Data Sheet
Programmable controller, 6 relays
Type MCX061V
Electronic controller suitable for all HVAC/R software application needs.
MCX061V is a standard MCX electronic controller with one integrated electronic expansion valve driver. It is available in the version with graphic LCD display and 110 / 230 V AC or 24 V AC power supply. It holds all the typical functionalities of MCX controllers in the compact size of 8 DIN modules:
• Programmability
• Connection to the CANbus local network
• Modbus RS485 serial communication interface
It is moreover •tted with a slot for memory card SD / MMC and Ethernet connection. The memory card assures SW download and datalogging function; the Ethernet port allows the SW download, monitoring with web pages, datalogging and the alarms warning.
Features:
• 7 analog and 8 digital inputs
• 3 analog and 6 digital outputs
• Power supply 24 V AC and 110 V / 230 V AC
• Drives bipolar and unipolar electronic expansion valves
• SD / MMC card slot for easy software upload and datalogging
• Remote access to data through CANbus connection for additional display and keyboard
• RTC clock for managing weekly time programs and data logging information
• Ethernet / WebServer option
• Modbus RS485 opto-insulated serial interface
• Available with graphic LCD display for showing the desired information
• Dimensions 8 DIN modules
AI166386420921en-000901
Programmable controller, 6 relays, type MCX061V
Portfolio overview
Table 1: Portfolio overview
MCX family |
MCX06C |
MCX06D |
MCX061V |
MCX08M2 |
MCX152V |
MCX15B2 |
MCX20B2 |
|
Product image |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Power supply |
24 V |
24 V |
24 V or |
24 V or |
24 V or |
24/110/230 V |
24/110/230 V |
|
110/230 V |
110/230 V |
110/230 V |
||||||
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
Built-in display (optional) |
LED |
LCD |
LCD |
LCD |
LCD |
LCD |
LCD |
|
|
|
|
|
|
|
|
|
|
Analog Inputs |
4 |
4 |
7 |
8 |
14 |
10 |
16 |
|
|
|
|
|
|
|
|
|
|
Digital Inputs |
6 |
8 |
8 |
8 |
18 |
22 |
22 |
|
|
|
|
|
|
|
|
|
|
Analog Outputs |
2 |
3 |
3 |
4 |
6 |
6 |
6 |
|
|
|
|
|
|
|
|
|
|
Digital Outputs |
6 |
6 |
6 |
8 |
15 |
15 |
20 |
|
|
|
|
|
|
|
|
|
|
EXV driver embedded |
|
|
1 |
|
2 |
|
|
|
|
|
|
|
|
|
|
|
|
RS485 |
1 |
1 |
1 |
1 |
2 |
1 |
2 |
|
|
|
|
|
|
|
|
|
|
CANbus |
• |
• |
• |
• |
• |
• |
• |
|
|
|
|
|
|
|
|
|
|
Ethernet / Web server |
|
|
optional |
|
optional |
• |
• |
|
|
|
|
|
|
|
|
|
|
USB/Memory Card |
|
|
• |
|
• |
• |
• |
|
|
|
|
|
|
|
|
|
|
Dimensions |
|
|
|
|
|
|
|
|
(1 DIN module = 17,5 |
33 x 75 mm |
4 DIN |
8 DIN |
8 DIN |
16 DIN |
16 DIN |
16 DIN |
|
mm) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
© Danfoss | Climate Solutions | 2021.03 |
AI166386420921en-000901 | 2 |
Programmable controller, 6 relays, type MCX061V
Product speci€cation
General features
Table 2: General features
Features |
Description |
|
Power supply |
85 – 265 V AC, 50/60 Hz. Maximum power consumption: 18 W, 27 V A |
|
|
Insulation between power supply and the extra-low voltage: reinforced |
|
|
24 V AC ± 15% 50/60 Hz SELV. Maximum power consumption: 18 W, 22 V A |
|
|
Insulation between power supply and the extra-low voltage: functional |
|
Plastic housing |
DIN rail mounting complying with EN 60715 |
|
|
Self extinguishing V0 according to IEC 60695-11-10 and glowing / hot wire test at 960 °C according to IEC 60695-2-12 |
|
Ball test |
125 °C according to IEC 60730-1 |
|
|
Leakage current: ≥ 250 V according to IEC 60112 |
|
Operating conditions |
CE: -20T55, 90% RH non-condensing |
|
Storage conditions |
-30T80, 90% RH non-condensing |
|
Integration |
In Class I and / or II appliances |
|
Index of protection |
IP40 only on the front cover |
|
Period of electric stress across insulat- |
Long |
|
ing parts |
|
|
Resistance to heat and •re |
Category D |
|
Immunity against voltage surges |
Category II |
|
Software class and structure |
Class A |
|
|
|
Input/Output
Table 3: Analog inputs
Type |
Num |
Speci€cations |
|
|
|
|
Max 15 V input voltage |
|
|
|
Do not connect voltage sources without current limitation (overall 80 mA) to analog inputs while unit is not powered |
|
|
|
Open circuit HW diagnostics available for voltage input on: AI1,2,3,4,6 |
0 |
/ 1 V |
7 |
AI1, AI2, AI3, AI4, AI5, AI6, AI7 |
0 / 5 V |
|
0 / 1 V, 0 / 5 V, 0 / 10 V |
|
0 |
/ 10 V |
|
AI1, AI2, AI3, AI4, AI6 impedance is 33 kΩ (by software can be set greater than 1 MΩ) |
|
|
|
AI7 impedance is greater than 1 MΩ |
NTC |
5 |
AI1, AI2, AI3, AI4, AI6 |
|
|
|
|
NTC temperature probes, default: 10 kΩ at 25 °C |
0 |
/ 20 mA |
6 |
AI1, AI2, AI3, AI4, AI5, AI6 |
4 |
/ 20 mA |
|
0 / 20 mA; 4 / 20 mA |
Pt1000 |
4 |
AI1, AI2, AI3, AI7 |
|
|
|
|
Pt1000 |
Diˆerential input |
1 |
AI5(-), AI6(+) |
|
|
|
|
Diˆerential input, DM Voltage 0.300 mV; CM voltage max 14 V |
Auxiliary Supplies |
2 |
15 V+ and 5 V+ |
|
|
|
|
5 V+ max: 70 mA |
|
|
|
15 V+ max: 100 mA |
|
|
|
|
Table 4: Digital inputs
Type |
Num |
Speci€cations |
Voltage free contacts |
8 |
DI1 |
|
|
Frequency input: 200 Hz Max (pulse time about 2.5 ms) |
|
|
DI2, DI3, DI4, DI5, DI6, DI7, DI8 |
|
|
Frequency input: 5 Hz Max (pulse time about 100 ms) |
|
|
|
Table 5: Analog outputs
Type |
Num |
Speci€cations |
|
0 |
/ 10 V DC |
2 |
AO1, AO2 |
|
|
|
Minimum load 1 kΩ (10 mA) |
0 |
/ 10 V |
1 |
AO3 |
PWM |
|
Minimum load 1 kΩ (10 mA) |
|
PPM |
|
• 0 / 10 V |
|
|
|
|
• pulse output, synchronous with mains, at modulation of impulse position (PPM) or modulation of impulse width (PWM): |
|
|
|
6.8 V open circuit |
|
|
|
• pulse output, PWM with range from 1 – 1000 Hz: 6.8 V open circuit |
|
|
|
|
© Danfoss | Climate Solutions | 2021.03 |
AI166386420921en-000901 | 3 |