Toshiba RAV-SM561KRT-E, RAV-SM801KRT-E SERVICE MANUAL

0 (0)

INSTALLATION MANUAL

MANUEL D’INSTALLATION INSTALLATIONS-HANDBUCH MANUALE D’INSTALLAZIONE MANUAL DE INSTALACIÓN

MANUAL DE INSTALAÇÃO

INSTALLATIEHANDLEIDING

ΕΓ ΕΙΡΙ∆Ι ΕΓΚΑΤΑΣΤΑΣΗΣ

AIR CONDITIONER (SPLIT TYPE) CLIMATISEUR (TYPE SPLIT) KLIMAGERÄT (SPLIT-SYSTEM)

CONDIZIONATORE D’ARIA (TIPO MULTIAMBIENTI) APARATO DE AIRE ACONDICIONADO (TIPO SPLIT) AR CONDICIONADO (TIPO SPLIT)

AIRCONDITIONER (GESPLITST TYPE)

ΚΛΙΜΑΤΙΣΤΙΚ ΜΗ ΑΝΗΜΑ (∆ΙΑΙΡ ΎΜΕΝ Σ ΤΎΠ Σ)

<High-Wall Type>/<Type mural haut> <Wandmontierter Typ>/<Tipo a condotto nascosto> <Modelo de pared>/<Tipo Mural> <Hoog-Wandtype>/<Τύττ ς Υψηλ ύ Τ ί& υ>

Heat Pump Model/Modèle à thermopompe

Geräte mit Heizung/Modello con pompa di riscaldamento

Modelo con bomba de calor/Modelo de bomba térmica

Model met warmtepomp/Μ ντέλ µε Αντλία Θερµ*τητας

Indoor Unit/Unité intérieure

 

Raumeinheit/Unità interna

 

Unidad interior/Unidade interior

3

Binnenunit/Εσωτερική Μ νάδα

 

RAV-SM561KRT-E

 

RAV-SM801KRT-E

 

Please read this Installation Manual carefully before installing the Air Conditioner.

This Manual describes the installation method of the indoor unit.

For installation of the outdoor unit, follow the Installation Manual attached to the outdoor unit.

Veuillez lire attentivement ce Manuel d’installation avant d’installer le climatiseur.

Ce manuel décrit la procédure d’installation de l’unité intérieure.

Pour installer l’unité extérieure, reportez-vous au Manuel d’installation fourni avec l’unité extérieure.

Bitte lesen Sie dieses Handbuch sorgfältig, bevor Sie mit der Installation des Klimagerätes beginnen.

In diesem Handbuch wird die Installation der Raumeinheit beschrieben.

Um die Außeneinheit zu installieren, folgen Sie den Anweisungen in dem Handbuch, das der Außeneinheit beiliegt.

Prima di installare il condizionatore d’aria, leggere con attenzione questo manuale d’installazione.

Questo manuale descrive il metodo d’installazione dell’unità interna.

Per l’installazione dell’unità esterna, fare riferimento al manuale d’installazione fornito insieme all’unità esterna.

Lea atentamente este Manual de instalación antes de proceder a la instalación del aparato de aire acondicionado.

Este manual describe el método de instalación de la unidad interior.

Para la instalación de la unidad exterior, consulte el Manual de instalación que acompaña a la unidad exterior.

Leia atentamente o presente Manual de Instalação antes de instalar o Ar Condicionado.

O presente manual descreve o método de instalar a unidade interior.

Para a instalação de uma unidade exterior, siga o Manual de Instalação que acompanha a unidade exterior.

Lees deze installatiehandleiding zorgvuldig door voordat u de airconditioner gaat installeren.

Deze installatiemethode beschrijft de installatiemethode van de binnenunit.

Zie voor de installatie van de buitenunit, de installatiehandleiding bij de buitenunit.

Παρακαλώ διαßάστε πρ σε&τικά τ Εν&ειρίδι Ενκατάστασης πριν απ* την ενκατασταση τ υ Κλιµατιστικ ύ.

Τ παρ*ν Εν&ειρίδι περινρά/ει τη µέθ δ ενκατάστασης της εσωτερικής µ νάδας.

Για την ενκατάσταση της ε2ωθερικής µ νάδας, ακ λ υθήστε τ Εν&ειρίδι Ενκατάστασης π υ συν δεύει την ε2ωτερική µ νάδα.

Toshiba 1074007701_COVER

3

7/16/04, 13:38

TOSHIBA RAV-SM561KRT-E (EN) 1074007701

ADOPTION OF NEW REFRIGERANT

This Air Conditioner is a new type which adopts a new refrigerant HFC (R410A) instead of the conventional refrigerant R22 in order to prevent destruction of the ozone layer.

UTILISATION DU NOUVEAU REFRIGERANT

Ce climatiseur est d’un type inédit qui utilise le nouveau réfrigérant HFC (R410A) au lieu du réfrigérant traditionnel R22, afin d’éviter la destruction de la couche d’ozone.

EINFÜHRUNG EINES NEUEN KÜHLMITTELS

Dies ist ein neuartiges Klimagerät. Anstatt des herkömmlichen Kühlmittels R22 verwendet es das neue ozonschicht-schonende HFC Kühlmittel R410A.

ADOZIONE DI UN NUOVO REFRIGERANTE

Questo condizionatore d’aria è di un tipo nuovo che adotta un nuovo refrigerate HFC (R410A) al posto del refrigerante convenzionale R22, per prevenire la distruzione dello strato di ozono dell’atmosfera terrestre.

ADOPCIÓN DE NUEVO REFRIGERANTE

Este aparato de aire acondicionado es un modelo reciente que incorpora el nuevo refrigerante HFC (R410A) en lugar del refrigerante convencional R22 para así evitar daños en la capa de ozono.

ADOPÇÃO DO NOVO REFRIGERANTE

Este ar condicionado é um modelo novo que adopta um novo refrigerante HFC (R410A) em vez do refrigerante convencional R22 para evitar a destruição da cama de ozono.

TOEPASSING VAN EEN NIEUW KOELMIDDEL

Deze airconditioner is een nieuwe type dat werkt met een nieuw koelmiddel HFC (R410A) in plaats van met het conventionele koelmiddel R22, als bijdrage om de aantasting van de ozonlaag te reduceren.

YIOΘETHΣH NEOY ΨYKTIKOY

To παρ v Kλιµατιστικ είναι νέ ς τύπ ς π υ υι θετεί νέ ψυκτικ HFC (R410A) στη θέση τ υ συµ%ατικ ύ ψυκτικ ύ R22 πρ κειµέν υ να % ηθήσει στην πρ στασία τ υ ( ντ ς.

3

Toshiba 1074007701_TOC

2

7/16/04, 13:38

TOSHIBA RAV-SM561KRT-E (EN) 1074007701

CONTENTS

Accessory parts and parts to be procured locally ....................

1

6

REFRIGERANT PIPING .........................................................

8

1

PRECAUTIONS FOR SAFETY ..............................................

2

7

ELECTRICAL WORK ...........................................................

11

2

INSTALLATION PROCEDURE ..............................................

4

8

TEST RUN ............................................................................

14

3

SELECTION OF INSTALLATION PLACE .............................

5

9

TROUBLESHOOTING ..........................................................

15

4

INSTALLATION OF INDOOR UNIT .......................................

5

10

INDOOR UNIT OPERATION WHEN

 

5

DRAIN PIPING WORK ...........................................................

6

 

CONNECTED TO MULTIPLE UNITS ...................................

17

3

EΛΛΗΝΙΚΑ NEDERLANDS PORTUGUÊ S ESPAÑ OL ITALIANO DEUTSCH FRANÇ AIS ENGLISH

Toshiba 1074007701_TOC

3

7/16/04, 13:39

TOSHIBA RAV-SM561KRT-E (EN) 1074007701

Accessory parts and parts to be procured locally

Accessory parts

Part

Part name

Q’ty

Shape

No.

 

 

 

1 Installation plate

1

 

Part

Part name

Q’ty

Shape

No.

 

 

 

 

 

 

 

6

Service contact

1

 

address label

 

 

 

 

2

Installation Manual

1

7

Wireless remote

1

control

 

 

 

 

 

3

Owner’s Manual

1

8

Remote control

1

holder

 

 

 

 

 

4

Mounting screw

8

9

Screw for remote

2

4 mm x 25 mm

control holder

 

 

 

 

5

Pattern paper

1

Wired remote controller is an optional part sold separately.

Parts to be procured locally

Connecting pipe (Liquid side)

(6.35 mm (diam.), Nominal (diam.) 1/4" thick 0.8 mm) RAV-SM561KRT-E

(9.52 mm (diam.), Nominal (diam.) 3/8" thick 0.8 mm) RAV-SM801KRT-E

Connecting pipe (Gas side)

(12.7 mm (diam.), Nominal (diam.) 1/2" thick 0.8 mm) RAV-SM561KRT-E

(15.9 mm (diam.), Nominal (diam.) 5/8" thick 1.0 mm) RAV-SM801KRT-E

Connecting cable

H07RN-F or 245IEC66 (1.5 mm2 or more)

Thermal insulation for refrigerant pipe

(10 mm or more, thermal insulating foam polyethylene)

Thermal insulation for drain pipe (10 mm or more, foam polyethylene)

Drain pipe (Outer 16 mm (diam.))

Tapes

Grounding cable (2.0 mm (diam.) or more)

3

EN

 

1

Toshiba 1074007701(01EN)_P01-10

2

7/16/04, 13:30

TOSHIBA RAV-SM561KRT-E (EN) 1074007701

1 PRECAUTIONS FOR SAFETY

 

 

 

 

ENGLISH

 

 

 

 

Ensure that all Local, National and International regulations are satisfied.

 

Read this “PRECAUTIONS FOR SAFETY” carefully before Installation.

 

The precautions described below include the important items regarding safety. Observe them without fail.

 

After the installation work, perform a trial operation to check for any problem.

 

 

Follow the Owner’s Manual to explain how to use and maintain the unit to the customer.

 

Turn off the main power supply switch (or breaker) before the unit maintenance.

 

Ask the customer to keep the Installation Manual together with the Owner’s Manual.

 

 

 

 

 

 

 

CAUTION

New refrigerant air conditioner installation

 

 

THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT (R410A) WHICH DOES NOT DESTROY OZONE LAYER.

The characteristics of R410A refrigerant are ; easy to absorb water, oxidizing membrane or oil, and its pressure is approx. 1.6 times higher than that of refrigerant R22. Accompanied with the new refrigerant, refrigerating oil has also been changed. Therefore, during installation work, be sure that water, dust, former refrigerant, or refrigerating oil does not enter the refrigerating cycle.

To prevent charging an incorrect refrigerant and refrigerating oil, the sizes of connecting sections of charging port of the main unit and installation tools are charged from those for the conventional refrigerant.

Accordingly the exclusive tools are required for the new refrigerant (R410A).

For connecting pipes, use new and clean piping designed for R410A, and please care so that water or dust does not enter. Moreover, do not use the existing piping because there are problems with pressure-resistance force and impurity in it.

CAUTION

To disconnect the appliance from main power supply

This appliance must be connected to the main power supply by means of a switch with a contact separation of at least 3 mm.

The installation fuse (25A D type ) must be used for the power supply line of this conditioner.

WARNING

Ask an authorized dealer or qualified installation professional to install/maintain the air conditioner.

Inappropriate installation may result in water leakage, electric shock or fire.

Turn off the main power supply switch or breaker before attempting any electrical work.

Make sure all power switches are off. Failure to do so may cause electric shock.

Connect the connecting cable correctly.

If the connecting cable is connected in a wrong way, electric parts may be damaged.

When moving the air conditioner for the installation into another place, be very careful not to enter any gaseous matter other than the specified refrigerant into the refrigeration cycle.

If air or any other gas is mixed in the refrigerant, the gas pressure in the refrigeration cycle becomes abnormally high and it may resultingly causes pipe burst and injuries on persons.

Do not modify this unit by removing any of the safety guards or by by-passing any of the safety interlock switches.

Exposure of unit to water or other moisture before installation may cause a short-circuit of electrical parts.

Do not store it in a wet basement or expose to rain or water.

3

 

2

EN

Toshiba 1074007701(01EN)_P01-10

3

7/16/04, 13:30

TOSHIBA RAV-SM561KRT-E (EN) 1074007701

1 PRECAUTIONS FOR SAFETY

After unpacking the unit, examine it carefully if there are possible damage.

Do not install in a place that might increase the vibration of the unit.

To avoid personal injury (with sharp edges), be careful when handling parts.

Perform installation work properly according to the Installation Manual.

Inappropriate installation may result in water leakage, electric shock or fire.

When the air conditioner is installed in a small room, provide appropriate measures to ensure that the concentration of refrigerant leakage occur in the room does not exceed the critical level.

Install the air conditioner securely in a location where the base can sustain the weight adequately.

Perform the specified installation work to guard against an earthquake.

If the air conditioner is not installed appropriately, accidents may occur due to the falling unit.

If refrigerant gas has leaked during the installation work, ventilate the room immediately.

If the leaked refrigerant gas comes in contact with fire, noxious gas may generate.

After the installation work, confirm that refrigerant gas does not leak.

If refrigerant gas leaks into the room and flows near a fire source, such as a cooking range, noxious gas might generate.

Electrical work must be performed by a qualified electrician in accordance with the Installation Manual. Make sure the air conditioner uses an exclusive power supply.

An insufficient power supply capacity or inappropriate installation may cause fire.

Use the specified cables for wiring connect the terminals securely fix. To prevent external forces applied to the terminals from affecting the terminals.

Conform to the regulations of the local electric company when wiring the power supply.

Inappropriate grounding may cause electric shock.

Do not install the air conditioner in a location subject to a risk of exposure to a combustible gas.

If a combustible gas leaks, and stays around the unit, a fire may occur.

3

EN

 

3

Toshiba 1074007701(01EN)_P01-10

4

7/16/04, 13:30

TOSHIBA RAV-SM561KRT-E (EN) 1074007701

Toshiba RAV-SM561KRT-E, RAV-SM801KRT-E SERVICE MANUAL

2 INSTALLATION PROCEDURE

Installation diagram of indoor unit

For rear left and side pipe exit

Wall

Insert the cushion between the indoor unit and wall, and lift indoor unit to make work easier.

Do not allow the drain hose to sag.

Cut the piping hole sloped slightly

Make sure to run the drain hose sloped downward.

Mounting the installation plate

For installation of the indoor unit, use the paper template included.

170

m

m

or

 

m

 

 

ore

Hook

ormore

Hook 1 Installation

mm

plate

65

 

 

 

 

170

m

m

 

or m

 

 

ore

Insulate the refrigerant pipes separately with insulation, not together.

Min. 6 mm thick heat resisting polyethylene foam

 

 

 

 

 

 

The auxiliary piping can be

 

 

 

 

 

 

 

connected the left, rear left, rear,

A

ir

 

 

 

 

right or bottom.

 

 

 

filter

 

 

 

 

 

 

 

 

 

Pipe

 

 

 

Right

 

 

 

 

insulation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rear

 

 

 

 

 

 

 

 

Bottom

 

Left

 

 

 

 

 

 

Rear left

 

 

Mounting screw

 

 

 

55

65

 

 

 

 

 

 

 

 

 

 

Hook

 

 

 

 

 

 

 

170

 

 

 

 

180

Installation

 

 

 

0

80

100

plate

 

 

 

 

 

 

 

120

 

 

 

 

 

 

 

 

 

 

 

 

 

100mm

 

 

 

 

100mm

 

 

 

 

 

 

 

 

 

 

 

 

Hook

Indoor unit

 

Pipe hole

Hook

 

 

 

Pipe hole

 

 

 

Thread

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor unit

Weight

 

 

Mounting screw

 

 

When the installation plate is directly mounted on the wall

1.Securely fix the installation plate to the wall by screwing it through the upper and lower fixing holes.

2.To mount the installation plate on a concrete wall with anchor bolts, utilize the anchor bolt holes as illustrated in the above figure.

3.Attach the installation plate horizontally to the wall.

CAUTION

When installing the installation plate with mounting screw, do not use the anchor bolt hole.

Otherwise the unit may fall down and result in personal injury and property damage.

5 mm hole

 

 

 

 

 

Mounting screw

Anchor bolt

 

 

4 x 25 mm

 

 

 

 

 

 

Projection

 

 

 

15 mm or less

Clip anchor

 

 

(local parts)

 

 

 

3

4

EN

 

 

Toshiba 1074007701(01EN)_P01-10

5

 

7/16/04, 13:30

TOSHIBA RAV-SM561KRT-E (EN) 1074007701

3 SELECTION OF INSTALLATION PLACE

WARNING

Install the air conditioner where there is sufficient strength to withstand the weight of the unit.

If the strength is not sufficient, the unit may fall down resulting in injury.

CAUTION

Upon approval of the customer, install the air conditioner in a place that satisfies the following conditions.

Place where the unit can be installed horizontally.

Place where a sufficient servicing space can be ensured for safe maintenance and check.

Place where drained water will not cause any problem.

Avoid installing in the following places.

Place exposed to air with high salt content (seaside area), or place exposed to large quantities of sulfide gas (hot spring). (Should the unit be used in these places, special protective measures are needed.)

Place exposed to oil, vapor, oil smoke or corrosive gas.

Place where organic solvent is used nearby.

Place close to a machine generating high frequency.

Place where the discharged air blows directly into the window of the neighboring house. (For outdoor unit)

Place where noise of the outdoor unit is easy to transmit.

(When installing the air conditioner on the boundary with the neighbor, pay due attention to the level of noise.)

Place with poor ventilation.

Where the ceiling height is more than 3 m.

Where the floor/wall/ceiling structure is unable to support the weight of the unit.

4 INSTALLATION OF INDOOR UNIT

WARNING

Install the air conditioner certainly at a place to sufficiently withstand the weight.

If the strength is insufficient, the unit may fall down resulting in human injury.

Perform a specified installation work to guard against an earthquake.

An incomplete installation can cause accidents by the units falling and dropping.

Locate the unit so as to provide uniform circulation of chilled air.

Avoid locating the unit as shown in the bad-marked figures below:

 

Good location

 

Bad location

 

Bad location

Evenly hot or cooled

Shaded area well hot or cooled

Shaded area well hot or cooled

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

If a good location is not possible, use a fan to circulate the air evenly throughout the room.

EN

 

5

3

Toshiba 1074007701(01EN)_P01-10

6

 

7/16/04, 13:30

TOSHIBA RAV-SM561KRT-E (EN) 1074007701