Honeywell MS-2 User Manual

0 (0)

 

 

 

 

 

 

 

 

 

 

PN: 51512:E

ECN 05-040

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fire Alarm Control Panel

MS-2 & MS-4 MS-2E & MS-4E

Document #51512 E

01/18/05 Revision:

Fire Alarm System Limitations

An automatic fire alarm system–typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control with remote notification capability–can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.

The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer's recommendations, State and local codes, and the recommendations contained in the Guide for Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. A study by the Federal Emergency Management Agency (an agency of the United States government) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons:

Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a first-floor or basement fire.

Particles of combustion or "smoke" from a developing fire may not reach the sensing chambers of smoke detectors because:

Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow.

Smoke particles may become "cold," stratify, and not reach the ceiling or upper walls where detectors are located.

Smoke particles may be blown away from detectors by air outlets.

Smoke particles may be drawn into air returns before reaching the detector.

The amount of "smoke" present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm.

Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ion- izing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.

Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper storage of flammable materials, etc.).

While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!

Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire protection specialist.

Heat detectors are designed to protect property, not life.

IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so located, a developing fire may damage the alarm system, crippling its ability to report a fire.

Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently consumed drugs, alcohol or medication. Please note that:

Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy.

Studies have shown that certain people, even when they hear a fire alarm signal, do not respond or comprehend the meaning of the signal. It is the property owner's responsibility to conduct fire drills and other training exercise to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals.

In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.

A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly.

Equipment used in the system may not be technically compatible with the control. It is essential to use only equipment listed for service with your control panel.

Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. For added protection against telephone line failure, backup radio transmission systems are recommended.

The most common cause of fire alarm malfunction is inadequate maintenance. To keep the entire fire alarm system in excellent working order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA standards. At a minimum, the requirements of NFPA 72 shall be followed. Environments with large amounts of dust, dirt or high air velocity require more frequent maintenance. A maintenance agreement should be arranged through the local manufacturer's representative. Maintenance should be scheduled monthly or as required by National and/or local fire codes and should be performed by authorized professional fire alarm installers only. Adequate written records of all inspections should be kept.

PrecauLarge.PMD 01/10/2005

Installation Precautions

WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until this manual is read and understood.

CAUTION - System Reacceptance Test after Software Changes. To ensure proper system operation, this product must be tested in accordance with NFPA 72 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring.

All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.

This system meets NFPA requirements for indoor dry operation at 0-49° C/32-120° F and at a relative humidity of 93 ±2% RH (non-condensing) at 32 ±2° C/90 ±3° F. However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and all peripherals be installed in an environment with a nominal room temperature of 15-27° C/60-80° F.

Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage.

Adherence to the following will aid in problem-free installation with long-term reliability:

Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning-induced transients. Although no system is completely immune from lightning transients and interferences, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Services Department if any problems are anticipated or encountered.

Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.

Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, and printed circuit board location.

Do not tighten screw terminals more than 9 in-lbs. Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.

Though designed to last many years, system components can fail at any time. This system contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static-suppressive packaging

to protect electronic assemblies removed from the unit.

Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation by authorized personnel.

FCC Warning

WARNING: This equipment generates, uses, and can ra-

Canadian Requirements

diate radio frequency energy and if not installed and used

This digital apparatus does not exceed the Class A

in accordance with the instruction manual, may cause in-

limits for radiation noise emissions from digital

terference to radio communications. It has been tested

apparatus set out in the Radio Interference Regulations

and found to comply with the limits for class A computing

of the Canadian Department of Communications.

device pursuant to Subpart B of Part 15 of FCC Rules,

Le present appareil numerique n'emet pas de bruits

which is designed to provide reasonable protection against

radioelectriques depassant les limites applicables aux

such interference when operated in a commercial environ-

appareils numeriques de la classe A prescrites dans le

ment. Operation of this equipment in a residential area is

Reglement sur le brouillage radioelectrique edicte par le

likely to cause interference, in which case the user will be

ministere des Communications du Canada.

required to correct the interference at his own expense.

 

PrecauLarge.PMD 01/10/2005

Notes

4

MS-2/MS-4 PN 51512:E 01/18/05

Table of Contents

SECTION 1: Product Description ........................................................................................................................

10

1.1: Product Features..........................................................................................................................................

10

1.2: Specifications ..............................................................................................................................................

12

1.3: Controls and Indicators ...............................................................................................................................

13

1.4: Circuits ........................................................................................................................................................

14

1.5: Components.................................................................................................................................................

14

1.6: Optional Modules and Accessories .............................................................................................................

15

SECTION 2: Installation .......................................................................................................................................

17

2.1: Backbox Mounting......................................................................................................................................

17

2.2: Operating Power..........................................................................................................................................

19

2.3: Input Circuits...............................................................................................................................................

20

2.4: Output Circuits ............................................................................................................................................

22

2.4.1: Notification Appliance Circuits ........................................................................................................

22

2.4.2: Special Application DC Power Output Connections ........................................................................

23

2.4.3: Relays................................................................................................................................................

23

2.5: Power-limited Wiring Requirements...........................................................................................................

24

2.6: Installation of Optional Modules.................................................................................................................

25

2.6.1: CAC-4 Class A Converter Module (MS-4 only) ..............................................................................

25

2.6.1.1 Installation ...............................................................................................................................

25

2.6.1.2 Wiring NACs and IDCs for Class A .......................................................................................

26

2.6.2: 4XTMF, 4XLMF and 4XZMF Option Modules...............................................................................

27

2.6.2.1 4XTMF Transmitter Module Installation ...............................................................................

28

2.6.2.2 4XZMF Zone Relay Module (MS-4 only) ..............................................................................

29

2.6.2.3 4XLMF LED Interface Module (MS-4 only) .........................................................................

30

SECTION 3: Program Options via DIP Switch ..................................................................................................

31

3.1: DIP Switch Settings ....................................................................................................................................

32

3.1.1: SW1 DIP Switch Settings .................................................................................................................

34

3.1.1.1 Silence Inhibit .........................................................................................................................

34

3.1.1.2 Auto-silence ............................................................................................................................

34

3.1.1.3 Temporal Coding ....................................................................................................................

34

3.1.1.4 Selective Silence .....................................................................................................................

34

3.1.1.5 Trouble Reminder ...................................................................................................................

34

3.1.1.6 AC Trouble Delay ...................................................................................................................

34

3.1.1.7 Autoresettable Supervisory .....................................................................................................

34

3.1.1.8 IDC Combination Circuit ........................................................................................................

34

3.1.2: SW2 DIP Switch Settings .................................................................................................................

35

3.1.2.1 IDC1 Verification (MS-4 only) ..............................................................................................

35

3.1.2.2 IDC1 Supervisory (MS-4 only) ...............................................................................................

35

3.1.2.3 IDC1 Verification for MS-2 or IDC2 Verification for MS-4 .................................................

35

3.1.2.4 IDC1 Supervisory for MS-2 or IDC2 Supervisory for MS-4 .................................................

35

3.1.2.5 IDC2 Verification for MS-2 or IDC3 Verification for MS-4 .................................................

36

3.1.2.6 IDC2 Supervisory for MS-2 or IDC3 Supervisory for MS-4 .................................................

36

3.1.2.7 IDC4 Verification (MS-4 only) ...............................................................................................

36

3.1.2.8 IDC4 Supervisory (MS-4 only) ...............................................................................................

36

3.1.3: SW3 DIP Switch Settings .................................................................................................................

36

3.1.3.1 NAC1 Nonsilenceable .............................................................................................................

36

3.1.3.2 NAC1 Disable .........................................................................................................................

36

3.1.3.3 NAC2 Nonsilenceable (MS-4 only) ........................................................................................

36

3.1.3.4 NAC2 Disable (MS-4 only) ....................................................................................................

36

3.1.3.5 Strobe Synchronization ...........................................................................................................

37

3.1.3.5.1 Maximum Number of Strobes for Synchronization .............................................................

37

3.1.3.6 Nonsilenceable Waterflow for Combination Circuit ..............................................................

37

3.1.3.7 Spares ......................................................................................................................................

37

MS-2/MS-4 P/N: 51512:E 01/18/05

5

Table of Contents

 

SECTION 4: Operating Instructions ....................................................................................................................

38

4.1: Switch Functions in Normal Mode..............................................................................................................

38

4.1.1: ACK - Acknowledge.........................................................................................................................

38

4.1.2: Silence ...............................................................................................................................................

38

4.1.3: Zone Enable/Disable .........................................................................................................................

38

4.1.4: Reset/(Lamp Test) .............................................................................................................................

38

4.1.5: Walktest .............................................................................................................................................

39

4.2: Walktest .......................................................................................................................................................

39

4.3: Status LEDs .................................................................................................................................................

40

4.4: Operation .....................................................................................................................................................

41

4.4.1: Fire Alarm Response.........................................................................................................................

42

4.4.2: Fire Alarm Restoral...........................................................................................................................

42

4.4.3: System Supervisory Condition Response .........................................................................................

42

4.4.4: System Supervisory Restoral Response ............................................................................................

42

4.4.5: Trouble Condition Response .............................................................................................................

43

4.4.6: Trouble Condition Restoral ...............................................................................................................

43

SECTION 5: Power Supply Calculations .............................................................................................................

44

5.1: Overview .....................................................................................................................................................

44

5.2: Calculating the AC Branch Circuit..............................................................................................................

44

5.3: Calculating the System Current Draw.........................................................................................................

45

5.3.1: Overview ...........................................................................................................................................

45

5.3.2: How to Use Table 5-3 on page 46 to Calculate System Current Draw .............................................

45

5.4: Calculating the Battery Size ........................................................................................................................

47

5.4.1: NFPA Battery Requirements .............................................................................................................

47

5.4.2: Selecting and Locating Batteries.......................................................................................................

47

6

MS-2/MS-4 P/N: 51512:E 01/18/05

It is imperative that the installer understand the requirements of the Authority Having Jurisdiction (AHJ) and be familiar with the standards set forth by the following regulatory agencies:

Underwriters Laboratories Standards

NFPA 72 National Fire Alarm Code

Before proceeding, the installer should be familiar with the following documents.

NFPA Standards

This Fire Alarm Control Panel complies with the following NFPA Standards:

NFPA 72 National Fire Alarm Code for Local Fire Alarm Systems and Remote Station Fire Alarm Systems (requires an optional Remote Station Output Module)

Underwriters Laboratories Documents for Reference:

UL 38 Manually Actuated Signaling Boxes

UL 217 Smoke Detectors, Single and Multiple Station

UL 228 Door Closers–Holders for Fire Protective Signaling Systems

UL 268 Smoke Detectors for Fire Protective Signaling Systems

UL 268A Smoke Detectors for Duct Applications

UL 346 Waterflow Indicators for Fire Protective Signaling Systems

UL 464 Audible Signaling Appliances

UL 521 Heat Detectors for Fire Protective Signaling Systems

UL 864 Standard for Control Units for Fire Protective Signaling Systems

UL 1481 Power Supplies for Fire Protective Signaling Systems

UL 1638 Visual Signaling Appliances

UL 1971 Signaling Devices for Hearing Impaired

Other:

NEC Article 250 Grounding

NEC Article 300 Wiring Methods

NEC Article 760 Fire Protective Signaling Systems

Applicable Local and State Building Codes

Requirements of the Local Authority Having Jurisdiction (LAHJ)

Fire•Lite Documents

 

Fire•Lite Device Compatibility Document

Document #15384

411 Digital Alarm Communicator/Transmitter

Document #50921

411UD Digital Alarm Communicator/Transmitter

Document #50759

This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, 9th Edition. Operation of this product with products not tested for UL 864, 9th Edition has not been evaluated. Such operation requires the approval of the local Authority Having Jurisdiction (AHJ).

MS-2/MS-4 PN 51512:E 01/18/05

7

 

 

 

MS-2(E) Main Circuit Board

IDC (4.7 K, ½ watt ELR)

 

 

 

 

 

 

 

 

 

 

 

(supervised, power-limited)

 

 

 

 

 

 

 

 

 

 

Trouble Relay (fail-safe)

 

Zone 2 B-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Zone 2 B+

 

 

 

 

 

 

 

 

 

 

2 amps @ 30 VAC

 

 

 

 

 

 

 

 

 

 

 

NAC (4.7K, ½ watt ELR)

Zone 1 B-

 

 

 

 

 

 

 

 

 

 

(nonsupervised)

 

 

 

 

 

 

 

 

 

 

Zone 1 B+

 

 

 

 

 

 

 

 

 

 

Common

 

 

 

 

 

 

 

 

 

 

2.5A max.

 

 

 

 

 

 

 

 

 

 

 

Trouble (Normally Open)

 

 

 

 

 

 

 

 

 

 

 

(supervised, power-limited)

 

 

 

 

 

 

 

 

 

 

 

Normal (Normally Closed)

 

 

 

 

 

 

 

 

 

 

 

B-

Alarm Relay

B+

24 VDC Special Application

2 amps @ 30 VAC

(nonsupervised)

Resettable Power

500 mA max. (nonsupervised,

Common

power-limited)

Normally Closed

- 24 VDC

Normally Open

+ 24 VDC

 

 

JP3 - Cut to disable

 

Ground Fault

 

detection (only with

 

approval of AHJ)

 

J3 and J5

 

4XTMF Option

 

Module

 

Connectors

 

120 VAC, 2.3A or

ms2bord.cdr

 

 

J7 Transformer

220/240 VAC, 1.15A

SW1, SW2 and SW3

Earth

Programming DIP Switches

Connector

Neutral

 

 

Hot

 

 

(supervised,

Module Placement Supervision (if installed)

 

nonpower-limited)

 

 

JP1 - cut to supervise module on J3 & J5

J8 Battery Connector

 

(supervised, nonpower-limited)

Charger Fault LED

18 Amp Hour max.

 

Battery Fault LED

 

 

Earth Fault LED

8

MS-2/MS-4 PN 51512:E 01/18/05

Honeywell MS-2 User Manual

MS-4(E) Main Circuit Board

IDC (4.7 K, ½ watt ELR)

NAC (4.7K, ½ watt ELR)

TB2 2.5A max. per NAC (supervised, power-limited)

NAC 2 B-

NAC 2 B+

NAC 1 B-

NAC 1 B+

24 VDC Special

Application Power TB1 500 mA per circuit (nonsupervised, powerlimited)

-Reset + Reset

-Nonreset +Nonreset

TB3 (supervised, power-limited)

Zone 4 B-

Zone 4 B+

Zone 3 B-

Zone 3 B+

Zone 2 B-

Zone 2 B+

Zone 1 B-

Zone 1 B+

Trouble Relay TB5 (fail-safe)

2A @ 30 VAC (nonsupervised)

Common

Trouble (Normally Open)

Normal (Normally Closed)

Alarm Relay TB6 2A @ 30 VAC (nonsupervised)

Common Normally Closed Normally Open

Supv. Relay TB7

2A @ 30 VAC (nonsupervised)

Common Normally Closed Normally Open

TB1

+

-

+

-

TB2

B+ B-

B+

B-

TB3

B+

B-

B+

B-

B+

B-

B+

B-

C TRBL NORM

C

NC NOTB6

C

NC

NO TB7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TB5

 

 

 

 

 

 

Nonreset

Reset

 

NAC 1

NAC 2

 

ZONE 1 ZONE 2

ZONE 3 ZONE 4

TROUBLE

 

ALARM

 

SUPV

 

 

 

 

 

 

CLASS A

 

 

 

 

 

 

CONVERTER

J1

 

 

 

 

Class A

 

 

 

 

 

 

 

 

Converter Module

 

 

 

 

ZONE 1

 

 

 

FIRE ALARM

SUPERVISORY

TROUBLE

MAINTENANCE

 

 

 

ZONE 2

 

 

 

FIRE ALARM

SUPERVISORY

TROUBLE

MAINTENANCE

 

 

 

ZONE 3

 

 

 

FIRE ALARM

SUPERVISORY

TROUBLE

MAINTENANCE

 

 

 

ZONE 4

 

 

 

FIRE ALARM

SUPERVISORY

TROUBLE

MAINTENANCE

AC

NAC

ZONE

NAC

SYSTEM

POWER

WALK

ALARM

POWER

DISABLE

DISABLE

FAULT

TROUBLE

TROUBLE TEST

SILENCE

JP3

JP3 - Cut to disable

Ground Fault

J3

detection (only with

 

J5

approval of AHJ)

 

J3 and J5

Option Module

Connectors

2 TRANSFORMER

J9

1 TRANSFORMER

J7

J7 Transformer

Connector

J9 Transformer (optional)

120 VAC, 2.3A or 220/240 VAC, 1.15A

Hot Neutral Earth

(supervised, nonpower-limited)

ACK

ALARM

RESET

WALK

 

 

SILENCE

ZONE

TEST

 

1

ENABLE/DISABLE

4

 

2

3

J4

 

 

 

 

 

 

J6

J4 and J6

 

 

JP2

 

JP1

 

Option Module

 

 

 

 

 

TB8

 

2 1

ON

ON 2 1

ON 2 1

 

Connectors

HOT NEUT EARTH

BATTERY

 

ms4bord.cdr

SW1876543

SW2876543

SW3876543

 

 

EARTH BATT CHG

 

 

 

 

 

 

J8

 

 

 

 

 

 

J8 Battery

Connector (supervised, nonpower-limited)

18 Amp Hour max.

SW1, SW2 and SW3

Programming DIP Switches

Module Placement Supervision (if installed) JP1 - cut to supervise module on J3 & J5

JP2 - cut to supervise module on J4 and J6

Charger Fault LED

Battery Fault LED

Earth Fault LED

MS-2/MS-4 PN 51512:E 01/18/05

9

Product Description

SECTION 1

Product Features

Product Description

The MS-2 is a two zone FACP (Fire Alarm Control Panel) and the MS-4 is a four zone FACP. The information in this manual refers to both the MS-2 and MS-4 unless otherwise specified. These control panels provide reliable fire signaling protection for small to medium sized commercial, industrial and institutional buildings. The FACP is compatible with System Sensor’s I3 detectors which are microprocessor-based conventional smoke detectors that can transmit a maintenance trouble signal to the FACP indicating the need for cleaning and a supervisory ‘freeze’ signal when the ambient temperature falls below the detector rating (refer to System Sensor’s I3 Installation and Maintenance Instructions document I56-1800-00 for device specifications). In addition, the control panel is compatible with conventional input devices such as two-wire smoke detectors, four-wire smoke detectors, pull stations, waterflow devices, tamper switches and other normally-open contact devices. Refer to Fire•Lite Device Compatibility Document for a complete listing of compatible devices.

Outputs include one NAC (Notification Appliance Circuit) on the MS-2 and two NACs on the MS-4. Each FACP has a Form-C Alarm and Trouble relay and 24 VDC special application resettable power. In addition, the MS-4 has a Form-C Supervisory relay and a nonresettable special application power output. The FACP supervises wiring, AC voltage and battery level.

Activation of a compatible smoke detector or any normally-open fire alarm initiating device will activate audible and visual signaling devices, illuminate an indicating LED, sound the piezo sounder at the FACP, activate the FACP alarm relay and operate an optional module used to notify a remote station or initiate a auxiliary control function. The MS-2E and MS-4E offer the same features as the MS-2 and MS-4 but allows connection to 220/240 VAC.

Note: Unless otherwise specified, the terms MS-2 and MS-4 are used in this manual to refer to the MS-2 and MS-2E as well as the MS-4 and MS-4E FACPs respectively.

1.1Product Features

Style B (Class B) IDC (Initiating Device Circuit)

one zone programmable for combination supervisory and waterflow

MS-2 - two IDCs

 

MS-4

ZONE1

 

FIRE ALARM SUPERVISORY

TROUBLE MAINTENANCE

 

ZONE2

 

MS-4 - four IDCs

FIRE ALARM SUPERVISORY

TROUBLE MAINTENANCE

ZONE3

 

FIRE ALARM SUPERVISORY

TROUBLE MAINTENANCE

ZONE4

 

FIRE ALARM SUPERVISORY

TROUBLE MAINTENANCE

• Style Y (Class B) NAC (Notification Appliance

AC NAC ZONE NAC SYSTEM POWER WALK ALARM

POWER DISABLE DISABLE FAULT TROUBLE TROUBLE TEST SILENCE

 

 

Circuit)

 

 

MS-2- one NACMS-4 - two NACs

Form-C Alarm Relay

Form-C Trouble Relay

Form-C Supervisory Relay (MS-4 only)

3.0 amps total system current standard for MS-2 and MS-4

6.0 amps total system current available for MS-4 with optional second transformer

Dress Panel DP-MS2/4

Optional Trim Ring P/N: TR-1-R for semi-flush mounting the cabinet

10

MS-2/MS-4 PN 51512:E 01/18/05

Product Features

Product Description

Control Buttons

ACK (Acknowledge)

Alarm Silence

Reset

Walktest

Zone Enable/Disable (one per zone)

LED Indicators

Fire Alarm (one per zone)

Supervisory (one per zone)

Trouble (one per zone)

Maintenance (one per zone)

AC Power

NAC Disable

Zone Disable

NAC Fault

System Trouble

Power Trouble

Walktest

Alarm Silence

Earth Fault LED (on circuit board) lights if zero impedance between FACP and ground exist

Battery Fault (on circuit board)

Charger Fault (on circuit board)

Piezo sounder for alarm, trouble and supervisory

24 volt operation

Low AC voltage sense

Alarm Verification

NACs Programmable for:

Silence Inhibit

Auto-Silence

Strobe Synchronization

Selective Silence (horn-strobe mute)

Temporal or Steady Signal

Silenceable or Nonsilenceable

Automatic battery trickle charger

Silent or audible walktest capabilities

Optional NAC Class A converter module (MS-4 only)

Optional 4XTMF Transmitter Module (MS-2 and MS-4)

Optional 4XZMF Zone Relay Module (MS-4 only)

Optional 4XLMF Module for RZA-4XF Remote LED Annunciator (MS-4 only)

MS-2/MS-4 PN 51512:E 01/18/05

11

Product Description

Specifications

1.2 Specifications

AC Power - TB8

MS-2/MS-4: 120 VAC, 50/60 Hz, 2.3 amps MS-2E/MS-4E: 240 VAC, 50 Hz, 1.15 amps

Wire size: minimum #14 AWG (2.0 mm2) with 600V insulation

Battery (sealed lead acid only) - J8

Maximum Charging Circuit - Normal Flat Charge: 27.6 VDC @ 0.8 amp Maximum Charger Capacity: 18 Amp Hour battery (two 7 Amp Hour batteries can be housed in the FACP cabinet. Larger batteries require a separate battery box such as the Fire•Lite BB-17F)

Initiating Device Circuits - TB3

Alarm Zones 1 & 2 (MS-2 and MS-4) Alarm Zones 3 & 4 (MS-4 only) Power-limited circuitry

Operation: All zones Style B (Class B)

Normal Operating Voltage: Nominal 20 VDC, Maximum 27 VDC Alarm Current: 15 mA minimum

Short Circuit Current: 40 mA maximum Maximum Loop Resistance: 100 ohms

End-of-Line Resistor: 4.7K, 1/2 watt (Part #71252) Standby Current: 4 mA

Refer to Fire•Lite Device Compatibility Document for listed compatible devices

Notification Appliance Circuit(s) - TB21

One NAC on MS-2, two NACs on MS-4 Operation: Style Y (Class B) Power-limited Circuitry

Normal Operating Voltage: Nominal 24 VDC, Maximum 27 VDC

Maximum Signaling Current: 2.5 amps total with standard transformer. 5.0 amps total (2.5 amp maximum per NAC) with optional transformer on MS-4 only Maximum Line Impedance: 1.5 volt drop end-of-line

End-of-Line Resistor: 4.7K, 1/2 watt (Part #71252)

Refer to Fire•Lite Device Compatibility Document for compatible listed devices

Form-C Relays

Trouble Relay TB5 (fail-safe) Alarm Relay TB6

Supervisory Relay TB7 (MS-4 only)

Relay Contact Ratings: 2 amps @ 30 VAC (resistive)

Resettable Special Application Power - TB1

Operating Voltage: Nominal 24 VDC

Maximum Available Current: 500 mA - appropriate for powering 4-wire smoke detectors (see note 1)

Power-limited Circuitry

Refer to Fire•Lite Device Compatibility Document for compatible listed devices

Nonresettable Special Application Power - TB1 (MS-4 only)

Operating Voltage: Nominal 24 VDC

Maximum Available Current: 500 mA (see note 1) Power-limited Circuitry

Refer to Fire•Lite Device Compatibility Document for compatible listed devices

1.Total current for resettable power and one Notification Appliance Circuit must not exceed 3.0 amps for the MS-2. Total current for nonresettable power, resettable power and two Notification Appliance Circuits must not exceed 6.0 amps for the MS-4 (requires optional second transformer)

12

MS-2/MS-4 PN 51512:E 01/18/05

Controls and Indicators

Product Description

1.3 Controls and Indicators

Front Panel Membrane Buttons

Acknowledge

Alarm Silence

Reset

Walktest

Zone Enable/Disable - Zone 1

Zone Enable/Disable - Zone 2

Zone Enable/Disable - Zone 3 (MS-4 only)

Zone Enable/Disable - Zone 4 (MS-4 only)

LED Indicators

Fire Alarm Zone 1 - red LED

Fire Alarm Zone 2 - red LED

Fire Alarm Zone 3 - red LED (MS-4 only)

Fire Alarm Zone 4 - red LED (MS-4 only)

Supervisory Zone 1 - yellow LED

Supervisory Zone 2 - yellow LED

Supervisory Zone 3 - yellow LED (MS-4 only)

Supervisory Zone 4 - yellow LED (MS-4 only)

Trouble Zone 1 - yellow LED

Trouble Zone 2 - yellow LED

Trouble Zone 3 - yellow LED (MS-4 only)

Trouble Zone 4 - yellow LED (MS-4 only)

Maintenance Zone 1 - yellow LED

Maintenance Zone 2 - yellow LED

Maintenance Zone 3 - yellow LED (MS-4 only)

Maintenance Zone 4 - yellow LED (MS-4 only)

AC Power - green LED

NAC Disable - yellow LED

Zone Disable - yellow LED

NAC Fault - yellow LED

System Trouble - yellow LED

Power Trouble - yellow LED

Walktest - yellow LED

Alarm Silence - yellow LED

Earth Fault - yellow LED (on main circuit board) lights if zero impedance between FACP and ground exists

Battery Fault - yellow LED (on main circuit board)

Charger Fault - yellow LED (on main circuit board)

MS-2/MS-4 PN 51512:E 01/18/05

13

Product Description

Circuits

Local Piezo Sounder

A piezo sounder provides separate and distinct sounds for alarm, trouble, maintenance and supervisory conditions as follows:

Alarm - on steady

Trouble - pulse 1 second on and 1 second off

Maintenance - pulse ½ second on and ½ second off

Supervisory - pulse ½ second on and ½ second off

1.4 Circuits

Input Circuits

Two input IDCs (Initiating Device Circuits) on the MS-2 and four IDCs on the MS-4 provide Style B (Class B) configurations. All IDCs accept I3 detectors as well as conventional two-wire smoke detectors, four-wire smoke detectors and normally-open contact devices.

Output Circuits

24 VDC resettable special application power output - 500 mA

24 VDC nonresettable special application power output (MS-4 only) - 500 mA

24 volt battery charger (up to 18 Amp Hour batteries)

Notification Appliance Circuits

One NAC (Notification Appliance Circuit) Style Y (Class B) on the MS-2

Two NACs Style Y (Class B) on the MS-4

Relays

Alarm Relay

Trouble Relay (fail-safe)

Supervisory Relay (MS-4 only)

Form-C contacts rated 2.0 amps @ 30 VAC (resistive)

1.5 Components

Main Circuit Board

The main circuit board contains the system’s CPU, power supply, other primary components and wiring interface connectors. Optional modules plug in and are mounted to the main circuit board.

Cabinet

The backbox measures 14.5” (36.8 cm) x 15.218” (38.65 cm) x 2.875” (7.3 cm) and provides space for two batteries (up to 7 Amp Hours). Also included is a dress panel which mounts inside the cabinet.

Transformer Assembly

One 100VA transformer is provided standard with the FACP. An optional second 100VA transformer is available for the MS-4 to provide maximum accessory power.

Batteries

The cabinet provides space for two 7 Amp Hour batteries (larger batteries up to 18 Amp Hour, require use of a UL listed battery box such as the BB-17F). Batteries must be ordered separately.

14

MS-2/MS-4 PN 51512:E 01/18/05

Optional Modules and Accessories

Product Description

1.6 Optional Modules and Accessories

CAC-4 Class A Converter Module (MS-4 only)

The CAC-4 Module can be used to convert the Style B (Class B) Initiating Device

Circuits to Style D (Class A) and Style Y (Class B) Notification Appliance Circuits to

Style Z (Class A). The module connects to J1 on the MS-4 main circuit board.

4XTMF Transmitter Module (MS-2 and MS-4)

The 4XTMF provides a supervised output for local energy municipal box transmitter and alarm and trouble reverse polarity. It includes a disable switch and disable trouble LED. A module jumper option allows the reverse polarity circuit to open with a system trouble condition if no alarm condition exists. The 4XTMF mounts to the MS-2 main circuit board option module connectors J3 & J5 or the MS-4 main circuit board, occupying one of the two sets of option module connectors J3 & J5 or J4 & J6.

4XLMF LED Interface Module (MS-4 only)

The LED Interface Module supports the RZA-4XF Remote Annunciator module. Annunciator wiring is supervised for open conditions by this module. The 4XLMF mounts to the MS-4 main circuit board option module connectors J3 and J5 only.

RZA-4XF Remote Annunciator (MS-4 only)

The Remote Annunciator mounts on a standard single-gang electrical box and provides

LED indication of the following:

Alarm Zone 1 (red LED)

Alarm Zone 2 (red LED)

Alarm Zone 3 (red LED)

Alarm Zone 4 (red LED)

System Trouble (yellow LED)

A Local Trouble Sounder and Silence Switch are also provided. All LED wiring is supervised for open conditions. Any open condition will cause the System Trouble LED to illuminate. Slide-in paper labels permit an easy change of zone information.

Note: The RZA-4XF Remote Annunciator requires the use of the LED Interface Module (4XLMF).

4XZMF Zone Relay Module (MS-4 only)

The Zone Relay Module provides Form-C relay contacts for the following:

Alarm Zone 1

Alarm Zone 2

Alarm Zone 3

Alarm Zone 4

System Alarm

System Trouble

As a jumper option, the first four relays described above can be made silenceable. The 4XZMF mounts to the MS-4 main circuit board, occupying one of the two sets of option module connectors.

Dress Panel DP-MS2/4

A dress panel DP-MS2/4 is included. The dress panel restricts access to the system wiring while allowing access to the membrane switch panel.

MS-2/MS-4 PN 51512:E 01/18/05

15

Product Description

Optional Modules and Accessories

Battery Box

The Fire•Lite BB-17F battery box may be used to house two batteries greater than 7 Amp Hour to a maximum of 18 Amp Hour. The battery box mounts directly below the control panel cabinet, centered to the main circuit board. The BB-17F is red and is provided with knockouts.

411 and 411UD Digital Alarm Communicator/Transmitter

The three input/channel 411 and the four input/channel 411UD are dual line, digital alarm communicator/transmitters which can be used as slave communicators with the MS-4 FACP. The inputs/channels are compatible with normally open relay contacts, require ELRs (End-of-Line Resistors), are supervised and are fully programmable. The communicators interface with the public switched telephone network and are compatible with most central station receivers. Power supplied must be 12 or 24 volts, filtered and nonresettable. The communicators are mounted in a small metal enclosure, providing a variety of mounting options. Refer to the 411 or 411UD manual for additional information.

16

MS-2/MS-4 PN 51512:E 01/18/05

Backbox Mounting

SECTION 2

Installation

Installation

The cabinet can be surface mounted or semi-flush mounted using the optional Trim Ring P/N: TR-1-R. The door is removable during the installation period by opening and lifting if off the hinges. The cabinet mounts using two key slots at the top of the backbox and two additional 0.250” diameter holes located at the bottom.

Carefully unpack the system and check for shipping damage. Select a location for the cabinet that is in a clean, dry, vibration-free area where extreme temperatures are not encountered. The area should be readily accessible with sufficient room to easily install and maintain the control panel. Locate the top of the cabinet approximately five feet above the floor with the hinge mounting on the left.

Determine the number of conductors required for the devices to be installed and determine the appropriate knockouts. All wiring must be in accordance with the National and/or Local codes for fire alarm systems and power supplies.

2.1Backbox Mounting

1.Mark and predrill holes for the top two keyhole mounting bolts

2.Install two upper fasteners in the wall with the screw heads protruding approximately ¼”

3.Using the upper keyholes, mount the backbox over the two screws

4.Mark the lower two holes, remove the backbox from the wall and drill the mounting holes

5.Mount the backbox, install the remaining fasteners and tighten all screws

Top

2.875” (7.3 cm)

 

Backbox = 14.5”

 

 

(36.8 cm)

 

0.75”(1.9 cm)

 

 

 

 

2.7”

 

9.1” (23.1 cm)

(6.86cm)

10.375”

 

 

Height=15.000” (26.35 cm)

Pem Studs

 

(38.10 cm)

 

 

Backbox Mounting Holes

Depth = 3.000”

(7.62 cm)

ms2-4cab.cdr

Bottom

 

 

 

 

 

 

 

1.125” (2.868 cm)

 

 

 

 

 

 

 

 

 

 

 

Figure 2.1 Backbox Mounting Dimensions

MS-2/MS-4 PN 51512:E 01/18/05

17

Loading...
+ 39 hidden pages