• Switch display to:
MIN / MAX / DIFF / ACTL / START / PRINT
• Go to parameter list after switch-on
• Page forward in parameter list
IndicatorMeaning
REFIf the decimal points have stopped blinking:
Reference mark was crossed over — datum points are now stored
in nonvolatile memory.
Blinking: Waiting for operator to press ENT or CL.
in.Position values displayed in inches.
1 / 2Datum 1 / Datum 2 currently active.
PRINTBlinking: Waiting for ENT for data output.
SETBlinking: Waiting for operator to confirm entry.
• Clear entry
• Reset to zero (P80!)
• CL plus MOD:
parameter list
• CL plus 2-digit number: select parameter
• Clear parameter entry
and show parameter
number
123
.
0
–CL
• Algebraic
sign
• Decrease
parameter
value
• Decimal point
• Increase parameter value
< / = / >Sorting mode: Measured value less than lower limit / within
tolerances / greater than upper limit.
MIN / MAXMeasuring series: Minimum / Maximum /
DIFF / ACTLlargest difference (MAX–MIN) / current measured value.
Blinking: Waiting for confirmation of value to be displayed.
STARTMeasuring series in progress.
Blinking: Waiting for start signal for measuring series.
Page 2
The ND 286 position display unit is designed for use with HEIDENHAIN linear or
rotary encoders with square-wave output signals. These encoders have one or more
reference marks, which may also be
When a reference mark is crossed over, it generates a signal identifying that position
as a reference point. After switch-on, simply crossing over the reference mark
restores the relationship between axis positions and display values as it was last
defined by datum setting.
With distance-coded reference marks, a maximum traverse of only 20 mm suffices to
re-establish the datum.
distance-coded
.
Switch-On
0 ➤1
Ent...CL
5 , 6 9 7
If you do not wish reference mark evaluation, press CL instead of ENT.
Turn on the power (switch located on rear panel).
• Display shows .
• REF indicator blinks.
• Data interface shows ERROR 07
Switch on reference mark evaluation.
• Display shows the value last assigned to the
reference mark position.
• REF indicator glows.
• Decimal point blinks.
Cross over reference mark.
Move the axis until the display becomes active and the
decimal point no longer blinks.
Setting the Datum
The datum setting procedure assigns a display value to a specific axis position.
The ND 286 allows you to set two independent datums.
Select datum 1 or 2.
Enter a value, such as 40.
4 0
Confirm entered value.
You can switch from one datum to the other at any time.
Use datum 2 when you want to display incremental values.
Page 3
Measuring Series
The ND 282 display unit can calculate and display one of the following values from a
measuring series:
Smallest value (MIN), largest value (MAX), difference between largest and smallest
value (DIFF), last value measured (ACTL)
A new value is captured every 550 µs during a measuring series.
To start a measuring series:
➤ Press the MOD key repeatedly until the desired indicator starts blinking.
Example: to display the largest value, press MOD until MAX blinks.
➤ Confirm your selection by pressing ENT.
➤ Press MOD repeatedly until the START indicator blinks.
➤ Start the measuring series by pressing ENT.
You can switch between MIN, MAX, DIFF and ACTL at any time:
➤ Press MOD until the desired indicator blinks, then confirm with ENT. Or
➤ Use operating parameter P21 (see list of operating parameters).
Note:
When the switching input for remote control of the measuring series is active (pin 6
of D-sub connection EXT), you cannot switch over the display as described here.
To abort a measuring series and restart:
➤ Press MOD until START blinks, then confirm with ENT.
To end a measuring series:
➤ Press MOD until the glowing indicator blinks, then confirm with ENT.
It is also possible to start a measuring series and switch over the display with a
switching input over the D-sub connection EXT (see that section).
Sorting and Tolerance Check Mode
In this mode, the display value is compared with an upper and a lower limit value.
Status indicators and the switching outputs at the D-sub connection EXT indicate
whether the display value is less than the lower limit, greater than the upper limit, or
between the two limit values.
IndicatorMeaning
=Measured value is between the limit values
<Measured value is less than the lower limit value
>Measured value is greater than the upper limit value
Operating parameters for the sorting mode:
• P17: sorting on / off, P18, P19: limit values
Distance-to-go Mode
The standard setting for the display unit is to show the encoder position value.
Code number 246 582 provides access to the distance-to-go mode.
“Traverse to zero” with distance-to-go display
➤ Select datum 2.
➤ Enter the nominal position.
➤ Move the axis to the display value zero.
In distance-to-go mode the trigger outputs A1 (Pin 15) and A2 (Pin 16) change their
meaning: they become symmetrical to the display value zero.
Page 4
Data Output
There are four ways to output data:
➤ Press the MOD key until the PRINT indicator starts blinking (only possible with
"slow" data output), and start data output with the ENT key; or
➤ Send measuring data to the data output periodically; or
➤ Input a latch command over the D-sub connection EXT; or
➤ Input a latch command over the BCD connection.
Interface mode (see operating parameter P53)
Slow:Output display values
Fast:Output instantaneous values referenced to datum 1
(MIN/MAX/DIFF display values are not output)
A connecting cable (to a PC, for example) is available from HEIDENHAIN
(Id.-Nr. 206 420 ..); cable length up to 10 m (32.8 ft).
Output levelsLow: U ≤ 0.4 V with I ≤ 6 mA High: U ≥ 3.8 V with I ≤ 2.6 mA
The output signals are TTL-compatible.
Latch levelsLow: U ≤ 0.9 V with I
≤ 6 mAHigh: U ≥ 3.9 V; or
max
TTL levels (internal 10 kΩ pull-up resistor).
Signal transit times
The following table lists approximate signal transit times. If you use the slow
data output and run functions such as measuring series or inch display at the
same time, the actual transit times can be twice as long as those listed here.
Concurrent data output (P55 )
ModeP53Latch timeData output after
FastP54Value from P54 / 2
Slowt ≤ 30 mst ≤ 8 ms
Data output after external latch (P55 or )
ModeP53Min. pulse durationMeasured value stored after
Pulse / BCDContactBCDPulseContact
Fast3 µs7 ms0.3 µs1.1 µs4.8 ms
Slowt ≥ 8 mst ≥ 13 ms 0.3 µs1.1 µs4.8 ms
Data outputLatch again after
Pulse/BCD Contact
Fast≤ 0.3 µs after internal latching3 µs7 ms
Slow≤ 7.5 ms after internal latching3 µs7 ms
Page 5
D-Sub Connection EXT (25-pin, male)
Danger to internal components!
Voltage sources for external circuitry must conform to the recommendations in
EN 50 178 for low-voltage electrical separation. Connect inductive loads only
with a quenching diode parallel to the inductance.
Use only shielded cable!
Connect the shield to the connector housing.
Pin FunctionPinFunction
15Meas. value ≥ trigger limit A1 (P62)10 V
16Meas. value ≥ trigger limit A2 (P63)100 V
17Meas. value < lower sorting limit (P18)12Do not assign
18Meas. value > upper sorting limit (P19)13Do not assign
19Error (see
OutputsInputs
14Display value is zero20Vacant
2Reset display to zero, clear error message21Vacant
3Preset display to value from P79
25Cross over reference marks
4Ignore reference mark signals
5Start measuring series
6Remote selection of display val. f. meas. ser.
7Display minimum value from meas. series
8Display maximum value from meas. series
9Display MAX – MIN diff. from meas. series
22Pulse: output measured value
23Contact: output measured value
24Deactivate BCD data output
Error Messages
)11Vacant
Display current measured value (ACTL):
Inputs 7, 8 and 9 are
not active, or more
than one of these
inputs is active
Signal levels LowHigh
Inputs–0.5 V ≤ U ≤ 0.9 VI ≤ 6 mA3.9 V ≤ U ≤ 15 V
OutputsU ≤ 0.4 VI ≤ 100 mAU ≤ 32 VI ≤ 10 µA
Description of input and output signals
Input signals• Triggering by make contact against 0 V or
• Low level over TTL component
• Internal pull-up resistor 1 kΩ
• Min. pulse duration: t ≥ 30 ms, for fast reset/preset: t ≥ 30 µs
• Min. pulse interval: t ≥ 30 ms, for reset/preset: t ≥ 1,5 ms;
for fast reset/preset: t ≥ 30 µs
• Delay for zero reset/preset: fast data output t
• slow data output t
≤ 2 ms
d
Output signals • Open collector outputs,
active Low
• Signal output delay: t
d
• Zero crossover signal
minimum duration, trigger
output A1, A2: t
Note that these times increase if additional
features are active (such as sorting).
≥ 180 ms
0
≤ 8 ms
C
B
U
CE
E
Pin 1.10
≤ 25 µs;
d
I ≤ 100 mA
+ UB ≤ 32 V
0 V
Page 6
Data Output and Display Freeze by Output Signal
The effect of a signal for measured value output is defined in operating parameter
P55.
➤ Concurrent display: No output value freeze. The output describes the current
measured value ( ).
➤ Frozen display: The output value is frozen and is updated with each signal for
measured value output ( ).
➤ Frozen/concurrent display: The output value freezes only as long as the signal is
present ( ).
P23 defines whether the display shows the current measured value ( ) or the
value at the data output ( ).
Error Messages
To clear error message :
When you have removed the cause of the error,
➤ press CL.
MessageCause and Effect
Last measured value not yet latched
Attempt to reset to zero or preset not permissible.
The display is not reset or preset.
Incorrect input value
Overflow caused by external preset
Value entered cannot be displayed
Overflow, trigger limit 1
Overflow, trigger limit 2
Overflow, lower sorting limit
Overflow, upper sorting limit
Encoder signal too weak1) (encoder may be contaminated)
Input frequency too high for encoder input
(will occur for example when traverse speed too high)
Internal counter overflow
1)
Error while crossing over reference marks
To clear the error message: Switch off the display unit.
Should any of these error codes recur, contact your HEIDENHAIN
service agency.
1)
1)
1)
Erase the operating parameters.
If all decimal points light up, the measured value is too large or too small.
In this case, set a new datum or retract.
If all sorting indicators light up, this means that the upper sorting limit is less than
the lower limit.
1)
These errors are significant for a connected device. The error signal (pin 19) at the
D-sub connection EXT is active.
Page 7
Operating Parameters
The parameters are divided into “user parameters“ and “protected operating
parameters," which can only be accessed by entering a code number.
User parameters
User parameters are operating parameters that you can change without entering the
code number: They are designated P00 to P30, P79, P86
Calling user parameters
To call user parameters immediately after switch-on:
➤➤
➤ Press the MOD key as long as is visible in the display.
➤➤
To call user parameters during operation:
➤➤
➤ Press and hold the CL key, then press MOD.
➤➤
To go directly to a specific user parameter:
➤➤
➤ Press and hold the CL key, then press the first digit of the parameter number.
➤➤
➤➤
➤ Release both keys and press the second digit.
➤➤
Protected operating parameters
Before you can change protected operating parameters you must enter the code
number 95 148 through : They remain accessible until you switch off
the position display.
To page through the parameter list
➤➤
➤ Forward paging: Press the MOD key.
➤➤
➤➤
➤ Backward paging: Press the 1 / 2 key.
➤➤
By paging on, you automatically enter any change you've made in a parameter.
To change operating parameters
➤➤
➤ Increase the parameter value with the decimal point key, or
➤➤
➤➤
➤ Decrease the parameter value with the minus key, or
➤➤
➤➤
➤ Enter the numerical value for the operating parameter, e.g. for P79 ( SET blinks).
➤➤
To correct your entries and show the parameter designation
➤➤
➤ Press the CL key.
➤➤
To exit the operating parameters
➤➤
➤ Press ENT. All changes made become effective.
➤➤
Operating Parameter List
ParameterMeaningFunction / EffectSetting
To change a protected operating parameter, enter code
number 95 148.
Unit ofDisplay in millimeters
measurementDisplay in inches
Sorting modeSorting on
Speed ofSlow
data outputFast, storage rate: P54
Latch speed0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 12.8 / 25.6 [µs]
Data outputData output concurrent (
from outputFrozen
signalFrozen/concurrent
Sign levelLow = Minus (
Behavior w/oData output always active
latch signalOutput high impedance (
Trigger limit 1Enter numerical value
Trigger limit 2Enter numerical value
Value forEnter numerical value
datumswitching input or with the ENT key
DisplayNo zero reset/preset with CL/ENT
reset/presetZero reset with CL (
Display after message displayed
switch-on message not displayed
Output ofError signal sent to data output
error signalError signal not sent to data output
(SP = signal period)
Distance-coded with 1000 • SP
(e.g. for LS 303 C / LS 603 C)
Distance-coded with 2000 • SP
Distance-coded with 5000 • SP
Alarm Off
Frequency
Contamination and frequency
)
Actual
High = Minus (
Sign Low
Sign High
)
)
Tristate
for datum setting via
Set Zero
no preset with ENT
Zero reset with CL and
preset with ENT to value in P79
),
)
)
Page 9
ParameterMeaningFunction / EffectSetting
External REFREF over D-sub connection EXT
No REF over EXT connection
First status indicator after MOD is pressed
Mod
e START PRINT MIN ACTL MAX DIFF
FastFast external reset/preset
Fast Set
repeated(setting of P53: )
externalREF mode, datum 2 and
reset/presetmeasuring series are not usable
No fast preset
Parameter Settings for HEIDENHAIN Linear Encoders
ModelSignal
LIF 171
LI M 172200o nesingl e0,2
LS 176
LS 476
LS 776
LS 623
LT 171
MT xx71
ST 12714 none0,002
Example:
period
[µm]
Set parameters for any encoder; Linear encoder with signal period