSFORMER

 

 

FOR THERMOSTAT

 

 

CIRCUIT

 

 

DIFFERENTIAL

 

 

SETTING

 

 

CIRCULATOR

 

 

RELAY (1K)

 

 

BURNER MOTOR

 

 

AND IGNITION

 

 

RELAY (2K)

 

 

LOW LIMIT

 

 

SETTING

 

 

VOLTAGE BARRIER

HIGH LIMIT

TRANSFORMER FOR

CAD CELL CIRCUIT

SETTING

CAD CELL

 

 

M4524

 

LEADS (YELLOW)

 

 

Fig. 7. Internal view of R8182H.

SAFETY SWITCH

RESET BUTTON

TRANSFORMER

FOR THERMOSTAT

CIRCUIT

AQUASTAT SWITCH

2K RELAY

1K RELAY

VOLTAGE BARRIER

TRANSFORMER

FOR CAD CELL

CIRCUIT

HIGH LIMIT

SETTING

CAD CELL LEADS (YELLOW)

M4531

Fig. 8. Internal view of R8182J.

INSTALLATION

When Installing this Product…

Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.

Check the ratings given in these instructions and on the product to be sure the product is suitable for your application.

Be sure the installer is a trained, experienced service technician.

After completing installation, use these instructions to check product operation.

CAUTION

1.Disconnect the power supply before beginning installation to prevent electrical shock or equipment damage.

2.Be sure that the combustion chamber is clear of oil or oil vapor before starting burner.

3.Be sure that the ambient temperature at the element does not exceed 250°F (121°C).

IMPORTANT

Be sure that the sensing bulb fits snugly inside the immersion well and that the sensing bulb rests against the bottom of the immersion well. Refer to Fig. 3.

Mounting the R8182

Disconnect power supply.

Drain all water from boiler.

Most boilers are equipped with a tapping that allows horizontal mounting of immersion well where average temperature boiler water circulates freely. If no tapping is provided, prepare one.

Install immersion well or compression fitting (ordered separately) by threading immersion well into tapped hole.

For R8182D,E,F models:

a.Loosen immersion well clamp screw on side of R8182 case.

b.Insert bulb into immersion well until it bottoms.

c.If necessary, bend capillary tube to hold bulb against bottom of immersion well.

NOTE: Do not make sharp bends in the tubing. A sharp bend can break the tubing and cause a loss of fill. In models with an adjustable tubing length, pull the extra tubing out of the controller case.

d.Fit controller case onto immersion well so that immersion well clamp slides over flange of immersion well.

e.Securely tighten immersion well clamp screw.

For R8182H,J models:

a.Loosen the screw holding the hinged backplate to the controller case and swing the backplate away from the controller case.

b.Screw the backplate to a 4 by 4 inch junction box.

c.Insert bulb into immersion well until it bottoms.

d.If necessary, bend capillary tube to hold bulb against bottom of immersion well.

NOTE: Do not make sharp bends in the tubing. A sharp bend can break the tubing and cause a loss of fill. In models with an adjustable tubing length, pull the extra tubing out of the controller case.

e.Tighten immersion well screw over brass collar.

f.After wiring, swing the control against the backplate and refasten the screw.

Refill the boiler and check for water leakage.

3