Delfield™ ®
F5 and F15 Series
Service and Installation Manual
Please read this manual completely before attempting to install or operate this equipment! Notify carrier of damage! Inspect all components immediately. See page 2.
F5 and F15 SERIES
Drop-In and Serview Display Cases
|
|
|
IMPORTANT |
INFORMATION |
|||||
|
|
|
|
|
USE |
||||
|
|
|
|
READ |
BEFORE |
|
|||
|
|
|
|
|
|
INSTRUCTIONS! |
|||
|
|
N |
|
|
THESE |
||||
|
IO |
|
|
|
|
||||
UT |
|
|
|
|
|
|
|
|
|
CA |
|
|
|
SAVE |
|
|
|
|
|
|
PLEASE |
|
|
|
|
Effective Date June 2008 |
|||
|
|
|
|
|
|
F5 & F15 Series Service and Installation Manual
Contents
Serial Number Location......................................................... |
2 |
Receiving & Inspecting Equipment........................................ |
2 |
Specifications |
|
F5 Series........................................................................ |
3 |
F15 Series...................................................................... |
4 |
Installation |
|
F5 Series........................................................................ |
5 |
F15 Series...................................................................... |
6 |
Shelf Installation.................................................................... |
7 |
Display Lock Operation.......................................................... |
7 |
General Operation.................................................................. |
7 |
Pressure Control Settings...................................................... |
7 |
Maintenance.......................................................................... |
8 |
Sliding Door Assembly Maintenance..................................... |
9 |
Sliding Door Removal and Reinstall...................................... |
9 |
Condenser Air Flow............................................................. |
10 |
Pike Door Components List................................................. |
11 |
Condensing Unit Assembly.................................................. |
12 |
Fluorescent Fixture.............................................................. |
13 |
Door Assembly — Serview Bases....................................... |
13 |
Coil Assembly...................................................................... |
14 |
Replacement Parts.............................................................. |
15 |
Wiring Diagram................................................................... |
16 |
Standard Labor Guidelines.................................................. |
17 |
Standard Warranties...................................................... |
18-19 |
Serial Number Location
The serial number on all self-contained F5 Series units is located near the condensing unit. On all remote F5 Series units the serial number is located on the drop-in frame.
The serial number on all self-contained F15 Series units is located behind the compressor housing. On all remote F15 Series units the serial number is located behind the six inch panel in the base.
Always have the serial number of your unit available when calling for parts or service. A complete list of authorized Delfield parts depots is available at www.delfield.com.
©2008 The Delfield Company. All rights reserved. Reproduction without written permission is prohibited.
SERIAL #
MODEL #
INSTALLATION DATE:
Receiving And Inspecting The Equipment
Even though most equipment is shipped crated, care should be taken during unloading so the equipment is not damaged while being moved into the building.
1.Visually inspect the exterior of the package and skid or container. Any damage should be noted and reported to the delivering carrier immediately.
2.If damaged, open and inspect the contents with the carrier.
3.In the event that the exterior is not damaged, yet upon opening, there is concealed damage to the equipment notify the carrier. Notification should be made verbally as well as in written form.
4.Request an inspection by the shipping company of the damaged equipment. This should be done within 10 days from receipt of the equipment.
5.Check the lower portion of the unit to be sure legs or casters are not bent.
6.Also open the compressor compartment housing and visually inspect the refrigeration package. Be sure lines are secure and base is still intact.
7.Freight carriers can supply the necessary damage forms upon request.
8.Retain all crating material until an inspection has been made or waived.
Uncrating the Equipment
First cut and remove the banding from around the crate. Remove the front of the crate material, use of some tools will be required. If the unit is on legs remove the top of the crate as well and lift the unit off the skid. If the unit is on casters it can be "rolled" off the skid.
For customer service, call (800) 733-8829, (800) 733-8821, Fax (989) 773-3210, www.delfield.com |
Delfield® |
|
™ |
|
|
|
|
|
|
F5 & F15 Series Service and Installation Manual |
||||||
|
|
|
|
|
|
|
|
|
|
|||
|
F5 Series Specifications |
|
|
|
|
|
|
|
|
|||
|
24” (61cm) Deep Remote Drop-In Refrigerated Display Cases |
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
VOLTS/ |
|
CABINET |
EVAPORATOR DISPLAY |
|
|
|
|
|
|
|
|
|
|
CAPACITY |
|
|
|
|
||
|
|
|
|
|
HERTZ/ |
|
LOAD BTU/ |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
MODEL |
L |
D |
H |
PHASE |
AMPS |
HOUR |
BTU |
°TD |
TEMP |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
F5MR48N |
48" (121.9cm) |
24" (61.0cm) |
42" (106.7cm) |
115/60/1 |
4.0 |
1215 |
150 |
20° |
15° |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
F5SR48N |
48" (121.9cm) |
24" (61.0cm) |
42" (106.7cm) |
115/60/1 |
4.0 |
1867 |
150 |
20° |
15° |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
F5PR48N |
48" (121.9cm) |
24" (61.0cm) |
42" (106.7cm) |
115/60/1 |
4.0 |
1945 |
150 |
20° |
15° |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
F5MR72N |
72" (182.9cm) |
24" (61.0cm) |
42" (106.7cm) |
115/60/1 |
4.0 |
1783 |
450 |
13° |
22° |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
F5SR72N |
72" (182.9cm) |
24" (61.0cm) |
42" (106.7cm) |
115/60/1 |
4.0 |
2791 |
450 |
13° |
22° |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
F5PR72N |
72" (182.9cm) |
24" (61.0cm) |
42" (106.7cm) |
115/60/1 |
4.0 |
2884 |
450 |
13° |
22° |
|
|
|
|
|
|
|
|
|
|
|
||||
|
24” (61cm) Deep Self-Contained Drop-In Refrigerated Display Cases |
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
VOLTS/ |
|
CABINET |
SYSTEM |
|
R404A |
|
|
|
|
|
|
|
HERTZ/ |
|
LOAD BTU/ |
CAPACITY |
|
CHARGE, |
NEMA |
|
|
MODEL |
L |
D |
H |
PHASE |
AMPS |
HOUR |
BTU/HOUR |
H.P. |
OZ. |
PLUG |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
F5MC48N |
48" (121.9cm) |
24" (61.0cm) |
57.5" (146.1cm) |
115/60/1 |
12.0 |
1215 |
2970 |
1/2 |
32 |
5-15P |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
F5SC48N |
48" (121.9cm) |
24" (61.0cm) |
57.5" (146.1cm) |
115/60/1 |
12.0 |
1867 |
2970 |
1/2 |
32 |
5-15P |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
F5PC48N |
48" (121.9cm) |
24" (61.0cm) |
57.5" (146.1cm) |
115/60/1 |
12.0 |
1945 |
2970 |
1/2 |
32 |
5-15P |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
F5MC72N |
72" (182.9cm) |
24" (61.0cm) |
57.5" (146.1cm) |
115/60/1 |
16.0 |
1783 |
5821 |
3/4 |
48 |
5-20P |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
F5SC72N |
72" (182.9cm) |
24" (61.0cm) |
57.5" (146.1cm) |
115/60/1 |
16.0 |
2791 |
5821 |
3/4 |
48 |
5-20P |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
F5PC72N |
72" (182.9cm) |
24" (61.0cm) |
57.5" (146.1cm) |
115/60/1 |
16.0 |
2884 |
5821 |
3/4 |
48 |
5-20P |
|
|
|
|
|
|
|
|
|
|
|
|||
|
30” (76.2cm) Deep Remote Drop-In Refrigerated Display Cases |
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
VOLTS/ |
|
CABINET |
EVAPORATOR DISPLAY |
|
|
|
|
|
|
|
|
|
|
CAPACITY |
|
|
|
|
||
|
|
|
|
|
HERTZ/ |
|
LOAD BTU/ |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
MODEL |
L |
D |
H |
PHASE |
AMPS |
HOUR |
BTU |
°TD |
TEMP |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
F5MR48D |
48" (121.9cm) |
30" (76.2cm) |
42" (106.7cm) |
115/60/1 |
4.0 |
1282 |
150 |
20° |
15° |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
F5SR48D |
48" (121.9cm) |
30" (76.2cm) |
42" (106.7cm) |
115/60/1 |
4.0 |
1934 |
150 |
20° |
15° |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
F5PR48D |
48" (121.9cm) |
30" (76.2cm) |
42" (106.7cm) |
115/60/1 |
4.0 |
2012 |
150 |
20° |
15° |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
F5MR72D |
72" (182.9cm) |
30" (76.2cm) |
42" (106.7cm) |
115/60/1 |
4.0 |
1870 |
450 |
13° |
22° |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
F5SR72D |
72" (182.9cm) |
30" (76.2cm) |
42" (106.7cm) |
115/60/1 |
4.0 |
2878 |
450 |
13° |
22° |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
F5PR72D |
72" (182.9cm) |
30" (76.2cm) |
42" (106.7cm) |
115/60/1 |
4.0 |
2971 |
450 |
13° |
22° |
|
|
|
|
|
|
|
|
|
|
|
||||
|
30” (76.2cm) Deep Self-Contained Drop-In Refrigerated Display Cases |
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
VOLTS/ |
|
CABINET |
SYSTEM |
|
R404A |
|
|
|
|
|
|
|
HERTZ/ |
|
LOAD BTU/ |
CAPACITY |
|
CHARGE, |
NEMA |
|
|
MODEL |
L |
D |
H |
PHASE |
AMPS |
HOUR |
BTU/HOUR |
H.P. |
OZ. |
PLUG |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
F5MC48D |
48" (121.9cm) |
30" (76.2cm) |
57.5" (146.1cm) |
115/60/1 |
12.0 |
1282 |
2970 |
1/2 |
32 |
5-15P |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
F5SC48D |
48" (121.9cm) |
30" (76.2cm) |
57.5" (146.1cm) |
115/60/1 |
12.0 |
1934 |
2970 |
1/2 |
32 |
5-15P |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
F5PC48D |
48" (121.9cm) |
30" (76.2cm) |
57.5" (146.1cm) |
115/60/1 |
12.0 |
2012 |
2970 |
1/2 |
32 |
5-15P |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
F5MC72D |
72" (182.9cm) |
30" (76.2cm) |
57.5" (146.1cm) |
115/60/1 |
16.0 |
1870 |
5821 |
3/4 |
48 |
5-20P |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
F5SC72D |
72" (182.9cm) |
30" (76.2cm) |
57.5" (146.1cm) |
115/60/1 |
16.0 |
2878 |
5821 |
3/4 |
48 |
5-20P |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
F5PC72D |
72" (182.9cm) |
30" (76.2cm) |
57.5" (146.1cm) |
115/60/1 |
16.0 |
2971 |
5821 |
3/4 |
48 |
5-20P |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
M = Mirror Back • P = Pass Thru • S = See Thru • R = Remote • C = Self-Contained • N = Narrow • D = Deep 30”
Delfield® |
For customer service, call (800) 733-8829, (800) 733-8821, Fax (989) 773-3210, www.delfield.com |
|
™ |
|
|
F5 & F15 Series Service and Installation Manual
F15 Series Specifications
24” (61cm) Deep Remote Serview Refrigerated Display Cases
|
|
|
|
VOLTS/ |
|
CABINET |
EVAPORATOR |
|
EVAPORATOR BASE |
|
|||
|
|
|
|
|
DISPLAY CAPACITY |
CAPACITY |
|
|
|
||||
|
|
|
|
HERTZ/ |
|
LOAD BTU/ |
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
||
MODEL |
L |
D |
H |
PHASE |
AMPS |
HOUR |
BTU |
°TD |
TEMP |
BTU |
°TD |
TEMP |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
F15MR48N |
48" (121.9cm) |
31.5" (80.0cm) |
78" (198.1cm) |
115/60/1 |
4.0 |
1644 |
200 |
23° |
12° |
120 |
30° |
|
5° |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
F15SR48N |
48" (121.9cm) |
33.38" (84.8cm) |
78" (198.1cm) |
115/60/1 |
4.0 |
2296 |
200 |
23° |
12° |
120 |
30° |
|
5° |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
F15PR48N |
48" (121.9cm) |
33.38" (84.8cm) |
78" (198.1cm) |
115/60/1 |
4.0 |
2374 |
200 |
23° |
12° |
120 |
30° |
|
5° |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
F15MR72N |
72" (182.9cm) |
31.5" (80.0cm) |
78" (198.1cm) |
115/60/1 |
4.0 |
2491 |
450 |
13° |
22° |
120 |
30° |
|
5° |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
F15SR72N |
72" (182.9cm) |
33.38" (84.8cm) |
78" (198.1cm) |
115/60/1 |
4.0 |
3499 |
450 |
13° |
22° |
120 |
30° |
|
5° |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
F15PR72N |
72" (182.9cm) |
33.38" (84.8cm) |
78" (198.1cm) |
115/60/1 |
4.0 |
3592 |
450 |
13° |
22° |
120 |
30° |
|
5° |
|
|
|
|
|
|
|
|
|
|
||||
24” (61cm) Deep Self-Contained Serview Refrigerated Display Cases |
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
VOLTS/ |
|
CABINET |
SYSTEM |
|
R404A |
|
|
|
|
|
|
|
|
HERTZ/ |
|
LOAD BTU/ |
CAPACITY |
|
CHARGE |
NEMA |
|
||
MODEL |
L |
D |
H |
PHASE |
AMPS |
HOUR |
BTU/HOUR |
H.P. |
OZ. |
PLUG |
|
|
|
F15MC48N |
48" (121.9cm) |
31.5" (80.0cm) |
78" (198.1cm) |
115/60/1 |
16.0 |
1569 |
8146 |
|
3/4 |
48 |
5-20P |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
F15SC48N |
48" (121.9cm) |
33.38" (84.8cm) |
78" (198.1cm) |
115/60/1 |
16.0 |
2221 |
8146 |
|
3/4 |
48 |
5-20P |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
F15PC48N |
48" (121.9cm) |
33.38" (84.8cm) |
78" (198.1cm) |
115/60/1 |
16.0 |
2299 |
8146 |
|
3/4 |
48 |
5-20P |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
F15MC72N |
72" (182.9cm) |
31.5" (80.0cm) |
78" (198.1cm) |
115/60/1 |
16.0 |
2361 |
9422 |
|
3/4 |
48 |
5-20P |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
F15SC72N |
72" (182.9cm) |
33.38" (84.8cm) |
78" (198.1cm) |
115/60/1 |
16.0 |
3369 |
9422 |
|
3/4 |
48 |
5-20P |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
F15PC72N |
72" (182.9cm) |
33.38" (84.8cm) |
78" (198.1cm) |
115/60/1 |
16.0 |
3462 |
9422 |
|
3/4 |
48 |
5-20P |
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
30” (76.2cm) Deep Remote Serview Refrigerated Display Cases |
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
VOLTS/ |
|
CABINET |
EVAPORATOR |
|
EVAPORATOR BASE |
|
|||
|
|
|
|
|
DISPLAY CAPACITY |
CAPACITY |
|
|
|
||||
|
|
|
|
HERTZ/ |
|
LOAD BTU/ |
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
||
MODEL |
L |
D |
H |
PHASE |
AMPS |
HOUR |
BTU |
°TD |
TEMP |
BTU |
°TD |
TEMP |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
F15MR48D |
48" (121.9cm) |
31.5" (80.0cm) |
78" (198.1cm) |
115/60/1 |
4.0 |
1711 |
200 |
23° |
12° |
120 |
30° |
|
5° |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
F15SR48D |
48" (121.9cm) |
33.38" (84.8cm) |
78" (198.1cm) |
115/60/1 |
4.0 |
2363 |
200 |
23° |
12° |
120 |
30° |
|
5° |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
F15PR48D |
48" (121.9cm) |
33.38" (84.8cm) |
78" (198.1cm) |
115/60/1 |
4.0 |
2441 |
200 |
23° |
12° |
120 |
30° |
|
5° |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
F15MR72D |
72" (182.9cm) |
31.5" (80.0cm) |
78" (198.1cm) |
115/60/1 |
4.0 |
2578 |
450 |
13° |
22° |
120 |
30° |
|
5° |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
F15SR72D |
72" (182.9cm) |
33.38" (84.8cm) |
78" (198.1cm) |
115/60/1 |
4.0 |
3586 |
450 |
13° |
22° |
120 |
30° |
|
5° |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
F15PR72D |
72" (182.9cm) |
33.38" (84.8cm) |
78" (198.1cm) |
115/60/1 |
4.0 |
3679 |
450 |
13° |
22° |
120 |
30° |
|
5° |
|
|
|
|
|
|
|
|
|
|
||||
30” (76.2cm) Deep Self-Contained Serview Refrigerated Display Cases |
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
VOLTS/ |
|
CABINET |
SYSTEM |
|
R404A |
|
|
|
|
|
|
|
|
HERTZ/ |
|
LOAD BTU/ |
CAPACITY |
|
CHARGE |
NEMA |
|
||
MODEL |
L |
D |
H |
PHASE |
AMPS |
HOUR |
BTU/HOUR |
H.P. |
OZ. |
PLUG |
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
F15MC48D |
48" (121.9cm) |
31.5" (80.0cm) |
78" (198.1cm) |
115/60/1 |
16.0 |
1636 |
8146 |
|
3/4 |
48 |
5-20P |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
F15SC48D |
48" (121.9cm) |
33.38" (84.8cm) |
78" (198.1cm) |
115/60/1 |
16.0 |
2288 |
8146 |
|
3/4 |
48 |
5-20P |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
F15PC48D |
48" (121.9cm) |
33.38" (84.8cm) |
78" (198.1cm) |
115/60/1 |
16.0 |
2366 |
8146 |
|
3/4 |
48 |
5-20P |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
F15MC72D |
72" (182.9cm) |
31.5" (80.0cm) |
78" (198.1cm) |
115/60/1 |
16.0 |
2448 |
9422 |
|
3/4 |
48 |
5-20P |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
F15SC72D |
72" (182.9cm) |
33.38" (84.8cm) |
78" (198.1cm) |
115/60/1 |
16.0 |
3456 |
9422 |
|
3/4 |
48 |
5-20P |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
F15PC72D |
72" (182.9cm) |
33.38" (84.8cm) |
78" (198.1cm) |
115/60/1 |
16.0 |
3549 |
9422 |
|
3/4 |
48 |
5-20P |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
M = Mirror Back • P = Pass Thru • S = See Thru • R = Remote • C = Self-Contained • N = Narrow 24" • D = Deep 30”
|
For customer service, call (800) 733-8829, (800) 733-8821, Fax (989) 773-3210, www.delfield.com |
Delfield® |
|
|
™ |
F5 & F15 Series Service and Installation Manual
Installation: Self-Contained F5 Series
Location
Units represented in this manual are for indoor use only. All self-contained units were tested at the factory to assure proper operation. The unit should not be installed directly next to high heat generating equipment (ranges, griddles, etc.). Be sure the location chosen has a counter strong enough to support the total weight of the cabinet and contents. A fully loaded model may weigh as much as 2,000 pounds! Reinforce the counter as necessary to provide for maximum loading.
These units are installed by “dropping” them into the counter from above. The counter cutout sizes are as follows:
48” wide units — 18.62" x 23.62" (47.3 cm x 60.0 cm) 72” wide units — 18.62" x 32.62" (47.3 cm x 82.9 cm)
Self-contained F5 Series units require airflow to the compressor. Two louvers are provided with each unit and should be installed as illustrated on page 10.
Unit is designed to maintain 36°F (2°C) to 40°F (4°C) interior cabinet temperature at 65% or lower ambient relative humidity.
Plumbing
Self-contained models are standard with a condensate evaporator. If, for some reason, a unit does not have a
condensate evaporator, or the evaporator fails, the unit’s drain must have an outlet to an appropriate drainage area or container.
Moisture collecting from improper drainage can create a slippery surface on the floor and a hazard to employees. It is the owner’s
CAUTION responsibility to provide a container or outlet for drainage.
Electrical connection
Refer to the amperage data on pages 3 & 4, the serial tag, your local code or the National Electrical Code to be sure the unit is connected to the proper power source. A protected circuit of the correct voltage and amperage must be run for connection of the line cord, or permanent connection to the unit.
Self-contained units have an ON/OFF switch in the junction box. Simply turn the switch to ON to begin operation.
The power switch should be turned to OFF and the unit disconnected from the power source DANGER whenever performing service or maintenance
functions.
Installation: Remote F5 Series
1.75" |
|
|
4.4cm |
|
|
CUTOUT |
3.75" |
|
9.5cm |
|
|
3.00" x 12.00"/ |
C |
|
7.6cm x 30.5cm— |
|
|
CENTEREDFRONT |
R |
|
TO BACK—0.25"/ |
|
0.6cm FROM END D
J |
3.75"
9.5cm
J=JUNCTION BOX R=REFRIGERATION
LINES, .25" LIQUID,
.37" SUCTION
D=.50" I.D. DRAIN
FRONT OF UNIT
Typical Mechanical Access (Plan View)
All F5 Models
Delfield® |
For customer service, call (800) 733-8829, (800) 733-8821, Fax (989) 773-3210, www.delfield.com |
|
™ |
|
|
F5 & F15 Series Service and Installation Manual
Installation: Self-Contained F15 Series
Location
Units represented in this manual are for indoor use only. Be sure the location chosen has a floor strong enough to support the total weight of the cabinet and contents. A fully loaded model may weigh as much as 3,000 pounds! Reinforce the floor as necessary to provide for maximum loading.
For the most efficient refrigeration, be sure to provide good air circulation inside and out. Don’t pack the refrigerator so full that air cannot circulate. Be sure that the exterior of the unit has access to ample air. Avoid hot corners and locations near stoves and ovens.
Unit is designed to maintain 36°F (2°C) to 40°F (4°C) interior cabinet temperature at 65% or lower ambient relative humidity.
Leveling
A level cabinet looks better and will perform better because the drain pan will drain properly, the doors will line up with the frames properly and the cabinet will not be subject to undue strain. Units come standard with adjustable legs and bullet feet to make leveling easier. If your unit has casters, install in a stable condition with the front casters locked before operating.
Plumbing
Self-contained models are standard with a condensate evaporator. If your unit does not have a condensate evaprator, or the evaporator fails, the unit’s drain must have an outlet to an appropriate drainage area or container.
|
Moisture collecting from improper drainage can |
|
create a slippery surface on the floor and a hazard |
CAUTION |
to employees. It is the owner’s responsibility to |
provide a container or outlet for drainage. |
Electrical connection
Refer to the amperage data on pages 3-4, the serial tag, your local code or the National Electrical Code to be sure the unit is connected to the proper power source. A protected circuit of the correct voltage and amperage must be run for connection of the line cord, or permanent connection to the unit.
Self-contained units have an ON/OFF switch located directly behind the louvered panel covering the compressor section. Simply turn the switch to ON to begin operation.
The power switch should be turned to OFF and the unit disconnected from the power source DANGER whenever performing service or maintenance
functions.
Installation: Remote F15 Series
|
|
30.00" |
|
|
|
76.2cm |
|
|
|
1.75" |
|
|
|
4.4cm |
|
D |
|
3.75" |
|
1.00" |
9.5cm |
C |
|
|
2.5cm |
|
R
D
J |
3.75"
9.5cm
FRONT OF UNIT
J=JUNCTION BOX R=REFRIGERATION
LINES, .25" LIQUID,
.37" SUCTION
D=.50" I.D. DRAIN
Typical Mechanical Access (Plan View)
All F15 Models
|
For customer service, call (800) 733-8829, (800) 733-8821, Fax (989) 773-3210, www.delfield.com |