tekmar 402 Installation

Page 1
tekmarNet®2 House Control 402
Introduction
The House Control 402 is designed to operate as part of a complete hydronic heating system with tekmarNet®2 (tN2) thermostats. It can provide operation of two outdoor reset water temperatures such as radiant floor heating on the first temperature and baseboard or fan coil heating on the second temperature. In addition the control has Domestic Hot Water and Setpoint capabilities. It is easy to add more zones, add schedules or other convenient accessories through the use of the tekmarNet®4 (tN4) Expansion terminals.
D 402
HVAC Systems
Features
Single on-off, two-stage or modulating boiler
Boiler outdoor reset temperature
Mixing outdoor reset temperature
Domestic Hot Water tank operation
Setpoint operation
Mix with variable speed injection, floating action, or proportional 0-10 V (dc), proportional 4-20 mA
For use with tekmarNet Four 24 V (ac) powered zone valve outputs
• Expand to 24 zones per temperature using
• tekmarNet®4 expansion ports
CSA C US Certified for use in USA and Canada
®
2 Thermostats
Replaces: 01/10
09/10
VIEW
Calls
Pumps
Boil Exp Boil System
Menu
Item
House Control 402
Zones 1 2 3 4
Benefi ts
Energy efficiency through Outdoor Temperature
• Reset with Indoor Feedback
Indoor Feedback minimizes the water temperature
• (increasing energy savings), and the efficiency of your mechanical equipment through integrated tekmarNet® Thermostats
Zone Synchronization reduces equipment cycling
• Auto Differential - Reduces boiler cycling
• Compact enclosure for flexible installation
• Simple zone expansion using Wiring Centers
1 of 32 © 2010 D 402 - 09/10
Page 2
Table of Contents
---------------------------------------------------------------------------------------
Installation ...................................................................... 2
Preparation ................................................................ 2
Physical Dimensions ................................................. 3
Installation Location .................................................. 3
Rough-In Wiring ........................................................ 3
Sizing the Transformer .............................................. 4
Control Wiring ........................................................... 4
Sensor Wiring ............................................................ 7
Testing the Sensor Wiring ......................................... 9
Testing the Control Wiring ......................................... 9
Max Heat ..................................................................10
Applic ations .................................................................. 11
User Interface ............................................................... 13
Display......................................................................13
Symbols ...................................................................13
Navigating The Display ............................................14
Access Levels and Thermostat Lock ........................14
Programming and Settings .......................................14
View Menu ...............................................................15
Adjust Menu ........................................................16-18
Monitor Menu ...........................................................19
Toolbox Menu .......................................................... 20
Sequence of Operation ................................................21
tekmarNet
Mix Temperature Reset Operation ...........................21
Boiler Temperature Reset Operation ....................... 22
Domestic Hot Water Tank Operation ....................... 23
Setpoint Operation .................................................. 25
Boiler Operation ...................................................... 25
Domestic Hot Water Heat Source ............................27
Pump Operation .......................................................27
Energy Saving Features .......................................... 28
Trouble shooting ............................................................ 28
Error Messages .................................................. 28-30
Frequently Asked Questions .............................. 30-31
Job Record ...............................................................31
Technical Data ..............................................................32
Limited Warranty and Product Return Procedure ........32
®
System ..................................................21
Getting Started
®
Congratulations on the purchase of your new tekmarNet This manual covers the complete installation, programming and sequence of operation for this control. You will also find
instruction on testing, commissioning, and troubleshooting the control and system that it operates.
House Control!
Installation
Caution
Improper installation and operation of this control could result in damage to the equipment and possibly even personal injury or death. It is your responsibility to ensure that this control is safely installed according to all applicable codes and standards. This electronic control is not intended for use as a primary limit control. Other controls that are intended and certified as safety limits must be placed into
Radio Frequency Interference
The installer must ensure that this control and its wiring are isolated and/or shielded from strong sources of electromagnetic noise. Conversely, this Class B digital apparatus complies with Part 15 of the FCC Rules and meets all requirements of the Canadian Interference-Causing Equipment Regulations. However, if this control does cause harmful interference to radio or television reception, which is determined by turning the control off and on, the user is encouraged to try
Preparation
the control circuit. Do not attempt to service the control. Refer to qualified personnel for servicing. There are no user serviceable parts. Attempting to do so voids warranty and could result in damage to the equipment and possibly even personal injury or death.
to correct the interference by re-orientating or relocating the receiving antenna, relocating the receiver with respect to this control, and/or connecting the control to a different circuit from that to which the receiver is connected.
Cet appareil numérique de la classe B respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.
Tools Required
tekmar or jeweller screwdriver
• Phillips head screwdriver
© 2010 D 402 - 09/10 2 of 32
---------------------------------------------------------------------------------------
Needle-nose Pliers
• Wire Stripper
Page 3
Materials Required
-----------------------------------------------------------------------------------
--------------------------------------------------------------------------------------
-----------------------------------------------------------------------------------
(2) #10 x 1” Wood Screws
• (3) Wire Nuts
• 18 AWG LVT Solid Wire (Low Voltage Connections)
-----------------------------------------------------------------------------------
14 AWG Solid Wire (Line Voltage Connections)
• tekmar 009K (24 V (ac) transformer with 4” x 4” junction box)
• Cable or Conduit Connectors
Power Required
120 V (ac), 1-phase, 15 A service from circuit breaker
Power disconnect (optional)
--------------------------------------------------------------------------------------
panel
Physical Dimensions
Side ViewCover Off Front View Back View
1/2” Knock-out (x 4)
Contro l designed to mo unt on 4” x 4” elect rical box (not include d). Electr ical box shown comes wit h 009K
tN2 C
ClsOpn
Floating Action
Boil Exp. Mix Exp.
tN4 tN4C C
+
Mod dc/mA
Stage 2Stage 1
Input Power
Use at least 167°F (75°C) conductors
VlvC
RC
2–1/4”
(57 mm)
2–1/4”
(57 mm)
5–1/2”
(140 mm)
7/8”
(22 mm)
CL
Made in Canada
Mix ComBoil Out DHW Com
Sensors - No Power
Setpoint DHW
Call Call
H8007B
1–1/8”
(30 mm)
tN2 tN2 tN2 tN2 tN2 tN2 tN2 Zone 1
Zone 2 Zone 3 Zone 4
Menu
Item
House Control 402
Zone 3Zone 1 Zone 2 Zone 4
VlvC VlvC VlvC
5–1/2”
(140 mm)
1/2” x 5/8”
(12 mm x 16 mm)
Knock-out (x 4)
Pump Power L
Speed Pump
∅1/ 8”
(3 mm)
Boil System Pump
DHW Pump
Variable
Mix System Pump
7/8” x 1/2” (23 mm x 12 mm)
Knock-out (x 4)
Installation Location
When choosing the location for the control, consider the
• following:
Keep dry. Avoid potential leakage onto the control.
• RH 90% to 104°F (40°C). Non-condensing environment.
Do not expose to operating temperatures beyond 32-
• 104°F (0-40°C)
Provide adequate ventilation.
• Keep away from equipment, appliances or other
• sources of electrical interference.
Rough-In Wiring
Line Voltage Wiring
The control operates a number of pumps through wiring on the back of the control. The control must be mounted to a 4” x 4” electrical junction box so that these electrical connections are safely contained.
For ease of service, the circuit breaker or power disconnect should be located in reasonably close proximity to the equipment.
All line voltage wire connections are recommended to be pulled inside a flexible or solid conduit. Always follow proper wiring practices, building and electrical codes for your jurisdiction.
-----------------------------------------------------------------------------------
Locate the control near pumps and/or zone valves if
• possible.
Provide easy access for wiring, viewing and adjusting
• the control.
Mount approximately 5 ft. (1.5 m) off the finished floor.
• Install the electrical junction box to a wall using #10
• x 1” wood screws. Wall anchors are recommended when mounting to sheet rock wallboard or masonry.
Each cable must be pulled from the equipment to the electrical junction box. It is recommended to label each cable for easy identification. All line voltage wires should be stripped to a length of 1/2” (13 mm).
Pull a three conductor 14 AWG cable for the following equipment:
Circuit Breaker or Power Disconnect
• Mix System Pump
• Boiler System Pump
• DHW Tank Pump (if applicable)
• Variable Speed Injection Pump (if applicable)
3 of 32 © 2010 D 402 - 09/10
Page 4
-----------------------------------------------------------------------------------
Low Voltage Wiring
-----------------------------------------------------------------------------------
Each cable must be pulled from the equipment to the control’s plastic enclosure. All low voltage wiring connections enter the enclosure through conduit knockouts on the sides, or through the square knockouts on the rear. It is recommended to label each cable for easy identification. All low voltage wires are to be stripped to a length of 3/8” (9 mm) to ensure proper connection to the control.
Pull two conductor 18 AWG LVT cable, up to 500 feet (150 m) for the following equipment:
tekmarNet®2 Thermostats
• Zone Valves
• Mixing Valve Actuator Proportional 0-10 V (dc)
• Boiler Stage 1 T-T
-----------------------------------------------------------------------------------
Sizing the Transformer
The control requires an external transformer. A tekmar Transformer 009 (or 009K which includes a 4”x 4” electrical box) can supply up to 40 VA, and includes an in-line fuse to protect the transformer and control.
In order to correctly size the external transformer, all loads connected to the control must be taken into account.
When adding up the loads, consider the following:
tekmarNet®2 Thermostats draw approximately 2 VA each.
• Each zone valve must be sized for peak load. This can
• be obtained by multiplying the peak current draw (in Amps) by 24 V (ac).
Boiler Stage 2 T-T (if applicable)
• Modulating Boiler 0-10 V (dc) or 4-20 mA (if applicable)
• Outdoor Temperature Sensor
• Boiler Supply Temperature Sensor
• Mix Supply Temperature Sensor
• DHW Tank Temperature Sensor (if applicable)
• DHW Tank Aquastat (if applicable)
• Setpoint Devices (if applicable)
Pull three conductor 18 AWG LVT cable for the following equipment:
Mixing Valve Actuator Floating Action
• tekmarNet®4 Accessories (User Switch, Timer)
If using a Floating Action mixing valve, add the VA
• draw for the actuating motor. A tekmar Actuating Motor 741 draws 1.5 VA during normal operation.
The total power capacity of the power supply should be larger than the total load of all the devices connected to the control. This total load must not exceed 100 VA. Multiple tekmar Transformer 009’s can be wired together to increase total VA capacity.
The following chart is provided to simplify transformer sizing:
Zone
Thermostat Load
Zone Valve Load
Total Zone Load
1234
Floating
Action (VA)
+ +++ +
Control
Load (VA)
Control Wiring
Line Voltage Wiring
CAUTION: TURN ALL POWER OFF BEFORE PERFORMING ANY WIRING.
Ground the Pumps
Connect the pump grounds to the power supply
• ground as shown in Figure 1. The ground wire must also be grounded to the electrical box.
Wire the Pump Neutrals
Connect the Neutral (N) wires from each pump and wire
• to the 115 V (ac) Neutral (N) wire. If the transformer has been mounted to this electrical box, connect its neutral wire with this group. This is shown in Figure 2.
-----------------------------------------------------------------------------------
Wire the Pump Power (L)
Connect the 115 V (ac) line voltage (L) wire to the red
• Pump Power (L) wire on the back of the House Control and to the 115 V (ac) side of the transformer. Use a wire nut or approved connector. See Figure 3.
Wire the Pumps
Wire each remaining line voltage pump wire into the
• push-in wire connector of the corresponding pump lead on the back of the House Control. This is shown in Figure 4.
Transformer
must exceed:
2
VA
© 2010 D 402 - 09/10 4 of 32
Page 5
Figure 1 - Connect
-------------------------------------------------------------------
Ground Wires
Variable Speed Pump
Figure 2 - Connect Neutral Wires
Variable Speed Pump
Pump
Pump
DHW Pump
Pump
Boil System Pump
Figure 3 - Connect Line Voltage (Hot)
V. S. Pump
DHW Pump
Boil Sys Pump
Mix System
Pump
Mix System
Pump
Power
Source
(L,N)
Pump
Power Source
(L,N)
402
Mix System Pump
Boil System Pump
DHW Pump
Strip wires
Variable
1/2 inch (13 mm).
Speed Pump
Installed wires are not remov
able.
Pum
p Power L
12-18
AWG
Pump
DHW Pump
Boil System Pump
Figure 4 - Connect Pump Line (Hot)
V. S. Pump
DHW Pump
Boil Sys Pump
Mix System
Pump
Pump
Pump
Power
Source
(L,N)
Mix System
Pump
Pump
402
Mix System Pump
Boil System Pump
DHW Pump
Variab le Speed Pump
Pump Power L
Power Source
(L,N)
Strip wires 1/2 inch (13 mm). Installed wires are not removable. 12-18 AWG
Rear Line Voltage Wiring Diagram
N
G
L
N
115 V (ac)
-------------------------------------------------------------------
Back of House Control 402
Mix
(black)
Mix System Pump
Boil
(black)
Boil System Pump
DHW
(black)
DHW Pump
(red)
Pump Power L
L
Variable
Speed
to pump grounds
(blue)
Variable Speed Pump
Strip wires 1/2 inch (13 mm). Installed wires are not removable. 12-18 AWG
5 of 32 © 2010 D 402 - 09/10
Page 6
-----------------------------------------------------------------------------------
Install The Enclosure
---------------------------------------------------------------------------------
Ensure that the pump wires are neatly tucked inside
---------------------------------------------------------------------------------
the electrical box. Using 2 of the 4 holes in the back of the enclosure, se-
• curely fasten it to the electrical junction box with 2 #10 screws as shown in Figure 5.
Figure 5
Low Voltage Wiring
-----------------------------------------------------------------------------------
External Power Supply
It is strongly recommended that a transformer with an in-line fuse be used in order to protect the transformer from high currents. The tekmar Transformer 009 includes a fuse.
Connect the 24 V (ac) leads from the transformer to the
• C and R terminals marked “Input Power” on the 402.
tN2 Thermostats
The 402 is designed to operate with tekmarNet®2 Thermostats. They provide the heating and cooling control for each zone, and communicate with any other tekmarNet® device on the system.
Connect the tN2 terminals from each thermostat to the
• corresponding tN2 terminals for each zone on the 402.
Zone Valves
Wire the zone valves to the C and Vlv terminals on the
402. End switches on zone valves are not required when
• using the 402.
tN4 Expansion Terminals
The 402 uses the Expansion tN4 and C terminals to communicate with additional thermostats, setpoint controls, and other tekmarNet® devices. There are two sets of tN4 and C terminals on the 402.
Boil Exp.
To add additional boiler water temperature zones (typically baseboard or fan coil zones) to the system, install a tekmarNet® Wiring Center.
Connect the tN4 and C Boil Exp. terminals on the 402
• to the corresponding tN4 and C Expansion terminals on the external Wiring Center.
Mix Exp.
The 402 has the capacity to expand the number of mixing zones in the system beyond the four on board zones. To add additional mix water temperature zones (typically radiant floor zones) to the system, install a tekmarNet Wiring Center.
Connect the tN4 and C Mix Exp. terminals on the 402
• to the corresponding tN4 and C Expansion terminals on the external Wiring Center.
Domestic Hot Water (DHW) or Setpoint Call
When the control receives a DHW Call or Setpoint Call for heat it will override Outdoor Reset and Indoor Feedback and operate the boiler to heat the DHW tank or the Setpoint equipment.
To create a DHW call, wire a dry contact OR apply 24
• V (ac) to the DHW call terminals.
To create a Setpoint call, wire a dry contact OR apply
• 24 V (ac) to the Setpoint call terminals.
Wiring the Boiler
The 402 can operate a single modulating boiler, single on-off, or a single two-stage on-off boiler.
On/Off Boiler
Connect the Boiler Stage 1 terminals on the 402 to the
• T-T (or R-W) terminals on the boiler.
If required, connect the Boiler Stage 2 terminals on the
• 402 to the second stage T-T (or R-W) terminals on the boiler.
Modulating Boiler
Wire the Mod (dc/mA) positive (+) and negative (-) ter-
• minals on the 402 to the input signal terminals on the boiler. Correct polarity of the wires is important.
In some cases, the modulating boiler also requires
• contact closure on the T-T terminals to fire the boiler. If required, connect the Boiler Stage 1 terminals on the 402 to the T-T (or R-W) terminals on the boiler.
Floating Action Terminals
Applications that use a floating action mixing valve actuator (tekmar type 741) will use the Floating Action Opn, Cls, and C terminals. This is a powered output (24 V (ac)).
Wire the Opn, Cls, and C terminals on the 402 to the
• open, close, and C terminals on the floating action actuator.
Proportional Mixing (0-10 V (dc) or 4-20 mA)
®
Applications that use a proportional mixing valve actuator will use the Mod (dc/mA) terminals. Proportional mixing can only be used when a modulating boiler is not installed.
Wire the Mod positive (+) on the 402 to the positive (+)
• terminal on the actuator.
Wire the Mod negative (-) on the 402 to the negative (-)
• or common terminal on the actuator.
© 2010 D 402 - 09/10 6 of 32
Page 7
R C
L
N
Com Open Close
Expansion
tN4 Boil
CtN4
Modulating
Boiler
—+
Expansion
tN4 Mix
CtN4
2
1
WC
WC
Menu
House Control 402
Item
+
Mix ComBoil Out DHW
VlvC VlvC VlvC
Zone 3Zone 1 Zone 2 Zone 4
Made in Canada
VlvC
Com
Zone 1
H8007B
Zone 2 Zone 3 Zone 4
tN2 tN2 tN2 tN2 tN2 tN2 tN2 tN2
C
Floating Action
ClsOpn
Sensors - No Power
Call Call
tN4 tN4CC
Mod dc/mA Boil Exp. Mix Exp.
Setpoint DHW
Use at least 167°F (75°C) conductors
RC
Input Power
Stage 2Stage 1
Front Low Voltage Wiring Diagram
-------------------------------------------------------------------
--------------------------------------------------------------------
tekmarNet
Mix Supply
Sensor 082
Outdoor
Sensor
070
Boiler Supply
Sensor 082
DHW Tank
Sensor 082
Setpoint Call
-------------------------------------------------------------------
®
2 Thermostats
24 V (ac) Floating
Action Actuator
tekmarNet®4 Expansion to
Wiring Centers,
Timers, or
User Switch
One or Two Stage
Boiler T-T
DHW Call
from DHW
Tank Aquastat
(optional)
Zone Valves
Sensor Wiring
Mounting the Outdoor Sensor 070
Note: The temperature sensor (thermistor) is built into the 070 enclosure.
Remove the screw and pull the front cover off the
• sensor enclosure.
The 070 can either be mounted directly onto a wall or
• a 2” x 4” electrical box. When the 070 is wall mounted, the wiring should enter through the back or bottom of the enclosure. Do not mount the 070 with the conduit knockout facing upwards as rain could enter the enclo­sure and damage the sensor.
--------------------------------------------------------------------
24 V (ac) Transformer 009
In order to prevent heat transmitted through the wall
• from affecting the sensor reading, it may be necessary to install an insulating barrier behind the enclosure.
The 070 should be mounted on a wall which best rep-
• resents the heat load on the building (a northern wall for most buildings and a southern facing wall for build­ings with large south facing glass areas). The 070 should not be exposed to heat sources such as venti­lation or window openings.
The 070 should be installed at an elevation above
• the ground that will prevent accidental damage or tampering.
Sensor with rear entry wiring
Sensor with bottom entry wiring
7 of 32 © 2010 D 402 - 09/10
Sensor mounted onto 2" x 4" electrical box
Page 8
Wiring the Outdoor Sensor 070
-----------------------------------------------------------------------
-------------------------------------------------------------
Connect 18 AWG or similar wire to the two terminals
-----------------------------------------------------------------------
provided in the enclosure and run the wires from the 070 to the control. Do not run the wires parallel to tele­phone or power cables. If the sensor wires are located in an area with strong sources of electromagnetic in­terference (EMI), shielded cable or twisted pair should be used or the wires can be run in a grounded metal conduit. If using shielded cable, the shield wire should be connected to the Com or Com Sen terminal on the control and not to earth ground.
Follow the sensor testing instructions in this brochure
• and connect the wires to the control.
Replace the front cover of the sensor enclosure.
Wires from outdoor
sensor to control
terminals
(Com Sen - Out Sen)
Sensor is built into
the enclosure
Mounting the Boiler and Mix Sensor 082
-------------------------------------------------------------
Note: These sensors are designed to mount on a pipe or in a temperature immersion well.
The Universal Sensor should be placed downstream of a pump or after an elbow or similar fitting. This is especially important if large diameter pipes are used as the thermal stratification within the pipe can result in erroneous sensor readings. Proper sensor location requires that the fluid is thoroughly mixed within the pipe before it reaches the sensor.
Strapped to Pipe
The Universal Sensor can be strapped directly to the pipe using the cable tie provided. Insulation should be placed around the sensor to reduce the effect of air currents on the sensor measurement.
Immersion Well
If a Universal Sensor is mounted onto 1” (25 mm) diameter L type copper pipe, there is approximately an 8 second delay between a sudden change in water temperature and the time the sensor measures the temperature change. This delay increases considerably when mild steel (black iron) pipe is used. In general, it is recommended that a temperature well be used for steel pipe of diameter greater than 1-1/4” (32 mm). Temperature wells are also recommended when large diameter pipes are used and fluid stratification is present.
Conduit Connection
The Universal Sensor 082 and Universal Sensor Enclosure 080 (sold separately) are specifically designed to mount onto a 3/8” (10 mm) ID temperature well that is supplied with an end groove. To install the well, plumb a ‘T’ into the pipe and fix the well into the ‘T’. The 080 enclosure has a 7/8” (22 mm) back knockout that must be removed and fitted over the temperature well. The 082 is then inserted into the well and the retaining clip supplied with the enclosure is snapped onto the well end groove. If the well has a threaded end, the installer must supply a standard threaded conduit retaining ring. The two wires from the sensor are connected to the terminal block provided in the enclosure. The other side of the terminal block is used to connect wires from the control.
Retaining Clip
Universal Sensor 082
Universal Sensor 082
Sensor Well
Bottom of Enclosure 080
Cable Tie
© 2010 D 402 - 09/10 8 of 32
Page 9
Testing the Sensor Wiring
------------------------------
-----------------------
--------------------------------------
A good quality test meter capable of measuring up to 5,000 kΩ (1 kΩ = 1000 Ω) is required to measure the sensor resistance. In addition to this, the actual temperature must be measured with either a good quality digital thermometer, or if a thermometer is not available, a second sensor can be placed alongside the one to be tested and the readings compared.
First measure the temperature using the thermometer and then measure the resistance of the sensor at the control. The wires from the sensor must not be connected to the
estimate the temperature measured by the sensor. The sensor and thermometer readings should be close. If the test meter reads a very high resistance, there may be a broken wire, a poor wiring connection or a defective sensor. If the resistance is very low, the wiring may be shorted, there may be moisture in the sensor or the sensor may be defective. To test for a defective sensor, measure the resistance directly at the sensor location.
Do not apply voltage to a sensor at any time as damage to the sensor may result.
control while the test is performed. Using the chart below,
TemperatureResistanceTemperatureResistanceTemperatureResistanceTemperatureResistance
°F °C
-50 -46 490,813 20 -7 46,218 90 32 7,334 160 71 1,689
-45 -43 405,710 25 -4 39,913 95 35 6,532 165 74 1,538
-40 -40 336,606 30 -1 34,558 100 38 5,828 170 77 1,403
-35 -37 280,279 35 2 29,996 105 41 5,210 175 79 1,281
-30 -34 234,196 40 4 26,099 110 43 4,665 180 82 1,172
-25 -32 196,358 45 7 22,763 115 46 4,184 185 85 1,073
-20 -29 165,180 50 10 19,900 120 49 3,760 190 88 983
-15 -26 139,402 55 13 17,436 125 52 3,383 195 91 903
-10 -23 118,018 60 16 15,311 130 54 3,050 200 93 829
-5 -21 100,221 65 18 13,474 135 57 2,754 205 96 763 0 -18 85,362 70 21 11,883 140 60 2,490 210 99 703 5-15 72,918 7524 10,501 14563 2,255 215102 648
10 -12 62,465 80 27 9,299 150 66 2,045 220 104 598 15 -9 53,658 85 29 8,250 155 68 1,857 225 107 553
°F °C °F °C °F °C
Testing the Control Wiring
Testing the Power
If the control display does not turn on, check the Input Power wiring terminals using an electrical multimeter. The voltage should measure between 21.6 to 26.4 V (ac). If the voltage is below this range, measure the line voltage side of the transformer. The voltage should measure between 103.5 to 126.5 V (ac).
Testing the Thermostats
If the thermostat display turns on, this indicates that the thermostat is operating correctly and there are no electrical issues. In the event that the display is off, or the display is cycling on and off, follow this procedure.
1. Remove the tN2 wires from the thermostat.
2. Use an electrical meter to measure DC voltage between the tN2 terminals.
If the DC voltage is 0 V (dc) for 20 seconds, then there is an open or short circuit in the tN2 wires. If the DC voltage is 0 V (dc) for 10 seconds and then is 23 to 24 V (dc) for 5 seconds, this indicates the wiring is correct.
3. Connect the thermostat to the tN2 wires from a zone on a House Control, Wiring Center, or Zone Manager.
4. If the thermostat display is off, or is cycling on and off, move the thermostat to the next available zone on the House Control, Wiring Center, or Zone Manager.
If the thermostat display remains permanently on, there may be a fault with the previously tried zone on the House Control, Wiring Center, or Zone Manager.
------------------------------
-----------------------
If the thermostat display continues to be off, or is cycling on and off, there may be a fault on the thermostat. If a fault is suspected, contact your tekmar sales representative for assistance.
User Test
--------------------------------------
The User Test is found in the Toolbox menu of the control. Press the Menu button to access the Toolbox Menu. Press the Item button to locate the User Test. Start the test sequence by going to the User Test item and pressing the ‘Up’ arrow button. Pause the test sequence by pressing the Item button. To advance to the next step, press the Item button again. If the test sequence is paused for more than five minutes, the control exits the entire test routine and returns to normal operation. To advance to a particular step, repeatedly press and release the Item button to display the appropriate device.
User Test Sequence
Step 1
The Mix 1 device ramps up to 100% over 30 seconds or according to the motor speed setting.
Step 2
The Mix 1 device ramps down to 0% over 30 seconds
or according to the motor speed setting. Step 3 Step 4 Step 5 Step 6 Step 7
Zone 1 turns on for 10 seconds.
Zone 2 turns on for 10 seconds.
Zone 3 turns on for 10 seconds.
Zone 4 turns on for 10 seconds.
The mix system pump turns on for 10 seconds.
9 of 32 © 2010 D 402 - 09/10
Page 10
Step 8
----
----------------------
-----------------
------------------------
---------------
-------------
-------------
----------
--------------------------
----------------------
Step 9
Step 10
Step 11
Testing the Variable Speed Injection Pump
Activate the User Test sequence and pause at Step 1 by pressing the Item button once the injection pump is operating at 100%. Using an electrical meter, measure the voltage between the variable speed pump and a neutral. The voltage should measure between 103.5 V (ac) and
126.5 V (ac).
Testing the Zone Output
Activate the User Test sequence and pause at Step 3 by pressing the Item button once Zone 1 turns on. Using an electrical meter, measure the voltage between the zone valve and the common (C) terminals. The voltage should measure between 21.6 V (ac) and 26.4 V (ac). Repeat for Zones 2, 3, and 4.
Testing the Mix System Pump
Activate the User Test sequence and pause at Step 7 by pressing the Item button once the mix system pump turns on. Using an electrical meter, measure the voltage between the mix system pump and a neutral. The voltage should measure between 103.5 V (ac) and 126.5 V (ac).
The DHW pump turns on for 10 seconds. The boiler system pump turns on for 10
seconds. During the boiler test step, zone relays 1 through 4
turn on, the mix system pump turns on, and the boil system pump turns on. The mixing device operates up to 20%. This ensures there is a location for heat to move when the boiler is turned on.
If the Boil Type is 1 Stage, the boiler stage 1 relay is closed for 10 seconds and then opened.
If the Boil Type is 2 Stage, the boiler stage 1 relay is closed for 10 seconds, then the boiler stage 2 relay is closed for 10 seconds and then both relays are opened.
If Boiler Type is modulating 0 - 10, the boiler stage 1 relay is closed for 10 seconds and the modulating output operates at 50 % [5 V (dc)].
If Boiler Type is modulating 4 - 20, the boiler stage 1 relay is closed for 10 seconds and the modulating output operates at 50 % (12 mA).
Control returns to normal operation.
----
----------------------
-----------------
Testing the DHW Pump
Activate the User Test sequence and pause at Step 8 by pressing the Item button once the DHW pump turns on. Using an electrical meter, measure the voltage between the DHW pump and a neutral. The voltage should measure between 103.5 V (ac) and 126.5 V (ac).
Testing the Boiler System Pump
Activate the User Test sequence and pause at Step 9 by pressing the Item button once the boiler system pump turns on. Using an electrical meter, measure the voltage between the boiler system pump and a neutral. The voltage should measure between 103.5 V (ac) and 126.5 V (ac).
Testing the Boiler Stage 1 Contact
Activate the User Test sequence and pause at Step 10 by pressing the Item button once the boiler stage 1 turns on. Using an electrical meter, measure for continuity over the boiler stage 1 terminals.
Testing the Boiler Stage 2 Contact
This test applies for 2 stage on-off boilers only. Activate the User Test sequence and pause at Step 10 by pressing the Item button once the boiler stage 2 turns on. Using an electrical meter, measure for continuity over the boiler stage 2 terminals.
Testing the Boiler Modulating Output
This test applies for modulating boilers only. Active the User Test sequence and pause at Step 10 by pressing the Item button once the boiler stage 1 turns on. Using an electrical meter, measure for either a 5 V (dc) or 12 mA signal. The Boil Type setting selects whether the signal is V (dc) or mA.
Testing the DHW Call
Remove all wires from the DHW Call terminals. The control display should show no DHW Call. Reconnect wires. Then apply either a short circuit or 24 V (ac) over the DHW Call terminals. The control should now show a DHW Call.
Testing the Setpoint Call
Remove all wires from the Setpoint Call terminals. The control display should show no Setpoint Call. Reconnect wires. Then apply either a short circuit or 24 V (ac) over the Setpoint Call terminals. The control should now show a Setpoint Call.
------------------------
---------------
-------------
-------------
----------
--------------------------
----------------------
Max Heat
The control has a function called Max Heat. In this mode, the control turns on and operates the system up to the maximum set temperatures as long as there is a call for heat. Use this mode to run the circulators during system start-up and commissioning, purging air from the piping. This feature is useful when drying sheet rock and paint in the building.
To enable Max Heat, enter the Toolbox Menu and find Max Heat. Use the up arrow to select ‘On’.
When a space heating call is present, the boiler will
• run to maintain a target of Boil Design + 10°F (+ 6°C). (One can purge the system using this test and leave
© 2010 D 402 - 09/10 10 of 32
the boiler un-powered. This will prevent heat from en­tering the system during the purge.)
When a DHW Call or Setpoint Call is present, the
• boiler will operate at the DHW exchange or Setpoint temperature settings.
WWSD and DHW Priority is disabled during Max Heat
• mode.
When Max Heat is on the display will show ‘Max Heat
• Test ’.
Max Heat will automatically turn off after 24 hours.
To Cancel Max Heat, go to Max Heat in the Toolbox menu and use the down arrow to select ‘Off’.
Page 11
Applications
Single Boiler, DHW Tank, Variable Speed Mixing, 4 Mix Zones A402-1
Description: The House Control 402 operates an On/Off boiler with indirect Domestic Hot Water. Mixing is performed with
variable speed injection, which supplies an outdoor reset water temperature to the 4 onboard mix temperature hydronic zones. Additional zones (boiler or mix) can be added using the tN4 Expansion terminals.
Outdoor
Sensor
(S3)
P2
Mix Sensor (S2)
Boiler Sensor (S1)
S3
P1
tekmarNet
Made in Canada
Mix ComBoil Out DHW Com
Sensors - No Power
Setpoint DHW
Call Call
Menu
H8007B
VlvC VlvC VlvC
070
402
P3 P4
®
2 Thermostats
tN2 tN2 tN2 tN2 tN2 tN2 tN2 tN2
Zone 1
Zone 2 Zone 3 Zone 4
Item
House Control 402
Zone 3Zone 1 Zone 2 Zone 4
VlvC
Input Power
C
Floating Action
Use at least 167°F (75°C) conductors
RC
tekmarNet®2 Thermostats
Z1 Z2 Z3 Z4
S2S1
ClsOpn
tN4 tN4CC
+
Mod dc/mA Boil Exp. Mix Exp.
Stage 2Stage 1
CtN4
CtN4
1
tN4 Mix Expansion
tN4 Boil Expansion
tekmarNet®4 Expansion to
Wiring Centers,
Timers, or
User Switch
DHW Call
L
115 V (ac)
Boiler T-T
R C
24 V (ac)
L N
Transformer 009
Zone Valves (Z1 to Z4)
Back of House Control 402
(black)
(P4)
(P1)
(P2)
Mix
Boil
DHW
(black)
(black)
(red)
L
Variable
Speed
N
G
N
(P3)
to pump grounds
(blue)
Mix System Pump
Boil System Pump
DHW Pump
Pump Power L
Variable Speed Pump
Strip wires 1/2 inch (13 mm). Installed wires are not removable. 12-18 AWG
11 of 32 © 2010 D 402 - 09/10
Page 12
Single Boiler, 2 Boiler Zones, DHW, 3 Way Mix, 4 Mix Zones A402-2
Description: The House Control 402 operates a modulating boiler with indirect Domestic Hot Water. Mixing is performed with
a three-way floating action mixing valve, which supplies a reset water temperature to four mix temperature hydronic zones. Two boiler water temperature zones shown are operated by a Wiring Center through the tN4 Boil Expansion terminals.
Outdoor
Sensor
(S3)
P2
S1
Mix Sensor (S2)
Boiler Sensor (S1)
DHW Sensor (S4)
S4
P1
tekmarNet
Made in Canada
Mix ComBoil Out DHW Com
Sensors - No Power
Setpoint DHW
Call Call
H8007B
S3
313
®
2 Thermostats
tN2 tN2 tN2 tN2 tN2 tN2 tN2 tN2
Zone 1
Zone 2 Zone 3 Zone 4
Menu
Item
House Control 402
Zone 3Zone 1 Zone 2 Zone 4
VlvC VlvC VlvC
070
VlvC
Input Power
402
C
Floating Action
Use at least 167°F (75°C) conductors
RC
P3
ClsOpn
tN4 tN4CC
+
Mod dc/mA Boil Exp. Mix Exp.
Stage 2Stage 1
tekmarNet®2 ThermostatstekmarNet®2 Thermostats
Z1 Z2 Z3 Z4
S2
Com Open Close
1
CtN4
tN4 Mix Expansion
CtN4
tN4 Boil Expansion
—+
Modulating
Boiler
tekmarNet Expansion to
313
Wiring Centers,
Timers, or
User Switch
®
4
Zone Valves (Z1 to Z4)
Back of House Control 402
(black)
(P3)
(P1)
(P2)
Mix
Boil
DHW
(black)
(black)
(red)
L
(blue)
to pump grounds
G
L
N
115 V (ac)
© 2010 D 402 - 09/10 12 of 32
Mix System Pump
Boil System Pump
DHW Pump
Pump Power L
Variable Speed Pump
R C
Strip wires 1/2 inch (13 mm). Installed wires are not removable. 12-18 AWG
24 V (ac)
L N
Transformer 009
Page 13
User Interface
Display
Menu Field
Displays the
current menu
Status Fields
Displays the current
status of the control’s
inputs, outputs and
operation. Most symbols
in the status field are only visible when the
VIEW Menu is selected
Symbols
VIEW ADJUST
MONITOR
MAXMIN
Calls
Boil Exp
Mix Exp
DHW Setp
Pumps WWSD Saving
Boil System
Mix System Zones
DHW Var 1 2 3 4
1 2
min
sec
PM
hr
AM
Cls
Opn
Mix
Item Field
Displays the name of the selected item
Number Field
Displays the current value of the selected item
Calls
Pumps
Zones
1 2 3 4
Saving
WWSD
CALLS
Displays any call for heat the control is receiving.
PUMPS
Displays any pump currently operating.
ZONES
Displays if an on-board zone is operating.
WARNING
Displays if an error exists on the system.
ENERGY SAVING INDICATOR
Displays when the system is saving energy. See the Energy Saving Features section.
WWSD
Displays when the system is in Warm Weather Shut Down.
°F°C
minhr
sec%
Cls
Opn
MAXMIN
°F, °C, %, HOURS, MINUTES, SECOND
Units of measurement for current number.
UNOCCUPIED
Indicates that a User Switch or Timer has put the system into UnOccupied.
BOILER
Indicates that the boiler should be heating.
DEVICE OUTPUT SCALE
Displays output of the mixing valve or injection pump.
CLOSE / OPEN
Displays whether the mixing valve motor is opening or closing.
MIN / MAX
Displays when an operating temperature reaches a minimum or maximum value.
13 of 32 © 2010 D 402 - 09/10
Page 14
Navigating The Display
-----------------------------------------------------------------------------------------
------------------------------------------------------------------------------------------
--------------------------------------------------------------------------------
------------------------------------------------------------------------------------------
The 402 uses a simple user interface to accomplish a variety of functions. The four buttons beneath the display
Menu Button
The menus display in the Menu Field at the top left side of the LCD. Four menus are available: View, Adjust, Monitor and Toolbox (identified by the wrench symbol).
The View menu allows the user to view the current
• status of various system parameters.
The Adjust menu allows the installer to adjust settings
• to ensure control operation matches requirements of the mechanical system.
Item Button
Each menu contains a list of Items that can be viewed and, in some cases, adjusted. Press the item button to scroll through the list in each Menu.
Up and Down Buttons
The Up and Down buttons are primarily used for adjusting settings.
-----------------------------------------------------------------------------------------
------------------------------------------------------------------------------------------
--------------------------------------------------------------------------------
are used to change the menu, sort through Items, and adjust each setting as required.
The Monitor menu keeps track of run times and
• other important data that is collected during system operation.
The Toolbox menu is a source of system information
• and includes useful tools for commissioning and test­ing the system.
To view the next available item, press and release the
• Item button.
To view the previous item, hold down the Item button,
• and press and release the Up button.
To adjust a setting:
Select the appropriate menu using the Menu button.
• Select the item using the Item button.
• Use the Up or Down button to make the adjustment.
Default Item
When navigating menus, the display reverts back to the default item (View Menu) after 60 seconds of button inactivity.
------------------------------------------------------------------------------------------
Access Levels and Thermostat Lock
The 402 is shipped pre-programmed with common settings. The 402 has an ‘Installer’ access level that allows full access to all settings and a ‘User’ access level that restricts the number of settings to only the Warm Weather Shut Down and the temperature units. The 402 defaults to the ‘User’ access level after 12 hours of operation.
All thermostats are locked while the 402 is in the ‘User’ access level. Certain settings on the thermostat will be unavailable while the thermostat is locked.
Programming and Settings
The 402 settings can be found in the ‘Adjust’ menu. When changing the items value, the setting is saved to the control’s memory once the Item button is pressed to advance to the next item, or after 60 seconds, the control times out and reverts back to the ‘View’ menu.
To set the default item in the View menu, display the
• item for more than five seconds.
To change to the ‘Installer’ access level and Unlock the thermostats:
In the Toolbox menu, locate Access
• Adjust the access level to ‘Installer’ by pressing the
• up or down button. This prevents unwanted setting changes to the control.
All settings are stored in permanent memory and will be kept correctly during any loss of power.
© 2010 D 402 - 09/10 14 of 32
Page 15
View Menu (1 of 1)
Item Field Range Description
VIEW
Calls
Pumps
Zones
VIEW
Calls
Pumps
Zones
The View menu items display the current operating temperatures and status information of the system.
OUTDOOR SECTION B, C
-76 to 149°F
(-60.0 to 65.0°C)
Current outdoor air temperature as measured by the outdoor sensor. The outdoor air temperature is shared to all thermostats in the tekmarNet® system.
-22 to 266°F
(-30.0 to 130.0°C)
MIX SUPPLY
Current mix supply water temperature as measured by the mix supply sensor. The control operates the mixing device so that the mix supply
SECTION B
is equal to the mix target temperature.
VIEW MENU
VIEW
VIEW
VIEW
VIEW
Calls
Calls
Calls
Calls
Pumps
Pumps
Pumps
Pumps
Zones
Zones
Zones
Zones
– – –, 35 to 180°F
(1.5 to 82.0°C)
-22 to 266°F
(-30.0 to 130.0°C)
– – –, 35 to 200°F
(1.5 to 93.0°C)
0-100%
-22 to 266°F
(-30.0 to 130.0°C)
MIX TARGET SECTION B
The temperature the control is currently trying to maintain at the mix supply sensor. The mix target is calculated based on the outdoor design and mix design settings. “– – –” is displayed when no heat is required for mix zones.
BOILER SUPPLY SECTION C
Current boiler supply water temperature as measured by the boiler sensor. The control operates the boiler so that the boiler supply is within the boiler differential of the boiler target. ‘MIN’ is shown when the control is providing boiler minimum protection to the boiler.
BOILER TARGET SECTION C
The boiler target is the temperature the control is currently trying to maintain at the boiler supply sensor. The boiler target is calculated based on the outdoor design, boiler design, and boiler minimum settings. “– – –” is displayed when no heat is required for boiler zones. ‘MIN’ is shown when the control is providing boiler minimum protection to the boiler.
BOILER MODULATION SECTION F
Current percent modulation of the boiler’s burner. The boiler modulation increases when the boiler supply is less than the boiler target. The boiler modulation decreases when the boiler supply is greater than the boiler target.
Note: This item is only available when the Boil Type setting is set to 0-10 or 4-20.
DHW TANK SECTION D
Current Domestic Hot Water tank temperature as measured by the optional DHW sensor. If the DHW tank temperature falls 6°F (3.0°C) below the DHW Occ setting, a DHW call is created and the tank is heated.
Note: This item is only available when a DHW sensor is installed and DHW Mode is set to 1 to 4.
DHW SUPPLY SECTION D
-22 to 266°F
(-30.0 to 130.0°C)
Current supply water temperature to the indirect DHW tank heat exchanger as measured by the DHW sensor.
Note: This item is only available when a DHW sensor is installed and DHW Mode is set to 5.
SYSTEM IN AWAY SECTION I
--
The heating system is in the Away scene. The DHW tank will not be heated. Setpoint calls are still responded to.
Use the User Switch to change scene out of Away.
After the last item, the control returns to the first item in the menu.
15 of 32 © 2010 D 402 - 09/10
Page 16
Adjust Menu (1 of 3)
The Adjust menu items are the programmable settings used to operate the mechanical equipment.
Item Field Range
ADJUST
ADJUST
(21.0 to 82.0°C) Default = 120°F
ADJUST
-60 to 45°F
(-51.0 to 7.0°C)
Default = 10°F
(-12.0°C)
70 to 180°F
(49.0°C)
4-20 mA,
0-10 V (dc)
FLOT,
VAR
Default = VAR
Access
Installer
Installer
Installer
Description Set to
OUTDOOR DESIGN SECTION B, C
Typically set to the temperature of the coldest day of the year. The outdoor air temperature used in the boiler and mixing heating curves that determine the boiler target and the mix target temperatures.
MIX DESIGN
SECTION B
The supply water temperature required for the mix zones to heat the building on the typical coldest day of the year. Recommendations:
High mass radiant floor = 120°F (50°C) Low mass radiant floor = 140°F (60°C) Fancoil or air handling unit = 190°F (90°C) Copper fin-tube convector = 180°F (80°C) Radiators = 160°F (70°C) Low profile baseboard = 150°F (65°C)
MIX TYPE SECTION B
Select the type of mixing device. VAR = Variable speed injection pump FLOT = Floating action motor for mixing valves 0-10 = 0 -10 V (dc) analog signal for mixing valves 4-20 = 4-20 mA analog signal for mixing valves
Note: 0-10 and 4-20 are only available when Boiler Type = 1 Stage or 2 Stage.
ADJUST MENU
ADJUST
30 to 230 seconds
sec
Default = 105 seconds
Installer
MIX MOTOR
The time that the mix actuating motor requires to operate from fully closed to fully open.
tekmar actuating motors = 105 sec. Refer to actuating motor for correct setting.
Note: This item is only available when the Mix Type is set to FLOT (floating action motor), 0-10, or 4-20.
BOILER TYPE
EMS2, EMS1,
4-20
0-10,
2STG,
1STG
Default = 1STG
Installer
The type of boiler connected to the control. 1STG = single one-stage on-off boiler 2STG = single two-stage on-off boiler 0-10 = 0-10 V (dc) modulating boiler 4-20 = 4-20 mA modulating boiler EMS1 = tekmar boiler staging controls EMS2 = Viessmann modulating boilers with
OpenTherm Note: Only 1STG and 2STG are available when the
Mix Type is set to 0-10 V (dc) or 4-20 mA.
Continued on next page.
© 2010 D 402 - 09/10 16 of 32
SECTION B
SECTION F
Page 17
Adjust Menu (2 of 3)
Item Field Range
VIEW
(21.0 to 93.5°C)
OFF, 80 to 180°F
(26.5 to 82.0°C)
70 to 200°F
Default = 180
(82.0°C)
Default = 140
(60.0°C)
°F
°F
Access
Installer
Installer
Description Set to
BOILER DESIGN SECTION C
The supply water temperature required for the boiler zones to heat the building on the typical coldest day of the year. Recommendations:
High mass radiant floor = 120°F (50°C) Low mass radiant floor = 140°F (60°C) Fancoil or air handling unit = 190°F (90°C) Copper fin-tube convector = 180°F (80°C) Radiators = 160°F (70°C) Low profile baseboard = 150°F (65°C)
BOILER MINIMUM SECTION B, C
The minimum allowed boiler target temperature and temperature at which the mixing device begins to provide boiler protection against cold return water temperatures. The mixing valve or variable speed injection pump operate at low percent output when the boiler supply temperature drops below this setting.
Recommendations: Condensing gas or electric boiler = OFF Non-condensing gas and oil boilers = 140°F (60°C) Note: If Boiler Type is 0-10 V (dc), 4-20 mA, EMS1
or EMS2, this setting is defaulted to Off. The mixing device does not provide boiler protection when Boiler Type is set to EMS1 or EMS2.
ADJUST MENU
ADJUST
ADJUST
ADJUST
ADJUST
10 to 230 seconds
sec
Default = 30
seconds
0 to 50%
Default = 0%
0 to 3:00 minutes
sec
Default = 10
seconds
Off or On
Default = Off
Installer
Installer
Installer
Installer
BOILER MOTOR SECTION F
The time required for the modulating actuating motor to fully open the gas valve or ramp the burner fan from off to full speed on a modulating boiler. Set to 30 seconds unless otherwise recommended by the boiler manufacturer.
Note: This item is only available when the Boiler Type is 0-10 V (dc) or 4-20 mA.
MINIMUM MODULATION SECTION F
The minimum percent modulation of the boiler burner.
Note: This item is only available when the Boiler Type is 0-10 V (dc) or 4-20 mA.
MODULATION DELAY SECTION F
Delay time between the burner firing and the boiler releasing to modulation.
Note: This item is only available when the Boiler Type is 0-10 V (dc) or 4-20 mA.
FLUSHING SECTION G
Set to On when a domestic hot water tank is used to heat the building. When On, the control ensures that each zone is operated at least once daily to prevent stagnation.
Continued on next page.
17 of 32 © 2010 D 402 - 09/10
Page 18
Adjust Menu (3 of 3)
Item Field Range
ADJUST
(4.5 to 38.0°C)
ADJUST
(4.5 to 38.0°C)
Off, 1, 2, 3, 4, 5
(38.0 to 93.5°C)
40 to 100°F
Default = 70
°F
(21.0°C)
40 to 100°F
Default = 60
°F
(15.5°C)
Default = 2
100 to 200°F
Default = 180
(82°C)
°F
Access
Installer
User
Installer
Installer
Installer
Description Set to
WWSD OCCUPIED
SECTION I
The system’s Warm Weather Shut Down temperature during Occupied periods or when a schedule is not used.
WWSD UNOCCUPIED
SECTION I
The system’s Warm Weather Shut Down temperature during Unoccupied periods.
Note: Item is only available when a schedule or User Switch is present on the system.
DHW MODE SECTION D
Selects the DHW mode of operation. The mode determines the zone and boiler system pumps operation whenever the DHW pump is in operation.
DHW EXCHANGE SECTION D
Selects the minimum boiler target to the DHW heat exchanger.
Note: Item is only available in DHW Modes 1 through 4 when a DHW sensor is not connected. It is available in DHW Mode 5 when a DHW sensor is connected.
ADJUST MENU
ADJUST
ADJUST
ADJUST
70 to 180°F
(21.0 to 82.0°C)
Default = 125
°F
(51.5°C)
Off or On
Default = On
60 to 200°F
(15.5 to 93.5°C)
Default = 180
°F
(82.0°C)
°F or °C
Default =
°F
Installer
Installer
Installer
Installer
User
DHW OCCUPIED SECTION D
Selects the temperature of the indirect DHW tank. Note: Item is only available when an optional DHW
sensor is installed except in DHW Mode 5.
DHW UNOCCUPIED SECTION I
Selects whether or not the indirect DHW tank should be heated to during Unoccupied time periods.
Note: Item is only available when Schedule #1 is available or a User Switch is present on the system.
SETPOINT SECTION E
The minimum boiler target temperature when a Setpoint Call is present.
UNITS
Selects units for temperature display.
After the last item, the control returns to the first item in the menu.
© 2010 D 402 - 09/10 18 of 32
Page 19
Monitor Menu (1 of 1)
The Monitor menu items provide information about the system’s operation and performance. To clear any item back to default, press and hold the Up and Down buttons while viewing that item.
MONITOR
MONITOR
MONITOR
MONITOR
Item Field
Pumps
DHW
Range
Description
OUTDOOR HIGH
-76 to 149°F
(-60.0 to 65.0°C)
Records the highest outdoor temperature since the item was last cleared. Press and hold the Up and Down buttons while viewing to reset.
OUTDOOR LOW
-76 to 149°F
(-60.0 to 65.0°C)
Records the lowest outdoor temperature since the item was last cleared. Press and hold the Up and Down buttons while viewing to reset.
RUN TIME (BOILER)
hr
0 to 9999 Hours
Default = 0 hr
The total ‘on’ time of the boiler relay since the item was last cleared. Press and hold the Up and Down buttons while viewing to reset.
RUN TIME (DHW PUMP)
hr
0 to 9999 Hours
Default = 0 hr
The total running time of the DHW Pump since this item was last cleared. Press and hold the Up and Down buttons while viewing to reset.
MONITOR
MONITOR MENU
MONITOR
MONITOR
Pumps
Boil System
Pumps
Mix System
Saving
hr
0 to 9999 Hours
Default = 0 hr
hr
0 to 9999 Hours
Default = 0 hr
hr
0 to 9999 Hours
Default = 0 hr
RUN TIME (BOIL SYSTEM PUMP)
The total running time of the Boil System Pump since this item was last cleared. Press and hold the Up and Down buttons while viewing to reset.
RUN TIME (MIX SYSTEM PUMP)
The total running time of the Mix System Pump since this item was last cleared. Press and hold the Up and Down buttons while viewing to reset.
RUN TIME ($AVING)
Maintains a record of the total length of time the $aving icon has been active. Press and hold the Up and Down buttons while viewing to reset.
BOILER ENERGY USE
MONITOR
hr
0 to 9999 Hours
Default = 0 hr
Multiply this value by the BTU rating (input BTU/hr) of the boiler to get an approximate energy consumption (in BTU’s) for the boiler. Press and hold the Up and Down buttons while viewing to reset. Not available when Boiler Type is EMS1 or EMS2.
After the last item, the control returns to the first item in the menu.
19 of 32 © 2010 D 402 - 09/10
Page 20
Toolbox Menu (1 of 1)
The Toolbox Menu is a location for system information and Test functions. If any errors are present on the system, they will be located at the beginning of this menu.
Item Field
Range
On or Off
Default = Off
On or Off
Default = Off
402
J12 06B
INST (Installer)
or USER
Default = INST
Description
USER TEST TESTING
Begins the test routine which tests the main control’s functions. See the Testing the Control section for more details. Use the up button to turn the User Test On.
MAX HEAT TESTING
When selected, control operates the system up to maximum set temperatures. Will operate up to 24 hours, or can be manually turned Off. See Max Heat in the Testing the Control section for more details.
TYPE AND SOFTWARE VERSION
Displays the type number of the product, followed by the current software version beneath.
ACCESS LEVEL
Selects the Access Level of the control, which determines the Menu items available. USER provides the most limited level of access and shows the fewest possible items.
When set to USER, all thermostats are locked and the number of thermostat settings available are reduced.
OFF, SEL
Default = Off
FACTORY DEFAULTS
Loads the factory default settings. Hold the Up and Down buttons for 1 second until SEL is shown.
TOOLBOX MENU
MIX DEVICES
0 to 24 devices
0 to 24 devices
See Troubleshooting
Guide
After the last item, the control returns to the first item in the menu.
© 2010 D 402 - 09/10 20 of 32
Displays the number of devices on the Mix bus (Water Temperature). This is made up of thermostats connected to the House Control, and to the Mix Expansion terminals.
BOIL DEVICES
Displays the number of devices on the Boil Expansion bus (Water Temperature). This is made up of thermostats connected to the Boil Expansion terminals on the House Control.
HISTORY - 1 THROUGH 5
Displays a history of any past errors that have occurred on the system. Will clear after 30 days, or press Up and Down buttons for 1 second to manually clear. The last 5 history items will display if present.
Page 21
Sequence of Operation
-----------------------------------------------------------------------
--------------------------------------------------------------------------------------------
-------------------------------------------------------------------------------------------
tekmarNet® System
tekmarNet® is a family of products that use communication to operate the HVAC system in a comfortable and efficient manner. The House Control is the central component in a tekmarNet® system and requires tekmarNet®2 (tN2) Thermostats to be directly connected to the control.
The tekmarNet®4 (tN4) Expansion terminals can link the House Control with other tekmarNet® components:
Mix Temperature Reset Operation
Mix Call or Mix Expansion Call
When an onboard tN2 Thermostat calls for heat, the House Control registers a Mix call for hydronic heating.
When a device connected to the tN4 Mix Expansion terminals calls for heat, the House Control registers a Mix Expansion Call for hydronic heating on the mix loop.
Mix Target
When there are no Mix or Mix Expansion calls, the mix target in the View menu on the display will show ‘– – –’ to indicate there is no requirement for mixing operation.
Once a Mix Call or Mix Expansion Call is present, a mix target is determined by the control using the mixing heating curve (mix design and outdoor design settings) together with indoor temperature feedback from the thermostats. The heating curve operates based on the principle that a buildings heat loss increases with colder outdoor temperatures. The calculated Mix Target will be shown in the View menu on the display.
--------------------------------------------------------------------------------------------
-----------------------------------------------------------------------
Section A
Wiring Centers 313, 314, 315, 316 - Add additional zones
• tN2 and tN4 Thermostats - Add thermostats
• tN4 Timer 033 - Adds 4 programmable schedules
• tN4 User Switch 479 - Provides a system override for
• vacations and holidays
tN4 Setpoint Control 161 - Control hot tubs, pools and
• more
Section B
Calls
Mix
Mix Heating Curve
(Outdoor Design,
Mix Design)
Calls
Mix Exp
Mix Maximum
The control has a fixed mix maximum temperature of +10°F (+5.5°C) higher than the Mix Design setting. When this occurs, the “MAX” segment will display when viewing the mix target or mix supply temperature in the view menu.
Mix Supply
Once a Mix Target water temperature has been calculated, the House Control measures the temperature at the mix supply sensor location and then operates the mixing device to maintain the mix supply temperature. The heat source will also be turned on and operated so that the mixing device is able to maintain the mix target temperature.
-------------------------------------------------------------------------------------------
(70°F Outdoor,
70°F Mix Supply)
Increasing Water Temperatures
Decreasing Outdoor Temperatures
Boiler Minimum Protection
If the boiler supply water temperature is cooler than the boiler minimum setting, the control reduces the output of the mixing device. This limits the amount of cool return water to the boiler and allows the boiler return water temperature to recover. Once the boiler supply temperature exceeds the boiler minimum setting, the mixing device will return to normal operation.
Note: The mixing device does not provide boiler minimum protections when the Boiler Type setting is EMS1 or EMS2.
21 of 32 © 2010 D 402 - 09/10
Page 22
Mixing Device Type
-----------------------------------------------------------------------------------
--------------------------------------------------------------------------------
-----------------------------------------------------------------------------------------
The House Control can operate a mixing device such as a mixing valve or variable speed injection pump based upon one of four output signals. The device output bar graph on the display indicates the approximate position of the mixing device.
-----------------------------------------------------------------------------------
Variable Speed Injection Pump
A standard wet rotor circulator can be connected to the Variable Speed Pump output on the back of the control. The control varies the circulator speed to maintain the correct mixed supply water temperature at the mix supply sensor. For correct sizing and piping of the variable speed injection circulator, refer to essay E 021. Note: Pumps manufactured with an internal variable speed controller are not compatible with the House Control.
Floating Action 24 V (ac)
A 24 V (ac) floating action actuator motor and mixing valve can be connected to the Floating Action outputs on the front of the House Control. The control pulses the actuator motor open or closed to maintain the correct supply water temperature at the mix supply sensor when there is a requirement for mixing.
Modulating 0-10 V (dc)
*Only available if a one or two stage on-off boiler is used.
A modulating 0-10 V (dc) actuating motor can be used to operate the mixing valve. The control uses the Mod dc/mA output to provide an analog 0-10 V (dc) signal to the actuator in order to maintain the correct mix supply temperature.
Modulating 4-20 mA
*Only available if a one or two stage on-off boiler is used.
A modulating 4-20 mA actuating motor can be used to operate the mixing valve. The control uses the Mod dc/mA output to provide an analog 4-20 mA signal to the actuator in order to maintain the correct mix supply temperature.
Mixing Device Exercising
The control operates the mixing device from 0 to 100% output every 3 days to help prevent corrosion and / or precipitate build up on the mixing valve or pump that could lead to seizure of the mixing device. The control ensures that no heat is supplied to the zones during exercising.
Boiler Temperature Reset Operation
Boiler Expansion Call
When a device connected to the tN4 Boil Expansion terminals calls for heat, the House Control registers a Boil Expansion call for hydronic heating on the boiler loop.
Boiler Target
When there are no Boiler Expansion or Mix calls, the boiler target in the View menu on the display will show ‘– – –’ to indicate there is no requirement for boiler operation.
Once a Boiler Expansion Call is present, a boiler target is determined by the control using the boiler heating curve (boiler minimum, boiler design and outdoor design settings) together with indoor temperature feedback from the thermostats. The heating curve operates based on the principle that a buildings heat loss increases with colder outdoor temperatures. The calculated Boiler Target will be shown in the View menu on the display.
When a Mix or Mix Expansion Call is present, the control calculates a boiler target that is higher than the mix target using Boiler Load Reset.
-----------------------------------------------------------------------------------------
--------------------------------------------------------------------------------
Section C
Calls
Boil Exp
Boiler Heating Curve
(Outdoor Design,
Boiler Design)
(70°F Outdoor,
Boiler Minimum)
Increasing Water Temperatures
Decreasing Outdoor Temperatures
Boiler Minimum
The House Control protects non-condensing boilers from sustained flue gas condensation and thermal shock through the Boiler Minimum setting. The boiler minimum is the lowest temperature that the control is allowed to use as a boiler target temperature. If the boiler is operating at the boiler minimum temperature, the “MIN” segment is turned on in the display when viewing either the boiler supply temperature or the boiler target temperature.
© 2010 D 402 - 09/10 22 of 32
Boiler Maximum
The control has a fixed boiler maximum temperature of + 10°F (+5.5°C) higher than the Boiler Design setting for the Boiler Heating Curve. When this occurs, the “MAX” segment will display when viewing the boiler target or boiler supply temperature in the view menu. The control will operate the boiler so that the boiler supply temperature will never exceed 210°F (99.0°C).
Page 23
Domestic Hot Water Tank Operation
---------------------------------------------------------------------------------------------
-------------------------------------------------------------------------------------------
----------------------------------------------------------------------------------
Section D
DHW Call
---------------------------------------------------------------------------------------------
A DHW Call is required in order for the control to provide heat to a DHW tank. Once the control registers a DHW Call, it will display the “DHW” icon under Calls in the display. This can be done in three ways:
DHW Tank Aquastat
If a DHW aquastat (mechanical switch) is used to
• apply a DHW Call, the tank is heated to the aqua­stat temperature setting. A dry contact or 24 V (ac) signal is applied across the DHW Call terminals on the House Control.
DHW Tank Sensor
A DHW tank sensor provides superior temperature
• control of the tank compared to an aquastat. The House Control automatically detects whether a DHW sensor is installed. The upper limit of the DHW tem­perature is set by the DHW setting. The DHW tank dif­ferential is fixed to 6°F (3°C).
DHW - Boiler Target
----------------------------------------------------------------------------------
When a DHW Call is present, a boiler target is determined.
When using a DHW Tank Aquastat, the boiler target is
• set to the DHW Exchange setting.
When using a DHW Tank Sensor, the boiler target is
• set to the DHW Occupied setting plus 40°F (22°C).
Calls
DHW
tekmarNet® Setpoint Control with Sensor
A DHW Call is provided through the tekmarNet®
• system. This can be done through the Boil Expansion tN4 terminals with a tekmarNet® setpoint device such as a Setpoint Control 161.
®
When using a tekmarNet target is set to the devices Exchange Supply setting.
If there are multiple devices calling for heat, the boiler target is set to the highest temperature requirement.
Setpoint Control, the boiler
DHW Mode
-------------------------------------------------------------------------------------------
The control has five different settings available for DHW Mode that affect pump operation. The required DHW Mode setting will depend on the piping arrangement of the DHW tank and whether or not priority for the DHW tank is necessary. DHW Priority stops or limits the delivery of heat to the building heating system while the DHW tank calls for heat. This allows for quick DHW tank temperature recovery.
DHW MODE 1 - DHW in Parallel no Priority
When a DHW Call is present, the DHW pump is activated. The boiler system pump does not turn on, but may operate based on either a Boiler, Mixing, or Setpoint Call.
It is assumed that the DHW pump will provide adequate flow through the heat exchanger and the boiler.
DHW MODE 2 - DHW in Parallel with Priority
When a DHW Call is present, the DHW pump is activated. The boiler system pump and all boiler temperature zones are shut off through tekmarNet® communication to achieve DHW priority.
It is assumed that the DHW pump will provide adequate flow through the heat exchanger and the boiler.
DHW Mode = 1
DHW
Zone
Pump
Valve
ON Or
ON
OFF
Boiler System
Pump
ON Or OFF
DHW Mode = 2
DHW
Zone
Pump
Valve
ON
Boiler System
Pump
OFF
OFF
23 of 32 © 2010 D 402 - 09/10
Page 24
DHW MODE 3 - DHW in Primary / Secondary no
--------------------------
------------------------------
Priority
When a DHW Call is present, the DHW pump and the boiler system pump is operated. Boiler temperature zones can turn on if required.
DHW MODE 4 - DHW in Primary / Secondary with Priority
When a DHW Call is present, the DHW pump and the boiler system pump is operated. All boiler temperature zones are shut off through tekmarNet® communication to achieve DHW priority.
DHW Mode = 3
DHW
Pump
ON
Boiler System
Pump
ON
Zone
Valve
ON Or
OFF
DHW Mode 5 - DHW in Near Boiler Piping with Priority
DHW Mode 5 requires that a DHW sensor be located on the boiler outlet pipe and a DHW call from an aquastat inside the DHW tank. The aquastat operates the DHW tank temperature while the DHW sensor is used to control the boiler temperature delivered to the DHW indirect heat exchanger.
When a DHW Call is present, the DHW pump is activated. The boiler system pump and all boiler temperature zones are shut off through tekmarNet® communication to achieve DHW priority.
It is assumed that the DHW pump will provide adequate flow through the heat exchanger and the boiler.
DHW Priority Override
--------------------------
To prevent the building from cooling off too much or the possibility of a potential freeze up during DHW priority, the control limits the amount of time for DHW priority during cold weather. During warm weather the DHW priority is 120 minutes. During cold weather the DHW priority is 15 minutes. Once the allowed time for priority has elapsed, the control overrides the DHW priority and resumes space heating for 15 minutes. It will then revert back to DHW Priority and repeat.
DHW Mode = 4
Zone
DHW
Pump
ON
Boiler System
Pump
ON
Valve
OFF
DHW Mode = 5
DHW Pump
DHW
Sensor
ON
Boiler Pump
OFF
Boiler
Sensor
Boiler System
DHW Priority Override Time
Zone Valve
OFF
Pump
OFF
DHW Post Purge
------------------------------
After the DHW Call is removed, the control performs a purge on the boiler. The control shuts off the boiler and continues to operate the DHW pump and the Boiler System pump if applicable. This purges the residual heat from the boiler into the DHW tank. The control continues this purge for a maximum of two minutes. The control also stops the purge if the boiler supply temperature drops below the current boiler target temperature.
© 2010 D 402 - 09/10 24 of 32
Increasing Time
Decreasing Outdoor Air Temperature
Page 25
Setpoint Operation
--------------------------------
-------
-----------------------------
----------------------
----------------------
--------------------------------
Section E
A Setpoint Call is required in order for the control to provide heat to a setpoint load, such as a spa, pool, or snowmelt load. This can be done in two ways:
Contact Closure
A dry contact or 24 V (ac) signal is applied across the Setpoint Call terminals on the 402.
tekmarNet® Setpoint Control with Sensor
A Setpoint Call is provided through the tekmarNet® system. This can be done through the tN4 Expansion terminals with a setpoint device such as a Setpoint Control 161.
Once the control registers a Setpoint Call, it will display the “Setp” icon under Calls in the display.
Note: Setpoint operation has a fixed priority of on.
Setpoint Operation
The control can operate to satisfy the requirements of a setpoint load in addition to a space heating load and a DHW load. A setpoint load overrides the current outdoor reset temperature and WWSD setting in order to provide heat to the setpoint load.
Setpoint
--------------------------------
-------
-----------------------------
Setpoint Priority
Setpoint
Pump
ON
Boiler System Pump
If Mix demand = On Otherwise = Off
Zone
Valve
OFF
When the control receives a Setpoint Call:
All Boil zones are turned off.
• The Mix device is ramped down to a minimum level.
• The boiler will operate to maintain the Setpoint tem-
• perature as set in the Adjust menu, or as set on the tekmarNet
®
Setpoint control if one is being used.
Calls
Setp
It is assumed that the Setpoint pump will provide adequate flow through the heat exchanger and the boiler.
Setpoint calls will also be responded to when the system is in Away, which can be set using a 479 User Switch.
Setpoint Priority Override
To prevent the building from cooling off too much or the possibility of a potential freeze up during setpoint priority, the control attempts to limit the amount of time for setpoint priority.
As the outdoor air temperature becomes colder, the length of time the control provides setpoint priority is reduced. Once the allowed time for priority has elapsed, the control will check the space heating target.
If there is a space heating target, the boiler operates at
• that target for 15 minutes.
If after 15 minutes there is still a Setpoint Call, the con-
• trol will reduce mixing outputs, shut off all boiler heat­ing zones and target the Setpoint temperature.
Note: It is possible to disable Setpoint Priority by using
• a tekmarNet® Setpoint control and turning the priority to Off in the Setpoint control.
----------------------
Boiler Operation
The 402 is able to operate a single 1-stage or 2-stage on­off boiler or a single modulating boiler as a heat source. For proper operation of the boiler, the 402 must be the only control that determines when the boiler is to fire.
*Important note: The operating control in the boiler, also known as an aquastat, remains in the burner circuit and acts as a secondary upper limit on the boiler temperature. The boiler operator temperature setting can be adjusted above 210°F, which is the fixed Boiler Maximum on the 402.
Boiler Target Temperature
The boiler target temperature is the temperature which the control is trying to operate the boiler at. There are four items that determine the boiler target temperature:
Mix Call
• Boil Exp Call
• DHW Call
• Setpoint Call
If the control receives more than one call for heat at the same time, it will operate the boiler at the highest of the four calls.
----------------------
Section F
The control displays the temperature that it is currently trying to maintain as the boiler supply temperature in the View menu. If the control does not presently have a call for heat, it does not show a boiler target temperature. Instead, ‘– – –’ is displayed on the LCD.
Boiler Minimum
When operating non-condensing boilers, it is important to prevent cool water from returning to the boiler. Cold return temperatures create flue gas condensation, which if left too long, can severely damage the boiler.
The 402 protects the boiler through the Boiler Minimum setting. The boiler minimum is the lowest temperature that the control is allowed to use as a boiler target temperature. If the boiler is operating at the boiler minimum temperature, the “MIN” segment is turned on in the display when viewing either the boiler supply temperature or the boiler target temperature.
25 of 32 © 2010 D 402 - 09/10
--------------------------------
Page 26
Boiler Maximum
--------------------------------
-------------------------------------
-------------------------------
-------------------
--------------------------------
The 402 will operate the boiler so that the boiler supply temperature will never exceed 210°F (99.0°C). The highest allowed boiler target is the boiler design temperature + 10°F (5.5°C).
Boiler Type
-------------------------------------
The 402 can operate either of the following types of boilers:
One single-stage on-off boiler
• One two-stage on-off boiler
• Modulating boiler using a 0-10 V (dc) signal
• Modulating boiler using a 4-20 mA signal
• tekmar EMS signal (for use with multiple boiler
• stagers)
EMS signal for Viessmann modulating boilers
On-Off Operation
-------------------------------
The 402 operates a single hot-water on-off boiler to maintain the boiler target within a differential. The boiler target is the average temperature and the boiler supply temperature can fluctuate by 1/2 of the differential above and below of the boiler target.
Modulation Boiler Operation
-------------------
The 402 can operate a single hot-water modulating boiler using the Mod dc/mA output and the Boiler Stage contact. Not all boilers require the use of the Boiler Stage contact.
The control operates the boiler by first switching the boiler stage contact to allow the modulating boiler to go through the ignition sequence (the boiler stage contact may not be required on all modulating boilers). A 0-10 V (dc) or 4­20 mA analog signal is then used to modulate the boiler firing rate starting from 50% (5 V (dc) or 12 mA signal) for 30 seconds.
After the 30 second delay has elapsed, the control will then allow the boiler to modulate down to the minimum modulation setting and hold it there for the Modulation Delay time setting. The Modulation Delay setting is determined by the boiler manufacturer. It is the amount of time that the burner must operate before the internal boiler control allows an external signal to operate the burner.
After the Modulation Delay has elapsed, the control uses PID logic to change the boiler firing rate signal in order to satisfy the boiler target temperature. When the firing rate signal is reduced down to the Minimum Modulating setting and the boiler supply temperature exceeds the boiler target by 1/2 of the differential, the control will shut off the burner.
Minimum Modulation
The Minimum Modulation is the lowest signal the control can send to modulate the boiler. This operates the boiler at low fire.
Refer to the boiler manufacturer’s literature to deter­mine the minimum output voltage V (dc) or current (mA) that the boiler will successfully operate at.
For 0-10 V (dc):
Minimum Modulation =
Boiler’s Minimum Input Signal x 100%
10 V (dc)
For 4-20 mA:
Minimum Modulation =
Boiler’s Minimum Input Signal - 4mA x 100%
16 mA
Example:
A boiler requires a 1.8 V (dc) signal to fire the boiler at low fire. The boiler can be modulated to 10 V (dc) where it reaches high fire.
Minimum Modulation = 1.8 V x 100% = 18%
10 V
10 V (dc)
Control
Range
Boiler
Range
18%
0 Vdc
1.8 V (dc)
tekmar EMS Signal Operation
The 402 can provide a 0-10 V (dc) signal proportional to the boiler target which is compatible with tekmar Boiler Staging controls that accept an EMS input.
To use the tekmar EMS signal operation, the Boil Type setting in the Adjust menu must be set to EMS1.
Viessmann EMS Signal
The 402 has a special 0-10 V (dc) signal proportional to the boiler target that is designed to be compatible with Viessmann Open Therm 0-10 V (dc) inputs.
To use the Viessmann EMS signal operation, the Boil
• Type setting in the Adjust menu must be set to EMS2.
The signal is 0 V (dc) when the boiler is off. The voltage is 2.2 V (dc) to provide a boiler target of 81°F (27°C), up to maximum of 10 V (dc) to provide a boiler target of 176°F (80°C).
© 2010 D 402 - 09/10 26 of 32
Page 27
Auto Differential
--------------------------------
------------------------------
----------------------------
-------------------------------------
-----------------
------------------------------
Both on-off and modulating boilers are operated with a differential. In some cases, a modulating boiler must be operated with a differential while operating at low fire because this indicates the load is smaller than the minimum modulation of the boiler. For modulating boilers, the differential no longer applies once operating the boiler above low fire.
The differential operates by closing the boiler contact when the boiler supply water temperature is 1/2 of the differential below the boiler target temperature. As the supply temperature reaches 1/2 of the differential above the boiler target temperature, the boiler is shut off.
Boiler On
--------------------------------
Boiler Off
+1/2 Dif ferential
Boiler Target
- 1/2 Differential
In order to decrease temperature swings and increase boiler efficiency, the Auto Differential feature automatically adjusts the operating differential of the boiler based on the heating load. As the load increases, the differential will decrease to minimize temperature swings. As the load decreases, the differential will increase to prevent short cycling. This can significantly improve operating efficiency and prevent equipment failures through excessive cycling.
Off
Differential
Time
On
Heating Load
Domestic Hot Water Heat Source
The 402 can use a high-efficiency water heater as a source of heat for space heating zones in addition to providing domestic hot water. This is an open-loop system in which potable water is circulated through the zones. When the flushing feature is set to on, the mixing valve is moved to the fully open position, all four zone valves are opened, and the mix system pump is turned on for 5 minutes each day. This prevents stagnation of the water in the heating system.
Pump Operation
Mix System Pump
The mix system pump operates whenever all the following conditions are met:
A Mix Call is present.
• The thermostat calling for heat has the Heat 1 pump
• setting set to On.
The heating system is not in Warm Weather Shut Down.
Boiler System Pump
The boiler system pump operates whenever all the following conditions are met:
A Mix or a Boiler Call is present.
• The thermostat calling for heat has the Heat 1 pump
• setting set to On.
There is no DHW priority.
• The heating system is not in Warm Weather Shut Down.
DHW Pump
The DHW pump operates whenever all the following conditions are met:
A DHW Call is present.
• The heating system is not in DHW priority override.
• DHW post purge.
-------------------------------------
------------------------------
----------------------------
Section G
070
402
Section H
Variable Speed Injection Pump
The variable speed pump operates whenever the following conditions are met:
A Mix Call is present.
• The heating system is not in Warm Weather Shut
• Down.
Note: The variable speed pump operates at minimum speed whenever the boiler supply temperature falls below the boiler minimum setting and whenever there is a DHW Call and DHW priority has been selected.
Pump Exercising
The control operates each pump every three days for 10 seconds to help prevent corrosion and / or precipitate build up on the pump components that can lead to pump seizure. The control ensures that no heat is supplied to the zones during exercising.
------------------------------
-----------------
27 of 32 © 2010 D 402 - 09/10
Page 28
----------------------------
--------------------------
-----------------------
------------
Energy Saving Features
-------------------------
------------------------------
Section I
The “$aving” icon is displayed when energy is being saved. The following features reduce energy consumption.
Network Schedules
Adding a schedule to a tekmarNet® system is both easy and valuable. A Timer 033 provides scheduling with up to 4 events per day for every tekmarNet® Thermostat. Turning down the room temperatures when they are unoccupied reduces boiler on-time and energy consumption which helps save money and the environment.
One-Touch Economy
A User Switch 479 allows for one-touch overrides of the system. For example, if leaving the building for vacation, simply press the “Away” button and all the thermostats will immediately operate at a lower temperature, instead of having to walk around the building lowering the heating temperature setting and raising the cooling temperature setting on each thermostat.
DHW Tank During Away
In addition to the One-Touch setback, a User Switch 479 also allows the user to press the ‘Away’ button and tell the House Control 402 to ignore DHW Calls, preventing the DHW tank from unnecessarily heating up when no one is living in the building.
Warm Weather Shut Down (WWSD)
During warmer weather, heating of the rooms is typically no longer required. To prevent energy waste from unnecessary boiler operation, the control goes into Warm Weather Shut Down (WWSD) when the outdoor temperature rises above the WWSD temperature set in the Adjust menu.
----------------------------
--------------------------
-----------------------
------------
Further Savings!
Use a Timer 033 with programmable schedule #1 to gain the WWSD Unoccupied setting. This provides an additional WWSD temperature that can be set even lower for Unoccupied and Sleep time periods.
This setting will appear after WWSD in the Adjust
• menu if a Timer 033 or User Switch is present on the system.
Zone Synchronization
Another feature of the House Control is Zone Synchronization. In typical zoned systems, the thermostats operate on a stand­alone basis. This means that a zone turns on and off as required without any regard for other zones. The net effect is random operation of the zones causing short cycling of the heat source. tekmarNet® thermostats communicate to ensure that their cycles are synchronized. Energy is saved by ensuring zones requiring heat operate on the same cycle, therefore reducing short cycling of the boiler.
Zone Post Purge
When the last zone is nearly satisfied for heating, the boiler is shut off and the zone continues to operate together with the boiler system pump and / or mix system pump. This purges the residual heat from the boiler into this zone. The control continues this purge for a maximum of two minutes. The control will stop the purge if the boiler supply temperature drops below the boiler minimum setting.
-------------------------
------------------------------
Troubleshooting
It is recommended to complete all wiring to ensure trouble free operation. Should an error occur, simply follow these steps:
1. Find: If the House Control or tekmarNet® Thermostat flashes on the screen, it is indicating a problem on the system.
2. Identify: Use the Menu button to locate the Toolbox Menu. The Error code should appear as the first item.
3. Solve: Using the lookup chart below, match the Error code to the one on the control. Use the Description in the chart to solve the problem.
Error Messages (1 of 3)
Error Message Description
ADJUST ERROR
The control failed to read the Adjust menu settings, and reloaded the factory default settings. Operation stops until all the Adjust menu settings are checked.
Note: To clear the error, the access level must be set to Installer and each setting in the Adjust menu must be checked.
OUTDOOR SENSOR SHORT CIRCUIT
Due to a short circuit, the control failed to read the outdoor sensor. As a result, the control assumes an outdoor temperature of 32°F (0°C) and continues operation. Locate and repair the problem as described in the “Test the Sensor Wiring” section.
© 2010 D 402 - 09/10 28 of 32
Page 29
Error Messages (2 of 3)
Error Message Description
OUTDOOR SENSOR OPEN CIRCUIT
Due to an open circuit (disconnected or broken wire), the control failed to read the outdoor sensor. As a result, the control assumes an outdoor temperature of 32°F (0.0°C) and continues operation. Locate and repair the problem as described in the “Test the Sensor Wiring” section.
MIX SENSOR SHORT CIRCUIT
Due to a short circuit, the control failed to read the Mix supply sensor. As a result, the control operates the mixing device at a fixed output as long as there is a call for heat. Locate and repair the problem as described in the “Test the Sensor Wiring” section.
MIX SENSOR OPEN CIRCUIT
Due to an open circuit (disconnected or broken wire), the control failed to read the Mix supply sensor. The control operates the mixing device at a fixed output as long as there is a call for heat. Locate and repair the problem as described in the “Test the Sensor Wiring” section.
BOILER SENSOR SHORT CIRCUIT
Due to a short circuit, the control failed to read the boiler sensor. When there is a call for heat, the control no longer controls the boiler. Instead, the control provides a boiler enable and the boiler operates on its aquastat/limit until the sensor is repaired. The control will not operate the boiler contact if the Boil Minimum setting is set to Off. Locate and repair the problem as described in the “Test the Sensor Wiring” section.
BOILER SENSOR OPEN CIRCUIT
Due to an open circuit, the control failed to read the boiler sensor. The control no longer controls the boiler. Instead, the control provides a boiler enable and the boiler operates on its aquastat/limit until the sensor is repaired. The control will not operate the boiler contact if the Boil Minimum setting is set to Off. Locate and repair the problem as described in the “Test the Sensor Wiring” section.
DOMESTIC HOT WATER SENSOR SHORT CIRCUIT
Due to a short circuit, the control failed to read the DHW sensor. As a result, the control no longer heats the DHW tank. Locate and repair the problem as described in the “Test the Sensor Wiring” section. DHW tank heating will resume once the sensor problem is corrected. The error message self clears once the error condition is corrected.
DOMESTIC HOT WATER SENSOR OPEN CIRCUIT
Due to an open circuit, the control failed to read the DHW sensor. As a result, the control no longer heats the DHW tank. Locate and repair the problem as described in the “Test the Sensor Wiring” section. DHW tank heating will resume once the sensor problem is corrected. The error message self clears once the error condition is corrected.
DOMESTIC HOT WATER CALL ERROR
A DHW sensor and a DHW call have been applied at the same time. The DHW tank will not be heated until the DHW call signal is removed. The error message self clears once the error condition is corrected.
BOILER DEVICE LOST (b:01 TO b:24)
Each tekmarNet® device (thermostat, setpoint control, timer) has an address. The device with this address on the boiler water temperature is no longer reporting back to the 402.
The device can be located by either the address, or by going to each device in the building, checking that the LCD is on, and the tekmarNet® communication symbol is on. Trace the wires from the control to the lost device looking for loose or damaged wires. Note: If you deliberately remove a tekmarNet
®
device, hold the Up and Down buttons to clear
this error.
29 of 32 © 2010 D 402 - 09/10
Page 30
Error Messages (3 of 3)
Error Message Description
MIX DEVICE LOST (1:01 TO 1:24)
Each tekmarNet® device (thermostat, setpoint control, timer) has an address. The device with this address on the mix water temperature is no longer reporting back to the 402.
The device can be located by either the address, or by going to each device in the building, checking that the LCD is on, and the tekmarNet® communication symbol is on. Trace the wires from the control to the lost device looking for loose or damaged wires. Note: If you deliberately remove a tekmarNet® device, hold the Up and Down buttons to clear this error.
MASTER DEVICE ERROR
More than one master has been detected on the tekmarNet®4 expansion terminals. The 402 is a “Master Device” and no other tekmarNet® reset controls can be added to the tekmarNet®4
expansion terminals. If one has been added, remove it from the system.
DEVICE ERROR AT ADDRESS b:01 to b:24
Each tekmarNet® device (thermostat, setpoint control, timer) has an address. One of the devices on the boiler water temperature has an error. If there is a record of the device address together with the room name, go to that device to correct the error. Otherwise, go to each device in the building, checking for the flashing Warning symbol. Once the error on the device is corrected, the error message will clear.
DEVICE ERROR AT ADDRESS 1:01 to 1:24
Each tekmarNet® device (thermostat, setpoint control, timer) has an address. One of the devices on the mix water temperature has an error. If there is a record of the device address together with the room name, go to that device to correct the error. Otherwise, go to each device in the building, checking for the flashing Warning symbol. Once the error on the device is corrected, the error message will clear.
MIX MODULE ERROR
A Mixing Module has been connected to the Mix Exp. tN4 terminals. The 402 controls mixing devices through outputs on the control and cannot operate tekmarNet® mixing expansion
modules. Remove the device and connect the mixing actuator or pump directly to the appropriate output terminals on the 402.
Frequently Asked Questions (1 of 2)
Symptom Look For...
Fuse holder
LCD display is off
Power to control
DHW Call on LCD If a DHW call is present, the control is aware that the DHW tank requires heat. DHW tank reading Ensure the DHW tank temperature is accurate and replace if necessary. Burner symbol on
No DHW tank heating
LCD DHW pump symbol
on LCD
Corrective Action
Control power supply has a 24 V (ac) fuse which if blown, requires replacement.
Use electrical meter to measure 24 V (ac) voltage on input power R and C terminals.
If the burner symbol is on the LCD, there is a problem with the boiler. Ensure the boiler aquastat manual limit is reset to the on position.
If the DHW pump symbol is on, check to ensure the DHW pump is in operation by checking for pump vibration or voltage on the pump wiring terminals.
DHW pump in operation
© 2010 D 402 - 09/10 30 of 32
If DHW pump and boiler are operating, the system may require the boiler system pump to operate to heat the DHW tank. Ensure the DHW Mode setting is set correctly.
Page 31
Frequently Asked Questions (2 of 2)
Symptom Look For...
Burner symbol on LCD
WWSD symbol on LCD
No central heating
Boiler short cycling
Single zone over heating
Mix or Boil Calls on LCD
DHW Call on LCD During DHW tank heating, the central heating may not be heated.
System in AWAY
“MIN” shown together with boiler target or boiler supply on LCD
Burner symbol cycling on and off
LCD shows zone on
LCD shows zone off
Corrective Action
If the burner symbol is on the LCD, there is a problem with the boiler. Ensure the boiler aquastat manual limit is reset to the on position.
Warm Weather Shut Down (WWSD) is an energy saving feature that prevents central heating during the summer. Ensure the outdoor temperature reading is accurate and replace outdoor sensor if necessary. WWSD setting can be increased if heating is required.
If there are no Mix or Boil Calls, there are no thermostats calling for heat.
During AWAY, the thermostats operate at a lower temperature. Locate a ‘User Switch’ and set to Normal to resume heating.
Boiler is operating below the boiler minimum setting and the mixing valve is closed or the mix injection pump is operating at low speed. The mixing device will operate normally once the boiler warms up.
Mixing using variable speed injection pumps requires the balancing valve to be set correctly. Lack of head pressure can lead the injection pump speed to ramp up and down.
Thermostats have a differential of +/- 1.5°F of the temperature setting. Due to the display rounding numbers up, heating can appear on when the temperature is 2°F above the setting. This is normal operation.
Ensure zone valve terminals measure 0 V (ac). Measuring 0 V (ac) indicates mechanical zone valve may have failed in open position. Measuring 24 V (ac) indicates control relay may have failed.
Single zone under heating
LCD shows zone on
LCD shows zone off Check for calls
Ensure zone valve terminals measure 24 V (ac). Measuring 24 V (ac) indicates mechanical zone valve may have failed in closed position. Measuring 0 V (ac) indicates control relay may have failed.
Job Record
Item Setting
OUTDOOR DESIGN
MIX DESIGN
MIX TYPE
MIX MOTOR
BOILER TYPE
BOILER DESIGN
BOILER MINIMUM
BOILER MOTOR
MINIMUM MODULATION
Item Setting
FLUSHING
WWSD OCCUPIED
WWSD UNOCCUPIED
DHW MODE
DHW EXCHANGE
DHW OCCUPIED
DHW UNOCCUPIED
SETPOINT
UNITS
MODULATION DELAY
31 of 32 © 2010 D 402 - 09/10
Page 32
Technical Data
tN2 House Control 402 Boiler, DHW & Setpoint, Mixing, Four Zone Valves
Literature D402, Q402, SB057 Control Microprocessor control. This is not a safety (limit) control. Packaged weight 1.4 lbs (640 g) Dimensions 5.5” H x 5.5” W x 2.25” D (140 x 140 x 57 mm) Enclosure NEMA 1 rated, blue PC+ABS plastic Approvals Ambient conditions Indoor use only, 32 to 104°F (0 to 40°C), RH 90% Non-condensing Power supply 24 V (ac) ±10% 60 Hz, 100 VA max, Class 2 Control load 2 VA Zone valve / floating action load 89 VA, 24 V (ac), 3.7 A for zones 1 to 4 plus fl oating action output Boiler stage 1, 2 relays 24 V (ac) 5 A Boiler system pump relay 115 V (ac) 5 A, 1/6 hp Mix system pump relay 115 V (ac) 5 A, 1/6 hp DHW pump relay 115 V (ac) 5 A, 1/6 hp Variable speed pump relay Pump power 115 V (ac) 12 A max Setpoint and DHW calls Short, 0 - 32 V (ac) Boil/Mix modulating output 0 - 10 V (dc) 500 Ω min load impedance, 4 - 20 mA 1 kΩ max load impedance Sensors NTC thermistor, 10k @ 77°F (25°C ± 0.2°C) ß=3892
- Included Outdoor Sensor 070 and 2 of Universal Sensors 082
Warranty Limited 3 Year
CSA C US, meets class B: ICES & FCC Part 15
115 V (ac) 2.4 A
Limited Warranty and Product Return Procedure
Limited Warranty The liability of tekmar under this warranty is lim-
ited. The Purchaser, by taking receipt of any tekmar product (“Prod­uct”), acknowledges the terms of the Limited Warranty in effect at the time of such Product sale and acknowledges that it has read and understands same.
The tekmar Limited Warranty to the Purchaser on the Products sold hereunder is a manufacturer’s pass-through warranty which the Purchaser is authorized to pass through to its customers. Under the Limited Warranty, each tekmar Product is warranted against defects in workmanship and materials if the Product is installed and used in compliance with tekmar’s instructions, ordinary wear and tear excepted. The pass-through warranty period is for a period of twenty-four (24) months from the production date if the Product is not installed during that period, or twelve (12) months from the docu­mented date of installation if installed within twenty-four (24) months from the production date.
The liability of tekmar under the Limited Warranty shall be limited to, at tekmar’s sole discretion: the cost of parts and labor provided by tekmar to repair defects in materials and/or workmanship of the defective prod­uct; or to the exchange of the defective product for a warranty replace­ment product; or to the granting of credit limited to the original cost of the defective product, and such repair, exchange or credit shall be the sole remedy available from tekmar, and, without limiting the foregoing in any way, tekmar is not responsible, in contract, tort or strict product liabil­ity, for any other losses, costs, expenses, inconveniences, or damages, whether direct, indirect, special, secondary, incidental or consequential, arising from ownership or use of the product, or from defects in work­manship or materials, including any liability for fundamental breach of contract.
The pass-through Limited Warranty applies only to those defective Prod­ucts returned to tekmar during the warranty period. This Limited War­ranty does not cover the cost of the parts or labor to remove or transport the defective Product, or to reinstall the repaired or replacement Product, all such costs and expenses being subject to Purchaser’s agreement and warranty with its customers.
Any representations or warranties about the Products made by Purchaser to its customers which are different from or in excess of the tekmar Lim­ited Warranty are the Purchaser’s sole responsibility and obligation. Pur­chaser shall indemnify and hold tekmar harmless from and against any and all claims, liabilities and damages of any kind or nature which arise out of or are related to any such representations or warranties by Pur­chaser to its customers.
The pass-through Limited Warranty does not apply if the returned Prod­uct has been damaged by negligence by persons other than tekmar, accident, fire, Act of God, abuse or misuse; or has been damaged by modifications, alterations or attachments made subsequent to purchase which have not been authorized by tekmar; or if the Product was not installed in compliance with tekmar’s instructions and/or the local codes and ordinances; or if due to defective installation of the Product; or if the Product was not used in compliance with tekmar’s instructions.
THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, WHICH THE GOVERNING LAW ALLOWS PARTIES TO CONTRACTUALLY EXCLUDE, INCLUDING, WITHOUT LIMITATION, IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, DURABILITY OR DESCRIPTION OF THE PRODUCT, ITS NON-INFRINGEMENT OF ANY RELEVANT PATENTS OR TRADEMARKS, AND ITS COMPLIANCE WITH OR NON-VIOLA­TION OF ANY APPLICABLE ENVIRONMENTAL, HEALTH OR SAFETY LEGISLATION; THE TERM OF ANY OTHER WARRANTY NOT HEREBY CONTRACTUALLY EXCLUDED IS LIMITED SUCH THAT IT SHALL NOT EX TEND BEYOND TWEN TY-FO UR (24) M ONTH S FR OM T HE PROD UC­TION DATE, TO THE EXTENT THAT SUCH LIMITATION IS ALLOWED BY THE GOVERNING LAW.
Product Warranty Return Procedure All Products that are believed to have defects in workmanship or materials must be returned, together with a written description of the defect, to the tekmar Representative assigned to the territory in which such Product is located. If tekmar receives an inquiry from someone other than a tekmar Representative, including an inquiry from Purchaser (if not a tekmar Representative) or Purchaser’s customers, regarding a potential warranty claim, tekmar’s sole obligation shall be to provide the address and other contact informa­tion regarding the appropriate Representative.
tekmar Control Systems Ltd., Canada, tekmar Control Systems, Inc., U.S.A.
Vernon, B.C. Canada V1B 3K4, 250-545-7749, Fax. 250-545-0650 Web Site: www.tekmarcontrols.com
Product design, software and literature are Copyright © 2010 by: tekmar Control Systems Ltd. and tekmar Control Systems, Inc.
32 of 32
Head Offi ce: 5100 Silver Star Road,
All specifications are subject to change without notice.
Printed in Canada. D 402 - 09/10.
Loading...