Quick Setup Guide
tekmarNet®2 House Control 400
HVAC Systems
1. Location 2. Install Junction Box
400 400
OR
3. Size Transformer
400_Q
02/14
Replaces: 01/14
Zone
1234
Thermostat Load
Zone Valve Load
Total Zone Load
+ ++++
4. Install Sensors
Outdoor Sensor
Sensor with bottom
entry wiring
Universal
Sensor 082
Pipe Sensors
Sensor with rear
entry wiring
Retaining Clip
Sensor mounted
onto 2" x 4"
electrical box
Floating
Action (VA)
Control
Load (VA)
2
5. Line Voltage Wiring
Boil
DHW
N
(black)
(black)
(red)
L
Boil System Pump
DHW Pump
Pump Power L
Transformer
must exceed:
VA
Strip wires
1/2 inch (13 mm).
Installed wires are
not removable.
12-18 AWG
A Watts Water Technologies Company
Sensor Well
G
N
L
to pump grounds
115 V (ac
1
© 2014 400_Q - 02/14
6. Install Enclosure
Expansion
tN4 Boil
CtN4
Modulating
Boiler
—+
2
1
R
C
L
N
Menu
House Control 400
Item
+
ComBoil Out DHW
VlvC VlvC VlvC
Zone 3Zone 1 Zone 2 Zone 4
VlvC
Com
Zone 1 Zone 2 Zone 3 Zone 4
tN2 tN2 tN2 tN2 tN2 tN2 tN2 tN2
Sensors - No Power
Call Call
tN4 C
Mod dc/mA Boil Exp.
Setpoint DHW
RC
Input Power
H8005D
Use at least 167°F
(75°C) conductors
Stage 2Stage 1
7. Low Voltage Wiring
tekmarNet
®
2 Thermostats
Outdoor
Sensor
070
Boiler Supply
Sensor 082
DHW Tank
Sensor 082
Setpoint Call
DHW Call
from DHW
Tank Aquast at
(optional)
8. Install Cover
Zone Valves
Menu
Item
House Control 402
One or Two Stage
Boiler T-T
24 V (ac) Transformer 009
tekmarNet®4
Expansion to
Wiring Centers,
Timers, or
User Switch
A Watts Water Technologies Company
2
© 2014 400_Q - 02/14
9. User Interface
Display
Symbols
Calls
Pumps
Menu Field
Displays the
current menu
VIEW
ADJUST
Status Fields
Displays the current
status of the control’s
inputs, outputs and
operation. Most symbols
in the status field are
only visible when the
VIEW Menu is selected
CALLS
Displays any call for heat the control is
receiving.
PUMPS
Displays any pump currently operating.
MONITOR
MAXMIN
Calls
Boil Exp
DHW Setp
Pumps WWSD Saving
Boil System
Zones
DHW Var 1 2 3 4
WWSD
°F°C
minhr
sec%
Item Field
Displays the name
of the selected item
min
sec
PM
hr
AM
Number Field
Displays the
current value of
the selected item
1 2
WWSD
Displays when the system is in Warm
Weather Shut Down.
°F, °C, %, HOURS, MINUTES, SECOND
Units of measurement for current number.
Zones
1 2 3 4
Saving
ZONES
Displays if an on-board zone is operating.
WARNING
Displays if an error exists on the system.
ENERGY SAVING INDICATOR
Displays when the system is saving
energy. See the Saving Indicator section.
10. Access Level
INST (Installer)
Default = INST
or USER
UNOCCUPIED
Indicates that a User Switch or Timer has
put the system into UnOccupied.
BOILER
Indicates that the boiler should be
heating.
MIN / MAX
MAXMIN
Press menu button until the Toolbox Menu is displayed. Press
item button to locate the access level setting.
ACCESS LEVEL
Selects the Access Level of the control, which determines the Menu items
available. USER provides the most limited level of access and shows
the fewest possible items.
When set to USER, all thermostats are locked and the number of thermostat
settings available are reduced.
Displays when an operating temperature
reaches a minimum or maximum value.
A Watts Water Technologies Company
3
© 2014 400_Q - 02/14
11. Critical Settings
Press menu button until the Adjust Menu is displayed. Press item button
to locate the desired setting.
Item Field Range Access Description Set to
ADJUST
-60 to 45°F
(-51.0 to 7.0°C)
Default = 10°F
(-12.0°C)
EMS2,
EMS1,
4-20
0-10,
2STG,
1STG
Default = 1STG
70 to 200°F
(21.0 to 93.5°C)
Default = 180
°F
(82.0°C)
Installer
Installer
Installer
OUTDOOR DESIGN
Typically set to the temperature of the coldest day of
the year. The outdoor air temperature used in the boiler
heating curve is used to determine the boiler target
temperature.
BOILER TYPE
The type of boiler connected to the control.
1STG = single one-stage on-off boiler
2STG = single two-stage on-off boiler
0-10 = 0-10 V (dc) modulating boiler
4-20 = 4-20 mA modulating boiler
EMS1 = tekmar boiler staging controls
EMS2 = Viessmann modulating boilers with
OpenTherm
BOILER DESIGN
The supply water temperature required for the boiler
zones to heat the building on the typical coldest day
of the year. Recommendations:
High mass radiant floor = 120°F (50°C)
Low mass radiant floor = 140°F (60°C)
Fancoil or air handling unit = 190°F (90°C)
Copper fin-tube convector = 180°F (80°C)
Radiators = 160°F (70°C)
Low profile baseboard = 150°F (65°C)
tekmar Control Systems Ltd., A Watts Water Technologies Company.
Vernon, B.C. Canada V1B 3K4, 250-545-7749, Fax. 250-545-0650 Web Site: www.tekmarControls.com
Product design, software and literature are Copyright ©2014 by
tekmar Control Systems Ltd.,
A Watts Water Technologies Company
Head Offi ce: 5100 Silver Star Road,
4
All specifications are subject to change without notice.
Printed in Canada. 400_Q - 02/14.