tekmar 403 Quick Start [en, es, fr]

Quick Setup Guide
tekmarNet®2 House Control 403
HVAC Systems
1. Location 2. Install Junction Box
403 403
OR
3. Install Extension Ring 4. Install Sensors
Outdoor Sensor
403_Q
02/14
Replaces: 01/14
5. Line Voltage Wiring
Back of House Control 403
Boil Sys
DHW
Variable
N
Speed
to pump grounds
N1L1 G
115 V (ac)
A Watts Water Technologies Company
(black)
(black)
(red)
L
(blue)
Zone 4
Boil Sys Pmp
DHW Pump
Pump Power
Variable Speed Pump
Zone 3
Zone 2
Zone 1
Zone Power
Sensor with rear entry wiring
Pipe Sensors
(black)
(black)
(black)
(black)
1
Zone 4
Zone 3
Zone 2
Zone 1
(red)
L
to pump grounds
Sensor with bottom entry wiring
N
N2GL2
115 V (ac)
Sensor mounted onto 2" x 4" electrical box
Retaining Clip
© 2014 403_Q - 02/14
Universal Sensor 082
Sensor Well
6. Install Enclosure
R C
L N
Com Open Close
Expansion
tN4 Boil
CtN4
Modulating
Boiler
—+
Expansion
tN4 Mix
CtN4
2 1
W
W
Menu
House Control 403
Item
+
Mix ComBoil Out DHWCom
Zone 1
H8008B
Zone 2 Zone 3 Zone 4
tN2 tN2 tN2 tN2 tN2 tN2 tN2 tN2
C
Floating Action
ClsOpn
Sensors - No Power
Call Call
tN4 tN4CC
Mod dc/mA Boil Exp. Mix Exp.
Setpoint DHW
RC
Input Power
Use at least 167°F (75°C) conductors
Stage 2Stage 1
7. Low Voltage Wiring
tekmarNet
Mix Supply Sensor 082
Boiler Supply
Sensor 082
®
2 Thermostats
24 V (ac) Floating
Action Actuator
®
tekmarNet
4 Expansion to
Wiring Centers, Timers, or User Switch
Outdoor
Sensor
070
DHW Tank
Sensor 082
Setpoint Call
DHW Call
from DHW
Tank Aquast at
(optional)
8. Install Cover
M
e
n
u
I
t
e
m
H
o
u
s
e
C
o
n
t
r
o
l
One or Two Stage
24 V (ac) Transformer 009
Boiler T-T
A Watts Water Technologies Company
2
© 2014 403_Q - 02/14
9. User Interface
Display
Symbols
Calls
Pumps
Menu Field
Displays the
current menu
VIEW ADJUST
Status Fields
Displays the current
status of the control’s
inputs, outputs and
operation. Most symbols
in the status field are only visible when the
VIEW Menu is selected
CALLS
Displays any call for heat the control is receiving.
PUMPS
Displays any pump currently operating.
MONITOR
MAXMIN
Calls
Boil Exp
Mix Exp
DHW Setp
Pumps WWSD Saving
Boil System
Mix System Zones
DHW Var 1 2 3 4
°F°C
minhr
sec%
Item Field
Displays the name of the selected item
min
sec
PM
hr
AM
Number Field
Displays the current value of the selected item
Cls
Opn
1 2
Mix
°F, °C, %, HOURS, MINUTES, SECOND
Units of measurement for current number.
UNOCCUPIED
Indicates that a User Switch or Timer has put the system into UnOccupied.
Zones
1 2 3 4
Saving
WWSD
ZONES
Displays if an on-board zone is operating.
WARNING
Displays if an error exists on the system.
ENERGY SAVING INDICATOR
Displays when the system is saving energy. See the Saving Indicator section.
WWSD
Displays when the system is in Warm Weather Shut Down.
10. Access Level
INST (Installer)
Default = INST
or USER
BOILER
Indicates that the boiler should be heating.
DEVICE OUTPUT SCALE
Displays output of the mixing valve or injection pump.
Cls
Opn
MAXMIN
Press menu button until the Toolbox Menu is displayed. Press item button to locate the access level setting.
ACCESS LEVEL
Selects the Access Level of the control, which determines the Menu items available. USER provides the most limited level of access and shows the fewest possible items.
When set to USER, all thermostats are locked and the number of thermostat settings available are reduced.
CLOSE / OPEN
Displays whether the mixing valve motor is opening or closing.
MIN / MAX
Displays when an operating temperature reaches a minimum or maximum value.
A Watts Water Technologies Company
3
© 2014 403_Q - 02/14
11. Critical Settings
Press menu button until the Adjust Menu is displayed. Press item button to locate the desired setting.
Item Field Range Access Description Set to
ADJUST
ADJUST
ADJUST
-60 to 45°F
(-51.0 to 7.0°C)
Default = 10°F
(-12.0°C)
70 to 180°F
(21.0 to 82.0°C) Default = 120°F
(49.0°C)
4-20 mA,
0-10 V (dc)
FLOT,
VAR
Default = VAR
Installer
Installer
Installer
OUTDOOR DESIGN
Typically set to the temperature of the coldest day of the year. The outdoor air temperature used in the boiler and mixing heating curves that determine the boiler target and the mix target temperatures.
MIX DESIGN
The supply water temperature required for the mix zones to heat the building on the typical coldest day of the year. Recommendations:
High mass radiant floor = 120°F (50°C) Low mass radiant floor = 140°F (60°C) Fancoil or air handling unit = 190°F (90°C) Copper fin-tube convector = 180°F (80°C) Radiators = 160°F (70°C) Low profile baseboard = 150°F (65°C)
MIX TYPE
Select the type of mixing device. VAR = Variable speed injection pump FLOT = Floating action motor for mixing valves 0-10 = 0 -10 V (dc) analog signal for mixing valves 4-20 = 4-20 mA analog signal for mixing valves Note: 0-10 and 4-20 are only available when Boiler
Type = 1 Stage or 2 Stage.
EMS2, EMS1,
4-20
0-10,
2STG,
1STG
Default = 1STG
tekmar Control Systems Ltd., A Watts Water Technologies Company.
Vernon, B.C. Canada V1B 3K4, 250-545-7749, Fax. 250-545-0650 Web Site: www.tekmarControls.com
Product design, software and literature are Copyright ©2014 by tekmar Control Systems Ltd.,
A Watts Water Technologies Company
Installer
BOILER TYPE
The type of boiler connected to the control. 1STG = single one-stage on-off boiler 2STG = single two-stage on-off boiler 0-10 = 0-10 V (dc) modulating boiler 4-20 = 4-20 mA modulating boiler EMS1 = tekmar boiler staging controls EMS2 = Viessmann modulating boilers with
OpenTherm Note: Only 1STG and 2STG are available when the
Mix Type is set to 0-10 V (dc) or 4-20 mA.
Head Offi ce: 5100 Silver Star Road,
4
All specifications are subject to change without notice.
Printed in Canada. 403_Q - 02/14.