Fire Alarm Systems | MTWP Weatherproof Multitone Electronic Appliances
MTWP Weatherproof Multitone Electronic
Appliances
www.boschsecurity.com
The Wheelock MTWP Weatherproof Appliances are four wire appliances listed for indoor or outdoor use. They provide eight tone patterns, two sound output levels, and a strobe rated at 75 cd at -31°F (-35°C) and 180 cd at +77°F (+25°C). The temporal (Code 3) horn and tone patterns meet ANSI/NFPA/ISO requirements for standard emergency evacuation signaling. The extended temperature range satisfies all severe weather outdoor applications.
The strobe portion can be synchronized using the SM (single) or DSM (dual) Synchronization modules or a compatible control panel. The audible portion cannot be synchronized, but it can be connected to a coded fire alarm system.
Notice
These products are not suitable for hearing impaired applications.
Certifications and approvals
Cooper Wheelock, Inc. holds these Listings and Approvals:
uField selectable choice of eight nationally and internationally recognized alerting signals
uTwo installer selectable sound output levels
uStrobe rated at 75 cd at -31°F (-35°C) and 180 cd at +77°F (+25°C)
uNFPA and ANSI compliant
uUL Listed for indoor or outdoor use
Region |
Certification |
|
|
|
|
USA |
UL |
ULSZ: Audible-signal Appliances |
|
|
(ANSI/UL 464) and UVAV: Visual-signal |
|
|
Appliances for Fire-protective Signaling |
|
|
Systems (ANSI/UL 1638) |
|
CSFM |
see our website |
|
|
|
Installation/configuration notes
Compatible Products
The following products are compatible with the MTWP Weatherproof Electronic Appliances:
Category |
Product ID |
Product Description |
Control |
D70221 |
Conventional FACP |
Panels |
|
|
|
D70242 |
Addressable FACP |
|
D7024 |
Conventional FACP |
|
D80241 |
Analog FACP |
|
D91241 |
Addressable FACP |
|
D10024A1 |
Analog FACP |
2 | MTWP Weatherproof Multitone Electronic Appliances
|
FPD-70242 |
Addressable FACP |
|
FPD-7024 |
Conventional FACP |
|
FPA-1000 |
Analog Addressable FACPs |
Modules |
SM 12/24 R |
Synchronization module (red) |
|
DSM 12/24 R |
Dual synchronization module (red) |
1 For synchronization, use the SM or DSM modules with these control panels. The synchronization module must be set for 24 V operation. When used, the D7022 must be set for 24 VDC operation.
2 When used with a D7039 Multiplex Expansion Module, the FPD-7024 and D7024 become addressable fire alarm control panels (FACPs).
Mounting Considerations
Outdoor or Severe Environment Applications
Notice
Mount the 2475C models only on flat ceilings and mount the 2475W models only on flat walls.
For an outdoor application or a severe environment (NEMA 3R) application, mount these multitone appliances with an IOB Indoor or Outdoor Back Box on a flat wall or ceiling so the entire rear surface of the back box is covered. The drain holes in the back box must point toward the ground. The knockouts on the rear surface of the back box must remain intact.
The knockout hole on top of the back box is sized for a half-inch conduit and matching connector. Use a proper watertight conduit fitting.
Indoor Applications
For inside applications, mount these multitone appliances on the indicated back boxes for the indicated applications:
|
Conduit |
Surface |
Semi Flush or |
|
Applications |
Mounted |
Flush Mount |
Double gang |
|
• |
• * |
Four inch square |
|
• |
• * |
DBB |
|
• |
• * |
IOB |
• |
• |
|
SBB |
|
• |
• |
* For semi flush applications use an ISP2 Surface Adapter.
All models have an attractive cover plate for a clean, finished appearance.
Indoor Retrofit Applications
Where an oversize electrical box is already installed, thsee multitone appliances can be installed with the RP R Retrofit Plate that measures 8 in. (20.3 cm) high by 5.875 in. (14.9 cm) wide.
Wiring
Notice
These strobe units are not recommended for use in coded or pulsed signaling circuits.
The input terminals accept wires with diameters between 18 AWG and 12 AWG (ISO 0.75 mm2 and 4 mm2).
Parts included
Quant. Component
1Weatherproof electronic appliance
1Cover plate
1Hardware pack
1Literature pack
Technical specifications
Audible Alarm Patterns and Ratings
Horn (continuous)
Current (maximum) |
High output: 108 mA VDC, 87 mA FWR |
at 24 V: |
Standard output:44 mA VDC, 45 mA FWR |
|
|
Pattern Description: |
Broadband continuous horn |
|
|
Sound output* at |
High output: 92 dBA |
10 ft (3 m): |
Standard output: 87 dBA |
|
|
Bell |
|
|
|
Current (maximum) |
High output: 53 mA VDC and 51 mA FWR |
at 24 V: |
Standard output: 24 mA VDC, 28 mA FWR |
|
|
Pattern Description: |
1560 Hz modulated (0.7 sec on, repeat) |
|
|
Sound output* at |
High output: 86 dBA |
10 ft (3 m): |
Standard output: 80 dBA |
|
|
Horn (march-time) |
|
|
|
Current (maximum) |
High output: 104 mA VDC, 87 mA FWR |
at 24 V: |
Standard output: 38 mA VDC, 45 mA FWR |
|
|
Pattern Description: |
Horn (0.25 sec on, 0.25 sec off, repeat) |
|
|
Sound output* at |
High output: 89 dBA |
10 ft (3 m): |
Standard output: 84 dBA |
|
|
Horn (Code 3) |
|
|
|
Current (maximum) |
High output: 91 mA VDC, 87 mA FWR |
at 24 V: |
Standard output: 35 mA VDC, 45 mA FWR |
|
|
Pattern Description: |
Horn (ANSI S3.41 temporal pattern) |
|
|
Sound output* at |
High output: 88 dBA |
10 ft (3 m): |
Standard output: 83 dBA |
|
|
Tone (Code 3) |
|
|
|
Current (maximum) |
High output: 75 mA VDC, 60 mA FWR |
at 24 V: |
Standard output: 35 mA VDC, 36 mA FWR |
|
|
Pattern Description: |
500 Hz (ANSI S3.41 temporal pattern) |
|
|