The Wheelock MT Mult candela Electronic Appliances are audible and visual alarm indicating devices engineered to comply with temporal pattern specifications without requiring an additional code mechanism. They have a selection of eight tone patterns, two sound output levels, and four light intensities (15 cd, 30 cd, 75 cd, or 110 cd). The temporal (Code 3) horn and tone patterns meet ANSI/ NFPA/ISO requirements for standard emergency evacuation signaling.

The extended temperature range satisfies all severe weather outdoor applications. The option to silence the audible signal allows emergency personnel to communicate while maintaining the visual alarm condition, a requirement in some jurisdictions.

Certifications and approvals

Cooper Wheelock, Inc. holds these Listings and Approvals:

uField selectable choice of eight nationally and internationally recognized alerting signals

uTwo installer selectable sound output levels

uStrobe selections of 15 cd, 30 cd, 75 cd, or 110 cd

uADA, NFPA, and ANSI compliant

uLow average current draw

Region

Certification

 

 

 

USA

UL

UCST: Audible Signal Appliances, Gener-

 

 

al Siganal (UL464), ULSZ: Audible Sig-

 

 

nal Appliances (UL464), UUKC: Signal-

 

 

ing Appliances and Equipment for the

 

 

Hearing Impaired (UL1971)

 

CSFM

see our website

 

 

 

Installation/configuration notes

Compatible Products

The following products are compatible with the MT Multi Candela Electronic Appliances:

Category

Product ID

Product Description

Control Panels

D70221

Conventional FACP

 

D70242

Addressable FACP

 

D7024

Conventional FACP

 

D80241

Analog FACP

 

D91241

Addressable FACP

 

D10024A1

Analog FACP

2 | MT Multi candela Multitone Electronic Appliances

 

FPA-1000

Analog Addressable FACPs

 

FPD-70242

Addressable FACP

 

FPD-7024

Conventional FACP

Modules

SM 12/24 R

Synchronization module (red)

 

DSM 12/24 R

Dual synchronization module

 

 

(red)

1 For synchronization, use the SM or DSM modules with these control panels. The synchronization module must be set for 24 V operation. When used, the D7022 must be set for 24 VDC operation.

2 When used with a D7039 Multiplex Expansion Module, the D7024 and FPD-7024 become addressable fire alarm control panels (FACPs).

Mounting Considerations

For inside applications, mount these multitone appliances on the indicated back boxes for the indicated applications:

 

Conduit

Surface

Semi Flush or

 

Applications

Mounted

Flush Mount

Double gang

 

• *

Four inch square

 

• *

DBB

 

• *

IOB

 

SBB

 

* For semi flush applications use an ISP2 Surface Adapter.

All models have an attractive cover plate for a clean, finished appearance.

Retrofit Applications

Where an oversize electrical box is already installed, the MT Series appliances can be installed with the RP R Retrofit Plate that measures 8 in. (20.3 cm) high by 5.875 in. (14.9 cm) wide.

Wiring

Notice

These strobe units are not recommended for use in coded or pulsed signaling circuits.

The input terminals accept wires with diameters between 18 AWG and 12 AWG (ISO 0.75 mm2 and 4 mm2).

Parts included

Quant. Component

1Electronic appliance

1Hardware pack

1Literature pack

Technical specifications

Electrical

Current (maximum) strobe only

VDC

15 cd: 60 mA; 30 cd: 92 mA; 75 cd: 165 mA;

 

 

110 cd: 220 mA

 

 

 

VFWR

15 cd: 102 mA; 30 cd: 155 mA;

 

 

75 cd: 253 mA; 110 cd: 347 mA

 

 

Voltage (input)

 

 

 

 

Nominal

24 VDC or FWR

 

 

 

Range

16.0 V to 33.0 V

 

 

 

Environmental

Relative Humidity:

Up to 95%, non condensing

 

 

Temperature

-31°F to +150°F (-35°C to +66°C)

(Operating):

 

 

 

Mechanical

 

 

 

Dimensions

5.125 in. x 5.125 in. x 4.125 in.

(H x W x D):

(13 cm x 13 cm x 10.5 cm)

 

 

Material:

High impact thermoplastic

 

 

Audible Alarm Patterns and Ratings

 

 

Horn (continuous)

 

 

 

Current (maximum)

High output: 108 mA VDC, 87 mA FWR

at 24 V:

Standard output: 44 mA VDC, 45 mA FWR

 

 

Pattern Description:

Broadband continuous horn

 

 

Sound output* at

High output: 92 dBA

10 ft (3 m):

Standard output: 87 dBA

 

 

Bell

 

 

 

Current (maximum)

High output: 53 mA VDC and 51 mA FWR

at 24 V:

Standard output: 24 mA VDC, 28 mA FWR

 

 

Pattern Description:

1560 Hz modulated (0.7 sec on, repeat)

 

 

Sound output* at

High output: 86 dBA

10 ft (3 m):

Standard output: 80 dBA

 

 

Horn (march-time)

 

 

 

Current (maximum)

High output: 104 mA VDC, 87 mA FWR

at 24 V:

Standard output: 38 mA VDC, 45 mA FWR

 

 

Pattern Description:

Horn (0.25 sec on, 0.25 sec off, repeat)

 

 

Sound output* at

High output: 89 dBA

10 ft (3 m):

Standard output: 84 dBA

 

 

Horn (Code 3)

 

 

 

Current (maximum)

High output: 91 mA VDC, 87 mA FWR

at 24 V:

Standard output: 35 mA VDC, 45 mA FWR

 

 

Pattern Description:

Horn (ANSI S3.41 temporal pattern)

 

 

Sound output* at

High output: 88 dBA

10 ft (3 m):

Standard output: 83 dBA

 

 