Interlogix NX-8V2 Installation Manual

5 (1)

NX-8V2 Control Panel Installation Instructions

Introduction

This is the NX-8V2-Control Panel Installation Instructions.

Installations should only be done by trained professionals. Use this document to install the system with default settings that comply with UL requirements.

To install the keypad, other peripherals, and sensors, refer to the documentation for those devices.

Installation

There are four slots for board insertions inside the metal enclosure, two on the top and two on the bottom. These allow the PC board to be positioned vertically (Figure 1 below). When you slide the board between the grooves of the slots, make sure the terminal strip is toward the front opening (toward you) to allow for the wire connections.

Note: Install the metal enclosure with the door opening from the top to bottom.

Figure 1: Board installation

NetworX keypad maximum wire run

Table 1 below lists wire lengths for one keypad at the end of the wire. When connecting more than one keypad to the end of the wire, a higher gauge wire is required

Table 1: Maximum keypad wire run

Length in feet

Wire gauge for NX-

Wire gauge for NX320-

 

8V2

E

 

 

 

250

24

22

 

 

 

500

20

18

 

 

 

1000

18

16

 

 

 

1500

16

14

 

 

 

2500

14

12

 

 

 

Terminal descriptions

Table 2 below describes the panel terminals.

Table 2: NX-8V2 terminals

Terminal

Description

R1

House telephone ring (grey)..

 

 

R

Telephone ring (red).

 

 

T

Telephone tip (green).

 

 

T1

House telephone tip (brown).

 

 

AC

AC input. Connect to a 16.5 V 40 or 50 VA Class ll UL

 

approved transformer.

 

 

EARTH

Earth ground. Connect to a cold water pipe or a 6 to 10 ft.

 

driven rod.

 

 

Bell + and

If used as a siren output (default), the speaker rating

Bell -

should be 15 watt at 8 or 16 ohm, or 30/40 watt at 4, 8, or

 

16 ohms. If voltage ouput is selected in location 37, this

 

output becomes voltage output, 12 VDC, 1 Amp maximum

 

load. Note: A 3.3 kohm resistor may be required across

 

the bell terminals when a 12 VDC siren is used. If no

 

resistor is used, you may experience voltage leakage into

 

the siren, which will cause these devices to output a small

 

signal.

 

 

KP Data

Connect to the data terminal on the keypads and the

 

expanders. Maximum number of devices (keypads plus

 

expanders) is 32. See Maximum Wire Run table.

 

 

KP COM

Connect to the common terminal on the keypads and the

 

expanders.

 

 

P/N 466-2339 • REV B • 02MAR11

Terminal

Description

KP POS

Connect to the POS terminal on the keypads and the

 

expanders. Individually, this terminal is limited to 1 amp.

 

Combined, this terminal and AUX PWR+ are limited to 2

 

amps total current.

 

 

SMOKE+

Smoke detector power 12 VDC, 1.5 amps maximum (for

 

those jurisdictions which allow the Priority zone to be used

 

with smoke detectors).

 

 

COM

Common negative wire of powered devices such as

 

motion detectors and smoke detectors.

 

 

AUX

Connect positive wire of all powered devices except

PWR +

smoke detectors and keypads. Individually, this terminal is

 

limited to 1 amp. Combined, this terminal and KP POS are

 

limited to 2 amps total current.

 

 

ZONE8

Connect to one side of zone 8 loop. Connect the other

 

side to com terminal. Open or short causes alarm. Only

 

zone 8 may be used for a two-wire smoke detector using

 

a 680 ohm EOL resistor. Refer to the wiring diagram.

 

Program location 37, segment 6, option 1.

 

 

COM

Common (-) terminal for zones 7 and 8.

 

 

ZONE7

Connect to one side of zone 7 loop. Connect the other

 

side to COM terminal. Open or short causes alarm.

 

 

ZONES 6

Connect as described for zones 7 and 8. Only zone 8 can

to 1

be a two-wire zone. Refer to the wiring diagram for

 

examples.

 

 

AUX1 to

Connect negative lead of low current device [relay, LED

AUX4

(install 1kohm resistor in series with LED), etc.] Connect

 

positive lead of device to COM. Current is limited to 50

 

mA when output is negative, and 250 uA when output is

 

positive.

 

 

Module list

Table 3 below shows the modules that are compatible with the NX-8V2 system. Additional information and a catalog listing all system components is available from Customer Support

Table 3: Modules that can be added to the NX-8V2

Terminal

Description

 

 

NX-108E

8-zone LED keypad

 

 

NX-116E

16-zone LED keypad

 

 

NX-124E

24-zone LED keypad

 

 

NX-148E

Alphanumeric 48-zone LCD keypad

 

 

NX-148E-

Alphanumeric 48-zone LCD keypad with built-in 48-zone

RFb

wireless receiver

NX-200 a

Zone doubling kit (includes one hundred 3.74k and one

 

hundred 6.98k resistors)

 

 

NX-320E

Smart power supply and bus extender

 

 

NX-408E

8-zone wireless expansion module (UL listed part #60-

 

904)

 

 

NX-416E

16-zone wireless expansion module (UL listed part #60-

 

904)

 

 

2

 

Terminal

Description

NX-448E

48-zone wireless expansion module (UL listed part #60-

 

904)

 

 

NX-508E

Eight-output module

 

 

NX-534E

Two-way listen-in module

 

Operator telephone interface module

NX-540E

a

 

 

 

NX-548Eb

48-zone wireless receiver

NX-591E-

Cell interface

GSM a

 

NX-

192-zone LCD keypad

1192E

 

 

 

NX-

8-zone LED keypad

1208E

 

 

 

NX-

48-zone LCD keypad

1248E

 

 

 

NX-

8-zone LED door design keypad

1308E

 

 

 

NX-

16-zone LED door design keypad

1316E

 

 

 

NX-

24-zone LED door design keypad

1324E

 

 

 

NX-

48-zone fixed language icon keypad

1448E

 

 

 

a> These products have not been tested and approved by Underwriters Laboratories, In.

b> These wireless devices are UL listed only for residential applications.

Note: The NX-8V2 control panel sends a trouble condition once each hour if it senses that no devices have been enrolled. This report shows expander trouble--device zero (0).

Control panel programming

Programming the control panel requires you to enter program mode, select the module to program, program a location, and then exit the location and program mode.

Enter program mode

To enter program mode, do the following:

1.Press 8. The five function LEDs (Stay, Chime, Exit, Bypass, and Cancel) begin flashing.

2.Enter the go to program code (default is 9, 7, 1, 3). If the go to program code entry is valid, the Service LED flashes, and the five function LEDs illuminate. You are now in program mode and can select the module to program.

NX-8V2 Control Panel Installation Instructions

Select the module to program

Since all modules connected to the NX-8V2 are programmed through the keypad, the module you are programming should be the first entry. To select the module to program, enter 0, #. The 0 is the module number of the control, and # is the entry key. You can find other module entry numbers in the module documentation.

Program a location

Once you enter the module number, the Armed LED illuminates, indicating the keypad is waiting for you to enter a programming location. To program a location, do the following:

1.To access any location, enter the desired programming location, followed by #. If the location is a valid location, the Armed LED extinguishes, the Ready LED illuminates, and the binary data for the first segment of the location is shown by the Zone LEDs.

2.While entering new data, the Ready LED begins flashing to indicate a data change in process.

3.Press to store the newly entered data. The keypad advances to the next segment and displays its data. Repeat this procedure until the last segment is reached.

4.To move to another location after exiting a location (Armed LED illuminated):

Press the Police key for the next sequential location.

Press the Fire key for the previous location.

Press the Medical key for the same location.

5.To review the data in a specific location, repeat the above procedure, pressing but with no numeric data entry. Each time you press , the programming data of the next segment displays.

Exit a location

To exit the current programming location, do the following:

1.Press the key. The Ready LED goes off and the Armed LED goes on. You must press the key to save the data.

2.To exit before the last segment, press # (Armed LED illuminates).

You are now ready to enter another programming location. If you attempt to program an invalid entry for a particular segment, the keypad beeps three times indicating an error and remains in that segment awaiting a valid entry.

Exit program mode

To exit program mode, do the following:

1.When you have completed all programming, press Exit to leave the selected module.

2.If there is another module to be programmed, select it by entering its address, followed by #. The procedure for programming these devices is the same as for the control panel, except the locations are for the module selected.

3.If no additional modules are to be programmed, press Exit again to leave program mode.

Loading factory defaults

To load factory defaults, enter program mode, enter the device address and number and then enter 9, 1, 0, #. The keypad beeps three times indicating that loading is in progress. The process takes about six seconds. You cannot exit the location until loading is completed.

Enrolling modules and keypads

The NX-8V2 automatically finds and stores all keypads, zone expanders, wireless receivers, and other modules connected to the data terminal into the NX-8V2 memory. This allows the modules to be supervised by the control panel.

To enroll the modules, do the following:

1.Enter program mode and program the desired settings for each module.

2.When you exit program mode, the NX-8V2 automatically enrolls the devices. The enrolling process takes about 12 seconds, during which time the Service LED illuminates. If a speaker is attached to the NX-8V2, it clicks at this time. If a siren or bell is attached to the NX-8V2, it sounds for about one second. If the module is not detected, the Service LED illuminates.

Note: User codes are not accepted during the enrolling process.

Quick start programming locations

For most routine installations, the quick start locations allow you to enable a majority of the options available with the NX8V2 (when communicating in Contact ID or SIA formats). The quick start locations include:

Location 0 - Phone 1

Location 1 - Phone 1 account code

Location 2 - Phone 1 communicator format

Location 3 - Phone 1 dial attempts/backup control

NX-8V2 Control Panel Installation Instructions

3

Interlogix NX-8V2 Installation Manual

Location 0 - Phone 1

Location 0 has 20 segments of numerical data. Use this location to program phone 1. The default for each segment is 14.

To program a delay of four seconds, enter 13 in the appropriate segment.

To program tone dialing, enter 15 in the segment where tone dialing begins.

If the entire number is tone dialing, enter 15 in the first segment.

Enter 11 for a *, and 12 for a #.

Caution: A call-waiting cancel on a non call-waiting line prevents successful connection to the central station.

Location 1 - Phone 1 account code

Location 1 has six segments of numerical data. Use this location to program the account code sent when phone 1 is dialed. The default for each segment is 10. Program a 10 in the segment immediately after the last digit of the account code. If the account code is six digits long, program all six segments.

Location 2 - Phone 1 communicator format

Location 2 has one segment of numerical data. Use this location to program the communicator format used to transmit to the receiver connected to phone 1. Refer to your central station receiver documentation to determine which format is compatible. Table 4 below describes the formats for this location. If you need a format other than those listed, review the override options described in “Location 18 - Custom communicator format” on page 5 to build the appropriate format. Program a 15 to create a special format (in addition to the entries in Location 18). The default is 0. If this location contains a 0, the built-in communicator is disabled and the NX8V2 functions as a local-only control.

Table 4: Communicator formats

Data

Format

Description

 

 

 

0

Local

Communicator is disabled

 

 

 

1

Universal 4+2

Two-digit event code 1800 Hz transmit

 

 

2300 Hz handshake double round parity

 

 

40 pps a

2

3+1 fast (or 4+1)

One-digit event code 1900 Hz transmit

 

 

1400 Hz handshake double round parity

 

 

20 pps

 

 

 

3

Reserved

Reserved

 

 

 

4

Pager

Two-digit event code DTMF

 

 

transmission

 

 

 

Data Format

53/1 or 4/1 slow

63/1 or 4/1 slow

73/1 or 4/1 fast

83/1 or 4/1 fast

93/1 or 4/1 fast with parity

103/1 or 4/1 fast with parity

114+2 express

124+2 fast

13Ademco contact ID

14SIA

15Custom format

163/1 or 4/1 slow

173/1 or 4/1 slow

183/1 or 4/1 fast

193/1 or 4/1 fast

203/1 or 4/1 fast with parity

213/1 or 4/1 fast with parity

22SIA

a> Pulses per second.

Description

1800 Hz transmit 2300 Hz handshake double round parity 20 pps hex capability

1800 Hz transmit 1400 Hz handshake double round parity 20 pps hex capability

1800 Hz transmit 2300 Hz handshake double round parity 40 pps hex capability

1800 Hz transmit 1400 Hz handshake double round parity 40 pps hex capability

1800 Hz transmit 2300 Hz handshake single round parity 40 pps hex capability

1800 Hz transmit 1400 Hz handshake single round parity 40 pps hex capability

Two-digit event code DTMF transmission

Two-digit event code 1900 Hz transmit 1400 Hz handshake double round parity 20 pps

DTMF

Frequency shift keys

See “Location 18 - Custom communicator format” on page 5

Same as 5, but sends the alarm event code rather than the zone number

Same as 6, but sends the alarm event code rather than the zone number

Same as 7, but sends the alarm event code rather than the zone number

Same as 8, but sends the alarm event code rather than the zone number

Same as 9, but sends the alarm event code rather than the zone number

Same as 10, but sends the alarm event code rather than the zone number

SIA with area modifiers

Location 3 - Phone 1 dial attempts/backup control

Location 3 has two segments of numerical data.

Segment 1 - Phone 1 dial attempts

Program the number of dial attempts (1 to 15) the communicator makes to phone 1 before ending the notification process. The default is 8, which means that the communicator makes eight attempts to the first number.

4

NX-8V2 Control Panel Installation Instructions

Loading...
+ 7 hidden pages