Interlogix NX-6V2 Installation Manual

0 (0)
Interlogix NX-6V2 Installation Manual

NX-6V2 Control Panel Installation Instructions

Introduction

This is the NX-6V2-Control Panel Installation Instructions.

Installations should only be done by trained professionals. Use this document to install the system with default settings that comply with UL requirements.

To install the keypad, other peripherals, and sensors, refer to the documentation for those devices.

Installation

There are four slots for board insertions inside the metal enclosure, two on the top and two on the bottom. These allow the PC board to be positioned vertically (Figure 1). When you slide the board between the grooves of the slots, make sure the terminal strip is toward the front opening (toward you) to allow for the wire connections.

Note: Install the metal enclosure with the door opening from the top to bottom.

Figure 1 Board Installation

NetworX keypad maximum wire run

Table 1 lists wire lengths for one keypad at the end of the wire. When connecting more than one keypad to the end of the wire, a higher gauge wire is required

Table 1: Maximum keypad wire run

Length in feet

Wire gauge for NX-6v2

Wire gauge for NX320-E

 

 

 

250

24

22

 

 

 

500

20

18

 

 

 

1000

18

16

 

 

 

1500

16

14

 

 

 

2000

14

12

 

 

 

Terminal descriptions

Table 2 describes the panel terminals

Table 2: NX-6V2 Terminals

Terminal

R1

R

T

T1

EARTH

AC

Bell + and

Bell -

KP DATA

KP COM

KP POS

COM

AUXPWR +

Description

House telephone ring (grey). Telephone ring (red). Telephone tip (green). House telephone tip (brown).

Earth ground. Connect to a cold water pipe or a 6 to 10 ft. driven rod.

AC input. Connect to a 16.5 V, 40 or 50 VA Class II UL approved transformer.

If used as a siren output (default), the speaker rating should be 15 watt at 8 or 16 ohm, or 30/40 watt at 4, 8, or 16 ohms. If voltage ouput is selected in location 37, this output becomes voltage output, 12 VDC, 1 Amp maximum load. Note: A 3.3 kohm resistor may be required across the bell terminals when a 12 VDC siren is used. If no resistor is used, you may experience voltage leakage into the siren, which will cause these devices to output a small signal.

Connect to the data terminal on the keypads and the expanders. Maximum number of devices is 16 keypads plus 3 other de vices. See Maximum Wire Run table.

Connect to the common terminal on the keypads and the expanders.

Connect to the POS terminal on the keypads and the expanders. Individually, this terminal is limited to 1 amp. Combined, this terminal and AUX PWR+ are limited to 2 amps total current.

Common negative wire of powered devices such as motion detectors and smoke detectors.

Connect positive wire of all powered devices except smoke detectors and keypads. Individually, this terminal is limited to 1 amp. Combined, this terminal and KP POS are limited to 2 amps total current.

P/N 466-2338 • REV B • January 2011

1

ZONE 7

Connect to one side of zone 6 loop. Connect the

 

other side to com terminal. Open or short causes

 

alarm. Only zone 6 can be used for a two-wire

 

smoke detector, connected with a 680 ohm EOL

 

resistor. Refer to the wiring diagram. Program

 

location 37, segment 6, option 1. Only zone 6 can be

 

a two-wire zone.

COM

Common (-) terminal for zones 5 and 6.

 

 

ZONE 6

Connect to one side of zone 5 loop. Connect the

 

other side to COM terminal. Open or short causes

 

alarm.

 

 

ZONES 1 to 5

Connect as described for zones 5 and 6.

 

 

AUXOUT 4

Smoke detector power 12 VDC (for those

(SMOKE +)

jurisdictions which allow the Priority zone to be used

with smoke detectors). Current limited to 250 mA

 

 

when output is positive and 250 uA when output is

 

negative. This output defaults to Smoke Power, but

 

can be reconfigured. Zone 7 may be used for a 2-

 

wire smoke detector using a 680 ohm EOL resistor.

AUXOUT 1 to

Connect negative lead of low current device [relay,

3

LED (install 1kohm resistor in series with LED), etc.]

 

Connect positive lead of device to COM. Current is

 

limited to 50 mA when output is negative, and 250

 

uA when output is positive.

 

 

NX-1192E 192-zone LCD keypad

NX-1208E 8-zone LED keypad

NX-1248E 48-zone LCD keypad

NX-1308E 8-zone LED door design keypad

NX-1316E 16-zone LED door design keypad

NX-1324E 24-zone LED door design keypad

NX-1448E 48-zone fixed language icon keypad

[1]These products have not been tested and approved by Underwriters Laboratories, In.

[2]These wireless devices are UL listed only for residential applications.

Note: The NX-6V2 control panel sends a trouble condition once each hour if it senses that no devices have been enrolled. This report shows expander trouble--device zero (0).

Control panel programming

Programming the control panel requires you to enter program mode, select the module to program, program a location, and then exit the location and program mode.

Module list

Table 3 shows the modules that are compatible with the NX6V2 system. Additional information and a catalog listing all system components is available from UTC Fire & Security Customer Support.

Table 3 Modules that can be added to the NX-6V2

Part

Description

 

 

NX-108E

8-zone LED keypad

 

 

NX-116E

16-zone LED keypad

 

 

NX-124E

24-zone LED keypad

 

 

NX-148E

Alphanumeric 48-zone LCD keypad

 

 

NX-148E-RF

Alphanumeric 48-zone LCD keypad with built-in 48-

 

zone wireless receiver

NX-200

Zone doubling kit (includes one hundred 3.74k and

 

one hundred 6.98k resistors)

 

 

NX-320E

Smart power supply and bus extender

 

 

NX-408E

8-zone wireless expansion module

 

(UL listed part #60-904)

 

 

NX-416E

16-zone wireless expansion module

 

(UL listed part #60-904)

 

 

NX-448E

48-zone wireless expansion module

 

(UL listed part #60-904)

 

 

NX-508E

Eight-output module

 

 

NX-534E

Two-way listen-in module

 

 

NX-540E

Operator telephone interface module

 

 

NX-548E

48-zone wireless receiver

 

 

NX-591E-

Cell interface

GSM

 

Enter program mode

To enter program mode, do the following:

1.Press 8. The five function LEDs (Stay, Chime, Exit, Bypass, and Cancel) begin flashing.

2.Enter the go to program code (default is 9, 7, 1, 3). If the go to program code entry is valid, the Service LED flashes, and the five function LEDs illuminate. You are now in program mode and can select the module to program.

Select the module to program

Since all modules connected to the NX-6V2 are programmed through the keypad, the module you are programming should be the first entry. To select the module to program, enter 0, #. The 0 is the module number of the control, and # is the entry key. You can find other module entry numbers in the module documentation.

Program a location

Once you enter the module number, the Armed LED illuminates, indicating the keypad is waiting for you to enter a programming location. To program a location, do the following:

1.To access any location, enter the desired programming location, followed by #. If the location is a valid location, the Armed LED extinguishes, the Ready LED illuminates, and the binary data for the first segment of the location is shown by the Zone LEDs.

2.While entering new data, the Ready LED begins flashing to indicate a data change in process.

2

NX-6V2 Control Panel Installation Instructions

3.Press to store the newly entered data. The keypad advances to the next segment and displays its data. Repeat this procedure until the last segment is reached.

4.To move to another location after exiting a location (Armed LED illuminated):

Press the Police key for the next sequential location.

Press the Fire key for the previous location.

Press the Medical key for the same location.

5.To review the data in a specific location, repeat the above procedure, pressing but with no numeric data entry. Each time you press , the programming data of the next segment displays.

Exit a location

To exit the current programming location, do the following:

1.Press the key. The Ready LED goes off and the Armed LED goes on. You must press the key to save the data.

2.To exit before the last segment, press # (Armed LED illuminates).

You are now ready to enter another programming location. If you attempt to program an invalid entry for a particular segment, the keypad beeps three times indicating an error and remains in that segment awaiting a valid entry.

to the data terminal into the NX-6V2 memory. This allows the modules to be supervised by the control panel.

To enroll the modules, do the following:

1.Enter program mode and program the desired settings for each module.

2.When you exit program mode, the NX-6V2 automatically enrolls the devices. The enrolling process takes about 12 seconds, during which time the Service LED illuminates. If a speaker is attached to the NX-6V2, it clicks at this time. If a siren or bell is attached to the NX-6V2, it sounds for about one second. If the module is not detected, the Service LED illuminates.

Note: User codes are not accepted during the enrolling process.

Quick start programming locations

For most routine installations, the quick start locations allow you to enable a majority of the options available with the NX6V2 (when communicating in Contact ID or SIA formats). The quick start locations include:

Location 0 - Phone 1

Location 1 - Phone 1 account code

Location 2 - Phone 1 communicator format

Location 3 - Phone 1 dial attempts/backup control

Exit program mode

To exit program mode, do the following:

1.When you have completed all programming, press Exit to leave the selected module.

2.If there is another module to be programmed, select it by entering its address, followed by #. The procedure for programming these devices is the same as for the control panel, except the locations are for the module selected.

3.If no additional modules are to be programmed, press Exit again to leave program mode.

Location 0 - Phone 1

Location 0 has 20 segments of numerical data. Use this location to program phone 1. The default for each segment is 14.

To program a delay of four seconds, enter 13 in the appropriate segment.

To program tone dialing, enter 15 in the segment where tone dialing begins.

If the entire number is tone dialing, enter 15 in the first segment.

Enter 11 for a *, and 12 for a #.

Loading factory defaults

To load factory defaults, enter program mode, enter the device address and number and then enter 9, 1, 0, #. The keypad beeps three times indicating that loading is in progress. The process takes about six seconds. You cannot exit the location until loading is completed.

Enrolling modules and keypads

The NX-6V2 automatically finds and stores all keypads, zone expanders, wireless receivers, and other modules connected

Location 2 - Phone 1 communicator format

Location 2 has one segment of numerical data. Use this location to program the communicator format used to transmit to the receiver connected to phone 1. Refer to your central station receiver documentation to determine which format is compatible. Table 4 describes the formats for this location. If you need a format other than those listed, review the override options described in Loc to build the appropriate format. Program a 15 to create a special format (in addition to the entries in Location 18). The default is 0. If this location contains

NX-6V2 Control Panel Installation Instructions

3

Loading...
+ 7 hidden pages