Gaggenau |
|
Installation instructions .......................... |
2 |
Notice de montage ............................... |
21 |
Instrucciones de instalación ................ |
40 |
AI 442 720 AI 442 760
Hood
Hotte aspirante
Campana extractora
9WARNING
This indicates that death or serious injuries may occur as a result of non-observance of this warning.
This indicates that minor or moderate injuries may occur as a result of non-observance of this warning.
2
READ AND SAVE THESE INSTRUCTIONS
INSTALLER: LEAVE THESE INSTRUCTIONS WITH THE APPLIANCE AFTER INSTALLATION IS COMPLETE.
IMPORTANT: SAVE THESE INSTRUCTIONS FOR THE LOCAL ELECTRICAL INSPECTOR'S USE.
If the information in this manual is not followed exactly, fire or shock may result causing property damage or personal injury.
Do not repair, replace or remove any part of the appliance unless specifically recommended in the manuals. Improper installation, service or maintenance can cause injury or property damage. Refer to this manual for guidance. All other servicing should be done by an authorized servicer.
WARNING – TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
‒Installation work and electrical wiring must be done by qualified person(s) in accordance with all applicable codes and standards, including firerated construction.
‒Sufficient air is needed for proper combustion and exhausting of gases through the flue (chimney) of fuel burning equipment to prevent back drafting. Follow the heating equipment manufacturer’s guideline and safety standards such as those published by the National Fire Protection Association (NFPA), and the American Society for Heating, Refrigeration and Air Conditioning Engineers (ASHRAE), and the local code authorities.
‒When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities.
‒Ducted fans must always be vented to the outdoors.
The applicable regulations of the energy supply companies and the regional construction regulations must be observed when installing the hood.
Grease deposits in the grease filter can catch fire. Never work with a naked flame near the appliance (e.g. flambéing). Install the unit near a heat-producing appliance for solid fuels (e.g. wood or coal) only if there is a closed, non-detachable cover. There must be no flying sparks.
Operating several gas burners at the same time gives rise to a great deal of heat. The ventilation appliance may become damaged or catch fire. The ventilation appliance must only be combined with gas burners that do not exceed the maximum total output of 61,000 BTU/ hr (18 kW). If 41,000 BTU/hr (12 kW) is exceeded, the local regulations concerning room ventilation, room size, and combination with ventilation devices in exhaust and recirculating operation must be followed.
To reduce risk of fire and to properly exhaust air, be sure to duct air outside. Do not vent exhaust air into spaces within walls, ceilings, attics, crawl spaces or garages.
To reduce the risk of fire, use only metal ductwork.
3
9 IMPORTANT SAFETY INSTRUCTIONS
READ AND SAVE THESE INSTRUCTIONS
When the hood is operated in exhaust-air mode simultaneously with a different burner which also makes use of the same chimney (such as gas, oil or coal-fired heaters, continuous-flow heaters, hot-water boilers) care must be taken to ensure that there is an adequate supply of fresh air which will be needed by the burner for combustion.
Safe operation is possible provided that the under pressure in the room where the burner is installed does not exceed 4 Pa (0.04 mbar).
This can be achieved if combustion air can flow through non-lockable openings, e.g. in doors, windows and via the air-intake/exhaust-air wall box or by other technical measures, such as reciprocal interlocking, etc.
Avoid carbon monoxide poisoning – Provide adequate air intake so combustion gases are not drawn back into the room.
An air-intake/exhaust-air wall box by itself is no guarantee that the limiting value will not be exceeded.
For general ventilating use only. Do not use to exhaust hazardous or explosive materials and vapors.
Risk of damage from condensation back flow. Install exhaust vent at a slight downward slope away from the appliance (1° slope).
The appliance may fall from the wall if it is not attached properly. All fastening components must be fixed firmly and securely in place.
UL 507 - Electric Fans
CAN/CSA C22.2 No. 113 - Fans and Ventilators
This appliance must be grounded. In the event of an electrical short circuit, grounding reduces the risk of electric shock by providing an escape wire for the electric current.
This appliance is equipped with a cord having a grounding wire with a grounding plug. The plug must be plugged into an outlet that is properly installed and grounded.
Improper grounding can result in a risk of electric shock. Consult a qualified electrician if the grounding instructions are not completely understood, or if doubt exists as to whether the appliance is properly grounded. Do not use an extension cord. If the power supply cord is too short, have a qualified electrician install an outlet near the appliance.
4
9 IMPORTANT SAFETY INSTRUCTIONS
READ AND SAVE THESE INSTRUCTIONS
Before you plug in an electrical cord or turn on power supply, make sure all controls are in the OFF position.
For appliances equipped with a cord and plug, do not cut or remove the ground prong. It must be plugged into a matching grounding type receptacle to avoid electrical shock. If there is any doubt as to whether the wall receptacle is properly grounded, the customer should have it checked by a qualified electrician.
To reduce the risk of fire or electric shock, do not use this fan with any solid-state speed control device.
‒Use this unit only in the manner intended by the manufacturer. If you have questions, contact the manufacturer.
‒Before servicing or cleaning unit, switch power off at service panel and lock the service disconnecting means to prevent power from being switched on accidentally.
When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel.
Parts inside the appliance can have sharp edges. The connection cable can be damaged. Do not bend or pinch connection cables during installation.
State of California Proposition 65
Warnings
This product contains chemicals known to the State of California to cause cancer, birth defects or other reproductive harm.
5
Installation preparation |
|
General notes |
Ensure that there are no electric wires, gas or water pipes in the area where holes are to be made.
The ceiling must be flat, horizontal and adequately load-bearing.
The depth of the bore holes must be the same length as the screws. The wall plugs must have a secure grip.
The enclosed screws and wall plugs are suitable for solid brickwork. Suitable fasteners must be used for other structures (e.g. plasterboard, porous concrete, poroton bricks).
The max. weight of the extractor hood is 198 lbs (90 kg).
9WARNING
Risk of poisoning from flue gases that are drawn back in. The exhaust air must not be conveyed into a functioning smoke or exhaust gas flue or into a shaft that is used to ventilate installation rooms that contain heating appliances. If the exhaust air is to be conveyed into a nonfunctioning smoke or exhaust gas flue, you must obtain the consent of the heating engineer responsible.
If the ventilation is intended to pass through a smoke or exhaust chimney that is not in operation, the responsible area heating inspector must give approval.
If the ventilation passes through an external wall, use a telescope wall sleeve.
The appliance achieves its optimum performance with a short, straight exhaust air pipe and as large a pipe diameter as possible.
As a result of long rough exhaust air pipes, many pipe bends or pipe diameters that are smaller than 6" (150 mm), the optimum extraction performance is not achieved and fan noise is increased.
The pipes or hoses for laying the exhaust air line must be made of non-combustible material.
Use sealing strip for deviating pipe diameters.
An inner diameter of 6" (150 mm), but at least 4¾" (120 mm), is recommended.
6
9WARNING
Parts inside the appliance can have sharp edges. The connection cable can be damaged. Do not bend or pinch connection cables during installation.
The required connection information is on the appliance's identification plate.
This appliance meets EC radio interference suppression requirements.
The grounded socket should be connected via its own circuit.
If the grounded socket is no longer accessible after installing the appliance, an all-pole isolating switch (e.g. circuit breaker, fuses, and contactors) with at least a 3 mm contact gap must be included in the installation.
Measuring tape
Pencil
Torx screwdriver TX20
Drill with the following bits: 5/16" (8 mm)
Spanner, 7 mm
Spirit-level
Aluminum tape (DO NOT use insulating tape)
Exhaust channel (configuration depends on the installation situation)
Additional sheet metal screws (if necessary for installation of the exhaust air duct)
7
$'
$$
$'
$5
8
è¼ʓʘ |
èè¼ʓʘ |
|
|
ç¼ʓʘ |
èç¼ʓʘ |
|
|
ç¼ʚ
ê |
|
|
è¼ʚ |
|
|
èʌ¼ʓʘ ë
èʊ¼ʓʘ |
ç¼ʓʘ |
ë |
|
|
|
|
|
é |
ê |
|
|
|
|
|
|
|
|
è¼ʓʘ èè¼ʓʘ
ç¼ʓʘ |
èç¼ʓʘ |
|
|
||
|
||
|
ç¼ʚ
ê |
è¼ʚ |
|
|
||
|
||
|
èʌ¼ʓʘ ë
èʊ¼ʓʘ |
ç¼ʓʘ |
ë |
|
|
|
||
|
|||
|
|
||
ê |
|
é |
|
|
|
||
|
|
|
PP
PP
9
9WARNING
Grease deposits in the grease filter may catch fire. The specified safety distances must be observed in order to prevent an accumulation of heat. Observe the specifications for your cooking appliance. If gas and electric cooktops are operated together, the largest specified distance applies.
Only one side of the appliance may be installed directly next to a high-sided unit or a wall. The distance between the appliance and wall or highsided unit must be at least 2" (50 mm).
The minimum distance between the supporting surface for the cooking equipment on the hob and the lowest part of the range hood must be not less than 30 "
(760 mm) from electric cookers and 30 " (760 mm) from gas or mixed cookers.
If the instructions for installation for the gas hob specify a greater distance, this must be adhered to.
DERYH JDV
VXU JD]
VREUH JDV
DERYH HOHFWULF VXU pOHFWULTXH VREUH HOpFWULFR
!
!
10
Notes |
‒Select the mounting holes in such a way that a maximum clearance is achieved between the screws. The purpose of this is to ensure stability.
‒Leave open at least one mounting hole between the screws.
11
12
ʎ¼ʓʘ è¼ʚ |
|
PP |
1For recirculation mode units only: Fit filters to both sides of the AA 442 810 air recirculation module. Slide the air recirculation module into the support frame from below and hook it in place. Secure it with two screws.
13
2 For combination with internal remote fan unit |
Connect the mains cable and control cable to the |
||||||||||
AR 400 743 only: Unscrew the cover plate from the |
control module. |
||||||||||
ventilation hood: Loosen the four screws, remove |
|
|
|
|
|
|
|||||
|
|
|
|
|
|
||||||
the cover plate and screw the four screws in again. |
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Slide the remote fan unit into the ventilation hood from above. Use four screws to secure it in place.
3For a combination with external remote fan unit AR4.. only: Use the network cable to connect the external remote fan unit and the ventilation hood’s control module. The plug must snap into place. Connect the mains cable to the control unit.
14
4Slide the ventilation hood up into the support frame from below and hook it into the two angle brackets
(a).
D |
D |
‒With operation in extraction air mode , a backpressure flap should be installed. If no backpressure flap is included with the appliance, it can be ordered from a specialist retailer.
‒If the exhaust air is conveyed through the outer wall, a telescopic wall box should be used.
‒If an aluminum duct is used, smooth the connection area beforehand.
1Recirculation mode units with internal remote fan unit AR 400 743: Attach the exhaust air pipe directly to the fan motor's air pipe connector (A).
% |
$ |
$5 |
15
2Extraction mode units with internal remote fan unit AR 400 743: Attach the exhaust air pipe directly to the fan motor's air pipe connector (A).
% |
$ |
$5 |
‒Unscrew the connecting pieces from the cover plate in the ventilation hood.
‒Secure the exhaust air pipe to the connecting piece (A).
‒Screw the connecting piece to the cover plate in the ventilation hood.
$5 |
% |
$ |
4Connect it to the air extractor opening (B).
2If a fixed connection is required, please follow the instructions in the Electrical Connection section.
16
Attaching flue duct |
Models with air recirculation mode |
9 WARNING
Components inside the appliance may have sharp edges. Wear protective gloves.
17 |
9WARNING
Work must only be carried out on the additional switching output by a qualified electrician in accordance with the country-specific requirements and standards.
The appliance has an additional switching output X16 (potential-free contact) that can be used to connect other appliances, such as a ventilation system that is available at the installation site. The contact is closed when the blower is switched on, and is opened when the blower is switched off.
The appliance has a connection (X17) for a window contact switch. The window contact switch can be flush mounted or surface mounted. You will receive the
18