FILE NO. A08-007
SERVICE MANUAL
AIR-CONDITIONER
INDOOR UNIT
<DIGITAL INVERTER>
RAV-SM404SDT-E RAV-SM454SDT-E RAV-SM564SDT-E
OUTDOOR UNIT
<SUPER DIGITAL INVERTER>
RAV-SP404AT-E RAV-SP404ATZ-E RAV-SP404ATZG-E
RAV-SP564AT-E RAV-SP564ATZ-E RAV-SP564ATZG-E
SPLIT TYPE
RAV-SP454AT-E RAV-SP454ATZ-E RAV-SP454ATZG-E
RAV-SP804AT-E RAV-SP804ATZ-E RAV-SP804ATZG-E
R410A
PRINTED IN JAPAN, Jan., 2009 ToMo
Adoption of New Refrigerant
This Air Conditioner is a new type which adopts a new refrigerant HFC (R410A) instead of the conventional refrigerant R22 in order to prevent destruction of the ozone layer.
WARNING
Cleaning of the air filter and other parts of the air filter involves dangerous work in high places, so be sure to have a service person do it. Do not attempt it yourself.
The cleaning diagram for the air filter is there for the service person, and not for the customer.
CONTENTS
SAFETY CAUTION ............................................................................................ |
4 |
||
1. |
SPECIFICATIONS ...................................................................................... |
9 |
|
|
1-1. |
Indoor Unit........................................................................................................... |
9 |
|
1-2. |
Outdoor Unit...................................................................................................... |
17 |
|
1-3. |
Operation Characteristic Curve ....................................................................... |
18 |
2. |
CONSTRUCTION VIEWS (EXTERNAL VIEWS)....................................... |
20 |
|
|
2-1. |
Indoor Unit......................................................................................................... |
20 |
|
2-2. |
Outdoor Unit...................................................................................................... |
21 |
3. |
SYSTEMATIC REFRIGERATING CYCLE DIAGRAM .............................. |
24 |
|
|
3-1. |
Indoor Unit......................................................................................................... |
24 |
|
3-2. |
Outdoor Unit...................................................................................................... |
25 |
4. |
FAN CHARACTERISTICS ........................................................................ |
28 |
|
|
4-1. Slim Duct (Filter Attached) ............................................................................... |
28 |
|
5. |
WIRING DIAGRAM ................................................................................... |
29 |
|
|
5-1. |
Indoor Unit......................................................................................................... |
29 |
|
5-2. |
Outdoor Unit...................................................................................................... |
30 |
6. |
SPECIFICATIONS OF ELECTRICAL PARTS .......................................... |
32 |
|
|
6-1. |
Indoor Unit......................................................................................................... |
32 |
|
6-2. |
Outdoor Unit (Parts Ratings) ........................................................................... |
32 |
– 2 –
7. REFRIGERANT R410A ............................................................................ |
33 |
|
7-1. |
Safety During Installation/Servicing ............................................................... |
33 |
7-2. Refrigerant Piping Installation ....................................................................... |
33 |
|
7-3. |
Tools .................................................................................................................. |
37 |
7-4. |
Recharging of Refrigerant................................................................................ |
37 |
7-5. |
Brazing of Pipes ................................................................................................ |
38 |
7-6. |
Instructions for Re-use Piping of R22 or R407C ............................................ |
40 |
8. INDOOR CONTROL CIRCUIT (SLIM DUCT TYPE) ................................. |
43 |
|
8-1. |
Indoor Controller Block Diagram..................................................................... |
43 |
8-2. |
Indoor Controls (Slim Duct Type) .................................................................... |
46 |
8-3. |
Optional Connector Specifications of Indoor P.C. Board .............................. |
55 |
8-4. |
Indoor Print Circuit Board ................................................................................ |
56 |
9. |
OUTDOOR CONTROL CIRCUIT .............................................................. |
57 |
|
|
9-1. |
Outdoor Controls .............................................................................................. |
57 |
|
9-2. |
Outdoor Print Circuit Board ............................................................................. |
68 |
10. |
TROUBLESHOOTING .............................................................................. |
70 |
|
|
10-1. |
Summary of Troubleshooting ........................................................................... |
70 |
|
10-2. |
Troubleshooting ................................................................................................ |
72 |
11. |
REPLACEMENT OF SERVICE P.C. BOARD.......................................... |
107 |
|
|
11-1. |
Indoort Unit (Slim Duct Type) ......................................................................... |
107 |
12. |
SETUP AT LOCAL SITE AND OTHERS ................................................ |
112 |
|
|
12-1. |
Indoor Unit (Slim Duct Type) .......................................................................... |
112 |
|
12-2. |
Setup at Local Site / Others ........................................................................... |
119 |
|
12-3. |
How to Set up Central Control Address Number ......................................... |
121 |
|
12-4. |
Outdoor Unit.................................................................................................... |
126 |
13. |
ADDRESS SETUP .................................................................................. |
134 |
|
|
13-1. |
Address Setup Procedure .............................................................................. |
134 |
|
13-2. |
Address Setup & Group Control .................................................................... |
135 |
|
13-3. |
Remote Controller Wiring ............................................................................... |
138 |
|
13-4. |
Address Setup (Manual setting from remote controller) ............................. |
139 |
|
13-5. |
Confirmation of Indoor Unit No. Position ..................................................... |
140 |
14. |
DETACHMENTS ..................................................................................... |
142 |
|
|
14-1. |
Indoor Unit...................................................................................................... |
142 |
|
14-2. |
Outdoor Unit.................................................................................................... |
147 |
15. |
EXPLODED VIEWS AND PARTS LIST .................................................. |
164 |
|
|
15-1. |
Indoor Unit....................................................................................................... |
164 |
|
15-2. |
Outdoor Unit.................................................................................................... |
167 |
– 3 –
SAFETY CAUTION
The important contents concerned to the safety are described on the product itself and on this Service Manual.
Please read this Service Manual after understanding the described items thoroughly in the following contents (Indications/Illustrated marks), and keep them.
[Explanation of indications]
Indication |
Explanation |
|
|
DANGER |
Indicates contents assumed that an imminent danger causing a death or serious injury of |
the repair engineers and the third parties when an incorrect work has been executed. |
|
|
|
WARNING |
Indicates possibilities assumed that a danger causing a death or serious injury of the |
repair engineers, the third parties, and the users due to troubles of the product after work |
|
|
when an incorrect work has been executed. |
|
|
CAUTION |
Indicates contents assumed that an injury or property damage ( ) may be caused on the |
repair engineers, the third parties, and the users due to troubles of the product after work |
|
|
when an incorrect work has been executed. |
|
|
Property damage : Enlarged damage concerned to property, furniture, and domestic animal/pet
[Explanation of illustrated marks]
Mark |
Explanation |
Indicates prohibited items (Forbidden items to do)
The sentences near an illustrated mark describe the concrete prohibited contents.
Indicates mandatory items (Compulsory items to do)
The sentences near an illustrated mark describe the concrete mandatory contents.
Indicates cautions (Including danger/warning)
The sentences or illustration near or in an illustrated mark describe the concrete cautious contents.
[Confirmation of warning label on the main unit]
Confirm that labels are indicated on the specified positions (Refer to the Parts disassembly diagram (Outdoor unit).)
If removing the label during parts replace, stick it as the original.
DANGER
|
Turn “OFF” the breaker before removing the front panel and cabinet, otherwise an electric |
|
shock is caused by high voltage resulted in a death or injury. |
|
During operation, a high voltage with 400V or higher of circuit ( ) at secondary circuit of the |
|
high-voltage transformer is applied. |
Turn off breaker. |
If touching a high voltage with the naked hands or body, an electric shock is caused even if using an |
electric insulator. |
|
|
: For details, refer to the electric wiring diagram. |
|
When removing the front panel or cabinet, execute short-circuit and discharge between |
|
high-voltage capacitor terminals. |
Execute discharge |
If discharge is not executed, an electric shock is caused by high voltage resulted in a death or injury. |
|
|
between terminals. After turning off the breaker, high voltage also keeps to apply to the high-voltage capacitor. |
|
|
|
|
Do not turn on the breaker under condition that the front panel and cabinet are removed. |
|
An electric shock is caused by high voltage resulted in a death or injury. |
Prohibition |
|
– 4 –
WARNING
|
Before troubleshooting or repair work, check the earth wire is connected to the earth |
|
|
terminals of the main unit, otherwise an electric shock is caused when a leak occurs. |
|
Check earth wires. |
If the earth wire is not correctly connected, contact an electric engineer for rework. |
|
|
||
|
|
|
|
Do not modify the products. |
|
|
Do not also disassemble or modify the parts. It may cause a fire, electric shock or injury. |
|
Prohibition of modification. |
|
|
|
For spare parts, use those specified ( ). |
|
|
If unspecified parts are used, a fire or electric shock may be caused. |
|
Use specified parts. |
: For details, refer to the parts list. |
|
|
|
|
|
Before troubleshooting or repair work, do not bring a third party (a child, etc.) except |
|
|
the repair engineers close to the equipment. |
|
Do not bring a child |
It causes an injury with tools or disassembled parts. |
|
Please inform the users so that the third party (a child, etc.) does not approach the equipment. |
||
close to the equipment. |
||
|
|
|
|
Connect the cut-off lead wires with crimp contact, etc, put the closed end side |
|
|
upward and then apply a water-cut method, otherwise a leak or production of fire is |
|
|
caused at the users’ side. |
|
Insulating measures |
|
When repairing the refrigerating cycle, take the following measures.
1)Be attentive to fire around the cycle. When using a gas stove, etc, be sure to put out fire before work; otherwise the oil mixed with refrigerant gas may catch fire.
|
2) Do not use a welder in the closed room. |
No fire |
When using it without ventilation, carbon monoxide poisoning may be caused. |
3)Do not bring inflammables close to the refrigerant cycle, otherwise fire of the welder may catch the inflammables.
Check the used refrigerant name and use tools and materials of the parts which match with it.
For the products which use R410A refrigerant, the refrigerant name is indicated at a position on the outdoor unit where is easy to see. To prevent miss-charging, the route of the service port is changed from one of the former R22.
For an air conditioner which uses R410A, never use other refrigerant than R410A. For an air conditioner which uses other refrigerant (R22, etc.), never use R410A.
If different types of refrigerant are mixed, abnormal high pressure generates in the refrigerating cycle and an injury due to breakage may be caused.
Do not charge refrigerant additionally.
If charging refrigerant additionally when refrigerant gas leaks, the refrigerant composition in the refrigerating cycle changes resulted in change of air conditioner characteristics or refrigerant over the specified standard amount is charged and an abnormal high pressure is applied to the inside of the refrigerating cycle resulted in cause of breakage or injury. Therefore if the refrigerant gas leaks, recover the refrigerant in the air conditioner, execute
Refrigerant
vacuuming, and then newly recharge the specified amount of liquid refrigerant. In this time, never charge the refrigerant over the specified amount.
When recharging the refrigerant in the refrigerating cycle, do not mix the refrigerant or air other than R410A into the specified refrigerant.
If air or others is mixed with the refrigerant, abnormal high pressure generates in the refrigerating cycle resulted in cause of injury due to breakage.
After installation work, check the refrigerant gas does not leak.
If the refrigerant gas leaks in the room, poisonous gas generates when gas touches to fire such as fan heater, stove or cocking stove though the refrigerant gas itself is innocuous.
Never recover the refrigerant into the outdoor unit.
When the equipment is moved or repaired, be sure to recover the refrigerant with recovering device. The refrigerant cannot be recovered in the outdoor unit; otherwise a serious accident such as breakage or injury is caused.
After repair work, surely assemble the disassembled parts, and connect and lead the removed wires as before. Perform the work so that the cabinet or panel does not catch the inner wires.
Assembly/Cabling
If incorrect assembly or incorrect wire connection was done, a disaster such as a leak or fire is caused at user’s side.
– 5 –
WARNING
|
After the work has finished, be sure to use an insulation tester set (500V Megger) to |
|
|
check the resistance is 2MΩ or more between the charge section and the non-charge |
|
|
metal section (Earth position). |
|
Insulator check |
If the resistance value is low, a disaster such as a leak or electric shock is caused at user’s |
|
side. |
||
|
||
|
|
|
|
When the refrigerant gas leaks during work, execute ventilation. |
|
|
If the refrigerant gas touches to a fire, poisonous gas generates. |
|
|
A case of leakage of the refrigerant and the closed room full with gas is dangerous because |
|
Ventilation |
a shortage of oxygen occurs. Be sure to execute ventilation. |
|
|
|
|
|
When checking the circuit inevitably under condition of the power-ON, use rubber |
|
|
gloves and others not to touch to the charging section. |
|
|
If touching to the charging section, an electric shock may be caused. |
|
Be attentive to |
|
|
electric shock |
|
|
|
|
|
|
When the refrigerant gas leaks, find up the leaked position and repair it surely. |
|
|
If the leaked position cannot be found up and the repair work is interrupted, pump-down |
|
|
and tighten the service valve, otherwise the refrigerant gas may leak into the room. |
|
|
The poisonous gas generates when gas touches to fire such as fan heater, stove or cocking |
|
|
stove though the refrigerant gas itself is innocuous. |
|
|
When installing equipment which includes a large amount of charged refrigerant |
|
|
such as a multi air conditioner in a sub-room, it is necessary that the density does |
|
|
not the limit even if the refrigerant leaks. |
|
Compulsion |
If the refrigerant leaks and exceeds the limit density, an accident of shortage of oxygen is |
|
|
caused. |
|
|
For the installation/moving/reinstallation work, follow to the Installation Manual. |
|
|
If an incorrect installation is done, a trouble of the refrigerating cycle, water leak, electric |
|
|
shock or fire is caused. |
|
|
|
|
|
After repair work has finished, check there is no trouble. |
|
|
If check is not executed, a fire, electric shock or injury may be caused. |
|
|
For a check, turn off the power breaker. |
|
Check after repair |
|
|
|
|
|
|
After repair work (installation of front panel and cabinet) has finished, execute a test |
|
|
run to check there is no generation of smoke or abnormal sound. |
|
|
If check is not executed, a fire or an electric shock is caused. |
|
|
Before test run, install the front panel and cabinet. |
Check the following items after reinstallation.
Check after reinstallation |
1) |
The earth wire is correctly connected. |
|
||
|
2) |
The power cord is not caught in the product. |
|
3) |
There is no inclination or unsteadiness and the installation is stable. |
|
|
If check is not executed, a fire, an electric shock or an injury is caused. |
CAUTION
|
Be sure to put on the gloves ( ) and a long sleeved shirt: |
|
otherwise an injury may be caused with the parts, etc. |
Put on gloves |
( ) Heavy gloves such as work gloves |
|
|
|
|
|
When the power was turned on, start to work after the equipment has been |
|
sufficiently cooled. |
Cooling check |
As temperature of the compressor pipes and others became high due to cooling/heating |
operation, a burn may be caused. |
|
|
|
– 6 –
• New Refrigerant (R410A)
This air conditioner adopts a new HFC type refrigerant (R410A) which does not deplete the ozone layer.
1. Safety Caution Concerned to New Refrigerant
The pressure of R410A is high 1.6 times of that of the former refrigerant (R22).
Accompanied with change of refrigerant, the refrigerating oil has been also changed.
Therefore, be sure that water, dust, the former refrigerant or the former refrigerating oil is not mixed into the refrigerating cycle of the air conditioner with new refrigerant during installation work or service work.
If an incorrect work or incorrect service is performed, there is a possibility to cause a serious accident.
Use the tools and materials exclusive to R410A to purpose a safe work.
2.Cautions on Installation/Service
1)Do not mix the other refrigerant or refrigerating oil.
For the tools exclusive to R410A, shapes of all the joints including the service port differ from those of the former refrigerant in order to prevent mixture of them.
2)As the use pressure of the new refrigerant is high, use material thickness of the pipe and tools which are specified for R410A.
3)In the installation time, use clean pipe materials and work with great attention so that water and others do not mix in because pipes are affected by impurities such as water, oxide scales, oil, etc.
Use the clean pipes.
Be sure to brazing with flowing nitrogen gas. (Never use gas other than nitrogen gas.)
4)For the earth protection, use a vacuum pump for air purge.
5)R410A refrigerant is azeotropic mixture type refrigerant.
Therefore use liquid type to charge the refrigerant. (If using gas for charging, composition of the refrigerant changes and then characteristics of the air conditioner change.)
3.Pipe Materials
For the refrigerant pipes, copper pipe and joints are mainly used.
It is necessary to select the most appropriate pipes to conform to the standard.
Use clean material in which impurities adhere inside of pipe or joint to a minimum.
1) Copper pipe
<Piping>
The pipe thickness, flare finishing size, flare nut and others differ according to a refrigerant type.
When using a long copper pipe for R410A, it is recommended to select “Copper or copper-base pipe without seam” and one with bonded oil amount 40mg/10m or less.
Also do not use crushed, deformed, discolored (especially inside) pipes. (Impurities cause clogging of expansion valves and capillary tubes.)
<Flare nut>
Use the flare nuts which are attached to the air conditioner unit.
2)Joint
The flare joint and socket joint are used for joints of the copper pipe.
The joints are rarely used for installation of the air conditioner. However clear impurities when using them.
–7 –
4.Tools
1.Required Tools for R410A
Mixing of different types of oil may cause a trouble such as generation of sludge, clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types.
1)Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22))
2)Tools exclusive for R410A, but can be also used for conventional refrigerant (R22)
3)Tools commonly used for R410A and for conventional refrigerant (R22)
The table below shows the tools exclusive for R410A and their interchangeability.
Tools exclusive for R410A (The following tools for R410A are required.)
Tools whose specifications are changed for R410A and their interchangeability
|
|
|
|
R410A |
Conventional air |
|
|
|
|
air conditioner installation |
conditioner installation |
||
No. |
Used tool |
Usage |
|
|
|
|
Existence of |
|
Whether conventional |
Whether conventional |
|||
|
|
|
|
|||
|
|
|
new equipment |
|
equipment |
|
|
|
|
|
equipment can be used |
||
|
|
|
for R410A |
|
can be used |
|
|
|
|
|
|
||
|
|
|
|
|
|
|
Q |
Flare tool |
Pipe flaring |
Yes |
|
*(Note) |
Yes |
|
|
|
|
|
|
|
|
Copper pipe gauge |
Flaring by conventional |
Yes |
|
*(Note) |
*(Note) |
R |
for adjusting |
|
||||
flare tool |
|
|||||
|
projection margin |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
S |
Torque wrench |
Tightening of flare nut |
Yes |
|
No |
No |
|
|
|
|
|
|
|
T |
Gauge manifold |
Evacuating, refrigerant |
Yes |
|
No |
No |
|
|
|
||||
U |
Charge hose |
charge, run check, etc. |
|
|||
|
|
|
|
|||
|
|
|
|
|
||
|
|
|
|
|
|
|
V |
Vacuum pump adapter |
Vacuum evacuating |
Yes |
|
No |
Yes |
|
|
|
|
|
|
|
W |
Electronic balance for |
Refrigerant charge |
Yes |
|
Yes |
Yes |
refrigerant charging |
|
|||||
|
|
|
|
|
|
|
X |
Leakage detector |
Gas leakage check |
Yes |
|
No |
Yes |
|
|
|
|
|
|
|
(Note) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary.
General tools (Conventional tools can be used.)
In addition to the above exclusive tools, the following equipments which serve also for R22 are necessary as the general tools.
1)Vacuum pump. Use vacuum pump by attaching vacuum pump adapter.
2)Torque wrench
3)Pipe cutter
4)Reamer
5)Pipe bender
6)Level vial
7)Screwdriver (+, –)
8)Spanner or Monkey wrench
9)Hole core drill
10)Hexagon wrench (Opposite side 4mm)
11)Tape measure
12)Metal saw
Also prepare the following equipments for other installation method and run check.
1) |
Clamp meter |
3) |
Insulation resistance tester (Megger) |
2) |
Thermometer |
4) |
Electroscope |
– 8 –
1. SPECIFICATIONS
1-1. Indoor Unit
1-1-1. 4-Way Air Discharge Cassette Type
<Single type>
Model |
|
Indoor unit |
|
|
RAV-SM564UT-E |
RAV-SM804UT-E |
|
|
|
|
|
|
|
|
Outdoor unit |
|
|
RAV-SP564AT(Z)(ZG)-E |
RAV-SP804AT(Z)(ZG)-E |
|
|
|
|
|
|||
|
|
|
|
|
|
|
Cooling capacity |
|
|
(kW) |
5.3 |
7.1 |
|
|
|
|
|
|
|
|
Heating capacity |
|
|
(kW) |
5.6 |
8.0 |
|
|
|
|
|
|
|
|
Power supply |
|
|
|
1 phase 230V (220 – 240V) 50Hz |
||
|
|
|
|
|
|
|
|
|
|
Running current |
(A) |
6.82 – 6.25 |
8.72 – 7.99 |
|
|
|
|
|
|
|
|
|
|
Power consumption |
(kW) |
1.47 |
1.86 |
|
|
|
|
|
|
|
|
|
Cooling |
Power factor |
(%) |
98 |
97 |
|
|
|
|
|
|
|
|
|
|
EER |
|
3.61 |
3.82 |
|
|
|
|
|
|
|
|
|
|
Energy efficiency class |
A |
A |
|
Electrical |
|
|
|
|
|
|
|
|
Running current |
(A) |
5.61 – 5.14 |
8.95 – 8.20 |
|
characteristics |
|
|
||||
|
|
|
|
|
|
|
|
Power consumption |
(kW) |
1.21 |
1.91 |
||
|
|
|
||||
|
|
|
|
|
|
|
|
|
Heating |
Power factor |
(%) |
98 |
97 |
|
|
|
|
|
|
|
|
|
|
COP |
|
4.63 |
4.19 |
|
|
|
|
|
|
|
|
|
|
Energy efficiency class |
A |
A |
|
|
|
|
|
|
|
|
|
|
Maximum current |
|
(A) |
13.30 |
20.30 |
|
|
|
|
|
|
|
|
|
Main unit |
|
|
Zinc hot dipping steel plate |
|
|
|
|
|
|
|
|
Appearance |
|
Ceiling panel |
Model |
|
RBC-U31PG (W, WS)-E, RBC-U31PGS (W, WS)-E |
|
|
|
|
|
|
|
|
|
|
(Sold separately) |
Panel color |
|
(W) : 2.5GY 9.0/0.5, (WS) : 2.5GY 9.0/0.5, 8B3/0.3 |
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
Height |
(mm) |
256 |
256 |
|
|
|
|
|
|
|
|
|
Main unit |
Width |
(mm) |
840 |
840 |
|
|
|
|
|
|
|
Outer |
|
|
Depth |
(mm) |
840 |
840 |
|
|
|
|
|
|
|
dimension |
|
|
Height |
(mm) |
30 |
30 |
|
|
|
||||
|
|
Ceiling panel |
|
|
|
|
|
|
Width |
(mm) |
950 |
950 |
|
|
|
(Sold separately) |
||||
|
|
|
|
|
|
|
|
|
Depth |
(mm) |
950 |
950 |
|
|
|
|
||||
|
|
|
|
|
|
|
Total weight |
|
Main unit |
|
(kg) |
20 |
20 |
|
|
|
|
|
|
|
|
Ceiling panel (Sold separately) |
(kg) |
4.2 |
4.2 |
||
|
|
|||||
|
|
|
|
|
|
|
Heat exchanger |
|
|
|
Finned tube |
||
|
|
|
|
|
|
|
|
|
Fan |
|
|
Turbo fan |
|
|
|
|
|
|
|
|
Fan unit |
|
Standard air flow |
H/M/L |
(m³/min.) |
17.5 / 14.5 / 13.0 |
20.5 / 16.0 / 13.5 |
|
|
|
|
|
|
|
|
|
Motor |
|
(W) |
14 |
20 |
|
|
|
|
|
|
|
Air filter |
|
|
|
Standard filter attached (Long life filter) |
||
|
|
|
|
|
|
|
Controller (Sold separately) |
|
|
RBC-AMT31E, AMT32E, AMS41E, AS21E2, |
|||
|
|
AX31U (W, WS)-E, TCB-AX21E2 |
||||
|
|
|
|
|
||
|
|
|
|
|
|
|
Sound pressure level |
H/M/L |
(dB•A) |
32 / 29 / 28 |
35 / 31 / 28 |
||
|
|
|
|
|
|
|
Sound power level |
H/M/L |
(dB•A) |
47 / 44 / 43 |
50 / 46 / 43 |
||
|
|
|
|
|
|
|
|
|
|
Gas side |
(mm) |
12.7 |
15.9 |
|
|
|
|
|
|
|
Connecting pipe |
|
Liquid side |
(mm) |
6.4 |
9.5 |
|
|
|
|
|
|
|
|
|
|
|
Drain port |
(mm) |
VP25 |
|
|
|
|
|
|
|
|
: IEC standard
– 9 –
1-1-2. Concealed Duct Type
<Single type>
|
|
Indoor unit |
|
|
RAV-SM562BT-E |
RAV-SM802BT-E |
Model |
|
|
|
|
|
|
|
Outdoor unit |
|
|
RAV-SP564AT(Z)(ZG)-E |
RAV-SP804AT(Z)(ZG)-E |
|
|
|
|
|
|||
|
|
|
|
|
|
|
Cooling capacity |
|
|
(kW) |
5.0 |
7.1 |
|
|
|
|
|
|
|
|
Heating capacity |
|
|
(kW) |
5.6 |
8.0 |
|
|
|
|
|
|
|
|
Power supply |
|
|
|
1 phase 230V (220 – 240V) 50Hz |
||
|
|
|
|
|
|
|
|
|
|
Running current |
(A) |
7.24 – 6.63 |
10.36 – 9.49 |
|
|
|
|
|
|
|
|
|
|
Power consumption |
(kW) |
1.56 |
2.21 |
|
|
|
|
|
|
|
|
|
Cooling |
Power factor |
(%) |
98 |
97 |
|
|
|
|
|
|
|
|
|
|
EER |
|
3.21 |
3.21 |
|
|
|
|
|
|
|
|
|
|
Energy efficiency class* |
A |
A |
|
Electrical |
|
|
|
|
|
|
|
|
Running current |
(A) |
7.19 – 6.59 |
10.36 – 9.49 |
|
characteristics |
|
|
||||
|
|
|
|
|
|
|
|
|
|
Power consumption |
(kW) |
1.55 |
2.21 |
|
|
|
|
|
|
|
|
|
Heating |
Power factor |
(%) |
98 |
97 |
|
|
|
|
|
|
|
|
|
|
COP |
|
3.61 |
3.62 |
|
|
|
|
|
|
|
|
|
|
Energy efficiency class * |
A |
A |
|
|
|
|
|
|
|
|
|
|
Maximum current |
|
(A) |
13.60 |
20.60 |
|
|
|
|
|
|
|
Appearance |
|
Main unit |
|
|
Zinc hot dipping steel plate |
|
|
|
|
|
|
|
|
|
|
|
Height |
(mm) |
320 |
320 |
Outer |
|
|
|
|
|
|
|
Main unit |
Width |
(mm) |
700 |
1000 |
|
dimension |
|
|||||
|
|
|
|
|
|
|
|
|
|
Depth |
(mm) |
800 |
800 |
|
|
|
|
|
|
|
Total weight |
|
Main unit |
|
(kg) |
30 |
39 |
|
|
|
|
|
|
|
Heat exchanger |
|
|
|
Finned tube |
||
|
|
|
|
|
|
|
|
|
Fan |
|
|
Centrifugal |
|
|
|
|
|
|
|
|
Fan unit |
|
Standard air flow |
H/M/L |
(m³/min.) |
13.0 / 11.9 / 9.8 |
19.0 / 16.2 / 13.3 |
|
|
|
|
|
|
|
|
|
Motor |
|
(W) |
120 |
120 |
|
|
|
|
|
|
|
|
|
|
|
|
TCB-UFM21BE |
TCB-UFM31BE |
Air filter (Sold separately) |
|
|
TCB-UFH61BE |
TCB-UFH71BE |
||
|
|
TCB-UFM21BFCE |
TCB-UFM21BFCE |
|||
|
|
|
|
|
||
|
|
|
|
|
TCB-UFH61BFCE |
TCB-UFH61BFCE |
|
|
|
|
|
|
|
Controller (Sold separately) |
|
|
RBC-AMT31E, AMT32E, AMS41E, AS21E2, |
|||
|
|
TCB-AX21E2 |
||||
|
|
|
|
|
||
|
|
|
|
|
|
|
Sound pressure level |
H/M/L |
(dB•A) |
40 / 37 / 33 |
40 / 37 / 34 |
||
|
|
|
|
|
|
|
Sound power level |
H/M/L |
(dB•A) |
55 / 52 / 48 |
55 / 52 / 49 |
||
|
|
|
|
|
|
|
|
|
|
Gas side |
(mm) |
12.7 |
15.9 |
|
|
|
|
|
|
|
Connecting pipe |
|
Liquid side |
(mm) |
6.4 |
9.5 |
|
|
|
|
|
|
|
|
|
|
|
Drain port |
(mm) |
VP25 |
|
|
|
|
|
|
|
|
: IEC standard
– 10 –
1-1-3. Under Ceiling Type
<Single type>
|
|
Indoor unit |
|
|
RAV-SM562CT-E |
RAV-SM802CT-E |
|
Model |
|
|
|
|
|
|
|
|
Outdoor unit |
|
|
RAV-SP564AT(Z)(ZG)-E |
RAV-SP804AT(Z)(ZG)-E |
||
|
|
|
|
||||
|
|
|
|
|
|
|
|
Cooling capacity |
|
|
(kW) |
5.0 |
7.1 |
||
|
|
|
|
|
|
|
|
Heating capacity |
|
|
(kW) |
5.6 |
8.0 |
||
|
|
|
|
|
|
|
|
Power supply |
|
|
|
1 phase 230V (220 – 240V) 50Hz |
|||
|
|
|
|
|
|
|
|
|
|
|
Running current |
(A) |
7.24 – 6.63 |
10.36 – 9.49 |
|
|
|
|
|
|
|
|
|
|
|
|
Power consumption |
(kW) |
1.56 |
2.21 |
|
|
|
|
|
|
|
|
|
|
|
Cooling |
Power factor |
(%) |
98 |
97 |
|
|
|
|
|
|
|
|
|
|
|
|
EER |
|
3.21 |
3.21 |
|
|
|
|
|
|
|
||
|
|
|
Energy efficiency class |
A |
A |
||
Electrical |
|
|
|
|
|
|
|
|
|
Running current |
(A) |
6.82 – 6.25 |
10.12 – 9.28 |
||
characteristics |
|
|
|||||
|
|
|
|
|
|
||
|
|
|
Power consumption |
(kW) |
1.47 |
2.16 |
|
|
|
|
|
|
|
|
|
|
|
Heating |
Power factor |
(%) |
98 |
97 |
|
|
|
|
|
|
|
|
|
|
|
|
COP |
|
3.81 |
3.70 |
|
|
|
|
|
|
|
||
|
|
|
Energy efficiency class |
A |
A |
||
|
|
|
|
|
|
|
|
|
|
Maximum current |
|
(A) |
13.50 |
20.50 |
|
|
|
|
|
|
|
|
|
Appearance |
|
Main unit |
|
|
Shine white |
||
|
|
|
|
|
|
|
|
|
|
|
Height |
(mm) |
210 |
210 |
|
Outer |
|
|
|
|
|
|
|
Main unit |
Width |
(mm) |
910 |
1180 |
|||
dimension |
|
||||||
|
|
|
|
|
|
||
|
|
|
Depth |
(mm) |
680 |
680 |
|
|
|
|
|
|
|
|
|
Total weight |
|
Main unit |
|
(kg) |
21 |
25 |
|
|
|
|
|
|
|
|
|
Heat exchanger |
|
|
|
Finned tube |
|||
|
|
|
|
|
|
|
|
|
|
Fan |
|
|
Centrifugal |
||
|
|
|
|
|
|
|
|
Fan unit |
|
Standard air flow |
H/M/L |
(m³/min.) |
13.0 / 11.2 / 10.0 |
18.5 / 16.7 / 14.6 |
|
|
|
|
|
|
|
|
|
|
|
Motor |
|
(W) |
60 |
60 |
|
|
|
|
|
|
|
|
|
Air filter |
|
|
|
Attached main unit |
|||
|
|
|
|
|
|
|
|
Controller (Sold separately) |
|
|
RBC-AMT31E, AMT32E, AMS41E, AS21E2, |
||||
|
|
TCB-AX21E2, AX22CE2 |
|||||
|
|
|
|
|
|||
|
|
|
|
|
|
||
Sound pressure level |
H/M/L |
(dB•A) |
36 / 33 / 30 |
38 / 36 / 33 |
|||
|
|
|
|
|
|
||
Sound power level |
H/M/L |
(dB•A) |
51 / 48 / 45 |
53 / 51 / 48 |
|||
|
|
|
|
|
|
|
|
|
|
|
Gas side |
(mm) |
12.7 |
15.9 |
|
|
|
|
|
|
|
|
|
Connecting pipe |
|
Liquid side |
(mm) |
6.4 |
9.5 |
||
|
|
|
|
|
|
|
|
|
|
|
Drain port |
(mm) |
VP25 |
||
|
|
|
|
|
|
|
: IEC standard
– 11 –
1-1-4. High Wall Type
<Single type>
|
|
Indoor unit |
|
|
RAV-SM562KRT-E |
RAV-SM802KRT-E |
|
Model |
|
|
|
|
|
|
|
|
Outdoor unit |
|
|
RAV-SP564AT(Z)(ZG)-E |
RAV-SP804AT(Z)(ZG)-E |
||
|
|
|
|
||||
|
|
|
|
|
|
|
|
Cooling capacity |
|
|
(kW) |
5.0 |
6.9 |
||
|
|
|
|
|
|
|
|
Heating capacity |
|
|
(kW) |
5.6 |
8.0 |
||
|
|
|
|
|
|
|
|
Power supply |
|
|
|
1 phase 230V (220 – 240V) 50Hz |
|||
|
|
|
|
|
|
|
|
|
|
|
Running current |
(A) |
7.24 – 6.63 |
11.25 – 10.31 |
|
|
|
|
|
|
|
|
|
|
|
|
Power consumption |
(kW) |
1.56 |
2.40 |
|
|
|
|
|
|
|
|
|
|
|
Cooling |
Power factor |
(%) |
98 |
97 |
|
|
|
|
|
|
|
|
|
|
|
|
EER |
|
3.21 |
2.88 |
|
|
|
|
|
|
|
||
|
|
|
Energy efficiency class |
A |
C |
||
Electrical |
|
|
|
|
|
|
|
|
|
Running current |
(A) |
7.19 – 6.59 |
11.25 – 10.31 |
||
characteristics |
|
|
|||||
|
|
|
|
|
|
||
|
|
|
Power consumption |
(kW) |
1.55 |
2.40 |
|
|
|
|
|
|
|
|
|
|
|
Heating |
Power factor |
(%) |
98 |
97 |
|
|
|
|
|
|
|
|
|
|
|
|
COP |
|
3.61 |
3.33 |
|
|
|
|
|
|
|
||
|
|
|
Energy efficiency class |
A |
C |
||
|
|
|
|
|
|
|
|
|
|
Maximum current |
|
(A) |
13.40 |
20.40 |
|
|
|
|
|
|
|
|
|
Appearance |
|
Main unit |
|
|
Pure white |
||
|
|
|
|
|
|
|
|
|
|
|
Height |
(mm) |
298 |
298 |
|
Outer |
|
|
|
|
|
|
|
Main unit |
Width |
(mm) |
998 |
998 |
|||
dimension |
|
||||||
|
|
|
|
|
|
||
|
|
|
Depth |
(mm) |
221 |
221 |
|
|
|
|
|
|
|
|
|
Total weight |
|
Main unit |
|
(kg) |
12 |
12 |
|
|
|
|
|
|
|
|
|
Heat exchanger |
|
|
|
Finned tube |
|||
|
|
|
|
|
|
|
|
|
|
Fan |
|
|
Cross flow fan |
||
|
|
|
|
|
|
|
|
Fan unit |
|
Standard air flow |
H/M/L |
(m³/min.) |
14.0 / 12.5 / 10.7 |
18.5 / 14.6 / 12.2 |
|
|
|
|
|
|
|
|
|
|
|
Motor |
|
(W) |
30 |
30 |
|
|
|
|
|
|
|
|
|
Air filter |
|
|
|
Attached main unit |
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
RBC-AMT31E, AMT32E, AMS41E, AS21E2, |
||
Controller (Sold separately) |
|
|
TCB-AX21E2 |
||||
|
|
|
|
|
(FCU comes with WH-H2UE) |
||
|
|
|
|
|
|
||
Sound pressure level |
H/M/L |
(dB•A) |
39 / 36 / 33 |
45 / 41 / 36 |
|||
|
|
|
|
|
|
||
Sound power level |
H/M/L |
(dB•A) |
54 / 51 / 48 |
60 / 56 / 51 |
|||
|
|
|
|
|
|
|
|
|
|
|
Gas side |
(mm) |
12.7 |
15.9 |
|
|
|
|
|
|
|
|
|
Connecting pipe |
|
Liquid side |
(mm) |
6.4 |
9.5 |
||
|
|
|
|
|
|
|
|
|
|
|
Drain port |
(mm) |
VP16 |
||
|
|
|
|
|
|
|
: IEC standard
– 12 –
1-1-5. Compact 4-Way Air Discharge Cassette Type (600 × 600)
<Single type>
Model |
|
Indoor unit |
|
RAV-SM |
402MUT-E |
|
452MUT-E |
|
562MUT-E |
|
|
|
|
|
|
|
|
|
|
|
Outdoor unit |
|
RAV-SP |
404AT(Z)(ZG)-E |
454AT(Z)(ZG)-E |
|
564AT(Z)(ZG)-E |
||
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
Cooling capacity |
|
|
(kW) |
3.6 |
|
4.0 |
|
5.0 |
|
|
|
|
|
|
|
|
|
|
|
Heating capacity |
|
|
(kW) |
4.0 |
|
4.5 |
|
5.6 |
|
|
|
|
|
|
|
|
|
||
Power supply |
|
|
|
1 phase 230V (220 – 240V) 50Hz |
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
Running current |
(A) |
5.05 – 4.63 |
|
5.82 – 5.33 |
|
7.24 – 6.63 |
|
|
|
|
|
|
|
|
|
|
|
|
|
Power consumption |
(kW) |
1.00 |
|
1.19 |
|
1.56 |
|
|
|
|
|
|
|
|
|
|
|
|
Cooling |
Power factor |
(%) |
90 |
|
93 |
|
98 |
|
|
|
|
|
|
|
|
|
|
|
|
|
EER |
|
3.60 |
|
3.36 |
|
3.21 |
|
|
|
|
|
|
|
|
|
|
|
|
|
Energy efficiency class |
A |
|
A |
|
A |
|
Electrical |
|
|
|
|
|
|
|
|
|
|
|
Running current |
(A) |
4.79 – 4.39 |
|
5.67 – 5.20 |
|
7.14 – 6.55 |
|
characteristics |
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
Power consumption |
(kW) |
0.97 |
|
1.16 |
|
1.54 |
|
|
|
|
|
|
|
|
|
|
|
|
Heating |
Power factor |
(%) |
92 |
|
93 |
|
98 |
|
|
|
|
|
|
|
|
|
|
|
|
|
COP |
|
4.12 |
|
3.88 |
|
3.64 |
|
|
|
|
|
|
|
|
|
|
|
|
|
Energy efficiency class |
A |
|
A |
|
A |
|
|
|
|
|
|
|
|
|
|
|
|
|
Maximum current |
|
(A) |
— |
|
— |
|
13.60 |
|
|
|
|
|
|
|
|
|
|
|
|
Main unit |
|
|
|
Zinc hot dipping steel plate |
|||
|
|
|
|
|
|
|
|
|
|
Appearance |
|
Ceiling panel |
Model |
|
|
RBC-UM11PG (W)-E |
|
||
|
|
|
|
|
|
|
|
|
|
|
|
(Sold separately) |
Panel color |
|
Moon-white (Muncel 2.5GY 9.0/0.5) |
||||
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
Height |
(mm) |
|
268 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Main unit |
Width |
(mm) |
|
575 |
|
|
|
|
|
|
|
|
|
|
|
|
|
Outer |
|
|
Depth |
(mm) |
|
575 |
|
|
|
|
|
|
|
|
|
|
|
|
|
dimension |
|
|
Height |
(mm) |
|
27 |
|
|
|
|
|
|
|
|
|
||||
|
|
Ceiling panel |
|
|
|
|
|
|
|
|
|
Width |
(mm) |
|
700 |
|
|
||
|
|
(Sold separately) |
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
Depth |
(mm) |
|
700 |
|
|
||
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
Total weight |
|
Main unit |
|
(kg) |
|
17 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Ceiling panel (Sold separately) |
(kg) |
|
3 |
|
|
|||
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
Heat exchanger |
|
|
|
|
|
Finned tube |
|
||
|
|
|
|
|
|
|
|
|
|
|
|
Fan |
|
|
|
|
Turbo fan |
|
|
|
|
|
|
|
|
|
|
|
|
Fan unit |
|
Standard air flow |
H/M/L |
(m³/min.) |
11.0 / 9.2 / 7.8 |
|
13.3 / 11.2 / 9.1 |
||
|
|
|
|
|
|
|
|
|
|
|
|
Motor |
|
(W) |
|
60 |
|
|
|
|
|
|
|
|
|
|
|
|
|
Air filter |
|
|
|
|
|
Long life filter |
|
||
|
|
|
|
|
|
|
|
||
Controller (Sold separately) |
|
|
RBC-AMT31E, AMT32E, AMS41E, AS21E2, |
||||||
|
|
|
|
TCB-AX21E2 |
|
||||
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
||
Sound pressure level |
H/M/L |
(dB•A) |
40 / 36 / 31 |
|
43 / 39 / 34 |
||||
|
|
|
|
|
|
|
|
|
|
Sound power level |
|
H/M/L |
(dB•A) |
55 / 51 / 46 |
|
58 / 54 / 49 |
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
Gas side |
(mm) |
|
12.7 |
|
|
|
|
|
|
|
|
|
|
|
|
|
Connecting pipe |
|
Liquid side |
(mm) |
|
6.4 |
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
Drain port |
(mm) |
|
|
VP25 |
|
|
|
|
|
|
|
|
|
|
|
|
: IEC standard
– 13 –
<Twin type>
|
|
Indoor unit 1 |
|
|
|
RAV-SM402MUT-E |
|
|
|
|
|
|
|
Model |
|
Indoor unit 2 |
|
|
|
RAV-SM402MUT-E |
|
|
|
|
|
|
|
|
|
Outdoor unit |
|
|
|
RAV-SP804AT(Z)(ZG)-E |
|
|
|
|
|
|
|
Cooling capacity |
|
|
(kW) |
|
7.1 |
|
|
|
|
|
|
|
|
Heating capacity |
|
|
(kW) |
|
8.0 |
|
|
|
|
|
|
|
|
|
|
|
Indoor unit |
|
||
|
|
|
|
|
|
|
Power supply |
|
|
|
|
1 phase 230V (220 – 240V) 50Hz |
|
|
|
|
|
|
|
|
|
|
|
Running current |
(A) |
|
10.36 – 9.49 |
|
|
|
|
|
|
|
|
|
|
Power consumption |
(kW) |
|
2.21 |
|
|
|
|
|
|
|
|
|
Cooling |
Power factor |
(%) |
|
97 |
|
|
|
|
|
|
|
|
|
|
EER |
|
|
3.21 |
|
|
|
|
|
|
|
Electrical |
|
|
Energy efficiency class |
|
A |
|
|
|
|
|
|
|
|
characteristics |
|
|
Running current |
(A) |
|
10.12 – 9.28 |
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
Power consumption |
(kW) |
|
2.16 |
|
|
|
|
|
|
|
|
|
Heating |
Power factor |
(%) |
|
97 |
|
|
|
|
|
|
|
|
|
|
COP |
|
|
3.70 |
|
|
|
|
|
|
|
|
|
|
Energy efficiency class |
|
A |
|
|
|
|
|
|
|
|
|
|
Fan |
|
|
|
Turbo fan |
|
|
|
|
|
|
|
Fan unit |
|
Standard air flow |
H/M/L |
(m³/min.) |
|
11.0 / 9.2 / 7.8 |
|
|
|
|
|
|
|
|
|
Motor |
|
(W) |
|
60 |
|
|
|
|
|
|
|
Sound pressure level |
H/M/L |
(dB•A) |
|
40 / 36 / 31 |
||
|
|
|
|
|
|
|
Sound power level |
H/M/L |
(dB•A) |
|
55 / 51 / 46 |
||
|
|
|
|
|
|
|
|
|
|
Outdoor unit |
|
||
|
|
|
|
|
|
|
Power supply |
|
|
|
|
1 phase 230V (220 – 240V) 50Hz |
|
|
|
|
|
|
|
|
|
|
Standard length |
|
(m) |
|
7.5 |
|
|
|
|
|
|
|
|
|
Min. length |
|
(m) |
|
5 |
|
|
|
|
|
|
|
Refrigerant |
|
Max. total length |
|
(m) |
|
50 |
|
|
|
|
|
|
|
|
Refrigerant charging amount |
|
|
40g/m |
||
pipe |
|
|
|
|||
|
|
(Charge-less up to 30m) |
|
|
(31m to 50m) |
|
|
|
|
|
|
|
|
|
|
Height |
Outdoor lower |
(m) |
|
30 |
|
|
|
|
|
|
|
|
|
difference |
Outdoor higher |
(m) |
|
30 |
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
Fan |
|
|
|
Propeller fan |
|
|
|
|
|
|
|
Fan unit |
|
Standard air flow volume |
(m³/min.) |
|
50 |
|
|
|
|
|
|
|
|
|
|
Motor |
|
(W) |
|
63 |
|
|
|
|
|
|
|
|
|
Gas side |
Main |
(mm) |
|
15.9 |
|
|
|
|
|
|
|
Connecting |
|
Sub |
(mm) |
|
12.7 |
|
|
|
|
||||
|
|
|
|
|
|
|
pipe |
|
|
Main |
(mm) |
|
9.5 |
|
|
Liquid side |
|
|||
|
|
|
|
|
|
|
|
|
Sub |
(mm) |
|
6.4 |
|
|
|
|
|
|||
|
|
|
|
|
|
|
Sound pressure level |
Cooling/Heating |
(dB•A) |
|
48 / 49 |
||
|
|
|
|
|
|
|
Sound power level |
Cooling/Heating |
(dB•A) |
|
64 / 65 |
||
|
|
|
|
|
|
|
: IEC standard
– 14 –
1-1-6. Slim Duct Type
<Single type>
Model |
Indoor unit |
|
RAV-SM |
404SDT-E |
|
454SDT-E |
564SDT-E |
|
|
|
|
|
|
|
|
Outdoor unit |
|
RAV-SP |
404AT(Z)(ZG)-E |
454AT(Z)(ZG)-E |
564AT(Z)(ZG)-E |
||
|
|
||||||
|
|
|
|
|
|
|
|
Cooling capacity |
|
|
(kW) |
3.6 |
|
4.0 |
5.0 |
|
|
|
|
|
|
|
|
Heating capacity |
|
|
(kW) |
4.0 |
|
4.5 |
5.6 |
|
|
|
|
|
|
|
|
Power supply |
|
|
|
1 phase 230V (220 – 240V) 50Hz |
|||
|
|
|
|
|
|
|
|
|
|
Running current |
(A) |
5.20 – 4.77 |
|
5.87 – 5.38 |
7.24 – 6.63 |
|
|
|
|
|
|
|
|
|
|
Power consumption |
(kW) |
1.03 |
|
1.20 |
1.56 |
|
|
|
|
|
|
|
|
|
Cooling |
Power factor |
(%) |
90 |
|
93 |
98 |
|
|
|
|
|
|
|
|
|
|
EER |
|
3.50 |
|
3.33 |
3.21 |
|
|
|
|
|
|
|
|
|
|
Energy efficiency class |
A |
|
A |
A |
|
Electrical |
|
|
|
|
|
|
|
|
Running current |
(A) |
4.94 – 4.53 |
|
5.62 – 5.15 |
6.68 – 6.12 |
|
characteristics |
|
|
|||||
|
|
|
|
|
|
|
|
|
Power consumption |
(kW) |
1.00 |
|
1.15 |
1.44 |
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
Heating |
Power factor |
(%) |
92 |
|
93 |
98 |
|
|
|
|
|
|
|
|
|
|
COP |
|
4.00 |
|
3.91 |
3.89 |
|
|
|
|
|
|
|
|
|
|
Energy efficiency class |
A |
|
A |
A |
|
|
|
|
|
|
|
|
|
|
Maximum current |
|
(A) |
15.00 |
|
15.00 |
13.60 |
|
|
|
|
|
|
|
|
Appearance |
Main unit |
|
|
|
Zinc hot dipping steel plate |
||
|
|
|
|
|
|
|
|
|
|
Height |
(mm) |
|
210 |
|
|
Outer |
|
|
|
|
|
|
|
Main unit |
Width |
(mm) |
|
845 |
|
||
dimension |
|
|
|||||
|
|
|
|
|
|
|
|
|
Depth |
(mm) |
|
645 |
|
||
|
|
|
|
||||
|
|
|
|
|
|
|
|
Total weight |
Main unit |
|
(kg) |
|
22 |
|
|
|
|
|
|
|
|
|
|
Heat exchanger |
|
|
|
|
|
Finned tube |
|
|
|
|
|
|
|
|
|
|
Fan |
|
|
|
|
Centrifugal |
|
|
|
|
|
|
|
|
|
Fan unit |
Standard air flow |
H/M/L |
(m³/min.) |
11.5 / 10.0 / 8.7 |
13.0 / 11.3 / 9.7 |
||
|
|
|
|
|
|
|
|
|
Motor |
|
(W) |
|
60 |
|
|
|
|
|
|
|
|
|
|
Air filter |
|
|
|
Standard filter attached (Long life filter) |
|||
|
|
|
|
|
|
|
|
Controller (Sold separately) |
|
|
RBC-AMT31E, AMT32E, AMS41E, AS21E2, |
||||
|
|
|
|
TCB-AX21E2 |
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Sound |
Under air inlet |
H/M/L |
(dB•A) |
39 / 36 / 33 |
45 / 40 / 36 |
||
|
|
|
|
|
|
|
|
pressure level |
Back air inlet |
H/M/L |
(dB•A) |
30 / 28 / 26 |
33 / 31 / 28 |
||
|
|||||||
|
|
|
|
|
|
|
|
Sound |
Under air inlet |
H/M/L |
(dB•A) |
54 / 51 / 48 |
60 / 55 / 51 |
||
|
|
|
|
|
|
|
|
power level |
Back air inlet |
H/M/L |
(dB•A) |
45 / 43 / 41 |
48 / 46 / 43 |
||
|
|||||||
|
|
|
|
|
|
|
|
|
|
Gas side |
(mm) |
|
12.7 |
|
|
|
|
|
|
|
|
|
|
Connecting pipe |
|
Liquid side |
(mm) |
|
6.4 |
|
|
|
|
|
|
|
|
|
|
|
|
Drain port |
(mm) |
|
|
VP25 |
|
|
|
|
|
|
|
|
|
: IEC standard
– 15 –
<Twin type>
|
|
Indoor unit 1 |
|
|
|
RAV-SM404SDT-E |
|
|
|
|
|
|
|
Model |
|
Indoor unit 2 |
|
|
|
RAV-SM404SDT-E |
|
|
|
|
|
|
|
|
|
Outdoor unit |
|
|
|
RAV-SP804AT(Z)(ZG)-E |
|
|
|
|
|
|
|
Cooling capacity |
|
|
(kW) |
|
7.1 |
|
|
|
|
|
|
|
|
Heating capacity |
|
|
(kW) |
|
8.0 |
|
|
|
|
|
|
|
|
|
|
|
Indoor unit |
|
||
|
|
|
|
|
|
|
Power supply |
|
|
|
|
1 phase 230V (220 – 240V) 50Hz |
|
|
|
|
|
|
|
|
|
|
|
Running current |
(A) |
|
10.36 – 9.49 |
|
|
|
|
|
|
|
|
|
|
Power consumption |
(kW) |
|
2.21 |
|
|
|
|
|
|
|
|
|
Cooling |
Power factor |
(%) |
|
97 |
|
|
|
|
|
|
|
|
|
|
EER |
|
|
3.21 |
|
|
|
|
|
|
|
Electrical |
|
|
Energy efficiency class |
|
A |
|
characteristics |
|
|
Running current |
(A) |
|
10.12 – 9.28 |
|
|
|
|
|
|
|
|
|
|
Power consumption |
(kW) |
|
2.16 |
|
|
|
|
|
|
|
|
|
Heating |
Power factor |
(%) |
|
97 |
|
|
|
|
|
|
|
|
|
|
COP |
|
|
3.70 |
|
|
|
|
|
|
|
|
|
|
Energy efficiency class |
|
A |
|
|
|
|
|
|
|
|
|
|
Fan |
|
|
|
Centrifugal |
|
|
|
|
|
|
|
Fan unit |
|
Standard air flow |
H/M/L |
(m³/min.) |
|
11.5 / 10.0 / 8.7 |
|
|
|
|
|
|
|
|
|
Motor |
|
(W) |
|
60 |
|
|
|
|
|
|
|
Sound |
|
Under air inlet |
H/M/L |
(dB•A) |
|
39 / 36 / 33 |
pressure level |
|
Back air inlet |
H/M/L |
(dB•A) |
|
30 / 28 / 26 |
|
|
|
|
|
|
|
Sound |
|
Under air inlet |
H/M/L |
(dB•A) |
|
54 / 51 / 48 |
power level |
|
Back air inlet |
H/M/L |
(dB•A) |
|
45 / 43 / 41 |
|
|
|
|
|
|
|
|
|
|
Outdoor unit |
|
||
|
|
|
|
|
|
|
Power supply |
|
|
|
|
1 phase 230V (220 – 240V) 50Hz |
|
|
|
|
|
|
|
|
|
|
Standard length |
|
(m) |
|
7.5 |
|
|
|
|
|
|
|
|
|
Min. length |
|
(m) |
|
5 |
|
|
|
|
|
|
|
Refrigerant |
|
Max. total length |
|
(m) |
|
50 |
|
|
|
|
|
|
|
|
Refrigerant charging amount |
|
|
40g/m |
||
pipe |
|
|
|
|||
|
|
(Charge-less up to 30m) |
|
|
(31m to 50m) |
|
|
|
Height |
Outdoor lower |
(m) |
|
30 |
|
|
difference |
Outdoor higher |
(m) |
|
30 |
|
|
|
|
|
|
|
|
|
Fan |
|
|
|
Propeller fan |
|
|
|
|
|
|
|
Fan unit |
|
Standard air flow volume |
(m³/min.) |
|
50 |
|
|
|
|
|
|
|
|
|
|
Motor |
|
(W) |
|
63 |
|
|
|
|
|
|
|
|
|
Gas side |
Main |
(mm) |
|
15.9 |
|
|
|
|
|
|
|
Connecting |
|
Sub |
(mm) |
|
12.7 |
|
|
|
|
||||
pipe |
|
Liquid side |
Main |
(mm) |
|
9.5 |
|
|
|
|
|
|
|
|
|
Sub |
(mm) |
|
6.4 |
|
|
|
|
|
|||
|
|
|
|
|
|
|
Sound pressure level |
Cooling/Heating |
(dB•A) |
|
48 / 49 |
||
|
|
|
|
|
|
|
Sound power level |
Cooling/Heating |
(dB•A) |
|
64 / 65 |
||
|
|
|
|
|
|
|
: IEC standard
– 16 –
1-2. Outdoor Unit
<Super Digital Inverter>
Model name |
|
Outdoor unit |
RAV-SP |
404AT(Z)(ZG)-E |
|
454AT(Z)(ZG)-E |
564AT(Z)(ZG)-E |
804AT(Z)(ZG)-E |
|
|
|
|
|
|
|
|
|
Power supply |
|
|
|
|
|
1 phase 230V (220 – 240V) 50Hz |
|
|
|
|
|
(Power exclusive to outdoor is required.) |
|||||
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
Type |
|
|
|
|
Hermetic compressor |
|
|
|
|
|
|
|
|
|
|
|
Compressor |
Motor |
|
(kW) |
1.1 |
|
1.1 |
1.1 |
2.0 |
|
|
|
|
|
|
|
|
|
|
Pole |
|
|
4 |
|
4 |
4 |
4 |
|
|
|
|
|
|
|
|
|
Refrigerant charged |
|
(kg) |
1.0 |
|
1.0 |
1.4 |
2.1 |
|
|
|
|
|
|
|
|
|
|
Refrigerant control |
|
|
|
|
Pulse motor valve |
|
||
|
|
|
|
|
|
|
|
|
|
Standard length |
(m) |
7.5 |
|
7.5 |
7.5 |
7.5 |
|
|
|
|
|
|
|
|
|
|
|
Min. length |
|
(m) |
5 |
|
5 |
5 |
5 |
|
|
|
|
|
|
|
|
|
Inter |
Max. total length |
(m) |
30 |
|
30 |
50 |
50 |
|
|
|
|
|
|
|
|
|
|
connecting |
Additional refrigerant charge |
|
20g/m |
|
20g/m |
20g/m |
40g/m |
|
pipe |
|
|
||||||
under long piping connector |
|
(21m to 30m) |
|
(21m to 30m) |
(21m to 50m) |
(31m to 50m) |
||
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
Height |
Outdoor lower |
(m) |
30 |
|
30 |
30 |
30 |
|
|
|
|
|
|
|
|
|
|
difference |
Outdoor higher |
(m) |
30 |
|
30 |
30 |
30 |
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
Height |
|
(mm) |
550 |
|
550 |
550 |
890 |
Outer |
|
|
|
|
|
|
|
|
Width |
|
(mm) |
780 |
|
780 |
780 |
900 |
|
dimension |
|
|
||||||
|
|
|
|
|
|
|
|
|
|
Depth |
|
(mm) |
290 |
|
290 |
290 |
320 |
|
|
|
|
|
|
|
|
|
Appearance |
|
|
|
|
|
Silky shade (Muncel 1Y 8.5/0.5) |
|
|
|
|
|
|
|
|
|
|
|
Total weight |
|
|
(kg) |
40 |
|
40 |
44 |
63 |
|
|
|
|
|
|
|
|
|
Heat exchanger |
|
|
|
|
Finned tube |
|
||
|
|
|
|
|
|
|
|
|
|
Fan |
|
|
|
|
Propeller fan |
|
|
|
|
|
|
|
|
|
||
Fan unit |
Standard air flow |
(m³/min.) |
40 |
|
40 |
40 |
50 |
|
|
|
|
|
|
|
|
|
|
|
Motor |
|
(W) |
43 |
|
43 |
43 |
63 |
|
|
|
|
|
|
|
|
|
Connecting |
Gas side |
|
(mm) |
12.7 |
|
12.7 |
12.7 |
15.9 |
|
|
|
|
|
|
|
|
|
pipe |
Liquid side |
|
(mm) |
6.4 |
|
6.4 |
6.4 |
9.5 |
|
|
|
||||||
|
|
|
|
|
|
|
|
|
Sound pressure level |
Cooling/Heating |
(dB•A) |
45 / 47 |
|
45 / 47 |
47 / 48 |
48 / 49 |
|
|
|
|
|
|
|
|
|
|
Sound power level |
Cooling/Heating |
(dB•A) |
62 / 64 |
|
62 / 64 |
63 / 64 |
64 / 65 |
|
|
|
|
|
|
|
|
|
|
Outside air temperature, Cooling |
(°C) |
|
|
43 to |
– 15°C |
|
||
|
|
|
|
|
|
|||
Outside air temperature, Heating |
(°C) |
15 to |
– 15°C |
15 to |
– 20°C |
|||
|
|
|
|
|
|
|
|
|
– 17 –
1-3. Operation Characteristic Curve
• Operation characteristic curve <Super Digital Inverter>
RAV-SP564AT-E, RAV-SP564ATZ-E, RAV-SP564ATZG-E
<Cooling> |
<Heating> |
Current (A)
10
9
8
7
6
5
4
3
2
1
0
0
RAV-SM562BT, CT, KRT, MUT-E, RAV-SM564SDT-E
RAV-SM564UT-E
• Conditions
Indoor : DB27˚C/WB19˚C Outdoor : DB35˚C
Air flow : High Pipe length : 7.5m 230V
10 |
20 |
30 |
40 |
50 |
60 |
70 |
80 |
Compressor speed (rps)
Current (A)
16
14
RAV-SM562BT, CT, KRT, MUT-E, RAV-SM564SDT-E
12
10
8
6
RAV-SM564UT-E
4
• Conditions Indoor : DB20˚C
Outdoor : DB7˚C/WB6˚C 2 Air flow : High
Pipe length : 7.5m 230V
0
0 |
10 |
20 |
30 |
40 |
50 |
60 |
70 |
80 |
90 100 110 120 |
Compressor speed (rps)
RAV-SP804AT-E, RAV-SP804ATZ-E, RAV-SP804ATZG-E
<Cooling> |
<Heating> |
Current (A)
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
RAV-SM802BT, CT, KRT-E
RAV-SM804UT-E
• Conditions
Indoor : DB27˚C/WB19˚C
Outdoor : DB35˚C Air flow : High Pipe length : 7.5m 230V
10 |
20 |
30 |
40 |
50 |
60 |
70 |
80 |
Compressor speed (rps)
Current (A)
22
20
18 RAV-SM802BT, CT, KRT-E
16 |
|
|
|
|
|
|
|
|
|
|
|
|
14 |
|
|
|
|
|
|
|
|
|
|
|
|
12 |
|
|
|
|
|
|
|
|
|
|
|
|
10 |
|
|
|
|
|
|
|
RAV-SM804UT-E |
||||
|
|
|
|
|
|
|
|
|||||
8 |
|
|
|
|
|
|
|
|
|
|
|
|
6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
• Conditions |
|
|
|
||
4 |
|
|
|
|
|
|
Indoor : DB20˚C |
|
||||
|
|
|
|
|
|
Outdoor : DB7˚C/WB6˚C |
|
|
||||
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
Air flow : High |
|
|
|
||
2 |
|
|
|
|
|
|
Pipe length : 7.5m |
|
||||
|
|
|
|
|
|
|
230V |
|
|
|
|
|
0 |
|
|
|
|
|
|
|
|
|
|
|
|
|
10 |
20 |
30 |
40 |
50 |
60 |
70 |
80 |
90 100 110 120 |
|||
0 |
Compressor speed (rps)
– 18 –
RAV-SP404AT-E, RAV-SP404ATZ-E, RAV-SP404ATZG-E |
|
|
|
|
|
|
|
||||||||||
RAV-SP454AT-E, RAV-SP454ATZ-E, RAV-SP454ATZG-E |
|
|
|
|
|
|
|
||||||||||
<Cooling> |
|
|
|
|
|
|
|
|
<Heating> |
|
|
|
|
|
|
||
|
14 |
|
|
|
|
|
|
|
|
|
16 |
|
|
|
|
|
|
|
12 |
|
|
|
|
|
|
|
|
|
14 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
SP45 |
|
|
|
|
|
|
|
12 |
|
|
SP45 |
|
|
|
|
10 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(A) |
|
|
|
|
|
|
|
|
|
(A) |
10 |
|
|
|
|
|
|
8 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
Current |
|
|
|
|
|
|
|
|
Current |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
8 |
|
SP40 |
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
SP40 |
|
|
|
6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
4 |
|
|
|
|
|
|
|
|
|
4 |
|
|
|
|
|
|
|
|
|
|
• Conditions |
|
|
|
|
|
|
|
• Conditions |
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
|
|
|
|
Indoor : DB27˚C/WB19˚C |
|
|
|
|
|
|
Indoor : DB20˚C |
|
|||||
|
2 |
|
|
Outdoor : DB35˚C |
|
|
|
2 |
|
|
|
Outdoor : DB7˚C/WB6˚C |
|||||
|
|
|
|
Air flow : High |
|
|
|
|
|
|
|
Air flow : High |
|
||||
|
|
|
|
Pipe length : 7.5m |
|
|
|
|
|
|
|
Pipe length : 7.5m |
|
||||
|
|
|
|
230V |
|
|
|
|
|
|
|
|
|
230V |
|
|
|
|
0 |
20 |
40 |
50 |
60 |
70 |
80 |
90 |
100 |
|
00 |
20 |
40 |
60 |
80 |
90 100 |
120 |
|
0 |
|
|||||||||||||||
|
|
Compressor speed (rps) |
|
|
|
|
|
|
Compressor speed (rps) |
|
• Capacity variation ratio according to temperature
RAV-SP404AT-E, RAV-SP404ATZ-E, RAV-SP404ATZG-E
RAV-SP454AT-E, RAV-SP454ATZ-E, RAV-SP454ATZG-E
RAV-SP564AT-E, RAV-SP564ATZ-E, RAV-SP564ATZG-E
RAV-SP804AT-E, RAV-SP804ATZ-E, RAV-SP804ATZG-E
<Cooling> |
|
|
|
|
|
|
|
|
|
|
<Heating> |
|
|
|
|
|
|
|
|||
|
105 |
|
|
|
|
|
|
|
|
|
|
|
|
120 |
|
|
|
|
|
|
|
|
100 |
|
|
|
|
|
|
|
|
|
|
|
|
110 |
|
|
|
|
|
|
|
|
95 |
|
|
|
|
|
|
|
|
|
|
|
|
100 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
90 |
|
|
|
|
|
|
|
|
|
|
|
|
90 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(%) |
85 |
|
|
|
|
|
|
|
|
|
|
|
(%) |
80 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ratio |
80 |
|
|
|
|
|
|
|
|
|
|
|
ratio |
70 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Capacity |
70 |
|
|
|
|
|
|
|
|
|
|
|
Capacity |
60 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
75 |
|
|
|
|
|
|
|
|
|
|
|
|
50 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
40 |
|
|
|
|
|
|
|
|
65 |
|
|
|
|
|
|
|
|
|
|
|
|
30 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
60 |
|
|
|
|
• Conditions |
|
|
|
|
|
20 |
|
• Conditions |
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||
|
55 |
|
|
|
|
Indoor : DB27˚C/WB19˚C |
|
|
|
|
Indoor : DB20˚C |
|
|
||||||||
|
|
|
|
|
Indoor air flow : High |
|
|
|
10 |
|
Indoor air flow : High |
|
|||||||||
|
|
|
|
|
|
Pipe length : 7.5m |
|
|
|
|
|
Pipe length : 7.5m |
|
|
|||||||
|
50 |
33 |
34 |
35 |
36 |
37 |
38 |
39 |
40 |
41 |
42 |
43 |
|
0 |
-6 |
-4 -2 0 |
2 |
4 |
6 |
8 |
10 |
|
32 |
|
-20 -18 -16 -14 -12 -10 -8 |
Outdoor temp. (˚C) |
Outdoor temp. (˚C) |
– 19 –
2. CONSTRUCTION VIEWS (EXTERNAL VIEWS)
2-1. Indoor Unit
RAV-SM404SDT-E, RAV-SM454SDT-E, RAV-SM564SDT-E
21 |
845 |
|
168 (inside)
21 |
21 |
803 (inside) |
|
Air filter |
|
20 |
|
|
Ø4-4 |
19 |
Ø92 |
80 |
168 |
|
|
|
|
|
120 |
|
|
805 |
80 |
59 |
910 |
Fresh air inlet (knock-out hole)
|
57 |
|
210 |
21 |
Refrigerant piping |
|
103 |
|
67 |
511 |
645 |
31
359 |
372 |
422 |
502 |
67 |
40 |
33
163
Drain-up port
Hung-up plate
– 20 –
2-2. Outdoor Unit
RAV-SP404AT(Z)(ZG)-E, RAV-SP454AT(Z)(ZG)-E, RAV-SP564AT(Z)(ZG)-E
Drain hole
(2-Ø20 × 88 long hole)
320 |
(Long hole pitch For anchor bolt) |
306 |
|
Ø6 hole pitch 290 |
|
|
|
||||
|
|
|
|
|
69.5 |
147 |
21 |
|
|
6
550 |
483 |
8 |
35 |
|
|
Drain hole (Ø25) |
|
|
|
|
|
|
|
|
600 |
90 |
|
|
|
|
|
A legs |
|
|
54 |
2-Ø11-14 U-shape hole |
|
|||
|
|
108 |
125 |
(For Ø8-Ø10 anchor bolts) |
|
|||
|
|
60 |
|
30 |
|
|
Connecting pipe port |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(Gas flare side: Ø12.7) |
|
|
30 |
|
|
|
|
|
Connecting pipe port |
|
|
|
|
|
|
|
(Liquid flare side: Ø6.4) |
||
|
|
|
|
|
|
|
||
|
|
|
20 27 |
|
|
8-Ø6 hole |
|
|
|
B legs |
|
|
|
(For fixing outdoor unit) |
|||
|
|
45: 56: |
2-Ø11 × L14 long hole |
|
||||
|
|
|
|
|||||
|
|
|
40, |
(For Ø8-Ø10 anchor bolts) |
|
|||
|
|
|
|
|
|
|
|
|
|
|
483 |
|
257 |
|
|
157 |
79 |
|
|
108 |
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
21 |
449 |
|
|
|
|
25 |
|
|
145 |
|
|
|
|
|
31 |
143 |
||
|
|
|
|
|
|
|||
|
|
|
|
|
22 |
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
93 |
137 |
|
54 |
|
|
|
|
|
|
|
|
|
52 |
32 |
500 |
|
|
71 |
342 |
|
|
|
780 |
|
|
|
|
|
||
|
|
|
|
|
|
|
||
|
|
Discharge guard |
Discharge guide mounting hole |
Charge port |
Earth |
|||
|
|
|
||||||
|
|
|
(4-Ø4.5 embossing) |
|
|
terminal |
||
|
|
|
|
|
|
|
Space required for service
2-Ø11 × 14 U-shape holes (For Ø8–Ø10 anchor bolt)
150 or more
320 |
150 |
or more |
600
Suction port
300
or more
Discharge |
|
|
(Minimum |
port |
|
|
distance up to wall) |
|
|
|
|
|
|
|
|
|
|
500 |
Discharge |
|
|
or more |
|
|
|
port |
|
|
|
|
|
|
|
600 |
|
|
|
54 |
|
|
|
38 |
|
|
R15 |
2-Ø6 hole |
|
320 |
3 |
Product |
|
external line |
|
||
|
|
|
|
|
Ø11 × 14 U-shape hole |
|
|
Details of A legs |
|
|
2-Ø11 × 14 long hole |
||
|
(For Ø8–Ø10 anchor bolt) |
||
Ø11 × 14 U-shape holes |
|||
320 |
2-Ø6 hole |
||
3 |
Product |
||
external |
|||
|
|
||
|
|
line |
|
|
38 |
R15 |
|
|
54 |
|
|
|
|
600 |
Details of B legs
– 21 –
– 22 –
|
|
|
|
|
|
380 |
|
|
|
|
|
|
|
|
|
|
|
Name |
|
|
|
|
|
|
|
Drain hole (Ø25 burring hole) |
|
|
|
|
|
|
|||||
|
|
|
|
|
|
200 |
60 |
|
|
|
1 |
Refrigerant piping hole |
||||||
|
17.5 |
|
|
|
|
Air inlet |
|
B legs |
|
|
|
|
|
|
Indoor/Outdoor unit |
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
connecting wire inlet hole |
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
port |
|
|
|
|
|
|
|
|
|
|
|
|
|
365 128118 |
|
|
|
|
4675 |
|
34 170 |
|
|
|
|
|
|
|
2 |
Power supply inlet hole |
|
|
Air inlet |
|
|
|
48 |
54 |
|
|
|
(Ø12 × 17 long hole) |
|
|
|
|||||
|
|
|
port |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Mounting bolt hole |
12 |
|
|
|
|
74 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
17.5 |
|
|
|
|
Air outlet |
70 |
|
39 |
|
|
40 |
|
|
40 |
|
|
(Ø12 × 17 U-shape hole) |
|
|
|
|
|
383 |
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
port |
|
A legs |
|
|
|
|
|
|
|
|
|
Mounting bolt hole |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
5-drain hole |
|
|
150 |
|
600 |
|
96 |
|
|
Details of A legs |
Details of B legs |
|
||||||
(Ø20 × 88 burring hole) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
900 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
52 |
|
|
550 |
|
|
|
|
|
|
|
|
320 |
|
|
|
|
|
|
|
|
|
|
|
|
Refrigerant pipe |
|
30 |
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
connecting port |
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
(Ø9.5 flare at liquid side) |
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
Refrigerant pipe |
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
connecting port |
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
(Ø15.9 flare at gas side) |
|
|
|
|
|||||
|
|
581 |
534 |
|
|
|
|
|
|
|
2 |
|
2 |
|
890 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1 |
|
1 |
|
|
1 |
|
|
|
|
148 |
165 |
|
|
|
|
|
55 95 |
155 |
247 |
255 |
55 95 |
94 |
24 |
|
55 95 |
|
Mounting hole sold separately |
60 |
178 |
178 |
178 |
80 |
18 |
|
|
|
|
|
|
|
|
||||
|
|
|
|
18 |
80 |
|
12 |
64 |
||||||||||
(12 - Ø3 emboss) |
|
|
|
|
|
|
|
|||||||||||
|
|
68 |
|
518 |
|
135 |
|
|
|
|
|
|
151 |
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
327 |
|
|
|
|
|
|
|
|
|
400 |
|
|
|
83 |
7 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Z |
|
|
|
|
|
|
|
|
|
|
||
|
7 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
65 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Knockout for downward piping |
|
|
|
|
|
|
|
|
|
|
|
|
Note
——
Ø 38 Kockout hole
Unit : mm
E-SP804AT(Z)(ZG)-RAV
Z views
RAV-TWP30E2, RAV-TWP50E2 (Simultaneous Twin)
Inner diameter Ø C
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
B |
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
Inner |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Inner |
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
diameter Ø D |
|
|
|
|
|
|
|
|
|
|
|
|
|
diameter Ø D |
|||||
|
|
|
|
|
|
|
|
A |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||
|
|
|
Model (RBC-) |
A |
B |
|
C |
D |
|
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
|
TWP30E2 |
|
Liquid side |
36 |
14 |
|
Ø9.5 |
Ø6.4 |
|
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||
|
|
Gas side |
43 |
23 |
|
Ø15.9 |
Ø12.7 |
|
|
|
|||||||||
|
|
|
|
|
|
|
|
|
|
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
|
TWP50E2 |
|
Liquid side |
34 |
14 |
|
Ø9.5 |
Ø9.5 |
|
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||
|
|
Gas side |
44 |
21 |
|
Ø15.9 |
Ø15.9 |
|
|
|
|||||||||
|
|
|
|
|
|
|
|
|
|
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
– 23 –
3. SYSTEMATIC REFRIGERATING CYCLE DIAGRAM
3-1. Indoor Unit
• Single type (Combination of 1 indoor unit and 1 outdoor unit)
(Indoor unit)
Distributor
(Strainer incorporated)
TCJ sensor
Strainer
Air heat
exchanger TC sensor
Heating Cooling
Refrigerant pipe at liquid side (Outer dia : ØB)
Refrigerant pipe at gas side (Outer dia : ØA)
To outdoor unit |
To outdoor unit |
Dimension table
Indoor unit |
Outer diameter of refrigerant pipe |
||
|
|
||
Gas side ØA |
Liquid side ØB |
||
|
|||
|
|
|
|
SM40, 45, 56 type |
12.7 |
6.4 |
|
|
|
|
|
SM80 type |
15.9 |
9.5 |
|
|
|
|
Capillary tube specifications
Model |
Inner dia. × Length × Q’ty |
||
RAV-SM UT |
|||
|
|
||
|
|
|
|
SM56 type |
Ø2 × 250 |
× 2, Ø2 × 350 × 1 |
|
Ø2 × 700 |
× 1 |
||
|
|||
|
|
|
|
SM80 type |
Ø2 × 250 |
× 3, Ø2 × 500 × 1 |
|
|
|
|
|
|
|
|
|
Model |
Inner dia. × Length × Q’ty |
||
RAV-SM SDT |
|||
|
|
||
|
|
|
|
SM40, 45, 56 type |
Ø2 × 200 |
× 2, Ø2 × 350 × 1 |
|
|
|
|
• Twin type (Combination of 2 indoor units and 1 outdoor unit)
(Indoor unit A) |
(Indoor unit B) |
Distributor |
Distributor |
(Strainer incorporated) |
(Strainer incorporated) |
TCJ sensor |
TCJ sensor |
Air heat |
Strainer |
Air heat |
|
exchanger |
exchanger |
TC sensor |
TC sensor |
Heating
Cooling
Strainer
Refrigerant pipe at liquid side (Outer dia : ØA)
Refrigerant pipe at gas side (Outer dia : ØB)
Refrigerant pipe at liquid side (Outer dia : ØA)
Refrigerant pipe at gas side (Outer dia : ØB)
Branch pipe Branch pipe
Refrigerant pipe at liquid side (Outer dia : ØC)
Refrigerant pipe at liquid side (Outer dia : ØD)
To outdoor unit |
|
|
|
|
To outdoor unit |
|
|
|
|
|
|
|
|
Indoor unit |
Branch pipe RBC- |
A |
B |
C |
D |
|
|
|
|
|
|
|
|
SM40 × 2 |
TWP30E2 |
6.4 |
12.7 |
9.5 |
15.9 |
|
|
|
|
|
|
|
|
– 24 –
3-2. Outdoor Unit |
|
|
RAV-SP404AT-E, RAV-SP404ATZ-E, RAV-SP404ATZG-E |
|
|
RAV-SP454AT-E, RAV-SP454ATZ-E, RAV-SP454ATZG-E |
|
|
|
Packed valve |
Packed valve |
|
Outer dia. ØA |
Outer dia. ØB |
TS sensor |
|
PMV |
|
(Pulse Motor Valve) |
|
|
|
|
2-step muffler |
TO sensor |
(CAM-B30YGTF-2) |
|
||
Ø19.05 × 200L |
|
|
TD sensor |
|
|
|
|
Strainer |
4-way valve |
TE |
|
(STF-0108Z) |
sensor |
|
Muffler |
Heat exchanger |
|
Ø19 × L160 |
Ø8 ripple, 2 rows, |
|
|
14 steps |
Distributor |
|
FP1.3 flat fin |
|
Rotary compressor |
|
|
|
|
|
(DA150A1F-20F) |
|
|
|
|
R410A 1.0 kg |
|
|
Cooling |
|
|
Heating |
RAV-SP404AT-E, RAV-SP404ATZ-E, RAV-SP404ATZG-E |
|
|
|
|
Pressure |
|
|
Pipe surface temperature (°C) |
Compressor |
|
Indoor/Outdoor |
||||
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
(MPa) |
(kg/cm²g) |
Discharge |
Suction |
Indoor heat |
Outdoor heat |
drive revolution |
Indoor |
temp. conditions |
|||
|
|
(DB/WB) (°C) |
|||||||||||
|
|
exchanger |
exchanger |
frequency |
fan |
||||||||
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
(rps) |
|
|
|
|
|
Pd |
Ps |
Pd |
Ps |
(TD) |
(TS) |
(TC) |
(TE) |
|
Indoor |
Outdoor |
|
|
|
|
|
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Standard |
2.68 |
0.94 |
27.3 |
9.6 |
61 |
12 |
11 |
43 |
47 |
HIGH |
27 / 19 |
35 / – |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Cooling |
Overload |
3.23 |
1.16 |
32.9 |
11.8 |
77 |
14 |
15 |
50 |
50 |
HIGH |
32 / 24 |
43 / – |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Low load |
1.34 |
0.70 |
13.7 |
7.1 |
36 |
4 |
2 |
8 |
44 |
LOW |
18 / 15.5 |
–5 / – |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Standard |
2.38 |
0.70 |
24.3 |
7.1 |
65 |
7 |
39 |
4 |
49 |
HIGH |
20 / – |
7 / 6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Heating |
Overload |
3.39 |
1.03 |
34.6 |
10.5 |
83 |
20 |
54 |
16 |
49 |
LOW |
30 / – |
24 / 18 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Low load |
1.95 |
0.26 |
19.9 |
2.7 |
90 |
–17 |
32 |
–19 |
90 |
HIGH |
15 / – |
–15 / – |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
This compressor has 4-pole motor. The value when compressor frequency (Hz) is measured by a clamp meter becomes 2 times of No. of compressor revolutions (rps).
RAV-SP454AT-E, RAV-SP454ATZ-E, RAV-SP454ATZG-E
|
|
|
Pressure |
|
|
Pipe surface temperature (°C) |
Compressor |
|
Indoor/Outdoor |
||||
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
(MPa) |
(kg/cm²g) |
Discharge |
Suction |
Indoor heat |
Outdoor heat |
drive revolution |
Indoor |
temp. conditions |
|||
|
|
(DB/WB) (°C) |
|||||||||||
|
|
exchanger |
exchanger |
frequency |
fan |
||||||||
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
(rps) |
|
|
|
|
|
Pd |
Ps |
Pd |
Ps |
(TD) |
(TS) |
(TC) |
(TE) |
|
Indoor |
Outdoor |
|
|
|
|
|
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Standard |
2.81 |
0.89 |
28.7 |
9.1 |
68 |
11 |
10 |
41 |
53 |
HIGH |
27 / 19 |
35 / – |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Cooling |
Overload |
3.24 |
1.16 |
33.0 |
11.8 |
78 |
14 |
15 |
51 |
53 |
HIGH |
32 / 24 |
43 / – |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Low load |
1.34 |
0.70 |
13.7 |
7.1 |
36 |
4 |
2 |
8 |
44 |
LOW |
18 / 15.5 |
–5 / – |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Standard |
2.53 |
0.68 |
25.8 |
6.9 |
70 |
7 |
41 |
4 |
56 |
HIGH |
20 / – |
7 / 6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Heating |
Overload |
3.39 |
1.03 |
34.6 |
10.5 |
83 |
20 |
54 |
16 |
49 |
LOW |
30 / – |
24 / 18 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Low load |
2.00 |
0.25 |
20.4 |
2.6 |
92 |
–17 |
33 |
–19 |
98 |
HIGH |
15 / – |
–15 / – |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
This compressor has 4-pole motor. The value when compressor frequency (Hz) is measured by a clamp meter becomes two times of No. of compressor revolutions (rps).
–25 –
RAV-SP564AT-E, RAV-SP564ATZ-E, RAV-SP564ATZG-E |
|
|
||
|
|
TO sensor |
PMV |
|
|
|
(Pulse Motor Valve) |
||
|
|
|
||
|
|
|
(CAM-B30YGTF-2) |
|
TS |
TD |
|
|
|
sensor |
sensor |
|
|
|
|
|
|
TE sensor |
|
|
4-way valve |
|
|
Muffler |
|
|
|
Ø31.75 × 200L |
|
|
(STF-0213Z) |
|
|
|
|
|
|
|
|
|
Muffler |
Heat exchanger |
|
|
|
Ø19.05 × 160L |
|
|
|
|
Ø8 ripple, 2 rows, 20 stages |
|
|
|
|
|
|
|
|
|
|
FP1.3, flat fin |
Distributor |
Strainer |
|
|
|
||
Accumulator |
|
|
|
Refrigerant pipe |
(1L) |
|
|
|
|
Rotary compressor |
|
|
at liquid side Ø6.4 |
|
|
|
Packed valve |
||
(DA150A1F-21F) |
|
|
||
|
|
Refrigerant pipe |
||
|
|
|
|
|
|
|
|
|
at gas side Ø12.7 |
|
|
|
2-step muffler |
Packed valve |
|
|
|
|
|
|
|
|
Ø25 × 200L |
|
|
|
|
|
In cooling operation |
|
|
|
|
In heating operation |
RAV-SP564AT-E, RAV-SP564ATZ-E, RAV-SP564ATZG-E
|
|
|
Pressure |
|
|
Pipe surface temperature (°C) |
Compressor |
|
Indoor/Outdoor |
||||
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
(MPa) |
(kg/cm²g) |
Discharge |
Suction |
Indoor heat |
Outdoor heat |
drive revolution |
Indoor |
temp. conditions |
|||
|
|
(DB/WB) (°C) |
|||||||||||
|
|
exchanger |
exchanger |
frequency |
fan |
||||||||
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
(rps) |
|
|
|
|
|
Pd |
Ps |
Pd |
Ps |
(TD) |
(TS) |
(TC) |
(TE) |
|
Indoor |
Outdoor |
|
|
|
|
|
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Standard |
2.87 |
1.00 |
29.3 |
10.2 |
72 |
16 |
13 |
42 |
58 |
HIGH |
27 / 19 |
35 / – |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Cooling |
Overload |
3.57 |
1.10 |
36.4 |
11.2 |
88 |
20 |
19 |
52 |
76 |
HIGH |
32 / 24 |
43 / – |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Low load |
1.71 |
0.76 |
17.4 |
7.8 |
45 |
12 |
7 |
13 |
30 |
LOW |
18 / 15.5 |
–5 / – |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Standard |
2.26 |
0.68 |
23.1 |
6.9 |
66 |
6 |
37 |
3 |
64 |
HIGH |
20 / – |
7 / 6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Heating |
Overload |
3.25 |
1.14 |
33.2 |
11.6 |
78 |
20 |
53 |
16 |
30 |
LOW |
30 / – |
24 / 18 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Low load |
2.00 |
0.25 |
20.4 |
2.6 |
78 |
–18 |
34 |
–18 |
88 |
HIGH |
15 / – |
–15 / – |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
– 26 –
RAV-SP804AT-E, RAV-SP804ATZ-E, RAV-SP804ATZG-E |
|
|||
TS sensor |
|
|
|
PMV |
|
|
TO sensor |
TL sensor |
|
|
|
(Pulse Motor Valve) |
||
|
|
|
|
(CAM-B30YGTF-2) |
|
|
|
|
Ø2 × Ø3 × 600L |
TD |
|
|
|
|
sensor |
|
|
|
Ø2 × Ø3 × 550L |
Accumulator |
|
|
|
Strainer |
Sub-ass’y |
|
|
|
Ø2 × Ø3 × 450L |
|
|
|
|
|
|
4-way valve |
|
|
TE sensor |
|
(STF-0218G) |
|
|
|
|
|
|
|
Ø2 × Ø3 |
|
|
|
|
× 450L |
Muffler |
|
|
|
Capillary |
|
|
|
|
|
|
|
Heat exchanger |
Refrigerant pipe |
|
|
Ø25 × L180 |
Ø8, 2 rows, 34 stages |
||
|
at liquid side Ø9.5 |
|||
|
FP1.45, flat fin |
|||
|
|
|||
|
|
Packed valve |
||
Accumulator |
|
|
|
|
|
|
|
|
|
(1.8L) |
|
|
|
|
Rotary compressor |
Ø25 × L210 |
|
|
|
(DA220A2F-22L) |
|
|
|
Refrigerant pipe |
|
|
|
|
at gas side Ø15.9 |
|
|
Strainer |
|
Ball valve |
|
|
|
|
|
In cooling operation |
|
|
|
|
In heating operation |
|
|
|
|
RAV-SP804AT-E, RAV-SP804ATZ-E, RAV-SP804ATZG-E
|
|
|
Pressure |
|
|
Pipe surface temperature (°C) |
Compressor |
|
Indoor/Outdoor |
||||
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
(MPa) |
(kg/cm²g) |
Discharge |
Suction |
Indoor heat |
Outdoor heat |
drive revolution |
Indoor |
temp. conditions |
|||
|
|
(DB/WB) (°C) |
|||||||||||
|
|
exchanger |
exchanger |
frequency |
fan |
||||||||
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
(rps) |
|
|
|
|
|
Pd |
Ps |
Pd |
Ps |
(TD) |
(TS) |
(TC) |
(TE) |
|
Indoor |
Outdoor |
|
|
|
|
|
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Standard |
2.79 |
0.89 |
27.3 |
8.7 |
70 |
13 |
11 |
39 |
58.2 |
HIGH |
27 / 19 |
35 / – |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Cooling |
Overload |
3.53 |
1.07 |
34.6 |
10.5 |
81 |
17 |
14 |
48 |
65.0 |
HIGH |
32 / 24 |
43 / – |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Low load |
1.71 |
0.72 |
16.8 |
7.1 |
42 |
7 |
3 |
18 |
30.0 |
LOW |
18 / 15.5 |
–15 / – |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Standard |
2.65 |
0.68 |
26.0 |
6.7 |
74 |
4 |
44 |
3 |
61.5 |
HIGH |
20 / – |
7 / 6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Heating |
Overload |
3.20 |
1.11 |
31.4 |
10.9 |
76 |
19 |
52 |
15 |
28.0 |
LOW |
30 / – |
24 / 18 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Low load |
2.33 |
0.21 |
22.8 |
2.1 |
93 |
–18 |
31 |
–20 |
99.6 |
HIGH |
15 / – |
–20 / – |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
– 27 –
4. FAN CHARACTERISTICS
4-1. Slim Duct (Filter Attached)
RAV-SM404SDT-E, RAV-SM454SDT-E
Standard air volume : 690m³/h
|
60 |
|
|
|
|
|
|
|
Upper limit of external |
|
High (50Pa) |
||
|
|
|
|
|
||
|
|
static pressure(50Pa) |
|
|
|
|
|
50 |
|
|
|
|
|
|
|
|
|
|
High |
Lower limit of |
|
|
|
|
|
(35Pa) |
|
|
|
Upper limit of |
|
external static |
||
|
|
external static |
|
|
pressure (50Pa) |
|
|
|
pressure(35Pa) |
|
|
|
|
pressure(Pa) |
40 |
|
|
|
|
|
|
|
|
|
|
Lower limit of |
|
|
|
|
Low (50Pa) |
|
external static |
|
30 |
Upper limit of |
|
|
pressure (35Pa) |
||
external static |
|
|
|
|
||
static |
|
pressure |
|
|
|
|
|
(20Pa) |
|
|
High |
|
|
|
|
|
|
(20Pa) |
|
|
External |
20 |
|
|
Low (35Pa) |
|
|
|
|
|
|
|
Lower limit of |
|
|
|
|
|
|
|
external static |
|
|
Upper limit of |
|
|
|
pressure (20Pa) |
|
|
|
|
High |
|
|
|
|
external static |
|
|
|
|
|
|
|
|
(10Pa) |
|
|
|
|
pressure(10Pa) |
Low (20Pa) |
|
||
|
10 |
|
|
|||
|
|
|
|
|
|
|
|
|
Low (10Pa) |
|
|
|
|
|
|
|
|
|
Standard filte |
|
|
0 |
|
|
|
pressure loss |
|
|
|
500 |
600 |
700 |
800 |
|
|
400 |
Air volume (m³/h)
RAV-SM564SDT-E
Standard air volume : 780m³/h
|
60 |
|
|
|
|
|
|
|
|
|
|
High (50Pa) |
|
|
|
Upper limit of external |
|
|
|
|
|
|
static pressure(50Pa) |
|
|
|
|
|
50 |
|
|
|
|
Lower limit of |
|
|
|
|
|
|
|
|
|
|
|
|
|
external static |
|
|
|
|
High |
|
pressure (50Pa) |
|
Upper limit of |
|
(35Pa) |
|
|
|
|
|
|
|
|
||
|
external static |
|
|
|
|
|
|
pressure(35Pa) |
|
|
|
|
|
pressure(Pa) |
40 |
|
|
|
|
|
|
|
|
|
|
Lower limit of |
|
30 |
|
|
|
|
external static |
|
|
|
|
|
pressure (35Pa) |
||
static |
|
|
Low (50Pa) |
|
|
|
|
Upper limit of |
|
|
High |
|
|
External |
|
external static |
|
|
(20Pa) |
|
|
pressure |
|
|
|
|
|
20 |
(20Pa) |
|
|
|
|
|
|
|
Low (35Pa) |
|
|
||
|
|
|
|
Lower limit of |
||
|
|
|
|
|
||
|
|
|
|
|
|
external static |
|
|
|
|
|
|
pressure (20Pa) |
|
Upper limit of |
|
|
|
|
|
|
external static |
|
High |
|
|
|
|
pressure(10Pa) |
|
(10Pa) |
|
|
|
|
10 |
|
|
Low (20Pa) |
|
|
|
|
|
|
|
|
|
|
|
Low (10Pa) |
|
|
|
|
|
|
|
|
Standard filte |
|
|
|
|
|
|
pressure loss |
|
|
|
0 |
500 |
600 |
700 |
800 |
900 |
|
400 |
Air volume (m³/h)
– 28 –
5. WIRING DIAGRAM
5-1. Indoor Unit
5-1-1. Slim Duct Type
RAV-SM404SDT-E, RAV-SM454SDT-E, RAV-SM564SDT-E
FM
DM
FS
RED
WHI
BLK
Indoor unit earth screw
1 2 3
1 2 3
Serial signal
|
|
1 |
3 |
5 |
CN333 |
|
|
|
|
1 |
2 |
1 |
2 |
3 |
|
|
|
|
|
1 |
3 |
5 |
(WHI) |
1 2 3 |
4 5 6 |
7 8 9 10 11 12 13 14 15 16 17 18 19 20 |
1 |
2 |
1 |
2 |
3 |
|
|
||
|
|
|
|
|
|
|
|
|
CN510 |
|
CN504 |
CN34 |
|
|
|||
|
|
|
|
|
|
|
|
|
(WHI) |
|
(WHI) |
(RED) |
|
|
|||
|
|
|
|
|
|
|
Motor drive |
|
|
|
CN104 |
1 |
1 |
||||
|
|
|
|
|
|
|
circuit |
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
(YEL) |
2 |
2 |
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
3 |
3 |
CN334 |
|
|
|
|
|
|
|
|
|
|
|
|
|
TA |
|
2 |
2 |
|
|
|
|
|
|
|
|
|
CN102 |
1 |
1 |
||||
(WHI) |
|
|
|
|
|
|
|
|
|
||||||||
1 |
1 |
|
|
|
|
|
|
|
|
|
(RED) |
2 |
2 |
||||
|
|
|
|
|
|
|
|
|
|
|
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
TCJ |
|
|
|
|
|
|
|
|
|
|
|
|
|
CN101 |
1 |
1 |
||
|
|
Fuse, F01 |
|
|
|
|
Fuse, F02 |
|
|
|
(BLK) |
2 |
2 |
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
TC |
||||
|
|
T6.3A, 250V~ |
~ |
+ |
T3.15A, 250V~ |
|
|
|
|
|
|
|
|||||
1 |
1 |
Power |
DC20V |
CN519 |
1 |
|
|||||||||||
|
|
|
|
|
|
|
|
2 |
|
||||||||
|
|
|
|
|
|
|
|
|
|
supply |
DC15V |
(WHI) |
|
||||
|
|
|
|
|
|
|
|
|
|
DC12V |
3 |
|
|||||
3 |
3 |
|
|
|
|
|
|
|
|
circuit |
|
|
|
|
|||
CN67 |
|
|
|
~ |
– |
|
|
DC7V |
|
|
|
|
4 |
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
5 |
5 |
(BLK) |
|
|
|
|
|
|
|
|
|
|
CN508 |
1 |
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
(RED) |
2 |
|
||
|
|
P01 |
|
|
|
|
Control P.C. Board |
|
|
|
CN80 |
1 |
|
||||
BLK |
|
|
|
|
for Indoor Unit |
|
|
|
2 |
|
|||||||
|
|
|
|
|
|
|
|
(GRN) |
3 |
|
|||||||
|
|
|
|
|
|
|
MCC-1570 |
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
CN73 |
1 |
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
(EXCT) |
||||
|
|
CN66 |
|
|
|
|
|
|
|
|
|
|
(RED) |
2 |
|||
|
1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2 |
(WHI) |
|
|
|
|
|
|
|
|
|
|
CN70 |
1 |
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
(WHI) |
2 |
|
||
|
|
CN41 |
|
CN309 |
CN61 |
CN32 |
CN60 |
CN50 |
|
CN20 |
|
|
|
||||
|
|
(BLU) |
|
|
(YEL) |
(YEL) |
(WHI) |
(WHI) |
(WHI) |
|
(BLU) |
|
|
|
1 |
2 |
3 |
1 |
3 |
1 |
2 |
3 |
4 |
5 |
6 |
1 |
2 |
1 |
2 |
3 |
4 |
5 |
6 |
1 |
2 |
3 |
4 |
5 |
1 |
2 |
3 |
4 |
5 |
1 |
|
3 |
|
|
|
|
(T10) |
|
|
(Fan drive) |
|
|
|
|
|
|
1 |
2 |
3 |
4 |
5 |
|
|
|
|
|
BLK |
BLK |
CN51 |
1 |
2 |
3 |
4 |
5 |
|
(RED) 1 |
2 |
3 |
4 |
5 |
||||
|
|
|||||||
A |
B |
|
P.C. board |
|||||
|
|
|
MCC-1440 |
|
1 |
2 |
|
1 |
2 |
|
|
1 |
2 |
||
A |
1 |
2 |
|
||
B |
|
Terminal |
|
|
|
|
CN001 |
|
|
||
|
(WHI) |
for central |
U3 U4 |
||
|
|
|
remote controller |
|
L N
Wired |
Adapter for |
Connection interface |
remote controller |
wireless remote controller |
(Option) |
Signal phase 220–240V~, 50Hz
Outdoor unit
Outdoor unit earth screw
Color
Identification
BLK : BLACK BLU : BLUE RED : RED GRN : GREEN WHI : WHITE YEL : YELLOW
Symbol |
Parts name |
|
|
FM |
Fan Motor |
|
|
TA |
Indoor temp. sensor |
|
|
TC, TCJ |
Temp. sensor |
|
|
DM |
Drain pump Motor |
|
|
FS |
Float Switch |
|
|
– 29 –
– 30 –
|
2 |
2 |
ORN |
49C |
CN500 |
|
|||
1 |
1 |
ORN |
|
Compressor |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
CM |
1 1 |
RED |
P04 |
|
|
|
|
|
|
|
CN300 |
3 3 |
BLK |
|
FM |
2 2 |
WHI |
P05 |
Q200~205 |
|
P.C. Board |
Q300~305 |
|
|
2 2 |
WHI |
|
||||
|
3 3 |
BLK |
P06 |
IGBT |
|
|
MOS-FET |
|
|
1 1 |
RED |
|
|
||
|
|
|
|
|
R221 |
|
(MCC-5009) |
R321 |
|
|
|
|
|
Fan motor |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
YEL |
P25 |
|
|
|
|
|
|
|
|
|
6 6 |
|
|
|
|
|
P24 |
|
|
R220 |
|
|
|
R320 |
|
|
5 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
4 4 |
|
|
PMV |
|
|
YEL |
P23 |
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
CN700 |
3 3 |
|
|
|||
|
|
|
|
|
R219 |
|
|
|
R319 |
|
|
|
|
||
|
|
P22 |
|
|
|
|
|
|
2 2 |
|
|
|
|||
|
BRN |
P21 |
|
|
|
|
|
|
|
|
|
1 1 |
Pulse motor valve |
||
CAUTION : HIGH VOLTAGE |
|
P20 |
|
|
|
|
|
F03 |
|
|
|
|
|||
|
|
|
L03 |
C13 |
L01 |
Varistor |
|
|
|
|
|
||||
|
YEL |
P35 |
|
|
Fuse |
|
|
3 |
3 |
|
|||||
The high voltage circuit is |
|
|
|
|
|
T3.15A |
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
2 |
|
|
|||
incorporated. |
|
P34 |
|
|
|
|
|
AC250V |
|
|
|
|
|
|
|
|
|
DB01 |
|
|
|
|
|
|
|
CN603 |
1 |
1 |
|
||
Be careful to do the check service, |
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
TS |
|
as the electric shock may be |
|
|
|
|
|
|
|
|
Surge |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(Suction pipe |
||
caused in case of touching |
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
C12 |
C14 |
|
absorber |
|
|
|
2 |
2 |
temp. sensor) |
|
parts on the |
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
CN602 |
1 |
1 |
|
|
P.C. board by hand |
|
|
|
Power |
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
Varistor |
|
|
|
|
TO |
||||
|
|
|
|
relay |
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(Outdoor |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
The 4-way valve coil is turned on |
|
P19 |
|
DB02 |
|
|
|
|
|
|
|
|
3 |
3 |
temp. sensor) |
|
|
CT |
|
|
|
|
|
|
|
|
|||||
while the cooling operation |
ORN |
|
|
|
|
|
|
|
|
|
|
2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1 |
|
|||
|
|
P18 |
|
|
|
|
|
|
|
F01 |
|
CN601 |
1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
TD |
||
|
|
|
|
|
Relay |
|
|
|
|
Fuse |
|
|
|
|
|
|
2 2 |
P11 |
|
|
|
|
|
|
T25A |
|
|
|
|
(Discharge pipe |
|
|
|
|
|
|
|
|
|
|
|
2 |
2 |
temp. sensor) |
|||
|
1 1 |
|
|
|
|
|
|
|
|
AC250V |
|
|
|
||
Reactor |
P08 |
|
|
|
|
|
|
|
|
|
CN600 |
1 |
1 |
|
Q404 |
|
|
|
P03 |
P10 |
P02 |
TE |
|
|
|
(Condenser pipe |
||||
P33 |
P32 |
CN701 |
P7 |
ORN |
BLK |
WHI CN806 |
temp. sensor) |
|
|
1 2 3 |
CN605 |
|
P31 |
P30 |
1 |
3 |
BLK |
|
ORN |
BLK |
WHI |
1 2 3 4 5 |
|
|
|
1 2 3 |
BLK |
|
2 1 |
|
1 |
3 |
|
|
For optional P.C. Board |
||||
|
|
RED WHI BLK |
|
|
PUR |
2 1 |
|
|
|
|
|
|
|
|
|
|
NOTE |
|
|
|
|
|
|
|
Coil for |
Reactor |
|
|
|
||
|
1 2 3 |
|
|
|
|
|
|
4-WAY |
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
||||
CM |
: Compressor |
1 2 3 |
|
|
|
|
|
|
VALVE |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
SW802 |
|
|
|
|
|
|
|
|
|
|
|
|
|
||
PMV : Pulse Motor Valve |
|
|
|
|
|
|
|
|
|
|
|
|
GRN/YEL |
||
|
|
|
|
Reactor |
|
|
Fuse 250V~ |
WHI |
RED |
WHI |
|||||
FM |
: Fan Motor |
MCC-1530 |
|
|
|
|
|
T6.3A |
RED |
|
|||||
TE |
: Heat Exchanger Temp. Sensor |
Sub P.C. Board |
|
|
|
|
|
|
|
|
|
|
|
||
TD |
: Discharge Temp. Sensor |
|
|
Color Identification |
|
|
|
|
1 2 3 L N |
|
|||||
TO |
: Outdoor Temp. Sensor |
|
|
|
|
|
|
|
|||||||
TS |
: Suction Temp. Sensor |
BLK |
: BLACK |
WHI |
: WHITE |
|
|
|
|
|
|
|
|
|
|
IGBT : Insulated Gate Bipolar Transistor |
BLU |
: BLUE |
BRN : BROWN |
|
|
|
|
|
|
|
|
|
|||
DB |
: Rectifier |
RED : RED |
ORN : ORANGE |
|
|
|
|
|
|
|
|
|
|||
GRY : GRAY |
YEL |
: YELLOW |
|
|
|
|
|
|
|
|
|
||||
CT |
: Curreut Transformer |
|
|
|
|
|
|
|
|
|
|||||
PNK |
: PINK |
PUR : PURPLE |
|
|
|
|
To indoor |
Power supply |
|||||||
49C |
: Compressor Case Thermostat |
|
|
|
|
||||||||||
GRN : GREEN |
|
|
|
|
|
|
|
|
220-240V~ 50Hz |
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
-RAV |
-RAV |
-RAV |
.2-5 |
-RAV E,-SP564AT |
-RAV E,-SP454AT |
-RAV E,-SP404AT |
Unit Outdoor |
E-SP564ATZG-RAV E,-SP564ATZ |
E-SP454ATZG-RAV E,-SP454ATZ |
E-SP404ATZG-RAV E,-SP404ATZ |
|