Dell™ Basic Rack
Power Distribution Unit (PDU)
K558N
Product Overview and Specifications
English |
Français |
Español |
Deutsch |
|
|
Русский язык |
|
|
pdu0437a
The Dell Basic Rack PDU distributes power to the devices in the rack.
O UT L E T S — The Rack PDU has thirteen (13) C13 outlets.
P OW E R C OR D— The Rack PDU has an IEC-320 C20 inlet and can be used with a detached power cord (not provided).
K558N
Electrical
Input connection |
IEC-320 C20 inlet |
|
|
Acceptable input voltage |
100–240 VAC ± 10% (UL(C-UL)) |
|
200–240 VAC ± 10% (International) |
Maximum input current (phase) |
16 A (UL(C-UL) derated) |
|
20 A (PSE) |
|
16 A (International) |
|
|
Input frequency |
50/60 Hz |
|
|
Output voltage |
100–240 VAC ± 10% (UL(C-UL)) |
|
200–240 VAC ± 10% (International) |
Output connections |
(13) C13 |
|
|
Maximum output current (outlet) |
C13; 12 A (UL(C-UL) derated) |
|
C13; 15 A (PSE) |
|
C13; 10 A (International) |
|
|
Maximum output current (phase) |
16 A (UL(C-UL) derated) |
|
20 A (PSE) |
|
16 A (International) |
|
|
Physical |
|
|
|
|
|
Dimensions |
38.81 x 4.36 x 9.29 cm |
(H x W x D) |
(15.28 x 1.72 x 3.66 in) |
|
|
Shipping dimensions |
43.61 x 21.03 x 7.59 cm |
(H x W x D) |
(17.17 x 8.28 x 2.99 in) |
|
|
Weight |
1.50 kg (3.30 lb) |
|
|
Shipping weight |
2.00 kg (4.44 lb) |
|
|
Environmental |
|
|
|
|
|
Maximum elevation |
|
(above MSL) |
0 to 3048 m (0 to 10,000 ft) |
Operating |
|
Storage |
0 to 15 240 m (0 to 50,000 ft) |
|
|
Temperature |
0 to 50°C (32 to 122°F) |
Operating |
|
Storage |
–15 to 60°C (5 to 140°F) |
|
|
Humidity |
5 to 95%, non-condensing |
Operating |
|
Storage |
5 to 95%, non-condensing |
|
|
Compliance |
|
|
|
|
|
Safety approvals |
UL(C-UL), VDE, IRAM, SABS, GOST-R, |
|
PSE, SONCAP, KC, CE |
|
|
ROHS |
Dell 6T198 |
|
EU DIRECTIVE 2002/95/EC–latest revision |
|
|
2 |
|
Dell Basic Rack Power Distribution Unit—Product Overview and Specifications |
|
Information in this document is subject to change without notice. © 2009 Dell Inc. All rights reserved.
Reproduction of these materials in any manner whatsoever without the written permission of Dell Inc. is strictly forbidden.
Trademarks used in this text: Dell and the DELL logo are trademarks of Dell Inc.
Other trademarks and trade names may be used in this document to refer to either the entities claiming the marks and names or their products. Dell Inc. disclaims any proprietary interest in trademarks and trade names other than its own.
Model K558N
07/2009 |
Part Number 990-3566 |
w ww. dell. com | support.dell. com
Produktübersicht und technische Daten
pdu0437a
Die Dell Basis-PDU für Rack-Einbau verteilt Strom an die im Rack befindlichen Geräte.
ST R OMA US GÄN GE — Die Rack-PDU verfügt über dreizehn C13-Ausgänge.
N E T Z KA BE L — Die Rack-PDU verfügt über einen IEC-320 C20-Eingang und kann über ein abziehbares Netzkabel (nicht mitgeliefert) betrieben werden.
K558N
Elektrische Wartung
Eingangsanschluss |
IEC-320 C20-Eingang |
|
|
Zulässige Eingangsspannung |
100–240 V~ ± 10% (UL(C-UL)) |
|
200–240 V~ ± 10% (international) |
Maximaler Eingangsstrom (Phase) |
16 A (UL(C-UL) unterbelastet) |
|
20 A (PSE) |
|
16 A (international) |
|
|
Eingangsfrequenz |
50/60 Hz |
|
|
Ausgangsspannung |
100–240 V~ ± 10% (UL(C-UL)) |
|
200–240 V~ ± 10% (international) |
Ausgangsanschlüsse |
(13) C13 |
|
|
Maximaler Ausgangsstrom (Steckdosen) |
C13; 12 A (UL(C-UL) unterbelastet) |
|
C13; 15 A (PSE) |
|
C13; 10 A (international) |
|
|
Maximaler Ausgangsstrom (Phase) |
16 A (UL(C-UL) unterbelastet) |
|
20 A (PSE) |
|
16 A (international) |
|
|
Maße und Gewichte |
|
|
|
|
|
Abmessungen |
38,81 x 4,36 x 9,29 cm |
(H × B × T) |
(15,28 x 1,72 x 3,66 Zoll) |
|
|
Versandgröße |
43,61 x 21,03 x 7,59 cm |
(H × B × T) |
(17,17 x 8,28 x 7,59 cm) |
|
|
Gewicht |
1,5 kg (3,3 lb) |
|
|
Versandgewicht |
2,0 kg (4,44 lb) |
|
|
Umgebungsbedingungen |
|
|
|
Maximale Höhe |
|
(über Normalnull) |
0 bis 3048 m (0 bis 10.000 Fuß) |
Betrieb |
|
Lagerung |
0 bis 15 240 m (0 bis 50.000 Fuß) |
|
|
Temperatur |
0 bis 50 °C (32 bis 122 °F) |
Betrieb |
|
Lagerung |
–15 bis 60 °C (5 bis 140 °F) |
|
|
Luftfeuchtigkeit |
5 bis 95 %, nicht kondensierend |
Betrieb |
|
Lagerung |
5 bis 95 %, nicht kondensierend |
|
|
Konformität |
|
|
|
|
|
Sicherheitszulassungen |
UL(C-UL), VDE, IRAM, SABS, GOST-R, PSE, |
|
SONCAP, KC, CE |
|
|
ROHS |
Dell 6T198 |
|
EU-RICHTLINIE 2002/95/EG – neueste Fassung |
2 |
|
Dell Basis-Stromverteilerleiste für Rack-Einbau – Produktübersicht und technische |
|
Information in this document is subject to change without notice. © 2009 Dell Inc. All rights reserved.
Reproduction of these materials in any manner whatsoever without the written permission of Dell Inc. is strictly forbidden.
Trademarks used in this text: Dell and the DELL logo are trademarks of Dell Inc.
Other trademarks and trade names may be used in this document to refer to either the entities claiming the marks and names or their products. Dell Inc. disclaims any proprietary interest in trademarks and trade names other than its own.
Modell K558N
07/2009 |
Artikelnummer 990-3566 |
w ww. dell. com | support.dell. com
Descripción general y especificaciones del producto
pdu0437a
La PDU de rack básica Dell distribuye la alimentación a los dispositivos del rack.
E NC HUF E S— La PDU de rack tiene trece (13) enchufes C13.
C AB L E DE AL I ME N T AC IÓ N— La PDU de rack tiene una entrada IEC-320 C20 que se puede utilizar con un cable de alimentación desconectable (no suministrado).
K558N
Eléctricas
Conexión de entrada |
Entrada IEC-320 C20 |
|
|
Tensión de entrada aceptable |
100–240 V de CA ± 10% (UL(C-UL)) |
|
200–240 V de CA ± 10% (Internacional) |
Corriente de entrada máxima (fase) |
16 A (UL(C-UL) limitada) |
|
20 A (PSE) |
|
16 A (Internacional) |
|
|
Frecuencia de entrada |
50/60 Hz |
|
|
Tensión de salida |
100–240 V de CA ± 10% (UL(C-UL)) |
|
200–240 V de CA ± 10% (Internacional) |
Conexiones de salida |
(13) C13 |
|
|
Corriente de salida máxima (enchufe) |
C13; 12 A (UL(C-UL) limitada) |
|
C13; 15 A (PSE) |
|
C13; 10 A (Internacional) |
|
|
Corriente de salida máxima (fase) |
16 A (UL(C-UL) limitada) |
|
20 A (PSE) |
|
16 A (Internacional) |
|
|
Físicas |
|
|
|
|
|
Dimensiones |
38,81 x 4,36 x 9,29 cm |
(Altura x Anchura x Profundidad) |
(15,28 x 1,72 x 3,66 pulg.) |
|
|
Dimensiones de salida de fábrica |
43,61 x 21,03 x 7,59 cm |
(Altura x Anchura x Profundidad) |
(17,17 x 8,28 x 2,99 pulg.) |
|
|
Peso |
1,50 kg (3,30 lb) |
|
|
Peso de salida de fábrica |
2,00 kg (4,44 lb) |
|
|
Ambientales |
|
|
|
Altura máxima |
|
(sobre el nivel del mar) |
0 a 3048 m (0 a 10.000 ft) |
Funcionamiento |
|
Almacenamiento |
0 a 15 240 m (0 a 50.000 ft) |
|
|
Temperatura |
0 a 50 °C (32 a 122 °F) |
Funcionamiento |
|
Almacenamiento |
–15 a 60 °C (5 a 140 °F) |
|
|
Humedad |
5 a 95%, sin condensación |
Funcionamiento |
|
Almacenamiento |
5 a 95%, sin condensación |
|
|
Cumplimiento |
|
|
|
|
|
Aprobaciones de seguridad |
UL(C-UL), VDE, IRAM, SABS, GOST-R, PSE, |
|
SONCAP, KC, CE |
|
|
ROHS |
Dell 6T198 |
|
DIRECTIVA 2002/95/EC DE LA UE–última revisión |
2 |
|
Unidad de distribución de alimentación de rack básica Dell—Descripción general |
|
La información de este documento está sujeta a cambios sin previo aviso. © 2009 Dell Inc. All rights reserved.
Reproduction of these materials in any manner whatsoever without the written permission of Dell Inc. is strictly forbidden.
Trademarks used in this text: Dell and the DELL logo are trademarks of Dell Inc.
Other trademarks and trade names may be used in this document to refer to either the entities claiming the marks and names or their products. Dell Inc. disclaims any proprietary interest in trademarks and trade names other than its own.
Modelo K558N
07/2009 |
Número de pieza 990-3566 |
w ww. dell. com | support.dell. com