Honeywell C7068, LF20, T7411A, LF20-C Manual

0 (0)

T7411A / LF20 / LF20-C / C7068

DUCT TEMPERATURE SENSORS

PRODUCT DATA

T7411A

C7068

LF20-C

LF20

 

 

GENERAL

The T7411A/LF20/LF20-C/C7068 Duct Temperature Sensors are used in ventilating and air conditioning systems to measure discharge, return, or outside air temperature. They are designed for duct mounting. The T7411A is available with two different probe lengths.

These sensors are used in the following control systems:

Excel 5000

MicroniK 200

MicroniK 100

Excel Classic

Excel Plus

High Performance Excel Plus

Excel EMC

or other systems using PT100, PT1000, or NTC 20kΩ temperature sensing elements.

Further, the C7068 is also suitable for installation in fancoil units or at air outlets.

® U.S. Registered Trademark

Copyright © 2007 Honeywell Inc. • All rights reserved

FEATURES

PT100, PT1000, or NTC20ktemperature sensing element

Wide sensing range

High accuracy

Stainless steel probe

SPECIFICATION

Nominal value

100 Ω at 0 °C

PT100

PT1000

1000 Ω at 0 °C

NTC20kΩ

20 kΩ at 25 °C

Accuracy

 

 

PT100 / PT1000

IEC751 Class B

NTC20kΩ

0.3 K +0.5% • |t| (t in °C)

0.3 K at 25 °C

Sensitivity

 

 

PT100

≈ 0.385 Ω / K

PT1000

≈ 3.85 Ω / K

NTC20kΩ

≈ -934.5 Ω / K at 25 °C

 

(non-linear)

Response time (at air velocity of 5 m/s [16.4 ft/s])

LF20, LF20-C

τ0.5

≈ 42 s

T7411

τ0.5

≈ 45 s

C7068

τ0.5

≈ 4 min (at 1 m/s [3.3 ft/s])

Electrical connection

 

 

T7411A/LF20

terminals for 2 x 1.5 mm² cable

LF20-C

5 m cable, 2-core,

 

seawater-resistant,

 

conduit M16x1,5

C7068

1.5-m cable, 2-core

C7068-5m

5-m cable, 2-core

Ambient Limits

 

 

Storage temperature

-35...+70 °C (-31…+158 °F)

Humidity (T7411, LF20) 5…95% rh, non-condensing

Safety (terminal box)

 

 

Protection standard

 

 

T7411A

IP54

 

LF20

IP30

 

LF20-C

IP65

 

C7068

IP54

 

Flame retardant

V1 as per UL94

 

Plastic (PC)

Dimensions

See Fig. 1 on page 2

EN0B-0361GE51 R0907

Honeywell C7068, LF20, T7411A, LF20-C Manual

T7411A / LF20 / LF20-C / C7068 DUCT TEMPERATURE SENSORS

Models

 

OS number

 

sensor type

 

sensing range

 

length in mm (inches)

 

 

 

 

L1

 

T1

 

 

 

 

 

 

 

 

 

LF20

 

NTC20kΩ

 

-40...+80 °C

338 (13.30)

305

(12.00)

 

LF20-C

 

NTC20kΩ

 

-40...+80 °C

305

(12.00)

--

 

 

T7411A1001

 

PT1000

 

-40...+80 °C

185

(7.28)

152

(5.98)

 

T7411A1019

 

PT1000

 

-40...+80 °C

338

(13.30)

305

(12.00)

 

T7411A1043

 

PT100

 

-40...+80 °C

185

(7.28)

152

(5.98)

 

C7068A1007

 

NTC20kΩ

 

0...+70 °C

 

cable length: 1.5 m

 

C7068A1007-5m

 

NTC20kΩ

 

0...+70 °C

 

cable length: 5 m

DIMENSIONS OF T7411A / LF20

47 (1.85)

L1

23 (0.91)

max. 275 mm

(10.8 in.)

 

 

LF20-C

0

6 (0.23)

3

 

6

 

4

19.5

(0.75)

8

 

 

 

T7411A, LF20

55 (2.17)

 

 

 

 

50 (1.97)

L1

 

33 (1.3)

 

6 (0.23)

65

(2.55)

 

 

 

 

 

 

 

 

 

19.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(0.75)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

case hole diameter

 

 

 

 

7 (0.28)

 

 

 

 

 

 

 

 

allows Pg9 cable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 1. Dimensions of T7411A / LF20 and LF20-C in mm (inches)

EN0B-0361GE51 R0907

2

Loading...
+ 2 hidden pages