Bosch MTWPB-2475W-NW, MTWPA-2475W-NW, MTWP-2475W-FR, MTWP-2475C-FR Specsheet

0 (0)
Bosch MTWPB-2475W-NW, MTWPA-2475W-NW, MTWP-2475W-FR, MTWP-2475C-FR Specsheet

Fire Alarm Systems | MTWP Weatherproof Multitone Electronic Appliances

MTWP Weatherproof Multitone Electronic

Appliances

www.boschsecurity.com

The Wheelock MTWP Weatherproof Appliances are four wire appliances listed for indoor or outdoor use. They provide eight tone patterns, two sound output levels, and a strobe rated at 75 cd at -31°F (-35°C) and 180 cd at +77°F (+25°C). The temporal (Code 3) horn and tone patterns meet ANSI/NFPA/ISO requirements for standard emergency evacuation signaling. The extended temperature range satisfies all severe weather outdoor applications.

The strobe portion can be synchronized using the SM (single) or DSM (dual) Synchronization modules or a compatible control panel. The audible portion cannot be synchronized, but it can be connected to a coded fire alarm system.

Notice

These products are not suitable for hearing impaired applications.

Certifications and approvals

Cooper Wheelock, Inc. holds these Listings and Approvals:

uField selectable choice of eight nationally and internationally recognized alerting signals

uTwo installer selectable sound output levels

uStrobe rated at 75 cd at -31°F (-35°C) and 180 cd at +77°F (+25°C)

uNFPA and ANSI compliant

uUL Listed for indoor or outdoor use

Region

Certification

 

 

 

USA

UL

ULSZ: Audible-signal Appliances

 

 

(ANSI/UL 464) and UVAV: Visual-signal

 

 

Appliances for Fire-protective Signaling

 

 

Systems (ANSI/UL 1638)

 

CSFM

see our website

 

 

 

Installation/configuration notes

Compatible Products

The following products are compatible with the MTWP Weatherproof Electronic Appliances:

Category

Product ID

Product Description

Control

D70221

Conventional FACP

Panels

 

 

 

D70242

Addressable FACP

 

D7024

Conventional FACP

 

D80241

Analog FACP

 

D91241

Addressable FACP

 

D10024A1

Analog FACP

2 | MTWP Weatherproof Multitone Electronic Appliances

 

FPD-70242

Addressable FACP

 

FPD-7024

Conventional FACP

 

FPA-1000

Analog Addressable FACPs

Modules

SM 12/24 R

Synchronization module (red)

 

DSM 12/24 R

Dual synchronization module (red)

1 For synchronization, use the SM or DSM modules with these control panels. The synchronization module must be set for 24 V operation. When used, the D7022 must be set for 24 VDC operation.

2 When used with a D7039 Multiplex Expansion Module, the FPD-7024 and D7024 become addressable fire alarm control panels (FACPs).

Mounting Considerations

Outdoor or Severe Environment Applications

Notice

Mount the 2475C models only on flat ceilings and mount the 2475W models only on flat walls.

For an outdoor application or a severe environment (NEMA 3R) application, mount these multitone appliances with an IOB Indoor or Outdoor Back Box on a flat wall or ceiling so the entire rear surface of the back box is covered. The drain holes in the back box must point toward the ground. The knockouts on the rear surface of the back box must remain intact.

The knockout hole on top of the back box is sized for a half-inch conduit and matching connector. Use a proper watertight conduit fitting.

Indoor Applications

For inside applications, mount these multitone appliances on the indicated back boxes for the indicated applications:

 

Conduit

Surface

Semi Flush or

 

Applications

Mounted

Flush Mount

Double gang

 

• *

Four inch square

 

• *

DBB

 

• *

IOB

 

SBB

 

* For semi flush applications use an ISP2 Surface Adapter.

All models have an attractive cover plate for a clean, finished appearance.

Indoor Retrofit Applications

Where an oversize electrical box is already installed, thsee multitone appliances can be installed with the RP R Retrofit Plate that measures 8 in. (20.3 cm) high by 5.875 in. (14.9 cm) wide.

Wiring

Notice

These strobe units are not recommended for use in coded or pulsed signaling circuits.

The input terminals accept wires with diameters between 18 AWG and 12 AWG (ISO 0.75 mm2 and 4 mm2).

Parts included

Quant. Component

1Weatherproof electronic appliance

1Cover plate

1Hardware pack

1Literature pack

Technical specifications

Audible Alarm Patterns and Ratings

Horn (continuous)

Current (maximum)

High output: 108 mA VDC, 87 mA FWR

at 24 V:

Standard output:44 mA VDC, 45 mA FWR

 

 

Pattern Description:

Broadband continuous horn

 

 

Sound output* at

High output: 92 dBA

10 ft (3 m):

Standard output: 87 dBA

 

 

Bell

 

 

 

Current (maximum)

High output: 53 mA VDC and 51 mA FWR

at 24 V:

Standard output: 24 mA VDC, 28 mA FWR

 

 

Pattern Description:

1560 Hz modulated (0.7 sec on, repeat)

 

 

Sound output* at

High output: 86 dBA

10 ft (3 m):

Standard output: 80 dBA

 

 

Horn (march-time)

 

 

 

Current (maximum)

High output: 104 mA VDC, 87 mA FWR

at 24 V:

Standard output: 38 mA VDC, 45 mA FWR

 

 

Pattern Description:

Horn (0.25 sec on, 0.25 sec off, repeat)

 

 

Sound output* at

High output: 89 dBA

10 ft (3 m):

Standard output: 84 dBA

 

 

Horn (Code 3)

 

 

 

Current (maximum)

High output: 91 mA VDC, 87 mA FWR

at 24 V:

Standard output: 35 mA VDC, 45 mA FWR

 

 

Pattern Description:

Horn (ANSI S3.41 temporal pattern)

 

 

Sound output* at

High output: 88 dBA

10 ft (3 m):

Standard output: 83 dBA

 

 

Tone (Code 3)

 

 

 

Current (maximum)

High output: 75 mA VDC, 60 mA FWR

at 24 V:

Standard output: 35 mA VDC, 36 mA FWR

 

 

Pattern Description:

500 Hz (ANSI S3.41 temporal pattern)

 

 

Loading...
+ 2 hidden pages