Bosch DM 1103 BEX User Manual

0 (0)
Bosch DM 1103 BEX User Manual

Fire Alarm Systems | Conventional Manual Call Points for Ex Areas

Conventional Manual Call Points for Ex Areas

www.boschsecurity.com

The Conventional Manual Call Points for Ex Areas are used to manually activate the alarm in zones 1 and 2 at risk of explosion.

The K type call points are encapsulated, intrinsically safe call points and do not require any safety barriers. The DM 1103 B Ex Manual Call Points for ex zones must be connected via a Safety Barrier SB 3 incl. Input/Output Module DCA1192 (see system overview).

System Overview

 

1

2

 

 

 

 

EOL22(EX)

 

 

 

DFA1101A-EX

FLM-420/4-CON

 

 

 

 

 

DO1101A-EX

DCA1192

SB3

 

DO1101A-EX

 

 

 

DCA1192

SB3

DM 1103 B-EX

DM 1103 B-EX

 

 

For DM 1103 B Ex:

Pos. Description

1Non-ex area

2Ex area zone 1 or 2

2 | Conventional Manual Call Points for Ex Areas

Functions

In the event of an alarm, the glass pane (2) is broken first, then the pushbutton (3) is pressed hard. Thus the switch triggers the alarm.

A locking mechanism holds the pressed manual call point.

The pushbutton can be reset with the reset lever. This does not reset the alarm on the fire panel.

Certifications and Approvals

Region

Certification

 

 

 

Europe

CE

DM 1103

 

CE

DKM2014

Germany

VdS

G 297060 DKM 2014/2-ex/-GLU

 

VdS

G 295036 DM 1103 B-Ex

 

PTB

97 ATEX 3197 DKM 2014/2 / DKM

 

 

2014/2-GLU

Europe

BASEE-

Ex 98E2304 DM 1103 B-Ex

 

FA

 

 

 

 

Installation/Configuration Notes

Manual call points must be illuminated sufficiently with daylight or another light source (including emergency lighting, if present).

An installation height of 1400 mm ±200 mm, measured from the middle of the manual call point to the floor, must be maintained.

Manual call points must be installed along escape and rescue routes (e.g. exits, passageways, stairwells).

Further standards, guidelines and planning recommendations regarding the installation location etc., should also be taken into consideration (see Fire Detection manual).

Regulations of local fire departments must be observed.

Installation/configuration notes in accordance with VdS/VDE

The distance between manual call points should not exceed 100 m according to DIN 14675 or 80 m according to VdS.

In high risk areas, manual call points should be installed at a distance of max. 40 m (VDE 0833 Part 2, Point 7.2.6).

According to VdS, up to 10 manual call points can be connected to a primary line.

DKM 2014/2 ex Manual Call Point Type K

For connection to the LSN, an NBK 100 LSN Fire Interface is required.

Can be connected directly to the following conventional control panels:

BZ 1012

BZ 1060

UEZ 1000 GLT.

With an NBK 100 LSN Fire Interface, can be connected to the following control panels:

BZ 500 LSN

UEZ 1000 LSN

UEZ 2000 LSN

UGM 2020 LSN

DKM 2014/2 ex UGM Manual Call Point Type K, for Connection to UGM Conventional

Can be connected directly to the UGM GLT Universal Danger Detection System

DM 1103 B-Ex manual call point for ex area

For connection to the LSN, an NBK 100 LSN interface is required.

For use in explosive areas of zones 1 and 2, a safety barrier and an input/output module are required, which must be mounted in front of the ex area.

Cables can be inserted surface-mounted or flushmounted

Parts Included

Type

Qt

Components

 

y.

 

DKM 2014/2 ex

1

Manual Call Point Type K, for ex areas,

 

 

for surface mounting

DKM 2014/2 ex UG

1

Manual Call Point Type K, for

M

 

Connection to UGM Conventional, for

 

 

ex areas, for surface mounting

DM 1103 B-Ex

1

DM 1103 B-Ex manual call point, color

 

1

red

 

2

Key for DM1103B-Ex manual call point

 

 

PG11 cable screws

Technical Specifications

DKM 2014/2 ex Manual Call Point Type K

DKM 2014/2 ex UGM Manual Call Point Type K, for Connection to UGM Conventional

Operating voltage

24 V DC

 

 

Switch contact

Type 366 (encapsulated), II 2 G

 

EEx d II C

 

 

Maximum contact load

5 A / 250 V AC

 

0,25 A / 250 V DC

 

 

Cable entry

• 1x M16 x 1.5 tightening

 

diameter 4 8 mm, EEx e II

 

• Blind plug: 1x M16 x1.5

 

EEx e II

 

 

Housing material

Polyester, glass fiber reinforced

 

 

Colors

Red, RAL 3001

 

 

Dimensions (W x H x D)

136 x 138 x 88 mm

 

 

Weight

Approx. 1800 g

 

 

Protection class as per EN 60529

IP 66

 

 

Permissible operating

-25 °C to +40 °C

temperature

 

 

 

Ex classification

Eex emd IIC T6

 

 