Toshiba RAS-M13UKCV-E, RAS-3M26YAV-E, RAS-M13UKV-E, RAS-M16UKV-E, RAS-M10UKV-E SERVICE MANUAL

...
0 (0)

FILE NO.SVM-03017

SUPPLEMENT

SERVICE MANUAL

AIR-CONDITIONER

SPLIT TYPE

RAS-M10UKV-E, RAS-M13UKV-E, RAS-M16UKV-E RAS-4M27YAV-E

RAS-M10UKCV-E, RAS-M13UKCV-E, RAS-M16UKCV-E RAS-4M27YACV-E

RAS-M10UKV-E, RAS-M13UKV-E, RAS-M16UKV-E RAS-3M26YAV-E

R410A

June, 2003

 

CONTENTS

 

1.

SPECIFICATIONS.......................................................................................

3

2.

REFRIGERANT R410A ............................................................................

26

3.

CONSTRUCTION VIEWS .........................................................................

34

4.

WIRING DIAGRAM ...................................................................................

36

5.

SPECIFICATIONS OF ELECTRICAL PARTS ..........................................

38

6.

REFRIGERANT CYCLE DIAGRAM .........................................................

40

7.

CONTROL BLOCK DIAGRAM .................................................................

48

8.

OPERATION DESCRIPTION ....................................................................

50

9.

INSTALLATION PROCEDURE .................................................................

64

10.

HOW TO DIAGNOSE THE TROUBLE .......................................................

79

11.

HOW TO REPLACE THE MAIN PARTS ...................................................

100

12.

EXPLODED VIEWS AND PARTS LIST ..................................................

110

– 2 –

1. SPECIFICATIONS

1-1. Specifications

RAS-M10UKV-E, RAS-M13UKV-E, RAS-M16UKV-E/RAS-4M27YAV-E, RAS-3M26YAV-E

Unit model

Indoor

 

 

RAS-M10UKV-E, RAS-M13UKV-E, RAS-M16UKV-E

 

Outdoor

 

 

RAS-4M27YAV-E

 

 

RAS-3M26YAV-E

Cooling capacity

 

 

 

(kW)

8.0

 

 

 

 

 

 

7.5

Cooling capacity range

 

(kW)

1.4 – 9.2

 

 

 

1.4 – 8.9

Heating capacity

 

(kW)

9.0

 

 

 

 

 

 

9.0

Heating capacity range

 

(kW)

0.8 – 11.0

 

 

 

0.8 – 10.8

Power supply

 

 

 

 

 

 

220/230/240V,

1Ph, 50/60Hz

 

 

Electric

Indoor

 

Unit model

 

RAS-M10UKV-E

 

 

RAS-M13UKV-E

 

RAS-M16UKV-E

characteristics

 

 

Running current

(A)

0.15

 

 

 

0.15

 

0.15

 

 

 

Power consumption

(W)

30

 

 

 

 

30

 

30

 

 

 

Power factor

(%)

91/87/83

 

 

 

91/87/83

 

91/87/83

 

Total

 

Operation mode

 

Cooling

 

 

Heating

 

Cooling

 

 

Heating

 

 

 

Running current

(A)

11.60/11.09/10.63

 

10.44/9.98/9.57

 

10.44/9.98/9.57

 

11.83/11.31/10.84

 

 

 

Power consumption

(W)

2500

 

2250

 

2250

 

 

2550

 

 

 

Power factor

(%)

98

 

98

 

 

98

 

 

98

 

 

 

Starting current

(A)

11.60/11.09/10.63

 

 

11.83/11.31/10.84

C.O.P. (Cooling/Heating)

 

 

 

3.20/4.00

 

 

 

3.33/3.53

Operating

Indoor

 

Unit model

 

RAS-M10UKV-E

 

 

RAS-M13UKV-E

 

RAS-M16UKV-E

noise

(Cooling/Heating)

 

High

dB (A)

36/39

 

 

 

39/40

 

42/42

 

 

 

Medium

dB (A)

33/35

 

 

 

35/35

 

39/39

 

 

 

Low

dB (A)

28/29

 

 

 

28/29

 

33/33

 

Outdoor

 

Unit model

 

RAS-4M27YAV

-E

 

 

RAS-3M26YAV-E

 

(Cooling/Heating)

 

Full indoor units operating

dB (A)

48/48

 

 

 

48/48

Indoor unit

Unit model

 

 

 

RAS-M10UKV-E

 

 

RAS-M13UKV-E

 

RAS-M16UKV-E

 

Dimension

 

Height

(mm)

275

 

 

 

 

275

 

275

 

 

 

Width

(mm)

790

 

 

 

 

790

 

790

 

 

 

Depth

(mm)

208

 

 

 

 

208

 

208

 

Net weight

 

 

(kg)

10

 

 

 

 

10

 

10

 

Fan motor output

 

(W)

19

 

 

 

 

19

 

19

 

Air flow rate (Cooling/Heating)

(m³/h)

470/520

 

 

 

520/560

 

600/600

Outdoor unit

Unit model

 

 

RAS-4M27YAV

-E

 

 

RAS-3M26YAV-E

 

Dimension

 

Height

(mm)

795

 

 

 

 

 

795

 

 

 

Width

(mm)

900

 

 

 

 

 

900

 

 

 

Depth

(mm)

320

 

 

 

 

 

320

 

Net weight

 

 

(kg)

65

 

 

 

 

 

64

 

Compressor

 

Motor output

(W)

 

 

 

 

2000

 

 

 

 

 

 

Type

 

Twin rotary type with DC-inverter variable speed control

 

 

 

Model

 

 

 

 

 

DA220A2F-20L

 

 

 

Fan motor output

 

 

(W)

 

 

 

 

 

60

 

 

 

 

Air flow rate

 

(m³/h)

 

 

High : 3000, Medium : 2800

 

 

Piping

Type

 

 

 

 

 

 

Flare connection

 

 

connection

Indoor unit

 

Unit model

 

RAS-M10UKV-E

 

 

RAS-M13UKV-E

 

RAS-M16UKV-E

 

 

 

Liquid side

 

Ø 6.35

 

 

 

Ø 6.35

 

Ø 6.35

 

 

 

Gas side

 

Ø 9.52

 

 

 

Ø 9.52

 

Ø 12.7

 

Outdoor unit

 

Unit model

 

RAS-4M27YAV

-E

 

 

RAS-3M26YAV-E

 

 

 

A unit liquid side/gas side

 

Ø 6.35/Ø 12.7

 

 

 

Ø 6.35/Ø 12.7

 

 

 

B unit liquid side/gas side

 

Ø 6.35/Ø 9.52

 

 

 

Ø 6.35/Ø 9.52

 

 

 

C unit liquid side/gas side

 

Ø 6.35/Ø 9.52

 

 

 

Ø 6.35/Ø 9.52

 

 

 

D unit liquid side/gas side

 

Ø 6.35/Ø 9.52

 

 

 

 

 

 

Maximum length

(per unit)

(m)

25

 

 

 

 

 

 

25

 

Maximum length (total)

(m)

70

 

 

 

 

 

 

50

 

Maximum chargeless length

(m)

70

 

 

 

 

 

 

50

 

Maximum height difference

(m)

15

 

 

 

 

 

 

15

Refrigerant

Name of refrigerant

 

 

 

 

 

R410A

 

 

 

Weight

 

(kg)

 

 

 

 

 

2.4

 

 

 

Wiring connection

 

Power supply

 

 

 

 

3 wires : includes earth

 

 

 

 

 

Interconnection

 

 

 

 

4 wires : includes earth

 

 

Usable temperature range

 

Indoor

(°C)

 

 

 

 

21 – 32/0 – 28

 

 

 

 

 

Outdoor

(°C)

 

 

 

 

10 – 43/–10– 21

 

 

Accessory

Indoor unit

 

Installation plate

 

 

 

 

 

 

1

 

 

 

 

 

 

Wireless remote controller

 

 

 

 

 

 

1

 

 

 

 

 

 

Label

 

 

 

 

 

 

2

 

 

 

 

 

 

Remote controller holder

 

 

 

 

 

 

1

 

 

 

 

 

 

Pan head wood screw

 

 

 

 

 

2 (Ø3.1 x 16L)

 

 

 

 

 

Purifying filter

 

 

 

 

 

 

1

 

 

 

 

 

 

Deodorizing filter

 

 

 

 

 

 

1

 

 

 

 

 

 

Battery

 

 

 

 

 

 

2

 

 

 

 

 

 

Mounting screw

 

 

 

 

 

6 (Ø4 x 25L)

 

 

 

 

 

Installation manual

 

 

 

 

 

 

1

 

 

 

 

Outdoor unit

 

Installation manual

 

 

 

 

 

 

1

 

 

 

 

 

 

Owner's manual

 

 

 

 

 

 

1

 

 

 

For performance when each indoor unit is combined with other unit, refer to the separate table.

The specifications may be subject to change without notice for purpose of improvement.

3 –

RAS-M10UKCV-E, RAS-M13UKCV-E, RAS-M16UKCV-E/RAS-4M27YACV-E

Unit model

 

Indoor

 

 

RAS-M10UKCV-E, RAS-M13UKCV-E, RAS-M16UKCV-E

 

 

Outdoor

 

 

 

 

RAS-4M27YACV-E

 

Cooling capacity

 

 

(kW)

 

8.0

 

 

Cooling capacity range

 

(kW)

 

 

1.4 – 9.2

 

Power supply

 

 

 

 

220/230/240V, 1Ph, 50/60Hz

 

Electric

 

Indoor

Unit model

 

RAS-M10UKCV-E

 

RAS-M13UKCV-E

 

RAS-M16UKCV-E

characteristics

 

 

Running current

(A)

0.15

 

0.15

 

0.15

 

 

 

Power consumption

(W)

30

 

30

 

30

 

 

 

Power factor

(%)

91/87/83

 

91/87/83

 

91/87/83

 

 

Total

Running current

(A)

 

11.60/11.09/10.63

 

 

 

 

 

Power consumption

(W)

 

2500

 

 

 

 

 

Power factor

(%)

 

98

 

 

 

 

 

Starting current

(A)

 

11.60/11.09/10.63

 

 

C.O.P.

 

 

 

 

 

3.20

 

 

Operating

 

Indoor

Unit model

 

RAS-M10UKCV-E

 

RAS-M13UKCV-E

 

RAS-M16UKCV-E

noise

 

 

High

dB (A)

36

 

39

 

42

 

 

 

Medium

dB (A)

33

 

35

 

39

 

 

 

Low

B (A)

28

 

28

 

33

 

 

Outdoor

Unit model

 

 

 

RAS-4M27YACV-E

 

 

 

 

 

4 indoor units operating

dB (A)

 

48

 

 

Indoor unit

 

Unit model

 

 

RAS-M10UKCV-E

 

RAS-M13UKCV-E

 

RAS-M16UKCV-E

 

 

Dimension

Height

(mm)

275

 

275

 

275

 

 

 

Width

(mm)

790

 

790

 

790

 

 

 

Depth

(mm)

208

 

208

 

208

 

 

Net weight

 

(kg)

10

 

10

 

10

 

 

Fan motor output

 

(W)

19

 

19

 

19

 

 

Air flow rate

 

(m³/h)

470

 

520

 

600

Outdoor unit

 

Unit model

 

 

 

 

RAS-4M27YACV-E

 

 

 

 

Dimension

Height

(mm)

 

795

 

 

 

 

 

Width

(mm)

 

900

 

 

 

 

 

Depth

(mm)

 

320

 

 

 

 

Net weight

 

(kg)

 

63

 

 

 

 

Compressor

Motor output

(W)

 

2000

 

 

 

 

 

Type

 

Twin rotary type with DC-inverter variable speed control

 

 

 

Model

 

 

 

DA220A2F-20L

 

 

 

Fan motor output

 

(W)

 

60

 

 

 

 

Air flow rate

 

(m³/h)

 

High : 3000, Medium : 2800

 

Piping

 

Type

 

 

 

 

Flare connection

 

connection

 

Indoor unit

Unit model

 

RAS-M10UKCV-E

 

RAS-M13UKCV-E

 

RAS-M16UKCV-E

 

 

 

Liquid side

 

Ø 6.35

 

Ø 6.35

 

Ø 6.35

 

 

 

Gas side

 

Ø 9.52

 

Ø 9.52

 

Ø 12.7

 

 

Outdoor unit

Unit model

 

 

 

RAS-4M27YACV-E

 

 

 

 

 

A unit liquid side/gas side

 

 

Ø 6.35/Ø 12.7

 

 

 

 

 

B unit liquid side/gas side

 

 

Ø 6.35/Ø 9.52

 

 

 

 

 

C unit liquid side/gas side

 

 

Ø 6.35/Ø 9.52

 

 

 

 

 

D unit liquid side/gas side

 

 

Ø 6.35/Ø 9.52

 

 

 

 

Maximum length (per unit)

(m)

 

25

 

 

 

 

Maximum length (total)

(m)

 

70

 

 

 

 

Maximum chargeless length

(m)

 

70

 

 

 

 

Maximum height difference

(m)

 

15

 

 

Refrigerant

 

Name of refrigerant

 

 

 

R410A

 

 

 

Weight

 

(kg)

 

2.2

 

 

Wiring connection

Power supply

 

 

 

3 wires : includes earth

 

 

 

 

Interconnection

 

 

 

4 wires : includes earth

 

Usable temperature range

Indoor

(°C)

 

 

21 – 32

 

 

 

 

Outdoor

(°C)

 

 

10 – 43

 

Accessory

 

Indoor unit

Installation plate

 

 

1

 

 

 

 

 

Wireless remote controller

 

 

1

 

 

 

 

 

Label

 

 

2

 

 

 

 

 

Remote controller holder

 

 

1

 

 

 

 

 

Pan head wood screw

 

 

 

2 (Ø3.1 x 16L)

 

 

 

 

Purifying filter

 

 

1

 

 

 

 

 

Deodorizing filter

 

 

1

 

 

 

 

 

Battery

 

 

2

 

 

 

 

 

Mounting screw

 

 

 

6 (Ø4 x 25L)

 

 

 

 

Installation manual

 

 

1

 

 

 

 

Outdoor unit

Installation manual

 

 

1

 

 

 

 

 

Owner's manual

 

 

1

 

 

For performance when each indoor unit is combined with other unit, refer to the separate table.

The specifications may be subject to change without notice for purpose of improvement.

4 –

1-2. Specifications of Performance When Each Indoor Unit is Combined with other Unit

Outdoor Unit : RAS-4M27YAV-E

<Cooling/220V>

Power

Operating

 

Indoor unit

 

 

Unit capacity (kW)

 

Cooling

Power

Operating

Outdoor

supply

 

 

 

 

 

 

 

 

capacity

consumption

current

noise

status

A

B

C

D

A

B

C

D

(V)

(kW)

(W)

(A)

(dB)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

220

1 unit

10

2.7

2.7

750

3.87

48

(1.4 to 3.2)

(640 to 950)

(3.68 to 4.64)

 

 

 

 

 

 

 

 

 

 

 

 

 

13

3.7

3.7

1200

5.74

48

 

 

(1.4 to 4.4)

(640 to 1520)

(3.68 to 7.20)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

4.5

4.5

1650

7.81

48

 

 

(1.4 to 5.0)

(640 to 2000)

(3.68 to 9.28)

 

 

 

 

 

 

 

 

 

 

 

 

2 units

10

10

2.70

2.70

5.4

1530

7.10

48

 

(2.5 to 6.3)

(640 to 2040)

(3.64 to 9.46)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

10

3.41

2.49

5.9

1810

8.40

48

 

 

(2.7 to 6.6)

(660 to 2220)

(3.75 to 10.30)

 

 

 

 

 

 

 

 

 

 

 

 

 

16

10

3.94

2.36

6.3

2040

9.46

48

 

 

(2.9 to 6.9)

(670 to 2400)

(3.81 to 11.13)

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

3.15

3.15

6.3

2040

9.46

48

 

 

(2.9 to 6.9)

(670 to 2400)

(3.81 to 11.13)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

3.73

3.07

6.8

2320

10.76

48

 

 

(3.0 to 7.2)

(690 to 2570)

(3.92 to 11.92)

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

3.60

3.60

7.2

2550

11.83

48

 

 

(3.2 to 7.5)

(700 to 2750)

(3.98 to 12.76)

 

 

 

 

 

 

 

 

 

 

 

 

3 units

10

10

10

2.53

2.53

2.53

7.6

2400

11.13

48

 

(3.8 to 8.2)

(950 to 2720)

(4.80 to 12.62)

 

 

 

 

 

 

 

 

 

 

 

 

 

13

10

10

3.13

2.28

2.28

7.7

2410

11.18

48

 

 

(3.9 to 8.3)

(960 to 2740)

(4.85 to 12.71)

 

 

 

 

 

 

 

 

 

 

 

 

 

16

10

10

3.50

2.10

2.10

7.7

2410

11.18

48

 

 

(4.0 to 8.5)

(960 to 2790)

(4.85 to 12.94)

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

10

2.82

2.82

2.06

7.7

2410

11.18

48

 

 

(4.0 to 8.5)

(960 to 2790)

(4.85 to 12.94)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

10

3.22

2.65

1.93

7.8

2430

11.27

48

 

 

(4.1 to 8.6)

(970 to 2810)

(4.90 to 13.03)

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

13

2.60

2.60

2.60

7.8

2430

11.27

48

 

 

(4.1 to 8.6)

(970 to 2810)

(4.90 to 13.03)

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

10

3.04

3.04

1.82

7.9

2440

11.32

48

 

 

(4.1 to 8.7)

(970 to 2830)

(4.90 to 13.13)

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

13

2.99

2.46

2.46

7.9

2440

11.32

48

 

 

(4.1 to 8.7)

(970 to 2830)

(4.90 to 13.13)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

13

2.80

2.80

2.30

7.9

2440

11.32

48

 

 

(4.2 to 8.9)

(970 to 2880)

(4.90 to 13.36)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

16

2.67

2.67

2.67

8.0

2450

11.36

48

 

 

(4.3 to 9.0)

(980 to 2900)

(4.95 to 13.45)

 

 

 

 

 

 

 

 

 

 

 

 

4 units

10

10

10

10

1.98

1.98

1.98

1.98

7.9

2450

11.36

48

 

(4.0 to 8.7)

(930 to 2800)

(4.70 to 12.99)

 

 

 

 

 

 

 

 

 

 

 

 

 

13

10

10

10

2.48

1.81

1.81

1.81

7.9

2450

11.36

48

 

 

(4.1 to 8.8)

(940 to 2820)

(4.75 to 13.08)

 

 

 

 

 

 

 

 

 

 

 

 

 

16

10

10

10

2.86

1.71

1.71

1.71

8.0

2500

11.60

48

 

 

(4.1 to 9.0)

(940 to 2860)

(4.75 to 13.27)

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

10

10

2.31

2.31

1.69

1.69

8.0

2500

11.60

48

 

 

(4.1 to 9.0)

(940 to 2860)

(4.75 to 13.27)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

10

10

2.65

2.18

1.59

1.59

8.0

2500

11.60

48

 

 

(4.2 to 9.1)

(950 to 2880)

(4.80 to 13.36)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

13

10

2.14

2.14

2.14

1.57

8.0

2500

11.60

48

 

 

(4.2 to 9.1)

(950 to 2880)

(4.80 to 13.36)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

13

10

2.47

2.03

2.03

1.48

8.0

2500

11.60

48

 

 

(4.2 to 9.2)

(950 to 2900)

(4.80 to 13.45)

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

13

13

2.00

2.00

2.00

2.00

8.0

2500

11.60

48

 

 

(4.2 to 9.2)

(950 to 2900)

(4.80 to 13.45)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

10

10

2.50

2.50

1.50

1.50

8.0

2500

11.60

48

 

 

(4.2 to 9.2)

(950 to 2900)

(4.80 to 13.45)

 

 

 

 

 

 

 

 

 

 

 

The above specification values are those under the conditions that the indoor DB/WB=27/19°C and the outdoor DB/ WB=35/–°C.

Indoor unit 10 : RAS-M10UKV-E, 13 : RAS-M13UKV-E, 16 : RAS-M16UKV-E

5 –

Outdoor Unit : RAS-4M27YAV-E

<Cooling/230V>

Power

Operating

 

Indoor unit

 

 

Unit capacity (kW)

 

Cooling

Power

Operating

Outdoor

supply

 

 

 

 

 

 

 

 

capacity

consumption

current

noise

status

A

B

C

D

A

B

C

D

(V)

(kW)

(W)

(A)

(dB)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

230

1 unit

10

2.7

2.7

750

3.71

48

(1.4 to 3.2)

(640 to 950)

(3.52 to 4.44)

 

 

 

 

 

 

 

 

 

 

 

 

 

13

3.7

3.7

1200

5.49

48

 

 

(1.4 to 4.4)

(640 to 1520)

(3.52 to 6.88)

 

 

 

 

 

 

 

 

 

 

 

 

 

16

4.5

4.5

1650

7.47

48

 

 

(1.4 to 5.0)

(640 to 2000)

(3.52 to 8.87)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 units

10

10

2.70

2.70

5.4

1530

6.79

48

 

(2.5 to 6.3)

(640 to 2040)

(3.48 to 9.05)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

10

3.41

2.49

5.9

1810

8.03

48

 

 

(2.7 to 6.6)

(660 to 2220)

(3.59 to 9.85)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

10

3.94

2.36

6.3

2040

9.05

48

 

 

(2.9 to 6.9)

(670 to 2400)

(3.64 to 10.65)

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

3.15

3.15

6.3

2040

9.05

48

 

 

(2.9 to 6.9)

(670 to 2400)

(3.64 to 10.65)

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

3.73

3.07

6.8

2320

10.29

48

 

 

(3.0 to 7.2)

(690 to 2570)

(3.75 to 11.40)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

3.60

3.60

7.2

2550

11.31

48

 

 

(3.2 to 7.5)

(700 to 2750)

(3.80 to 12.20)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 units

10

10

10

2.53

2.53

2.53

7.6

2400

10.65

48

 

(3.8 to 8.2)

(950 to 2720)

(4.59 to 12.07)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

10

10

3.13

2.28

2.28

7.7

2410

10.69

48

 

 

(3.9 to 8.3)

(960 to 2740)

(4.64 to 12.16)

 

 

 

 

 

 

 

 

 

 

 

 

 

16

10

10

3.50

2.10

2.10

7.7

2410

10.69

48

 

 

(4.0 to 8.5)

(960 to 2790)

(4.64 to 12.38)

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

10

2.82

2.82

2.06

7.7

2410

10.69

48

 

 

(4.0 to 8.5)

(960 to 2790)

(4.64 to 12.38)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

10

3.22

2.65

1.93

7.8

2430

10.78

48

 

 

(4.1 to 8.6)

(970 to 2810)

(4.69 to 12.47)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

13

2.60

2.60

2.60

7.8

2430

10.78

48

 

 

(4.1 to 8.6)

(970 to 2810)

(4.69 to 12.47)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

10

3.04

3.04

1.82

7.9

2440

10.83

48

 

 

(4.1 to 8.7)

(970 to 2830)

(4.69 to 12.56)

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

13

2.99

2.46

2.46

7.9

2440

10.83

48

 

 

(4.1 to 8.7)

(970 to 2830)

(4.69 to 12.56)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

13

2.80

2.80

2.30

7.9

2440

10.83

48

 

 

(4.2 to 8.9)

(970 to 2880)

(4.69 to 12.78)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

16

2.67

2.67

2.67

8.0

2450

10.87

48

 

 

(4.3 to 9.0)

(980 to 2900)

(4.73 to 12.87)

 

 

 

 

 

 

 

 

 

 

 

 

4 units

10

10

10

10

1.98

1.98

1.98

1.98

7.9

2450

10.87

48

 

(4.0 to 8.7)

(930 to 2800)

(4.49 to 12.42)

 

 

 

 

 

 

 

 

 

 

 

 

 

13

10

10

10

2.48

1.81

1.81

1.81

7.9

2450

10.87

48

 

 

(4.1 to 8.8)

(940 to 2820)

(4.54 to 12.51)

 

 

 

 

 

 

 

 

 

 

 

 

 

16

10

10

10

2.86

1.71

1.71

1.71

8.0

2500

11.09

48

 

 

(4.1 to 9.0)

(940 to 2860)

(4.54 to 12.69)

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

10

10

2.31

2.31

1.69

1.69

8.0

2500

11.09

48

 

 

(4.1 to 9.0)

(940 to 2860)

(4.54 to 12.69)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

10

10

2.65

2.18

1.59

1.59

8.0

2500

11.09

48

 

 

(4.2 to 9.1)

(950 to 2880)

(4.59 to 12.78)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

13

10

2.14

2.14

2.14

1.57

8.0

2500

11.09

48

 

 

(4.2 to 9.1)

(950 to 2880)

(4.59 to 12.78)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

13

10

2.47

2.03

2.03

1.48

8.0

2500

11.09

48

 

 

(4.2 to 9.2)

(950 to 2900)

(4.59 to 12.87)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

13

13

2.00

2.00

2.00

2.00

8.0

2500

11.09

48

 

 

(4.2 to 9.2)

(950 to 2900)

(4.59 to 12.87)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

10

10

2.50

2.50

1.50

1.50

8.0

2500

11.09

48

 

 

(4.2 to 9.2)

(950 to 2900)

(4.59 to 12.87)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The above specification values are those under the conditions that the indoor DB/WB=27/19°C and the outdoor DB/ WB=35/–°C.

Indoor unit 10 : RAS-M10UKV-E, 13 : RAS-M13UKV-E, 16 : RAS-M16UKV-E

6 –

Outdoor Unit : RAS-4M27YAV-E

<Cooling/240V>

Power

Operating

 

Indoor unit

 

 

Unit capacity (kW)

 

Cooling

Power

Operating

Outdoor

supply

 

 

 

 

 

 

 

 

capacity

consumption

current

noise

status

A

B

C

D

A

B

C

D

(V)

(kW)

(W)

(A)

(dB)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

240

1 unit

10

2.7

2.7

750

3.55

48

(1.4 to 3.2)

(640 to 950)

(3.38 to 4.26)

 

 

 

 

 

 

 

 

 

 

 

 

 

13

3.7

3.7

1200

5.26

48

 

 

(1.4 to 4.4)

(640 to 1520)

(3.38 to 6.60)

 

 

 

 

 

 

 

 

 

 

 

 

 

16

4.5

4.5

1650

7.16

48

 

 

(1.4 to 5.0)

(640 to 2000)

(3.38 to 8.50)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 units

10

10

2.70

2.70

5.4

1530

6.51

48

 

(2.5 to 6.3)

(640 to 2040)

(3.33 to 8.67)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

10

3.41

2.49

5.9

1810

7.70

48

 

 

(2.7 to 6.6)

(660 to 2220)

(3.44 to 9.44)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

10

3.94

2.36

6.3

2040

8.67

48

 

 

(2.9 to 6.9)

(670 to 2400)

(3.49 to 10.20)

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

3.15

3.15

6.3

2040

8.67

48

 

 

(2.9 to 6.9)

(670 to 2400)

(3.49 to 10.20)

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

3.73

3.07

6.8

2320

9.86

48

 

 

(3.0 to 7.2)

(690 to 2570)

(3.59 to 10.93)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

3.60

3.60

7.2

2550

10.84

48

 

 

(3.2 to 7.5)

(700 to 2750)

(3.65 to 11.69)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 units

10

10

10

2.53

2.53

2.53

7.6

2400

10.20

48

 

(3.8 to 8.2)

(950 to 2720)

(4.40 to 11.56)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

10

10

3.13

2.28

2.28

7.7

2410

10.25

48

 

 

(3.9 to 8.3)

(960 to 2740)

(4.44 to 11.65)

 

 

 

 

 

 

 

 

 

 

 

 

 

16

10

10

3.50

2.10

2.10

7.7

2410

10.25

48

 

 

(4.0 to 8.5)

(960 to 2790)

(4.44 to 11.86)

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

10

2.82

2.82

2.06

7.7

2410

10.25

48

 

 

(4.0 to 8.5)

(960 to 2790)

(4.44 to 11.86)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

10

3.22

2.65

1.93

7.8

2430

10.33

48

 

 

(4.1 to 8.6)

(970 to 2810)

(4.49 to 11.95)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

13

2.60

2.60

2.60

7.8

2430

10.33

48

 

 

(4.1 to 8.6)

(970 to 2810)

(4.49 to 11.95)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

10

3.04

3.04

1.82

7.9

2440

10.37

48

 

 

(4.1 to 8.7)

(970 to 2830)

(4.49 to 12.03)

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

13

2.99

2.46

2.46

7.9

2440

10.37

48

 

 

(4.1 to 8.7)

(970 to 2830)

(4.49 to 12.03)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

13

2.80

2.80

2.30

7.9

2440

10.37

48

 

 

(4.2 to 8.9)

(970 to 2880)

(4.49 to 12.24)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

16

2.67

2.67

2.67

8.0

2450

10.42

48

 

 

(4.3 to 9.0)

(980 to 2900)

(4.54 to 12.33)

 

 

 

 

 

 

 

 

 

 

 

 

4 units

10

10

10

10

1.98

1.98

1.98

1.98

7.9

2450

10.42

48

 

(4.0 to 8.7)

(930 to 2800)

(4.31 to 11.90)

 

 

 

 

 

 

 

 

 

 

 

 

 

13

10

10

10

2.48

1.81

1.81

1.81

7.9

2450

10.42

48

 

 

(4.1 to 8.8)

(940 to 2820)

(4.35 to 11.99)

 

 

 

 

 

 

 

 

 

 

 

 

 

16

10

10

10

2.86

1.71

1.71

1.71

8.0

2500

10.63

48

 

 

(4.1 to 9.0)

(940 to 2860)

(4.35 to 12.16)

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

10

10

2.31

2.31

1.69

1.69

8.0

2500

10.63

48

 

 

(4.1 to 9.0)

(940 to 2860)

(4.35 to 12.16)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

10

10

2.65

2.18

1.59

1.59

8.0

2500

10.63

48

 

 

(4.2 to 9.1)

(950 to 2880)

(4.40 to 12.24)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

13

10

2.14

2.14

2.14

1.57

8.0

2500

10.63

48

 

 

(4.2 to 9.1)

(950 to 2880)

(4.40 to 12.24)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

13

10

2.47

2.03

2.03

1.48

8.0

2500

10.63

48

 

 

(4.2 to 9.2)

(950 to 2900)

(4.40 to 12.33)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

13

13

2.00

2.00

2.00

2.00

8.0

2500

10.63

48

 

 

(4.2 to 9.2)

(950 to 2900)

(4.40 to 12.33)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

10

10

2.50

2.50

1.50

1.50

8.0

2500

10.63

48

 

 

(4.2 to 9.2)

(950 to 2900)

(4.40 to 12.33)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The above specification values are those under the conditions that the indoor DB/WB=27/19°C and the outdoor DB/ WB=35/–°C.

Indoor unit 10 : RAS-M10UKV-E, 13 : RAS-M13UKV-E, 16 : RAS-M16UKV-E

7 –

Outdoor Unit : RAS-4M27YAV-E

<Heating/220V>

Power

Operating

 

Indoor unit

 

 

Unit capacity (kW)

 

Heating

Power

Operating

Outdoor

supply

 

 

 

 

 

 

 

 

capacity

consumption

current

noise

status

A

B

C

D

A

B

C

D

(V)

(kW)

(W)

(A)

(dB)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

220

1 unit

10

4.0

4.0

1450

6.73

48

(0.8 to 5.2)

(300 to 1980)

(1.87 to 9.18)

 

 

 

 

 

 

 

 

 

 

 

 

 

13

5.0

5.0

2050

9.51

48

 

 

(0.8 to 6.5)

(310 to 2750)

(1.93 to 12.76)

 

 

 

 

 

 

 

 

 

 

 

 

 

16

5.5

5.5

2400

11.13

48

 

 

(0.8 to 6.9)

(310 to 3000)

(1.93 to 13.91)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 units

10

10

3.60

3.60

7.2

2100

9.74

48

 

(1.5 to 10.0)

(320 to 3200)

(1.94 to 14.84)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

10

4.22

3.38

7.6

2320

10.76

48

 

 

(1.5 to 10.1)

(320 to 3210)

(1.94 to 14.89)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

10

4.57

3.33

7.9

2480

11.50

48

 

 

(1.5 to 10.1)

(320 to 3230)

(1.94 to 14.98)

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

3.95

3.95

7.9

2480

11.50

48

 

 

(1.5 to 10.1)

(320 to 3230)

(1.94 to 14.98)

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

4.35

3.95

8.3

2700

12.52

48

 

 

(1.5 to 10.2)

(320 to 3240)

(1.94 to 15.03)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

4.30

4.30

8.6

2860

13.27

48

 

 

(1.5 to 10.2)

(320 to 3250)

(1.94 to 15.07)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 units

10

10

10

2.87

2.87

2.87

8.6

2300

10.67

48

 

(2.0 to 10.4)

(380 to 2750)

(2.16 to 12.76)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

10

10

3.35

2.68

2.68

8.7

2350

10.90

48

 

 

(2.0 to 10.5)

(380 to 2760)

(2.16 to 12.80)

 

 

 

 

 

 

 

 

 

 

 

 

 

16

10

10

3.54

2.58

2.58

8.7

2350

10.90

48

 

 

(2.0 to 10.5)

(380 to 2760)

(2.16 to 12.80)

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

10

3.11

3.11

2.49

8.7

2350

10.90

48

 

 

(2.0 to 10.5)

(380 to 2760)

(2.16 to 12.80)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

10

3.34

3.03

2.43

8.8

2400

11.13

48

 

 

(2.0 to 10.6)

(380 to 2780)

(2.16 to 12.89)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

13

2.93

2.93

2.93

8.8

2400

11.13

48

 

 

(2.0 to 10.6)

(380 to 2780)

(2.16 to 12.89)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

10

3.26

3.26

2.37

8.9

2450

11.36

48

 

 

(2.0 to 10.7)

(380 to 2790)

(2.16 to 12.94)

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

13

3.16

2.87

2.87

8.9

2450

11.36

48

 

 

(2.0 to 10.7)

(380 to 2790)

(2.16 to 12.94)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

13

3.06

3.06

2.78

8.9

2450

11.36

48

 

 

(2.0 to 10.7)

(380 to 2790)

(2.16 to 12.94)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

16

3.00

3.00

3.00

9.0

2500

11.60

48

 

 

(2.0 to 10.8)

(380 to 2800)

(2.16 to 12.99)

 

 

 

 

 

 

 

 

 

 

 

 

4 units

10

10

10

10

2.23

2.23

2.23

2.23

8.9

2100

9.74

48

 

(2.2 to 10.8)

(450 to 2810)

(2.56 to 13.03)

 

 

 

 

 

 

 

 

 

 

 

 

 

13

10

10

10

2.62

2.09

2.09

2.09

8.9

2100

9.74

48

 

 

(2.2 to 10.9)

(460 to 2830)

(2.61 to 13.13)

 

 

 

 

 

 

 

 

 

 

 

 

 

16

10

10

10

2.83

2.06

2.06

2.06

9.0

2250

10.44

48

 

 

(2.2 to 10.9)

(460 to 2830)

(2.61 to 13.13)

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

10

10

2.50

2.50

2.00

2.00

9.0

2250

10.44

48

 

 

(2.2 to 10.9)

(470 to 2830)

(2.67 to 13.13)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

10

10

2.68

2.43

1.95

1.95

9.0

2250

10.44

48

 

 

(2.2 to 11.0)

(480 to 2850)

(2.73 to 13.22)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

13

10

2.37

2.37

2.37

1.89

9.0

2250

10.44

48

 

 

(2.2 to 11.0)

(480 to 2850)

(2.73 to 13.22)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

13

10

2.54

2.31

2.31

1.85

9.0

2250

10.44

48

 

 

(2.2 to 11.0)

(490 to 2850)

(2.78 to 13.22)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

13

13

2.25

2.25

2.25

2.25

9.0

2250

10.44

48

 

 

(2.2 to 11.0)

(490 to 2850)

(2.78 to 13.22)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

10

10

2.61

2.61

1.89

1.89

9.0

2250

10.44

48

 

 

(2.2 to 11.0)

(500 to 2850)

(2.84 to 13.22)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The above specification values are those under the conditions that the indoor DB/WB=27/19°C and the outdoor DB/ WB=35/–°C.

Indoor unit 10 : RAS-M10UKV-E, 13 : RAS-M13UKV-E, 16 : RAS-M16UKV-E

8 –

Outdoor Unit : RAS-4M27YAV-E

<Heating/230V>

Power

Operating

 

Indoor unit

 

 

Unit capacity (kW)

 

Heating

Power

Operating

Outdoor

supply

 

 

 

 

 

 

 

 

capacity

consumption

current

noise

status

A

B

C

D

A

B

C

D

(V)

(kW)

(W)

(A)

(dB)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

230

1 unit

10

4.0

4.0

1450

6.43

48

(0.8 to 5.2)

(300 to 1980)

(1.79 to 8.78)

 

 

 

 

 

 

 

 

 

 

 

 

 

13

5.0

5.0

2050

9.09

48

 

 

(0.8 to 6.5)

(310 to 2750)

(1.85 to 12.20)

 

 

 

 

 

 

 

 

 

 

 

 

 

16

5.5

5.5

2400

10.65

48

 

 

(0.8 to 6.9)

(310 to 3000)

(1.85 to 13.31)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 units

10

10

3.60

3.60

7.2

2100

9.32

48

 

(1.5 to 10.0)

(320 to 3200)

(1.86 to 14.20)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

10

4.22

3.38

7.6

2320

10.29

48

 

 

(1.5 to 10.1)

(320 to 3210)

(1.86 to 14.24)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

10

4.57

3.33

7.9

2480

11.00

48

 

 

(1.5 to 10.1)

(320 to 3230)

(1.86 to 14.33)

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

3.95

3.95

7.9

2480

11.00

48

 

 

(1.5 to 10.1)

(320 to 3230)

(1.86 to 14.33)

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

4.35

3.95

8.3

2700

11.98

48

 

 

(1.5 to 10.2)

(320 to 3240)

(1.86 to 14.37)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

4.30

4.30

8.6

2860

12.69

48

 

 

(1.5 to 10.2)

(320 to 3250)

(1.86 to 14.42)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 units

10

10

10

2.87

2.87

2.87

8.6

2300

10.20

48

 

(2.0 to 10.4)

(380 to 2750)

(2.07 to 12.20)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

10

10

3.35

2.68

2.68

8.7

2350

10.43

48

 

 

(2.0 to 10.5)

(380 to 2760)

(2.07 to 12.24)

 

 

 

 

 

 

 

 

 

 

 

 

 

16

10

10

3.54

2.58

2.58

8.7

2350

10.43

48

 

 

(2.0 to 10.5)

(380 to 2760)

(2.07 to 12.24)

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

10

3.11

3.11

2.49

8.7

2350

10.43

48

 

 

(2.0 to 10.5)

(380 to 2760)

(2.07 to 12.24)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

10

3.34

3.03

2.43

8.8

2400

10.65

48

 

 

(2.0 to 10.6)

(380 to 2780)

(2.07 to 12.33)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

13

2.93

2.93

2.93

8.8

2400

10.65

48

 

 

(2.0 to 10.6)

(380 to 2780)

(2.07 to 12.33)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

10

3.26

3.26

2.37

8.9

2450

10.87

48

 

 

(2.0 to 10.7)

(380 to 2790)

(2.07 to 12.38)

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

13

3.16

2.87

2.87

8.9

2450

10.87

48

 

 

(2.0 to 10.7)

(380 to 2790)

(2.07 to 12.38)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

13

3.06

3.06

2.78

8.9

2450

10.87

48

 

 

(2.0 to 10.7)

(380 to 2790)

(2.07 to 12.38)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

16

3.00

3.00

3.00

9.0

2500

11.09

48

 

 

(2.0 to 10.8)

(380 to 2800)

(2.07 to 12.42)

 

 

 

 

 

 

 

 

 

 

 

 

4 units

10

10

10

10

2.23

2.23

2.23

2.23

8.9

2100

9.32

48

 

(2.2 to 10.8)

(450 to 2810)

(2.45 to 12.47)

 

 

 

 

 

 

 

 

 

 

 

 

 

13

10

10

10

2.62

2.09

2.09

2.09

8.9

2100

9.32

48

 

 

(2.2 to 10.9)

(460 to 2830)

(2.50 to 12.56)

 

 

 

 

 

 

 

 

 

 

 

 

 

16

10

10

10

2.83

2.06

2.06

2.06

9.0

2250

9.98

48

 

 

(2.2 to 10.9)

(460 to 2830)

(2.50 to 12.56)

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

10

10

2.50

2.50

2.00

2.00

9.0

2250

9.98

48

 

 

(2.2 to 10.9)

(470 to 2830)

(2.55 to 12.56)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

10

10

2.68

2.43

1.95

1.95

9.0

2250

9.98

48

 

 

(2.2 to 11.0)

(480 to 2850)

(2.61 to 12.64)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

13

10

2.37

2.37

2.37

1.89

9.0

2250

9.98

48

 

 

(2.2 to 11.0)

(480 to 2850)

(2.61 to 12.64)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

13

10

2.54

2.31

2.31

1.85

9.0

2250

9.98

48

 

 

(2.2 to 11.0)

(490 to 2850)

(2.66 to 12.64)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

13

13

2.25

2.25

2.25

2.25

9.0

2250

9.98

48

 

 

(2.2 to 11.0)

(490 to 2850)

(2.66 to 12.64)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

10

10

2.61

2.61

1.89

1.89

9.0

2250

9.98

48

 

 

(2.2 to 11.0)

(500 to 2850)

(2.72 to 12.64)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The above specification values are those under the conditions that the indoor DB/WB=27/19°C and the outdoor DB/ WB=35/–°C.

Indoor unit 10 : RAS-M10UKV-E, 13 : RAS-M13UKV-E, 16 : RAS-M16UKV-E

9 –

Outdoor Unit : RAS-4M27YAV-E

<Heating/240V>

Power

Operating

 

Indoor unit

 

 

Unit capacity (kW)

 

Heating

Power

Operating

Outdoor

supply

 

 

 

 

 

 

 

 

capacity

consumption

current

noise

status

A

B

C

D

A

B

C

D

(V)

(kW)

(W)

(A)

(dB)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

240

1 unit

10

4.0

4.0

1450

6.16

48

(0.8 to 5.2)

(300 to 1980)

(1.71 to 8.42)

 

 

 

 

 

 

 

 

 

 

 

 

 

13

5.0

5.0

2050

8.72

48

 

 

(0.8 to 6.5)

(310 to 2750)

(1.77 to 11.69)

 

 

 

 

 

 

 

 

 

 

 

 

 

16

5.5

5.5

2400

10.20

48

 

 

(0.8 to 6.9)

(310 to 3000)

(1.77 to 12.76)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 units

10

10

3.60

3.60

7.2

2100

8.93

48

 

(1.5 to 10.0)

(320 to 3200)

(1.78 to 13.61)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

10

4.22

3.38

7.6

2320

9.86

48

 

 

(1.5 to 10.1)

(320 to 3210)

(1.78 to 13.65)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

10

4.57

3.33

7.9

2480

10.54

48

 

 

(1.5 to 10.1)

(320 to 3230)

(1.78 to 13.73)

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

3.95

3.95

7.9

2480

10.54

48

 

 

(1.5 to 10.1)

(320 to 3230)

(1.78 to 13.73)

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

4.35

3.95

8.3

2700

11.48

48

 

 

(1.5 to 10.2)

(320 to 3240)

(1.78 to 13.78)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

4.30

4.30

8.6

2860

12.16

48

 

 

(1.5 to 10.2)

(320 to 3250)

(1.78 to 13.82)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 units

10

10

10

2.87

2.87

2.87

8.6

2300

9.78

48

 

(2.0 to 10.4)

(380 to 2750)

(1.98 to 11.69)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

10

10

3.35

2.68

2.68

8.7

2350

9.99

48

 

 

(2.0 to 10.5)

(380 to 2760)

(1.98 to 11.73)

 

 

 

 

 

 

 

 

 

 

 

 

 

16

10

10

3.54

2.58

2.58

8.7

2350

9.99

48

 

 

(2.0 to 10.5)

(380 to 2760)

(1.98 to 11.73)

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

10

3.11

3.11

2.49

8.7

2350

9.99

48

 

 

(2.0 to 10.5)

(380 to 2760)

(1.98 to 11.73)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

10

3.34

3.03

2.43

8.8

2400

10.20

48

 

 

(2.0 to 10.6)

(380 to 2780)

(1.98 to 11.82)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

13

2.93

2.93

2.93

8.8

2400

10.20

48

 

 

(2.0 to 10.6)

(380 to 2780)

(1.98 to 11.82)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

10

3.26

3.26

2.37

8.9

2450

10.42

48

 

 

(2.0 to 10.7)

(380 to 2790)

(1.98 to 11.86)

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

13

3.16

2.87

2.87

8.9

2450

10.42

48

 

 

(2.0 to 10.7)

(380 to 2790)

(1.98 to 11.86)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

13

3.06

3.06

2.78

8.9

2450

10.42

48

 

 

(2.0 to 10.7)

(380 to 2790)

(1.98 to 11.86)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

16

3.00

3.00

3.00

9.0

2500

10.63

48

 

 

(2.0 to 10.8)

(380 to 2800)

(1.98 to 11.90)

 

 

 

 

 

 

 

 

 

 

 

 

4 units

10

10

10

10

2.23

2.23

2.23

2.23

8.9

2100

8.93

48

 

(2.2 to 10.8)

(450 to 2810)

(2.34 to 11.95)

 

 

 

 

 

 

 

 

 

 

 

 

 

13

10

10

10

2.62

2.09

2.09

2.09

8.9

2100

8.93

48

 

 

(2.2 to 10.9)

(460 to 2830)

(2.40 to 12.03)

 

 

 

 

 

 

 

 

 

 

 

 

 

16

10

10

10

2.83

2.06

2.06

2.06

9.0

2250

9.57

48

 

 

(2.2 to 10.9)

(460 to 2830)

(2.40 to 12.03)

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

10

10

2.50

2.50

2.00

2.00

9.0

2250

9.57

48

 

 

(2.2 to 10.9)

(470 to 2830)

(2.45 to 12.03)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

10

10

2.68

2.43

1.95

1.95

9.0

2250

9.57

48

 

 

(2.2 to 11.0)

(480 to 2850)

(2.50 to 12.12)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

13

10

2.37

2.37

2.37

1.89

9.0

2250

9.57

48

 

 

(2.2 to 11.0)

(480 to 2850)

(2.50 to 12.12)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

13

10

2.54

2.31

2.31

1.85

9.0

2250

9.57

48

 

 

(2.2 to 11.0)

(490 to 2850)

(2.55 to 12.12)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

13

13

2.25

2.25

2.25

2.25

9.0

2250

9.57

48

 

 

(2.2 to 11.0)

(490 to 2850)

(2.55 to 12.12)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

10

10

2.61

2.61

1.89

1.89

9.0

2250

9.57

48

 

 

(2.2 to 11.0)

(500 to 2850)

(2.60 to 12.12)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The above specification values are those under the conditions that the indoor DB/WB=27/19°C and the outdoor DB/ WB=35/–°C.

Indoor unit 10 : RAS-M10UKV-E, 13 : RAS-M13UKV-E, 16 : RAS-M16UKV-E

10 –

Outdoor Unit : RAS-4M27YACV-E

<Cooling/220V>

Power

Operating

 

Indoor unit

 

 

Unit capacity (kW)

 

Cooling

Power

Operating

Outdoor

supply

 

 

 

 

 

 

 

 

capacity

consumption

current

noise

status

A

B

C

D

A

B

C

D

(V)

(kW)

(W)

(A)

(dB)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

220

1 unit

10

2.7

2.7

750

3.87

48

(1.4 to 3.2)

(640 to 950)

(3.68 to 4.64)

 

 

 

 

 

 

 

 

 

 

 

 

 

13

3.7

3.7

1200

5.74

48

 

 

(1.4 to 4.4)

(640 to 1520)

(3.68 to 7.20)

 

 

 

 

 

 

 

 

 

 

 

 

 

16

4.5

4.5

1650

7.81

48

 

 

(1.4 to 5.0)

(640 to 2000)

(3.68 to 9.28)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 units

10

10

2.70

2.70

5.4

1530

7.10

48

 

(2.5 to 6.3)

(640 to 2040)

(3.64 to 9.46)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

10

3.41

2.49

5.9

1810

8.40

48

 

 

(2.7 to 6.6)

(660 to 2220)

(3.75 to 10.30)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

10

3.94

2.36

6.3

2040

9.46

48

 

 

(2.9 to 6.9)

(670 to 2400)

(3.81 to 11.13)

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

3.15

3.15

6.3

2040

9.46

48

 

 

(2.9 to 6.9)

(670 to 2400)

(3.81 to 11.13)

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

3.73

3.07

6.8

2320

10.76

48

 

 

(3.0 to 7.2)

(690 to 2570)

(3.92 to 11.92)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

3.60

3.60

7.2

2550

11.83

48

 

 

(3.2 to 7.5)

(700 to 2750)

(3.98 to 12.76)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 units

10

10

10

2.53

2.53

2.53

7.6

2400

11.13

48

 

(3.8 to 8.2)

(950 to 2720)

(4.80 to 12.62)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

10

10

3.13

2.28

2.28

7.7

2410

11.18

48

 

 

(3.9 to 8.3)

(960 to 2740)

(4.85 to 12.71)

 

 

 

 

 

 

 

 

 

 

 

 

 

16

10

10

3.50

2.10

2.10

7.7

2410

11.18

48

 

 

(4.0 to 8.5)

(960 to 2790)

(4.85 to 12.94)

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

10

2.82

2.82

2.06

7.7

2410

11.18

48

 

 

(4.0 to 8.5)

(960 to 2790)

(4.85 to 12.94)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

10

3.22

2.65

1.93

7.8

2430

11.27

48

 

 

(4.1 to 8.6)

(970 to 2810)

(4.90 to 13.03)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

13

2.60

2.60

2.60

7.8

2430

11.27

48

 

 

(4.1 to 8.6)

(970 to 2810)

(4.90 to 13.03)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

10

3.04

3.04

1.82

7.9

2440

11.32

48

 

 

(4.1 to 8.7)

(970 to 2830)

(4.90 to 13.13)

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

13

2.99

2.46

2.46

7.9

2440

11.32

48

 

 

(4.1 to 8.7)

(970 to 2830)

(4.90 to 13.13)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

13

2.80

2.80

2.30

7.9

2440

11.32

48

 

 

(4.2 to 8.9)

(970 to 2880)

(4.90 to 13.36)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

16

2.67

2.67

2.67

8.0

2450

11.36

48

 

 

(4.3 to 9.0)

(980 to 2900)

(4.95 to 13.45)

 

 

 

 

 

 

 

 

 

 

 

 

4 units

10

10

10

10

1.98

1.98

1.98

1.98

7.9

2450

11.36

48

 

(4.0 to 8.7)

(930 to 2800)

(4.70 to 12.99)

 

 

 

 

 

 

 

 

 

 

 

 

 

13

10

10

10

2.48

1.81

1.81

1.81

7.9

2450

11.36

48

 

 

(4.1 to 8.8)

(940 to 2820)

(4.75 to 13.08)

 

 

 

 

 

 

 

 

 

 

 

 

 

16

10

10

10

2.86

1.71

1.71

1.71

8.0

2500

11.60

48

 

 

(4.1 to 9.0)

(940 to 2860)

(4.75 to 13.27)

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

10

10

2.31

2.31

1.69

1.69

8.0

2500

11.60

48

 

 

(4.1 to 9.0)

(940 to 2860)

(4.75 to 13.27)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

10

10

2.65

2.18

1.59

1.59

8.0

2500

11.60

48

 

 

(4.2 to 9.1)

(950 to 2880)

(4.80 to 13.36)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

13

10

2.14

2.14

2.14

1.57

8.0

2500

11.60

48

 

 

(4.2 to 9.1)

(950 to 2880)

(4.80 to 13.36)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

13

10

2.47

2.03

2.03

1.48

8.0

2500

11.60

48

 

 

(4.2 to 9.2)

(950 to 2900)

(4.80 to 13.45)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

13

13

2.00

2.00

2.00

2.00

8.0

2500

11.60

48

 

 

(4.2 to 9.2)

(950 to 2900)

(4.80 to 13.45)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

10

10

2.50

2.50

1.50

1.50

8.0

2500

11.60

48

 

 

(4.2 to 9.2)

(950 to 2900)

(4.80 to 13.45)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The above specification values are those under the conditions that the indoor DB/WB=27/19°C and the outdoor DB/ WB=35/–°C.

Indoor unit 10 : RAS-M10UKCV-E, 13 : RAS-M13UKCV-E, 16 : RAS-M16UKCV-E

11 –

Outdoor Unit : RAS-4M27YACV-E

<Cooling/230V>

Power

Operating

 

Indoor unit

 

 

Unit capacity (kW)

 

Cooling

Power

Operating

Outdoor

supply

 

 

 

 

 

 

 

 

capacity

consumption

current

noise

status

A

B

C

D

A

B

C

D

(V)

(kW)

(W)

(A)

(dB)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

230

1 unit

10

2.7

2.7

750

3.71

48

(1.4 to 3.2)

(640 to 950)

(3.52 to 4.44)

 

 

 

 

 

 

 

 

 

 

 

 

 

13

3.7

3.7

1200

5.49

48

 

 

(1.4 to 4.4)

(640 to 1520)

(3.52 to 6.88)

 

 

 

 

 

 

 

 

 

 

 

 

 

16

4.5

4.5

1650

7.47

48

 

 

(1.4 to 5.0)

(640 to 2000)

(3.52 to 8.87)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 units

10

10

2.70

2.70

5.4

1530

6.79

48

 

(2.5 to 6.3)

(640 to 2040)

(3.48 to 9.05)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

10

3.41

2.49

5.9

1810

8.03

48

 

 

(2.7 to 6.6)

(660 to 2220)

(3.59 to 9.85)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

10

3.94

2.36

6.3

2040

9.05

48

 

 

(2.9 to 6.9)

(670 to 2400)

(3.64 to 10.65)

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

3.15

3.15

6.3

2040

9.05

48

 

 

(2.9 to 6.9)

(670 to 2400)

(3.64 to 10.65)

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

3.73

3.07

6.8

2320

10.29

48

 

 

(3.0 to 7.2)

(690 to 2570)

(3.75 to 11.40)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

3.60

3.60

7.2

2550

11.31

48

 

 

(3.2 to 7.5)

(700 to 2750)

(3.80 to 12.20)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 units

10

10

10

2.53

2.53

2.53

7.6

2400

10.65

48

 

(3.8 to 8.2)

(950 to 2720)

(4.59 to 12.07)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

10

10

3.13

2.28

2.28

7.7

2410

10.69

48

 

 

(3.9 to 8.3)

(960 to 2740)

(4.64 to 12.16)

 

 

 

 

 

 

 

 

 

 

 

 

 

16

10

10

3.50

2.10

2.10

7.7

2410

10.69

48

 

 

(4.0 to 8.5)

(960 to 2790)

(4.64 to 12.38)

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

10

2.82

2.82

2.06

7.7

2410

10.69

48

 

 

(4.0 to 8.5)

(960 to 2790)

(4.64 to 12.38)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

10

3.22

2.65

1.93

7.8

2430

10.78

48

 

 

(4.1 to 8.6)

(970 to 2810)

(4.69 to 12.47)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

13

2.60

2.60

2.60

7.8

2430

10.78

48

 

 

(4.1 to 8.6)

(970 to 2810)

(4.69 to 12.47)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

10

3.04

3.04

1.82

7.9

2440

10.83

48

 

 

(4.1 to 8.7)

(970 to 2830)

(4.69 to 12.56)

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

13

2.99

2.46

2.46

7.9

2440

10.83

48

 

 

(4.1 to 8.7)

(970 to 2830)

(4.69 to 12.56)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

13

2.80

2.80

2.30

7.9

2440

10.83

48

 

 

(4.2 to 8.9)

(970 to 2880)

(4.69 to 12.78)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

16

2.67

2.67

2.67

8.0

2450

10.87

48

 

 

(4.3 to 9.0)

(980 to 2900)

(4.73 to 12.87)

 

 

 

 

 

 

 

 

 

 

 

 

4 units

10

10

10

10

1.98

1.98

1.98

1.98

7.9

2450

10.87

48

 

(4.0 to 8.7)

(930 to 2800)

(4.49 to 12.42)

 

 

 

 

 

 

 

 

 

 

 

 

 

13

10

10

10

2.48

1.81

1.81

1.81

7.9

2450

10.87

48

 

 

(4.1 to 8.8)

(940 to 2820)

(4.54 to 12.51)

 

 

 

 

 

 

 

 

 

 

 

 

 

16

10

10

10

2.86

1.71

1.71

1.71

8.0

2500

11.09

48

 

 

(4.1 to 9.0)

(940 to 2860)

(4.54 to 12.69)

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

10

10

2.31

2.31

1.69

1.69

8.0

2500

11.09

48

 

 

(4.1 to 9.0)

(940 to 2860)

(4.54 to 12.69)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

10

10

2.65

2.18

1.59

1.59

8.0

2500

11.09

48

 

 

(4.2 to 9.1)

(950 to 2880)

(4.59 to 12.78)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

13

10

2.14

2.14

2.14

1.57

8.0

2500

11.09

48

 

 

(4.2 to 9.1)

(950 to 2880)

(4.59 to 12.78)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

13

10

2.47

2.03

2.03

1.48

8.0

2500

11.09

48

 

 

(4.2 to 9.2)

(950 to 2900)

(4.59 to 12.87)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

13

13

2.00

2.00

2.00

2.00

8.0

2500

11.09

48

 

 

(4.2 to 9.2)

(950 to 2900)

(4.59 to 12.87)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

10

10

2.50

2.50

1.50

1.50

8.0

2500

11.09

48

 

 

(4.2 to 9.2)

(950 to 2900)

(4.59 to 12.87)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The above specification values are those under the conditions that the indoor DB/WB=27/19°C and the outdoor DB/ WB=35/–°C.

Indoor unit 10 : RAS-M10UKCV-E, 13 : RAS-M13UKCV-E, 16 : RAS-M16UKCV-E

12 –

Outdoor Unit : RAS-4M27YACV-E

<Cooling/240V>

Power

Operating

 

Indoor unit

 

 

Unit capacity (kW)

 

Cooling

Power

Operating

Outdoor

supply

 

 

 

 

 

 

 

 

capacity

consumption

current

noise

status

A

B

C

D

A

B

C

D

(V)

(kW)

(W)

(A)

(dB)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

240

1 unit

10

2.7

2.7

750

3.55

48

(1.4 to 3.2)

(640 to 950)

(3.38 to 4.26)

 

 

 

 

 

 

 

 

 

 

 

 

 

13

3.7

3.7

1200

5.26

48

 

 

(1.4 to 4.4)

(640 to 1520)

(3.38 to 6.60)

 

 

 

 

 

 

 

 

 

 

 

 

 

16

4.5

4.5

1650

7.16

48

 

 

(1.4 to 5.0)

(640 to 2000)

(3.38 to 8.50)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 units

10

10

2.70

2.70

5.4

1530

6.51

48

 

(2.5 to 6.3)

(640 to 2040)

(3.33 to 8.67)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

10

3.41

2.49

5.9

1810

7.70

48

 

 

(2.7 to 6.6)

(660 to 2220)

(3.44 to 9.44)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

10

3.94

2.36

6.3

2040

8.67

48

 

 

(2.9 to 6.9)

(670 to 2400)

(3.49 to 10.20)

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

3.15

3.15

6.3

2040

8.67

48

 

 

(2.9 to 6.9)

(670 to 2400)

(3.49 to 10.20)

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

3.73

3.07

6.8

2320

9.86

48

 

 

(3.0 to 7.2)

(690 to 2570)

(3.59 to 10.93)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

3.60

3.60

7.2

2550

10.84

48

 

 

(3.2 to 7.5)

(700 to 2750)

(3.65 to 11.69)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 units

10

10

10

2.53

2.53

2.53

7.6

2400

10.20

48

 

(3.8 to 8.2)

(950 to 2720)

(4.40 to 11.56)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

10

10

3.13

2.28

2.28

7.7

2410

10.25

48

 

 

(3.9 to 8.3)

(960 to 2740)

(4.44 to 11.65)

 

 

 

 

 

 

 

 

 

 

 

 

 

16

10

10

3.50

2.10

2.10

7.7

2410

10.25

48

 

 

(4.0 to 8.5)

(960 to 2790)

(4.44 to 11.86)

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

10

2.82

2.82

2.06

7.7

2410

10.25

48

 

 

(4.0 to 8.5)

(960 to 2790)

(4.44 to 11.86)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

10

3.22

2.65

1.93

7.8

2430

10.33

48

 

 

(4.1 to 8.6)

(970 to 2810)

(4.49 to 11.95)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

13

2.60

2.60

2.60

7.8

2430

10.33

48

 

 

(4.1 to 8.6)

(970 to 2810)

(4.49 to 11.95)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

10

3.04

3.04

1.82

7.9

2440

10.37

48

 

 

(4.1 to 8.7)

(970 to 2830)

(4.49 to 12.03)

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

13

2.99

2.46

2.46

7.9

2440

10.37

48

 

 

(4.1 to 8.7)

(970 to 2830)

(4.49 to 12.03)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

13

2.80

2.80

2.30

7.9

2440

10.37

48

 

 

(4.2 to 8.9)

(970 to 2880)

(4.49 to 12.24)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

16

2.67

2.67

2.67

8.0

2450

10.42

48

 

 

(4.3 to 9.0)

(980 to 2900)

(4.54 to 12.33)

 

 

 

 

 

 

 

 

 

 

 

 

4 units

10

10

10

10

1.98

1.98

1.98

1.98

7.9

2450

10.42

48

 

(4.0 to 8.7)

(930 to 2800)

(4.31 to 11.90)

 

 

 

 

 

 

 

 

 

 

 

 

 

13

10

10

10

2.48

1.81

1.81

1.81

7.9

2450

10.42

48

 

 

(4.1 to 8.8)

(940 to 2820)

(4.35 to 11.99)

 

 

 

 

 

 

 

 

 

 

 

 

 

16

10

10

10

2.86

1.71

1.71

1.71

8.0

2500

10.63

48

 

 

(4.1 to 9.0)

(940 to 2860)

(4.35 to 12.16)

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

10

10

2.31

2.31

1.69

1.69

8.0

2500

10.63

48

 

 

(4.1 to 9.0)

(940 to 2860)

(4.35 to 12.16)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

10

10

2.65

2.18

1.59

1.59

8.0

2500

10.63

48

 

 

(4.2 to 9.1)

(950 to 2880)

(4.40 to 12.24)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

13

10

2.14

2.14

2.14

1.57

8.0

2500

10.63

48

 

 

(4.2 to 9.1)

(950 to 2880)

(4.40 to 12.24)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

13

10

2.47

2.03

2.03

1.48

8.0

2500

10.63

48

 

 

(4.2 to 9.2)

(950 to 2900)

(4.40 to 12.33)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

13

13

2.00

2.00

2.00

2.00

8.0

2500

10.63

48

 

 

(4.2 to 9.2)

(950 to 2900)

(4.40 to 12.33)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

10

10

2.50

2.50

1.50

1.50

8.0

2500

10.63

48

 

 

(4.2 to 9.2)

(950 to 2900)

(4.40 to 12.33)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The above specification values are those under the conditions that the indoor DB/WB=27/19°C and the outdoor DB/ WB=35/–°C.

Indoor unit 10 : RAS-M10UKCV-E, 13 : RAS-M13UKCV-E, 16 : RAS-M16UKCV-E

13 –

Outdoor Unit : RAS-3M26YAV-E <Cooling/220V>

Power

Operating

 

Indoor unit

 

Unit capacity (kW)

Cooling

Power

Operating

Outdoor

supply

 

 

 

 

 

 

capacity

consumption

current

noise

status

A

B

C

A

B

C

(V)

(kW)

(W)

(A)

(dB)

 

 

 

 

 

 

 

 

 

 

 

 

 

220

1 unit

10

2.7

2.7

750

3.87

48

(1.4 to 3.2)

(640 to 950)

(3.68 to 4.64)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

3.7

3.7

1200

5.74

48

 

 

(1.4 to 4.4)

(640 to 1520)

(3.68 to 7.20)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

4.5

4.5

1650

7.81

48

 

 

(1.4 to 5.0)

(640 to 2000)

(3.68 to 9.28)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 units

10

10

2.70

2.70

5.4

1530

7.10

48

 

(2.5 to 6.3)

(640 to 2040)

(3.64 to 9.46)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

10

3.41

2.49

5.9

1810

8.40

48

 

 

(2.7 to 6.6)

(660 to 2220)

(3.75 to 10.30)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

10

3.94

2.36

6.3

2040

9.46

48

 

 

(2.9 to 6.9)

(670 to 2400)

(3.81 to 11.13)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

3.15

3.15

6.3

2040

9.46

48

 

 

(2.9 to 6.9)

(670 to 2400)

(3.81 to 11.13)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

3.73

3.07

6.8

2320

10.76

48

 

 

(3.0 to 7.2)

(690 to 2570)

(3.92 to 11.92)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

3.60

3.60

7.2

2550

11.83

48

 

 

(3.2 to 7.5)

(700 to 2750)

(3.98 to 12.76)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 units

10

10

10

2.47

2.47

2.47

7.4

2230

10.34

48

 

(3.8 to 8.2)

(950 to 2720)

(4.80 to 12.62)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

10

10

3.01

2.20

2.20

7.4

2230

10.34

48

 

 

(3.9 to 8.3)

(950 to 2750)

(4.80 to 12.76)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

10

10

3.36

2.02

2.02

7.4

2230

10.34

48

 

 

(4.0 to 8.5)

(950 to 2820)

(4.80 to 13.08)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

10

2.71

2.71

1.98

7.4

2230

10.34

48

 

 

(4.0 to 8.5)

(950 to 2820)

(4.80 to 13.08)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

10

3.10

2.55

1.86

7.5

2250

10.44

48

 

 

(4.0 to 8.6)

(980 to 2850)

(4.95 to 13.22)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

13

2.50

2.50

2.50

7.5

2250

10.44

48

 

 

(4.0 to 8.6)

(980 to 2850)

(4.95 to 13.22)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

10

2.88

2.88

1.73

7.5

2250

10.44

48

 

 

(4.1 to 8.8)

(980 to 2920)

(4.95 to 13.54)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

13

2.84

2.33

2.33

7.5

2250

10.44

48

 

 

(4.1 to 8.8)

(980 to 2920)

(4.95 to 13.54)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

13

2.66

2.66

2.19

7.5

2250

10.44

48

 

 

(4.2 to 8.9)

(980 to 2950)

(4.95 to 13.68)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The above specification values are those under the conditions that the indoor DB/WB=27/19°C and the outdoor DB/ WB=35/–°C.

Indoor unit 10 : RAS-M10UKV-E, 13 : RAS-M13UKV-E, 16 : RAS-M16UKV-E

– 14 –

Outdoor Unit : RAS-3M26YAV-E <Cooling/230V>

Power

Operating

 

Indoor unit

 

Unit capacity (kW)

Cooling

Power

Operating

Outdoor

supply

 

 

 

 

 

 

capacity

consumption

current

noise

status

A

B

C

A

B

C

(V)

(kW)

(W)

(A)

(dB)

 

 

 

 

 

 

 

 

 

 

 

 

 

230

1 unit

10

2.7

2.7

750

3.71

48

(1.4 to 3.2)

(640 to 950)

(3.52 to 4.44)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

3.7

3.7

1200

5.49

48

 

 

(1.4 to 4.4)

(640 to 1520)

(3.52 to 6.88)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

4.5

4.5

1650

7.47

48

 

 

(1.4 to 5.0)

(640 to 2000)

(3.52 to 8.87)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 units

10

10

2.70

2.70

5.4

1530

6.79

48

 

(2.5 to 6.3)

(640 to 2040)

(3.48 to 9.05)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

10

3.41

2.49

5.9

1810

8.03

48

 

 

(2.7 to 6.6)

(660 to 2220)

(3.59 to 9.85)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

10

3.94

2.36

6.3

2040

9.05

48

 

 

(2.9 to 6.9)

(670 to 2400)

(3.64 to 10.65)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

3.15

3.15

6.3

2040

9.05

48

 

 

(2.9 to 6.9)

(670 to 2400)

(3.64 to 10.65)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

3.73

3.07

6.8

2320

10.29

48

 

 

(3.0 to 7.2)

(690 to 2570)

(3.75 to 11.40)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

3.60

3.60

7.2

2550

11.31

48

 

 

(3.2 to 7.5)

(700 to 2750)

(3.80 to 12.20)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 units

10

10

10

2.47

2.47

2.47

7.4

2230

9.89

48

 

(3.8 to 8.2)

(950 to 2720)

(4.59 to 12.07)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

10

10

3.01

2.20

2.20

7.4

2230

9.89

48

 

 

(3.9 to 8.3)

(950 to 2750)

(4.59 to 12.20)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

10

10

3.36

2.02

2.02

7.4

2230

9.89

48

 

 

(4.0 to 8.5)

(950 to 2820)

(4.59 to 12.51)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

10

2.71

2.71

1.98

7.4

2230

9.89

48

 

 

(4.0 to 8.5)

(950 to 2820)

(4.59 to 12.51)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

10

3.10

2.55

1.86

7.5

2250

9.98

48

 

 

(4.0 to 8.6)

(980 to 2850)

(4.73 to 12.64)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

13

2.50

2.50

2.50

7.5

2250

9.98

48

 

 

(4.0 to 8.6)

(980 to 2850)

(4.73 to 12.64)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

10

2.88

2.88

1.73

7.5

2250

9.98

48

 

 

(4.1 to 8.8)

(980 to 2920)

(4.73 to 12.95)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

13

2.84

2.33

2.33

7.5

2250

9.98

48

 

 

(4.1 to 8.8)

(980 to 2920)

(4.73 to 12.95)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

13

2.66

2.66

2.19

7.5

2250

9.98

48

 

 

(4.2 to 8.9)

(980 to 2950)

(4.73 to 13.09)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The above specification values are those under the conditions that the indoor DB/WB=27/19°C and the outdoor DB/ WB=35/–°C.

Indoor unit 10 : RAS-M10UKV-E, 13 : RAS-M13UKV-E, 16 : RAS-M16UKV-E

– 15 –

Outdoor Unit : RAS-3M26YAV-E <Cooling/240V>

Power

Operating

 

Indoor unit

 

Unit capacity (kW)

Cooling

Power

Operating

Outdoor

supply

 

 

 

 

 

 

capacity

consumption

current

noise

status

A

B

C

A

B

C

(V)

(kW)

(W)

(A)

(dB)

 

 

 

 

 

 

 

 

 

 

 

 

 

240

1 unit

10

2.7

2.7

750

3.55

48

(1.4 to 3.2)

(640 to 950)

(338 to 4.26)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

3.7

3.7

1200

5.26

48

 

 

(1.4 to 4.4)

(640 to 1520)

(3.38 to 6.60)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

4.5

4.5

1650

7.16

48

 

 

(1.4 to 5.0)

(640 to 2000)

(3.38 to 8.50)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 units

10

10

2.70

2.70

5.4

1530

6.51

48

 

(2.5 to 6.3)

(640 to 2040)

(3.33 to 8.67)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

10

3.41

2.49

5.9

1810

7.70

48

 

 

(2.7 to 6.6)

(660 to 2220)

(3.44 to 9.44)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

10

3.94

2.36

6.3

2040

8.67

48

 

 

(2.9 to 6.9)

(670 to 2400)

(3.49 to 10.20)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

3.15

3.15

6.3

2040

8.67

48

 

 

(2.9 to 6.9)

(670 to 2400)

(3.49 to 10.20)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

3.73

3.07

6.8

2320

9.86

48

 

 

(3.0 to 7.2)

(690 to 2570)

(3.59 to 10.93)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

3.60

3.60

7.2

2550

10.84

48

 

 

(3.2 to 7.5)

(700 to 2750)

(3.65 to 11.69)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 units

10

10

10

2.47

2.47

2.47

7.4

2230

9.48

48

 

(3.8 to 8.2)

(950 to 2720)

(4.40 to 11.56)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

10

10

3.01

2.20

2.20

7.4

2230

9.48

48

 

 

(3.9 to 8.3)

(950 to 2750)

(4.40 to 11.69)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

10

10

3.36

2.02

2.02

7.4

2230

9.48

48

 

 

(4.0 to 8.5)

(950 to 2820)

(4.40 to 11.99)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

10

2.71

2.71

1.98

7.4

2230

9.48

48

 

 

(4.0 to 8.5)

(950 to 2820)

(4.40 to 11.99)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

10

3.10

2.55

1.86

7.5

2250

9.57

48

 

 

(4.0 to 8.6)

(980 to 2850)

(4.54 to 12.12)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

13

2.50

2.50

2.50

7.5

2250

9.57

48

 

 

(4.0 to 8.6)

(980 to 2850)

(4.54 to 12.12)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

10

2.88

2.88

1.73

7.5

2250

9.57

48

 

 

(4.1 to 8.8)

(980 to 2920)

(4.54 to 12.41)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

13

2.84

2.33

2.33

7.5

2250

9.57

48

 

 

(4.1 to 8.8)

(980 to 2920)

(4.54 to 12.41)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

13

2.66

2.66

2.19

7.5

2250

9.57

48

 

 

(4.2 to 8.9)

(980 to 2950)

(4.54 to 12.54)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The above specification values are those under the conditions that the indoor DB/WB=27/19°C and the outdoor DB/ WB=35/–°C.

Indoor unit 10 : RAS-M10UKV-E, 13 : RAS-M13UKV-E, 16 : RAS-M16UKV-E

– 16 –

Outdoor Unit : RAS-3M26YAV-E <Heating/220V>

Power

Operating

 

Indoor unit

 

Unit capacity (kW)

Heating

Power

Operating

Outdoor

supply

 

 

 

 

 

 

capacity

consumption

current

noise

status

A

B

C

A

B

C

(V)

(kW)

(W)

(A)

(dB)

 

 

 

 

 

 

 

 

 

 

 

 

 

220

1 unit

10

4.0

4.0

1500

6.96

48

(0.8 to 5.2)

(300 to 1980)

(1.87 to 9.18)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

5.0

5.0

2050

9.51

48

 

 

(0.8 to 6.5)

(310 to 2750)

(1.93 to 12.76)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

5.5

5.5

2400

11.13

48

 

 

(0.8 to 6.9)

(310 to 3000)

(1.93 to 13.91)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 units

10

10

3.60

3.60

7.2

2050

9.51

48

 

(1.5 to 10.0)

(320 to 3200)

(1.94 to 14.84)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

10

4.22

3.38

7.6

2240

10.39

48

 

 

(1.5 to 10.1)

(320 to 3210)

(1.94 to 14.89)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

10

4.57

3.33

7.9

2380

11.04

48

 

 

(1.5 to 10.1)

(320 to 3230)

(1.94 to 14.98)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

3.95

3.95

7.9

2380

11.04

48

 

 

(1.5 to 10.1)

(320 to 3230)

(1.94 to 14.98)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

4.35

3.95

8.3

2560

11.87

48

 

 

(1.5 to 10.2)

(320 to 3240)

(1.94 to 15.03)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

4.30

4.30

8.6

2700

12.52

48

 

 

(1.5 to 10.2)

(320 to 3250)

(1.94 to 15.07)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 units

10

10

10

2.87

2.87

2.87

8.6

2300

10.67

48

 

(2.0 to 10.4)

(380 to 2750)

(2.16 to 12.76)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

10

10

3.35

2.68

2.68

8.7

2360

10.95

48

 

 

(2.0 to 10.5)

(380 to 2760)

(2.16 to 12.80)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

10

10

3.59

2.61

2.61

8.8

2430

11.27

48

 

 

(2.0 to 10.6)

(380 to 2780)

(2.16 to 12.89)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

10

3.14

3.14

2.51

8.8

2430

11.27

48

 

 

(2.0 to 10.6)

(380 to 2780)

(2.16 to 12.89)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

10

3.34

3.03

2.43

8.8

2430

11.27

48

 

 

(2.0 to 10.6)

(380 to 2780)

(2.16 to 12.89)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

13

2.93

2.93

2.93

8.8

2430

11.27

48

 

 

(2.0 to 10.6)

(380 to 2780)

(2.16 to 12.89)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

10

3.26

3.26

2.37

8.9

2490

11.55

48

 

 

(2.0 to 10.7)

(380 to 2790)

(2.16 to 12.94)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

13

3.16

2.87

2.87

8.9

2490

11.55

48

 

 

(2.0 to 10.7)

(380 to 2790)

(2.16 to 12.94)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

13

3.09

3.09

2.81

9.0

2550

11.83

48

 

 

(2.0 to 10.8)

(380 to 2800)

(2.16 to 12.99)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The above specification values are those under the conditions that the indoor DB/WB=27/19°C and the outdoor DB/ WB=35/–°C.

Indoor unit 10 : RAS-M10UKV-E, 13 : RAS-M13UKV-E, 16 : RAS-M16UKV-E

– 17 –

Outdoor Unit : RAS-3M26YAV-E <Heating/230V>

Power

Operating

 

Indoor unit

 

Unit capacity (kW)

Heating

Power

Operating

Outdoor

supply

 

 

 

 

 

 

capacity

consumption

current

noise

status

A

B

C

A

B

C

(V)

(kW)

(W)

(A)

(dB)

 

 

 

 

 

 

 

 

 

 

 

 

 

230

1 unit

10

4.0

4.0

1500

6.65

48

(0.8 to 5.2)

(300 to 1980)

(1.79 to 8.78)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

5.0

5.0

2050

9.09

48

 

 

(0.8 to 6.5)

(310 to 2750)

(1.85 to 12.20)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

5.5

5.5

2400

10.65

48

 

 

(0.8 to 6.9)

(310 to 3000)

(1.85 to 13.31)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 units

10

10

3.60

3.60

7.2

2050

9.09

48

 

(1.5 to 10.0)

(320 to 3200)

(1.86 to 14.20)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

10

4.22

3.38

7.6

2240

9.94

48

 

 

(1.5 to 10.1)

(320 to 3210)

(1.86 to 14.24)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

10

4.57

3.33

7.9

2380

10.56

48

 

 

(1.5 to 10.1)

(320 to 3230)

(1.86 to 14.33)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

3.95

3.95

7.9

2380

10.56

48

 

 

(1.5 to 10.1)

(320 to 3230)

(1.86 to 14.33)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

4.35

3.95

8.3

2560

11.36

48

 

 

(1.5 to 10.2)

(320 to 3240)

(1.86 to 14.37)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

4.30

4.30

8.6

2700

11.98

48

 

 

(1.5 to 10.2)

(320 to 3250)

(1.86 to 14.42)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 units

10

10

10

2.87

2.87

2.87

8.6

2300

10.20

48

 

(2.0 to 10.4)

(380 to 2750)

(2.07 to 12.20)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

10

10

3.35

2.68

2.68

8.7

2360

10.47

48

 

 

(2.0 to 10.5)

(380 to 2760)

(2.07 to 12.24)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

10

10

3.59

2.61

2.61

8.8

2430

10.78

48

 

 

(2.0 to 10.6)

(380 to 2780)

(2.07 to 12.33)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

10

3.14

3.14

2.51

8.8

2430

10.78

48

 

 

(2.0 to 10.6)

(380 to 2780)

(2.07 to 12.33)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

10

3.34

3.03

2.43

8.8

2430

10.78

48

 

 

(2.0 to 10.6)

(380 to 2780)

(2.07 to 12.33)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

13

2.93

2.93

2.93

8.8

2430

10.78

48

 

 

(2.0 to 10.6)

(380 to 2780)

(2.07 to 12.33)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

10

3.26

3.26

2.37

8.9

2490

11.05

48

 

 

(2.0 to 10.7)

(380 to 2790)

(2.07 to 12.38)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

13

3.16

2.87

2.87

8.9

2490

11.05

48

 

 

(2.0 to 10.7)

(380 to 2790)

(2.07 to 12.38)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

13

3.09

3.09

2.81

9.0

2550

11.31

48

 

 

(2.0 to 10.8)

(380 to 2800)

(2.07 to 12.42)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The above specification values are those under the conditions that the indoor DB/WB=27/19°C and the outdoor DB/ WB=35/–°C.

Indoor unit 10 : RAS-M10UKV-E, 13 : RAS-M13UKV-E, 16 : RAS-M16UKV-E

– 18 –

Outdoor Unit : RAS-3M26YAV-E <Heating/240V>

Power

Operating

 

Indoor unit

 

Unit capacity (kW)

Heating

Power

Operating

Outdoor

supply

 

 

 

 

 

 

capacity

consumption

current

noise

status

A

B

C

A

B

C

(V)

(kW)

(W)

(A)

(dB)

 

 

 

 

 

 

 

 

 

 

 

 

 

240

1 unit

10

4.0

4.0

1500

6.38

48

(0.8 to 5.2)

(300 to 1980)

(1.71 to 8.42)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

5.0

5.0

2050

8.72

48

 

 

(0.8 to 6.5)

(310 to 2750)

(1.77 to 11.69)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

5.5

5.5

2400

10.20

48

 

 

(0.8 to 6.9)

(310 to 3000)

(1.77 to 12.76)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 units

10

10

3.60

3.60

7.2

2050

8.72

48

 

(1.5 to 10.0)

(320 to 3200)

(1.78 to 13.61)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

10

4.22

3.38

7.6

2240

9.52

48

 

 

(1.5 to 10.1)

(320 to 3210)

(1.78 to 13.65)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

10

4.57

3.33

7.9

2380

10.12

48

 

 

(1.5 to 10.1)

(320 to 3230)

(1.78 to 13.73)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

3.95

3.95

7.9

2380

10.12

48

 

 

(1.5 to 10.1)

(320 to 3230)

(1.78 to 13.73)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

4.35

3.95

8.3

2560

10.88

48

 

 

(1.5 to 10.2)

(320 to 3240)

(1.78 to 13.78)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

4.30

4.30

8.6

2700

11.48

48

 

 

(1.5 to 10.2)

(320 to 3250)

(1.78 to 13.82)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 units

10

10

10

2.87

2.87

2.87

8.6

2300

9.78

48

 

(2.0 to 10.4)

(380 to 2750)

(1.98 to 11.69)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

10

10

3.35

2.68

2.68

8.7

2360

10.03

48

 

 

(2.0 to 10.5)

(380 to 2760)

(1.98 to 11.73)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

10

10

3.59

2.61

2.61

8.8

2430

10.33

48

 

 

(2.0 to 10.6)

(380 to 2780)

(1.98 to 11.82)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

10

3.14

3.14

2.51

8.8

2430

10.33

48

 

 

(2.0 to 10.6)

(380 to 2780)

(1.98 to 11.82)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

10

3.34

3.03

2.43

8.8

2430

10.33

48

 

 

(2.0 to 10.6)

(380 to 2780)

(1.98 to 11.82)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

13

2.93

2.93

2.93

8.8

2430

10.33

48

 

 

(2.0 to 10.6)

(380 to 2780)

(1.98 to 11.82)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

10

3.26

3.26

2.37

8.9

2490

10.59

48

 

 

(2.0 to 10.7)

(380 to 2790)

(1.98 to 11.86)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

13

3.16

2.87

2.87

8.9

2490

10.59

48

 

 

(2.0 to 10.7)

(380 to 2790)

(1.98 to 11.86)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

13

3.09

3.09

2.81

9.0

2550

10.84

48

 

 

(2.0 to 10.8)

(380 to 2800)

(1.98 to 11.90)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The above specification values are those under the conditions that the indoor DB/WB=27/19°C and the outdoor DB/ WB=35/–°C.

Indoor unit 10 : RAS-M10UKV-E, 13 : RAS-M13UKV-E, 16 : RAS-M16UKV-E

– 19 –

Toshiba RAS-M13UKCV-E, RAS-3M26YAV-E, RAS-M13UKV-E, RAS-M16UKV-E, RAS-M10UKV-E SERVICE MANUAL

1-2-1. Operation Characteristic Curve

 

 

<Cooling>

 

 

 

 

 

 

 

 

16

• Conditions

 

 

 

 

 

 

 

14

 

 

 

 

 

 

 

Indoor

: DB27˚C/WB19˚C

 

220V

 

 

 

 

Outdoor

: DB35˚C

 

 

 

 

 

12

Air flow

: High

 

 

 

 

 

 

 

 

Pipe length: 5m x 4

 

 

 

 

 

(A)

10

4 units operating

 

 

 

 

240V

 

 

 

 

 

 

 

 

 

Current

8

 

 

 

 

 

 

 

 

 

 

 

 

230V

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

0

10

20

30

40

50

60

70

80

 

0

Inverter output frequency (rps)

<Heating>

 

 

 

 

 

 

 

 

 

 

14

• Conditions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

220V

 

 

 

12

Indoor

 

: DB20˚C

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor

: DB7˚C / WB6˚C

 

 

 

 

 

 

 

 

 

 

 

 

 

10

Air flow

 

: High

 

 

 

 

 

 

 

 

Pipe length: 5m x 4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(A)

8

4 units operating

 

 

 

 

 

240V

 

 

 

 

 

 

 

 

 

 

Current

 

 

 

 

 

 

 

 

 

6

 

 

 

 

 

 

230V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

0

10

20

30

40

50

60

70

80

90

100

 

0

Inverter output frequency (rps)

1-2-2. Capacity Variation Ratio According to Outdoor Temperature

Cooling capacity ratio (%)

110

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100

 

 

 

Current limited start

 

 

 

 

 

 

 

90

 

 

 

 

 

 

80

 

 

 

 

 

 

70

 

 

 

 

 

 

 

• Conditions

 

 

 

 

 

 

Indoor

: DB27˚C/WB19˚C

60

 

Indoor air flow : High

 

Pipe length

: 5m x 4

 

 

 

 

4 units operating

50

33

34

35

36

37

38

39

40

41

42

43

44

32

Outdoor temp. (˚C)

Heating capacity ratio (%)

110

 

 

 

• Conditions

 

100

Indoor

: DB20˚C

Air flow

: High

 

 

Pipe length

: 5m x 4

90

4 units operating

80

 

 

70

 

 

60

 

 

50 -10 -9 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8 9 10

Outdoor temp. (˚C)

1-2-3. Capacity Variation Ratio According to Pipe Length

 

110

 

 

 

 

 

 

 

 

(%)

105

 

Standard pipe length 20m

 

 

 

 

 

 

 

 

 

 

 

 

ratio

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

capacity

95

 

 

 

 

 

 

 

 

 

• Conditions

 

 

 

 

 

 

Coolimg

90

: DB27˚C/WB19˚C

 

 

 

 

Indoor

 

 

 

 

85

Outdoor

 

: DB35˚C

 

 

 

 

 

Indoor air flow : High

 

 

 

 

 

 

 

4 units operating

 

 

 

 

 

 

80

10

20

30

40

50

60

70

80

 

0

Total pipe length (m)

 

110

 

 

 

 

 

 

 

 

(%)

105

 

Standard pipe length 20m

 

 

 

 

 

 

 

 

 

 

 

 

ratio

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

capacity

95

 

 

 

 

 

 

 

 

 

• Conditions

 

 

 

 

 

 

Heating

90

: DB20˚C

 

 

 

 

 

 

Indoor

 

 

 

 

 

 

85

Outdoor

 

: DB7˚C/WB6˚C

 

 

 

 

Indoor air flow : High

 

 

 

 

 

 

 

4 units operating

 

 

 

 

 

 

80

10

20

30

40

50

60

70

80

 

0

Total pipe length (m)

– 20 –

1-3. Electrical Data

Outdoor Unit : RAS-4M27YAV-E

<Cooling>

 

 

 

 

 

 

 

 

System

 

 

 

Compressor

Fan motor FLA

Combination of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage range

Power supply

 

 

 

 

 

indoor unit operation

Hz

Volts-

MOCP

MSC

RLA

Indoor

Outdoor

 

 

 

 

 

 

 

 

 

Ph.

Min.

Max.

MCA

ICF

(Amps)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 unit

10

 

 

 

 

4.48

4.48

20

3.06

3.06

0.15 x 1 = 0.15

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

 

 

 

6.70

6.70

20

4.84

4.84

0.15 x 1 = 0.15

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

 

 

 

9.18

9.18

20

6.82

6.82

0.15 x 1 = 0.15

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 units

10

10

 

 

 

 

8.29

8.29

20

5.99

5.99

0.15 x 2 = 0.30

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

10

 

 

 

 

9.84

9.84

20

7.23

7.23

0.15 x 2 = 0.30

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

10

 

 

 

 

11.11

11.11

20

8.25

8.25

0.15 x 2 = 0.30

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

 

 

 

 

11.11

11.11

20

8.25

8.25

0.15 x 2 = 0.30

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

 

 

 

 

12.66

12.66

20

9.49

9.49

0.15 x 2 = 0.30

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

 

 

 

 

13.94

13.94

20

10.51

10.51

0.15 x 2 = 0.30

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 units

10

10

10

 

 

 

 

13.08

13.08

20

9.70

9.70

0.15 x 3 = 0.45

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

10

10

 

 

 

 

13.13

13.13

20

9.74

9.74

0.15 x 3 = 0.45

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

10

10

 

 

 

 

13.13

13.13

20

9.74

9.74

0.15 x 3 = 0.45

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

10

 

 

 

 

13.13

13.13

20

9.74

9.74

0.15 x 3 = 0.45

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

10

50 or 60

230–1

198

264

13.24

13.24

20

9.83

9.83

0.15 x 3 = 0.45

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

13

13.24

13.24

20

9.83

9.83

0.15 x 3 = 0.45

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

10

 

 

 

 

13.30

13.30

20

9.88

9.88

0.15 x 3 = 0.45

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

13

 

 

 

 

13.30

13.30

20

9.88

9.88

0.15 x 3 = 0.45

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

13

 

 

 

 

13.30

13.30

20

9.88

9.88

0.15 x 3 = 0.45

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

16

 

 

 

 

13.35

13.35

20

9.92

9.92

0.15 x 3 = 0.45

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4 units

10

10

10

10

 

 

 

 

13.31

13.31

20

9.77

9.77

0.15 x 4 = 0.60

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

10

10

10

 

 

 

 

13.31

13.31

20

9.77

9.77

0.15 x 4 = 0.60

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

10

10

10

 

 

 

 

13.59

13.59

20

9.99

9.99

0.15 x 4 = 0.60

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

10

10

 

 

 

 

13.59

13.59

20

9.99

9.99

0.15 x 4 = 0.60

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

10

10

 

 

 

 

13.59

13.59

20

9.99

9.99

0.15 x 4 = 0.60

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

13

10

 

 

 

 

13.59

13.59

20

9.99

9.99

0.15 x 4 = 0.60

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

13

10

 

 

 

 

13.59

13.59

20

9.99

9.99

0.15 x 4 = 0.60

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

13

13

 

 

 

 

13.59

13.59

20

9.99

9.99

0.15 x 4 = 0.60

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

10

10

 

 

 

 

13.59

13.59

20

9.99

9.99

0.15 x 4 = 0.60

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE :

Model of Indoor unit 10 : RAS-M10UKV-E, 13 : RAS-M13UKV-E, 16 : RAS-M16UKV-E

MCA

: Minimum Circuit Amps.

 

 

 

 

ICF

: Maximum Instantaneous Current Flow (Equivalent to MCA in case of inverter air conditioner)

 

 

MOCP : Maximum Overcurrent Protection (Fuse only)

 

 

 

 

MSC

: Maximum Starting Current

 

 

DB

WB

Indoor temp. (°C)

 

27

19

FLA

: Full Load Amps.

 

Outdoor temp. (°C)

 

35

RLA

: Rated Load Amps. RLA under conditions on the right.

 

– 21 –

Outdoor Unit : RAS-4M27YAV-E

<Heating>

 

 

 

 

 

 

 

 

System

 

 

 

Compressor

Fan motor FLA

Combination of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage range

Power supply

 

 

 

 

 

indoor unit operation

Hz

Volts-

MOCP

MSC

RLA

Indoor

Outdoor

 

 

 

 

 

 

 

 

 

Ph.

Min.

Max.

MCA

ICF

(Amps)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 unit

10

 

 

 

 

7.88

7.88

20

5.78

5.78

0.15 x 1 = 0.15

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

 

 

 

11.20

11.20

20

8.44

8.44

0.15 x 1 = 0.15

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

 

 

 

13.15

13.15

20

10.00

10.00

0.15 x 1 = 0.15

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 units

10

10

 

 

 

 

11.45

11.45

20

8.52

8.52

0.15 x 2 = 0.30

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

10

 

 

 

 

12.66

12.66

20

9.49

9.49

0.15 x 2 = 0.30

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

10

 

 

 

 

13.55

13.55

20

10.20

10.20

0.15 x 2 = 0.30

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

 

 

 

 

13.55

13.55

20

10.20

10.20

0.15 x 2 = 0.30

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

 

 

 

 

14.78

14.78

20

11.18

11.18

0.15 x 2 = 0.30

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

 

 

 

 

15.66

15.66

20

11.89

11.89

0.15 x 2 = 0.30

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 units

10

10

10

 

 

 

 

12.51

12.51

20

9.25

9.25

0.15 x 3 = 0.45

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

10

10

 

 

 

 

12.80

12.80

20

9.48

9.48

0.15 x 3 = 0.45

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

10

10

 

 

 

 

12.80

12.80

20

9.48

9.48

0.15 x 3 = 0.45

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

10

 

 

 

 

12.80

12.80

20

9.48

9.48

0.15 x 3 = 0.45

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

10

50 or 60

230–1

198

264

13.08

13.08

20

9.70

9.70

0.15 x 3 = 0.45

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

13

13.08

13.08

20

9.70

9.70

0.15 x 3 = 0.45

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

10

 

 

 

 

13.35

13.35

20

9.92

9.92

0.15 x 3 = 0.45

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

13

 

 

 

 

13.35

13.35

20

9.92

9.92

0.15 x 3 = 0.45

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

13

 

 

 

 

13.35

13.35

20

9.92

9.92

0.15 x 3 = 0.45

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

16

 

 

 

 

13.63

13.63

20

10.14

10.14

0.15 x 3 = 0.45

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4 units

10

10

10

10

 

 

 

 

11.38

11.38

20

8.22

8.22

0.15 x 4 = 0.60

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

10

10

10

 

 

 

 

11.38

11.38

20

8.22

8.22

0.15 x 4 = 0.60

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

10

10

10

 

 

 

 

12.20

12.20

20

8.88

8.88

0.15 x 4 = 0.60

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

10

10

 

 

 

 

12.20

12.20

20

8.88

8.88

0.15 x 4 = 0.60

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

10

10

 

 

 

 

12.20

12.20

20

8.88

8.88

0.15 x 4 = 0.60

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

13

10

 

 

 

 

12.20

12.20

20

8.88

8.88

0.15 x 4 = 0.60

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

13

10

 

 

 

 

12.20

12.20

20

8.88

8.88

0.15 x 4 = 0.60

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

13

13

 

 

 

 

12.20

12.20

20

8.88

8.88

0.15 x 4 = 0.60

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

10

10

 

 

 

 

12.20

12.20

20

8.88

8.88

0.15 x 4 = 0.60

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE :

Model of Indoor unit 10 : RAS-M10UKV-E, 13 : RAS-M13UKV-E, 16 : RAS-M16UKV-E

MCA

: Minimum Circuit Amps.

 

 

 

 

ICF

: Maximum Instantaneous Current Flow (Equivalent to MCA in case of inverter air conditioner)

 

 

MOCP : Maximum Overcurrent Protection (Fuse only)

 

 

 

 

MSC

: Maximum Starting Current

 

 

DB

WB

Indoor temp. (°C)

 

20

FLA

: Full Load Amps.

 

Outdoor temp. (°C)

 

7

6

RLA

: Rated Load Amps. RLA under conditions on the right.

 

– 22 –

Outdoor Unit : RAS-4M27YACV-E <Cooling>

 

 

 

 

 

 

 

 

System

 

 

 

Compressor

Fan motor FLA

Combination of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage range

Power supply

 

 

 

 

 

indoor unit operation

Hz

Volts-

MOCP

MSC

RLA

Indoor

Outdoor

 

 

 

 

 

 

 

 

 

Ph.

Min.

Max.

MCA

ICF

(Amps)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 unit

10

 

 

 

 

4.48

4.48

20

3.06

3.06

0.15 x 1 = 0.15

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

 

 

 

6.70

6.70

20

4.84

4.84

0.15 x 1 = 0.15

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

 

 

 

9.18

9.18

20

6.82

6.82

0.15 x 1 = 0.15

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 units

10

10

 

 

 

 

8.29

8.29

20

5.99

5.99

0.15 x 2 = 0.30

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

10

 

 

 

 

9.84

9.84

20

7.23

7.23

0.15 x 2 = 0.30

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

10

 

 

 

 

11.11

11.11

20

8.25

8.25

0.15 x 2 = 0.30

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

 

 

 

 

11.11

11.11

20

8.25

8.25

0.15 x 2 = 0.30

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

 

 

 

 

12.66

12.66

20

9.49

9.49

0.15 x 2 = 0.30

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

 

 

 

 

13.94

13.94

20

10.51

10.51

0.15 x 2 = 0.30

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 units

10

10

10

 

 

 

 

13.08

13.08

20

9.70

9.70

0.15 x 3 = 0.45

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

10

10

 

 

 

 

13.13

13.13

20

9.74

9.74

0.15 x 3 = 0.45

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

10

10

 

 

 

 

13.13

13.13

20

9.74

9.74

0.15 x 3 = 0.45

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

10

 

 

 

 

13.13

13.13

20

9.74

9.74

0.15 x 3 = 0.45

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

10

50 or 60

230–1

198

264

13.24

13.24

20

9.83

9.83

0.15 x 3 = 0.45

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

13

13.24

13.24

20

9.83

9.83

0.15 x 3 = 0.45

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

10

 

 

 

 

13.30

13.30

20

9.88

9.88

0.15 x 3 = 0.45

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

13

 

 

 

 

13.30

13.30

20

9.88

9.88

0.15 x 3 = 0.45

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

13

 

 

 

 

13.30

13.30

20

9.88

9.88

0.15 x 3 = 0.45

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

16

 

 

 

 

13.35

13.35

20

9.92

9.92

0.15 x 3 = 0.45

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4 units

10

10

10

10

 

 

 

 

13.31

13.31

20

9.77

9.77

0.15 x 4 = 0.60

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

10

10

10

 

 

 

 

13.31

13.31

20

9.77

9.77

0.15 x 4 = 0.60

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

10

10

10

 

 

 

 

13.59

13.59

20

9.99

9.99

0.15 x 4 = 0.60

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

10

10

 

 

 

 

13.59

13.59

20

9.99

9.99

0.15 x 4 = 0.60

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

10

10

 

 

 

 

13.59

13.59

20

9.99

9.99

0.15 x 4 = 0.60

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

13

10

 

 

 

 

13.59

13.59

20

9.99

9.99

0.15 x 4 = 0.60

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

13

10

 

 

 

 

13.59

13.59

20

9.99

9.99

0.15 x 4 = 0.60

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

13

13

 

 

 

 

13.59

13.59

20

9.99

9.99

0.15 x 4 = 0.60

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

10

10

 

 

 

 

13.59

13.59

20

9.99

9.99

0.15 x 4 = 0.60

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE :

Model of Indoor unit 10 : RAS-M10UKCV-E, 13 : RAS-M13UKCV-E, 16 : RAS-M16UKCV-E

MCA

: Minimum Circuit Amps.

 

 

 

 

ICF

: Maximum Instantaneous Current Flow (Equivalent to MCA in case of inverter air conditioner)

 

 

MOCP : Maximum Overcurrent Protection (Fuse only)

 

 

 

 

MSC

: Maximum Starting Current

 

 

DB

WB

 

 

 

 

Indoor temp. (°C)

 

27

19

FLA

: Full Load Amps.

 

Outdoor temp. (°C)

 

35

RLA

: Rated Load Amps. RLA under conditions on the right.

 

– 23 –

Outdoor Unit : RAS-3M26YAV-E <Cooling>

 

 

 

 

 

 

 

System

 

 

 

Compressor

Fan motor FLA

Combination of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage range

Power supply

 

 

 

 

 

indoor unit operation

Hz

Volts-

MOCP

MSC

RLA

Indoor

Outdoor

 

 

 

 

 

 

 

 

Ph.

Min.

Max.

MCA

ICF

(Amps)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 unit

10

 

 

 

 

4.48

4.48

20

3.06

3.06

0.15 x 1 = 0.15

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

 

 

 

6.70

6.70

20

4.84

4.84

0.15 x 1 = 0.15

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

 

 

 

9.18

9.18

20

6.82

6.82

0.15 x 1 = 0.15

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 units

10

10

 

 

 

 

8.29

8.29

20

5.99

5.99

0.15 x 2 = 0.30

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

10

 

 

 

 

9.84

9.84

20

7.23

7.23

0.15 x 2 = 0.30

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

10

 

 

 

 

11.11

11.11

20

8.25

8.25

0.15 x 2 = 0.30

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

 

 

 

 

11.11

11.11

20

8.25

8.25

0.15 x 2 = 0.30

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

 

 

 

 

12.66

12.66

20

9.49

9.49

0.15 x 2 = 0.30

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

50 or 60

230–1

198

264

13.94

13.94

20

10.51

10.51

0.15 x 2 = 0.30

0.5

 

 

 

 

 

 

 

 

 

 

 

3 units

10

10

10

12.13

12.13

20

8.94

8.94

0.15 x 3 = 0.45

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

10

10

 

 

 

 

12.13

12.13

20

8.94

8.94

0.15 x 3 = 0.45

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

10

10

 

 

 

 

12.13

12.13

20

8.94

8.94

0.15 x 3 = 0.45

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

10

 

 

 

 

12.13

12.13

20

8.94

8.94

0.15 x 3 = 0.45

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

10

 

 

 

 

12.24

12.24

20

9.03

9.03

0.15 x 3 = 0.45

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

13

 

 

 

 

12.24

12.24

20

9.03

9.03

0.15 x 3 = 0.45

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

10

 

 

 

 

12.24

12.24

20

9.03

9.03

0.15 x 3 = 0.45

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

13

 

 

 

 

12.24

12.24

20

9.03

9.03

0.15 x 3 = 0.45

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

13

 

 

 

 

12.24

12.24

20

9.03

9.03

0.15 x 3 = 0.45

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE :

Model of Indoor unit 10 : RAS-M10UKV-E, 13 : RAS-M13UKV-E, 16 : RAS-M16UKV-E

MCA

: Minimum Circuit Amps.

ICF

: Maximum Instantaneous Current Flow (Equivalent to MCA in case of inverter air conditioner)

MOCP : Maximum Overcurrent Protection (Fuse only)

MSC

: Maximum Starting Current

FLA

: Full Load Amps.

RLA

: Rated Load Amps. RLA under conditions on the right.

 

 

DB

WB

Indoor temp.

(°C)

27

19

Outdoor temp.

(°C)

35

– 24 –

Outdoor Unit : RAS-3M26YAV-E <Heating>

 

 

 

 

 

 

 

System

 

 

 

Compressor

Fan motor FLA

Combination of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage range

Power supply

 

 

 

 

 

indoor unit operation

Hz

Volts-

MOCP

MSC

RLA

Indoor

Outdoor

 

 

 

 

 

 

 

 

Ph.

Min.

Max.

MCA

ICF

(Amps)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 unit

10

 

 

 

 

8.15

8.15

20

6.00

6.00

0.15 x 1 = 0.15

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

 

 

 

11.20

11.20

20

8.44

8.44

0.15 x 1 = 0.15

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

 

 

 

13.15

13.15

20

10.00

10.00

0.15 x 1 = 0.15

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 units

10

10

 

 

 

 

11.16

11.16

20

8.29

8.29

0.15 x 2 = 0.30

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

10

 

 

 

 

12.23

12.23

20

9.14

9.14

0.15 x 2 = 0.30

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

10

 

 

 

 

13.00

13.00

20

9.76

9.76

0.15 x 2 = 0.30

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

 

 

 

 

13.00

13.00

20

9.76

9.76

0.15 x 2 = 0.30

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

 

 

 

 

14.00

14.00

20

10.56

10.56

0.15 x 2 = 0.30

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

50 or 60

230–1

198

264

14.78

14.78

20

11.18

11.18

0.15 x 2 = 0.30

0.5

 

 

 

 

 

 

 

 

 

 

 

3 units

10

10

10

12.51

12.51

20

9.25

9.25

0.15 x 3 = 0.45

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

10

10

 

 

 

 

12.85

12.85

20

9.52

9.52

0.15 x 3 = 0.45

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

10

10

 

 

 

 

13.24

13.24

20

9.83

9.83

0.15 x 3 = 0.45

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

10

 

 

 

 

13.24

13.24

20

9.83

9.83

0.15 x 3 = 0.45

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

10

 

 

 

 

13.24

13.24

20

9.83

9.83

0.15 x 3 = 0.45

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

13

13

 

 

 

 

13.24

13.24

20

9.83

9.83

0.15 x 3 = 0.45

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

10

 

 

 

 

13.58

13.58

20

10.10

10.10

0.15 x 3 = 0.45

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

13

13

 

 

 

 

13.58

13.58

20

10.10

10.10

0.15 x 3 = 0.45

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

16

13

 

 

 

 

13.90

13.90

20

10.36

10.36

0.15 x 3 = 0.45

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE :

Model of Indoor unit 10 : RAS-M10UKV-E, 13 : RAS-M13UKV-E, 16 : RAS-M16UKV-E

MCA

: Minimum Circuit Amps.

ICF

: Maximum Instantaneous Current Flow (Equivalent to MCA in case of inverter air conditioner)

MOCP : Maximum Overcurrent Protection (Fuse only)

MSC

: Maximum Starting Current

FLA

: Full Load Amps.

RLA

: Rated Load Amps. RLA under conditions on the right.

 

 

DB

WB

Indoor temp.

(°C)

20

Outdoor temp.

(°C)

7

6

– 25 –

2. REFRIGERANT R410A

This air conditioner adopts the new refrigerant HFC (R410A) which does not damage the ozone layer.

The working pressure of the new refrigerant R410A is 1.6 times higher than conventional refrigerant (R22). The refrigerating oil is also changed in accordance with change of refrigerant, so be careful that water, dust, and existing refrigerant or refrigerating oil are not entered in the refrigerant cycle of the air conditioner using the new refrigerant during installation work or servicing time.

The next section describes the precautions for air conditioner using the new refrigerant. Conforming to contents of the next section together with the general cautions included in this manual, perform the correct and safe work.

2-1. Safety During Installation/Servicing

As R410A’s pressure is about 1.6 times higher than that of R22, improper installation/servicing may cause a serious trouble. By using tools and materials exclusive for R410A, it is necessary to carry out installation/servicing safely while taking the following precautions into consideration.

(1)Never use refrigerant other than R410A in an air conditioner which is designed to operate with R410A.

If other refrigerant than R410A is mixed, pressure in the refrigeration cycle becomes abnormally high, and it may cause personal injury, etc. by a rupture.

(2)Confirm the used refrigerant name, and use tools and materials exclusive for the refrigerant R410A.

The refrigerant name R410A is indicated on the visible place of the outdoor unit of the air conditioner using R410A as refrigerant. To prevent mischarging, the diameter of the service port differs from that of R22.

(3)If a refrigeration gas leakage occurs during installation/servicing, be sure to ventilate fully.

If the refrigerant gas comes into contact with fire, a poisonous gas may occur.

(4)When installing or removing an air conditioner, do not allow air or moisture to remain in the refrigeration cycle. Otherwise, pressure in the refrigeration cycle may become abnormally high so that a rupture or personal injury may be caused.

(5)After completion of installation work, check to make sure that there is no refrigeration gas leakage.

If the refrigerant gas leaks into the room, coming into contact with fire in the fan-driven heater, space heater, etc., a poisonous gas may occur.

(6)When an air conditioning system charged with a large volume of refrigerant is installed in a small room, it is necessary to exercise care so that, even when refrigerant leaks, its concentration does not exceed the marginal level.

If the refrigerant gas leakage occurs and its concentration exceeds the marginal level, an oxygen starvation accident may result.

(7)Be sure to carry out installation or removal according to the installation manual.

Improper installation may cause refrigeration trouble, water leakage, electric shock, fire, etc.

(8)Unauthorized modifications to the air conditioner may be dangerous. If a breakdown occurs please call a qualified air conditioner technician or electrician.

Improper repair’s may result in water leakage, electric shock and fire, etc.

2-2. Refrigerant Piping Installation

2-2-1. Piping Materials and Joints Used

For the refrigerant piping installation, copper pipes and joints are mainly used. Copper pipes and joints suitable for the refrigerant must be chosen and installed. Furthermore, it is necessary to use clean copper pipes and joints whose interior surfaces are less affected by contaminants.

(1)Copper Pipes

It is necessary to use seamless copper pipes which are made of either copper or copper alloy and it is desirable that the amount of residual oil is less than 40 mg/10 m. Do not use copper pipes having a collapsed, deformed or discolored portion (especially on the interior surface).

Otherwise, the expansion valve or capillary tube may become blocked with contaminants.

As an air conditioner using R410A incurs pressure higher than when using R22, it is necessary to choose adequate materials.

Thicknesses of copper pipes used with R410A are as shown in Table 2-2-1. Never use copper pipes thinner than 0.8 mm even when it is available on the market.

– 26 –

Table 2-2-1 Thicknesses of annealed copper pipes

 

 

 

Thickness (mm)

 

 

 

 

Nominal diameter

Outer diameter (mm)

R410A

R22

 

 

 

 

1/4

6.35

0.80

0.80

 

 

 

 

3/8

9.52

0.80

0.80

 

 

 

 

1/2

12.70

0.80

0.80

 

 

 

 

(2)Joints

For copper pipes, flare joints or socket joints are used. Prior to use, be sure to remove all contaminants.

a)Flare Joints

Flare joints used to connect the copper pipes cannot be used for pipings whose outer diameter exceeds 20 mm. In such a case, socket joints can be used.

Sizes of flare pipe ends, flare joint ends and flare nuts are as shown in Tables 2-2-3 to 2- 2-6 below.

b)Socket Joints

Socket joints are such that they are brazed for connections, and used mainly for thick pipings whose diameter is larger than 20 mm.

Thicknesses of socket joints are as shown in Table 2-2-2.

Table 2-2-2 Minimum thicknesses of socket joints

Nominal diameter

Reference outer diameter of

Minimum joint thickness (mm)

copper pipe jointed (mm)

 

 

 

 

 

1/4

6.35

0.50

 

 

 

3/8

9.52

0.60

 

 

 

1/2

12.70

0.70

 

 

 

2-2-2. Processing of Piping Materials

When performing the refrigerant piping installation, care should be taken to ensure that water or dust does not enter the pipe interior, that no other oil other than lubricating oils used in the installed air conditioner is used, and that refrigerant does not leak. When using lubricating oils in the piping processing, use such lubricating oils whose water content has been removed. When stored, be sure to seal the container with an airtight cap or any other cover.

(1)Flare Processing Procedures and Precautions

a)Cutting the Pipe

By means of a pipe cutter, slowly cut the pipe so that it is not deformed.

b)Removing Burrs and Chips

If the flared section has chips or burrs, refrigerant leakage may occur. Carefully remove all burrs and clean the cut surface before installation.

– 27 –

c)Insertion of Flare Nut

d)Flare Processing

Make certain that a clamp bar and copper pipe have been cleaned.

By means of the clamp bar, perform the flare processing correctly.

Use either a flare tool for R410A or conventional flare tool.

Flare processing dimensions differ according to the type of flare tool. When using a conventional flare tool, be sure to secure “dimension A” by using a gauge for size adjustment.

Ø D A

Fig. 2-2-1 Flare processing dimensions

Table 2-2-3 Dimensions related to flare processing for R410A

 

Outer

 

 

A (mm)

 

Nominal

Thickness

 

 

 

diameter

Flare tool for

Conventional flare tool

diameter

(mm)

(mm)

 

 

 

 

R410A clutch type

Clutch type

Wing nut type

 

 

 

 

 

 

 

 

 

 

 

 

 

1/4

6.35

0.8

0 to 0.5

1.0 to 1.5

1.5 to 2.0

 

 

 

 

 

 

3/8

9.52

0.8

0 to 0.5

1.0 to 1.5

1.5 to 2.0

 

 

 

 

 

 

1/2

12.70

0.8

0 to 0.5

1.0 to1.5

2.0 to 2.5

 

 

 

 

 

 

Table 2-2-4 Dimensions related to flare processing for R22

 

Outer

 

 

A (mm)

 

Nominal

Thickness

 

 

 

diameter

Flare tool for

Conventional flare tool

diameter

(mm)

(mm)

 

 

 

 

R22 clutch type

Clutch type

Wing nut type

 

 

 

 

 

 

 

 

 

 

 

 

 

1/4

6.35

0.8

0 to 0.5

0.5 to 1.0

1.0 to 1.5

 

 

 

 

 

 

3/8

9.52

0.8

0 to 0.5

0.5 to 1.0

1.0 to 1.5

 

 

 

 

 

 

1/2

12.70

0.8

0 to 0.5

0.5 to1.0

1.5 to 2.0

 

 

 

 

 

 

Table 2-2-5 Flare and flare nut dimensions for R410A

Nominal

Outer diameter

Thickness

 

Dimension (mm)

 

Flare nut

 

 

 

 

width

diameter

(mm)

(mm)

A

B

C

D

(mm)

 

 

 

 

 

 

 

 

 

 

 

1/4

6.35

0.8

9.1

9.2

6.5

13

17

 

 

 

 

 

 

 

 

3/8

9.52

0.8

13.2

13.5

9.7

20

22

 

 

 

 

 

 

 

 

1/2

12.70

0.8

16.6

16.0

12.9

23

26

 

 

 

 

 

 

 

 

– 28 –

Table 2-2-6 Flare and flare nut dimensions for R22

Nominal

Outer diameter

Thickness

 

Dimension (mm)

 

Flare nut

 

 

 

 

width

diameter

(mm)

(mm)

A

B

C

D

(mm)

 

 

 

 

 

 

 

 

 

 

 

1/4

6.35

0.8

9.0

9.2

6.5

13

17

 

 

 

 

 

 

 

 

3/8

9.52

0.8

13.0

13.5

9.7

20

22

 

 

 

 

 

 

 

 

1/2

12.70

0.8

16.2

16.0

12.9

20

24

 

 

 

 

 

 

 

 

to46˚ 45˚

B A

C D

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

43˚

to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

45˚

 

Fig. 2-2-2 Relations between flare nut and flare seal surface

(2)Flare Connecting Procedures and Precautions

a)Make sure that the flare and union portions do not have any scar or dust, etc.

b)Correctly align the processed flare surface with the union axis.

c)Tighten the flare with designated torque by means of a torque wrench. The tightening torque for R410A is the same as that for conventional R22. Incidentally, when the torque is weak, the gas leakage may occur.

When it is strong, the flare nut may crack and may be made non-removable. When choosing the tightening torque, comply with values designated by manufacturers. Table 2-2-7 shows reference values.

Note :

When applying oil to the flare surface, be sure to use oil designated by the manufacturer. If any other oil is

used, the lubricating oils may deteriorate and cause the compressor to burn out.

Table 2-2-7 Tightening torque of flare for R410A [Reference values]

Nominal

Outer diameter

Tightening torque

Tightening torque of torque

wrenches available on the market

diameter

(mm)

N•m (kgf•cm)

N•m (kgf•cm)

 

 

 

 

 

 

 

1/4

6.35

14 to 18 (140 to 180)

16 (160), 18 (180)

 

 

 

 

3/8

9.52

33 to 42 (330 to 420)

42 (420)

 

 

 

 

1/2

12.70

50 to 62 (500 to 620)

55 (550)

 

 

 

 

– 29 –

2-3. Tools

2-3-1. Required Tools

The service port diameter of packed valve of the outdoor unit in the air conditioner using R410A is changed to prevent mixing of other refrigerant. To reinforce the pressure-resisting strength, flare processing dimensions and opposite side dimension of flare nut (For Ø12.7 copper pipe) of the refrigerant piping are lengthened.

The used refrigerating oil is changed, and mixing of oil may cause a trouble such as generation of sludge, clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types.

(1)Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22))

(2)Tools exclusive for R410A, but can be also used for conventional refrigerant (R22)

(3)Tools commonly used for R410A and for conventional refrigerant (R22)

The table below shows the tools exclusive for R410A and their interchangeability.

Tools exclusive for R410A (The following tools for R410A are required.)

Tools whose specifications are changed for R410A and their interchangeability

 

 

 

 

R410A

Conventional air

 

 

 

air conditioner installation

conditioner installation

No.

Used tool

Usage

 

 

 

Existence of

Whether conventional

Whether new equipment

 

 

 

new equipment

can be used with

 

 

 

equipment can be used

 

 

 

for R410A

conventional refrigerant

 

 

 

 

 

 

 

 

 

 

 

Flare tool

Pipe flaring

Yes

* (Note 1)

 

Copper pipe gauge for

Flaring by conventional

 

* (Note 1)

* (Note 1)

adjusting projection

Yes

flare tool

 

margin

 

 

 

 

 

Torque wrench

Connection of flare nut

Yes

×

×

 

(For Ø12.7)

 

 

 

 

 

 

Gauge manifold

Evacuating, refrigerant

Yes

×

×

 

 

charge, run check, etc.

 

Charge hose

 

 

 

 

 

 

 

 

 

 

 

Vacuum pump adapter

Vacuum evacuating

Yes

×

 

 

 

 

 

 

 

Electronic balance for

Refrigerant charge

Yes

×

refrigerant charging

 

 

 

 

 

 

 

Refrigerant cylinder

Refrigerant charge

Yes

×

×

 

Leakage detector

Gas leakage check

Yes

×

 

Charging cylinder

Refrigerant charge

(Note 2)

×

×

 

 

 

 

 

 

(Note 1) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary.

(Note 2) Charging cylinder for R410A is being currently developed.

General tools (Conventional tools can be used.)

In addition to the above exclusive tools, the following equipments which serve also for R22 are necessary. as the general tools.

(1)

Vacuum pump

(4)

Reamer

(9) Hole core drill (Ø65)

 

Use vacuum pump by

(5)

Pipe bender

(10) Hexagon wrench

 

attaching vacuum pump adapter.

(6)

Level vial

(Opposite side 4mm)

(2)

Torque wrench (For Ø6.35)

 

(7)

Screwdriver (+, –)

(11) Tape measure

(3)

Pipe cutter

(8)

Spanner or Monkey wrench

(12) Metal saw

 

 

 

Also prepare the following equipments for other installation method and run check.

(1)

Clamp meter

(3)

Insulation resistance tester

(2)

Thermometer

(4)

Electroscope

– 30 –