Mitsubishi PCFY-40VGM, PCFY-63VGM, PCFY-100VGM, PCFY-125VGM Service Manual

0 (0)

1997

SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS

No. OC122

REVISED EDITION-A

TECHNICAL & SERVICE MANUAL

Series PCFY Ceiling Suspended

<Indoor unit>

Models PCFY-40VGM

PCFY-63VGM

PCFY-100VGM

PCFY-125VGM

 

CONTENTS

 

1.

FEATURES ···········································2

 

2. PART NAMES AND FUNCTIONS ········4

 

3.

SPECIFICATION···································6

 

4. OUTLINES AND DIMENSIONS············8

 

5.

WIRING DIAGRAM·····························12

 

6. REFRIGERANT SYSTEM DIAGRAM ···13

 

7. TROUBLE SHOOTING·······················14

INDOOR UNIT

8. DISASSEMBLY PROCEDURE···········19

9.

PARTS LIST········································23

 

Revision

Parts List has been partially modified.

Please destroy OC122.

1 FEATURES

Series PCFY Ceiling Suspended

Indoor unit

Models

Cooling capacity / Heating capacity

 

 

W

Kcal/h

 

PCFY-40VGM

4,700/5,200

4,000/4,500

PCFY-63VGM

7,300/8,300

6,300/7,100

PCFY-100VGM

11,600/13,000

10,000/11,200

PCFY-125VGM

14,500/16,300

12,500/14,000

 

 

 

1. AIR OUTLET

New PCFY series models have 1 air outlet (auto vane switching of horizontal air flow / down flow by switched by auto vane) instead of 2 (horizontal, and down frows).

 

 

 

 

Protruding portion A

2. EASY TO CLEAN ; FLOCKLESS VANE

 

 

 

Unifies the air speed

 

B

with the vane.

With our original air current control mechanism, a flockless vane is

 

 

 

+

 

 

 

Protruding portion B

newly adapted.

Flockless vane

Sending the air to the upper

The flockless vane prevents the condensation on the vane.

 

 

 

 

 

A

area of the vane

By changing the vane to the flockless type, the unit can be cleaned

 

 

=

 

 

 

much easier with mild household detergent.

 

 

 

Prevents the air comes from

 

Air outlet

 

outside the unit

 

 

 

 

3. NEW MATERIALS FOR BETTER OIL RESISTANCE

We have changed the materials of grill, filer, fan and fan casing from ABS to P.P. (polypropylene) for better oil resistance. As a result, oil crazing is cut in half.

2

4. SIMPLIFIED INSTALLATION WORK (DIRECT SUSPENDING METHOD)

Simplified the installation work by changing the suspending method to the direct suspending method (suspending the unit directly from the suspension fixture).

In this way, the unit can be attached to the suspension fixture without removing the installation parts off (Only the side cover is removed). This method is much simpler than the ¨One-time installation method¨.

5. IMPROVING EFFICIENCY OF PIPING WORK

1 Removed the knockout work by separating the piping space from the air outlet for efficiency of the piping work.

2 Improved the flexibility by making it possible for drainage pipe to exit not only from the right side back but also from the left side back.

Back panel

Side panel

 

G L

L Open G

D Open

U-cut

D

L : Liquid pipe

G: Gas pipe

D: Drain pipe

Drain pan

Rubber plug

Insulation cover Joint coupliy (attached) (attached)

Insulation

 

Drain pipe

cover

Band

(purchased locally)

 

(attached)

 

Knockout work is needed for the top part. When optional drain-up machine is installed, the refrigerant pipe exits out from the top.

Please move the rubber plug for the unit to the right joint when drainage pipe exits from the left side.

6.ADVANCED MICROPROCESSOR [PAR-F25MA]

(1)Easy to use microprocessor 1)Ultra-thin remote controller

The streamlinde,square controller is designed to blend well with any interior.Also,the sophisticated microproceeor allows you to easily carry out a wide range of operations.

2)Attractive liquid crystal display(LCD)

The unit´s operation mode,set temperature,room temperature,timer setting,fan speed,louver oper-ation,and air flow direction are displayed on the remote controller´s easy-to-read Liquid Crystal Dis-play(LCD).

3)Convenient 24-hour ON-OFF timer

The timer switches Mr.SLIM on and off automati-cally at the time you set. Once the timer is set,the remaining time is shown on the LCD.

3

Mitsubishi PCFY-40VGM, PCFY-63VGM, PCFY-100VGM, PCFY-125VGM Service Manual

2 PART NAMES AND FUNCTION

Indoor (Main) Unit

Left/right guide vanes

Air outlet

Change the direction of airflow from the horizontal blower.

Long-life fillter

Removes dust and foreigh matter from air coming in through the grille (Recommended cleaning interval : Approx, every 2,500 operating hours)

Up/down guide vanes

Air intake

 

Intake grille

Change the direction of airflow from the vartical blower.

Remote controller

[PAR-F25MA]

 

 

 

● Once the controls are set, the same operation mode can

 

be repeated by simply pressing the ON/OFF button.

Operation buttons

 

 

 

TIMER button

TIME SETTING button

AIR SPEED button

This switches between continuous

This sets of switches the current time.

This sets the ventilation fan speed.

operation and the timer operation.

start time and stop time.

 

 

 

OPERATION SWITCH button

 

 

ON/OFF button

Press this button to switch the cooler

 

 

This swiches between the operation

electronic dry (dehumidify) automatic and

 

 

and stop modes each time it is

heater modes.

 

 

pressed. The lamp on this button

 

 

 

lights during operation.

 

 

 

AIR DIRECTION button

TEMP ADJUSTMENT button

 

 

This adjusts the vertical angle of the

 

 

ventilation.

This sets the room temparature The

 

 

 

temparature setting can be performed in 1°C

 

 

FILTER button

units

 

 

Setting range

 

 

This resets the filter service indication

Cooler 19°C to 30°C

 

 

display.

LOUVER button

CHECK-TEST RUN button

This switches the horizontal fan

Only press this button to perform an

motion ON and OFF.

inspection check or test operation Do

(This button does not operate in this

not use it for nomal operation.

 

 

model)

 

 

4

Display

CENTRALLY CONTROLLED display

This indicates when the unit is controlled by optional features such as central control type remote controller.

TIMER display

This indicates when the continous operation and time operation modes are set.

It also display the time for the timer operation at the same time as when it is set.

OPERATION MODE display

This indicates the operation mode.

STANDBY display

This indicates when the standby mode is set from the time the sleep operation starts until the heating air is discharged.

DEFROST display

This indicates when the defrost operation is performed.

CLOCK display

In this display example on the

bottom left, a condition where all

 

The current time , start time and stop

display lamps light is shown for

time can be displayed in tensecond

explanation purposes although this

intervals by pressing the time switch

differs from actual operation.

button. The start time or stop time is

 

always displayed during the timer

 

operation.

 

 

AIR DIRECTION display

 

The selected fan speed is displayed.

 

FAN SPEED display

 

This displays the air direction.

 

ROOM TEMPERATURE display

 

The temperature of the suction air is

 

displayed during operation. The

 

display range is 8° to 39°C. The

 

display flashes 8°C when the actual

 

temperature is less than 8° and

 

flashes 39°C when the actual

 

temperature is greater than 39°C.

 

Operation lamp

4

This lamp lights during operation,

 

goes off when the unit stops and

 

flashes when amalfunction occurs.

 

CHECK MODE

 

display

 

TEST RUN

 

This display lights in the check mode

 

or when a test operation is

 

performed.

CHECK display

 

 

 

 

This indicates when a malfunction

 

SET TEMPERATURE display

 

POWER display

 

 

 

 

has occurred in the unit which should

 

This displays the selected setting

 

This lamp lights when electricity is

be checked.

 

 

 

temperature.

 

supplied to the unit.

 

 

 

 

 

 

 

 

Caution

FILTER display

This lamp lights when the filter need to be cleaned.

Only the Power display lights when the unit is stopped and power supplied to the unit.

When power is turned ON for the first time the (CENTRAL CTRL) display appears to go off momentarily but this is not a malfunction.

When the central control remote control unit, which is sold separately, is used the ON-OFF button, operation switch button and TEMP adjustment button do not operate.

“NOT AVAILABLE” is displayed when the Air speed button are pressed.This indicates that this room unit is not equipped

with the fan direction adjustment function and the louver function.

●When power is turned ON for the first time, it is normal that “HO” is displayed on room temperature indecation (For max.2minutes). Please wait until this “HO” indication disappear then start the operation.

5

3 SPECIFICATIONS

3-1. Specification

Item

 

Power

V•Hz

Cooling capacity

kW

Heating capacity

kW

charocteristic

Power

Cooling

kw

 

 

 

 

 

 

supply Heating

kW

 

Startin Cooling

A

 

g

 

A

Electric

current Heating

factor

Heating

%

 

Power

Cooling

%

 

 

 

 

Exteior

(munsell symbol)

 

 

 

Height

mm

Outdimensions

Width

mm

 

 

Depth

mm

Heat exchanger

-

 

Fan No

-

F

Air flow #3

k/min

a

External

Pa

n

static pressure

 

Fan motor

kW

 

Output

 

 

 

Insulator

 

Air filter

 

Gas

[mm

Pipe

side

dimensions

Liquid

[mm

 

side

Drain pipe size

[mm

Noise level

dB(A)

Product weight

kg

PCFY-40VGM

 

PCFY-63VGM

 

PCFY-100VGM

 

PCFY-125VGM

 

 

 

 

 

 

 

 

Single phase 220V-240V 50 HZ

 

 

4.7

 

7.3

 

 

14.5

 

 

11.6

 

5.2

 

8.3

 

13.0

 

14.5

0.10

 

0.13

 

0.16

 

0.24

0.10

 

0.13

 

0.16

 

0.24

0.43

 

0.55

 

0.70

 

1.06

0.43

 

0.55

 

0.70

 

1.06

92

 

93

 

92

 

92

92

 

93

 

92

 

92

 

 

Unit : Munsell<0.70Y 8.59/0.97>

 

 

210

 

 

 

270

 

 

 

1000

 

1310

 

1310

 

 

 

 

1620

 

 

 

 

 

 

 

 

 

 

680

 

 

 

 

 

crosfin

 

 

 

 

 

 

 

 

Sirocco fan 2

 

Sirocco fan 3

 

Sirocco fan 3

 

Sirocco fan 4

12-11-10-8

 

18-16-14-12

 

25-23-20-18

 

35-32-28-26

 

 

 

 

 

 

 

 

 

 

0

 

 

0.054

 

0.07

 

 

 

 

0.09

 

0.15

 

 

 

 

 

 

 

 

Polyethylene sheet

 

 

 

 

PP honey comb

 

 

 

 

 

 

12.7<1/2”>

 

15.88<5/8”>

 

19.05<3/4”>

6.35<1/4”>

 

9.52<3/8”>

 

9.52<3/8”>

 

 

PVC pipe VP-25 connectable

 

 

38-36-33-29

 

39-37-34-32

 

 

 

 

43-41-38-36

 

44-42-39-37

27

 

34

 

37

 

43

 

 

 

 

 

 

 

Note 1.

Rating conditions(JIS B 8616)

 

Cooling:

Indoor:

27°C DB. 19.5°C WB

 

 

outdoor:

35°C DB. 24°C WB

 

Heating:

Indoor:

21°C

 

 

outdoor:

7°C DB. 6°C WB

Note 2.

Air flow and the noise level are indicated as High-Middium 1-Middium 2-Low.

6

3-2. Electrical parts specifications

Parts

Model

Symbol

PCFY-40VGM

PCFY-63VGM

PCFY-100VGM

PCFY-125VGM

name

 

 

 

 

 

 

Tranrsformer

 

T

 

(Primary) 50/60Hz 220-240V (Secondary) (18.4V 1.7A)

Room temperature

 

 

 

 

 

 

thermistor

 

TH21

Resistance: 0:/15k',10:/9.6k',20:/6.3k',25:/5.4k',30:/4.3k',40:/3.0k'

Liquid pipe

 

 

 

 

 

 

thermistor

 

TH22

Resistance: 0:/15k',10:/9.6k',20:/6.3k',25:/5.4k',30:/4.3k',40:/3.0k'

Gas pipe

 

 

 

 

 

 

Thermistor

 

TH23

Resistance: 0:/15k',10:/9.6k',20:/6.3k',25:/5.4k',30:/4.3k',40:/3.0k'

Fuse

 

FUSE

 

250V 6.3A

 

(Indoor controller board)

 

 

 

 

 

Fan motor

 

MF1,2

4-Pole OUTPUT 54W 4-Pole Output 70W

4-Pole Output 90W

4-Pole Output 150W

(with Inner-thermostat)

 

D09B4P54MS

D09B4P70MS

D10B4P90MS

D10B4P150MS

 

 

 

Inner-thermostat

OFF 130:±5:

 

Fan motor capacitor

C1

3uF x 440V

4uF x 440V

4uF x 440V

6uF x 440V

Vane motor

 

MV

MP35EA

MP35EA

MP42EA

 

DC12V

DC12V

DC12V

 

 

 

 

 

 

DC12V Stepping motor

 

DC12V Stepping motor drive

Linear expansion valve

LEV

drive

 

{ 5.2 (0~2000pulse)

 

{ 3.2 (0~2000pulse)

 

 

 

 

 

 

EDM-804ME

 

 

 

 

EDM-402ME

 

 

Power supply

 

 

 

 

 

 

terminal block

 

TB2

 

(L,N,;) 330V 30A

 

Transmission

 

 

 

 

 

 

terminal block

 

TB5

 

(M1,M2,S) 330V 30A

 

7

8

 

 

 

 

 

5 Refrigerant-pipe connection (liquid pipe side/flared connection)

 

 

 

 

 

40VGM-PCFY

UNITINDOOR

1 Drainage pipe connection (26mm I.D.)

 

 

 

 

 

 

 

 

 

2 Drainage pipe connection (for the left arrangement)

 

6 Knock out hole for upper drain pipe arrangement

 

 

 

 

 

 

 

 

3 Knock out hole for left drain-piping arrangement

 

7 Knock out hole for left drain pipe arrangement

 

 

 

 

 

 

 

 

 

4 Refrigerant-pipe connection (gas pipe side/flared connection)

8 Knock out hole for wining arrangement

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTES:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1. Use M10 or W3/8 screws for anchor bolt.

 

 

 

 

 

 

 

 

 

 

 

 

 

2. Please be sure when installing the drain-up machine (option parts).

 

 

 

 

 

 

 

 

 

 

 

 

refrigerant pipe will be only upper drain pipe arrangement.

 

 

 

 

 

 

 

 

 

 

 

ceiling

 

 

6

 

 

 

 

 

 

 

2

Electrical box [FRONT VIEW]

5

1 4

 

17

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

32

 

8

 

Gapto

 

150

 

80

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

Celling

 

 

 

 

 

 

 

 

 

 

 

 

 

179

 

161

 

3879

 

131

175

 

 

140

70

320

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

42

 

 

 

38

86

 

46

 

 

 

 

 

 

 

 

 

 

6-7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

138

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

171

 

 

 

 

 

 

 

 

 

 

 

 

When electrical

 

 

 

 

263

 

 

 

 

 

 

 

 

 

 

 

 

 

 

525

 

352

 

 

 

 

 

 

 

 

 

 

 

 

box is pulled

 

 

 

 

 

933 (suspension bolt pitch)

 

 

 

 

 

 

 

 

 

928

 

 

 

 

 

 

 

85

 

 

 

down

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

983

 

 

 

 

 

 

 

 

 

Electrical box 70

 

 

 

 

 

 

 

 

 

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

81

180

210

157

 

 

 

 

 

 

1

 

 

 

 

 

 

 

76

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

226

2

 

 

Air outlet

904

 

 

 

 

182

(3/8F) liquid

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1000

201

(5/8F) gas

 

241

(Drainage)

 

680

 

 

254

 

Air intake

 

 

918

 

 

DIMENSIONS AND OUTLINES 4

1 Drainage pipe connection (26mm I.D.)

5 Refrigerant-pipe connection (liquid pipe side/flared connection)

2 Drainage pipe connection (for the left arrangement)

6 Knock out hole for upper drain pipe arrangement

3 Knock out hole for left drain-piping arrangement

7 Knock out hole for left drain pipe arrangement

4 Refrigerant-pipe connection (gas pipe side/flared connection)

8 Knock out hole for wining arrangement

NOTES:

1. Use M10 or W3/8 screws for anchor bolt.

2. Please be sure when installing the drain-up machine (option parts). refrigerant pipe will be only upper drain pipe arrangement.

2

 

Electnical box

[ FRONT VIEW ]

5

1 4

ceiling

 

 

 

to

3

 

 

8

 

 

 

 

32

 

 

1

Gap

 

 

Celling

 

 

 

 

 

 

 

 

 

179

 

161

3879

 

131

175

 

42

6~7

 

38

86

 

46

 

 

 

 

 

 

 

 

 

 

 

 

138

 

 

 

 

 

 

 

171

 

 

 

 

 

 

 

263

 

 

 

When electrical

 

525

416

 

 

 

box is pulled

 

 

1235

 

 

 

 

down

 

 

 

 

 

 

 

 

 

 

 

 

 

Electrical box

70

 

 

 

 

 

 

1

Air outlet

226 2

Air intake

150 17

140

1240 (suspension bolt pitch)

1290

1214

1310

1228

6

 

80

 

 

 

 

 

 

70

320

 

 

 

 

 

 

 

 

 

 

85

15

 

 

 

 

 

 

 

 

 

 

157

 

 

76

 

180

210

 

 

 

 

81

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

680

254

182 (3/8F liquid)

201 (5/8F gas)

241 (Drainage)

63VGM-PCFY

9

10

1 Drainage pipe connection (26mm I.D.)

5 Refrigerant-pipe connection (liquid pipe side/flared connection)

2 Drainage pipe connection (for the left arrangement)

6 Knock out hole for upper drain pipe arrangement

 

3 Knock out hole for left drain-piping arrangement

7 Knock out hole for left drain pipe arrangement

NOTES:

4 Refrigerant-pipe connection (gas pipe side/flared connection)

8 Knock out hole for wining arrangement

1. Use M10 or W3/8 screws for anchor bolt.

 

 

2. Please be sure when installing the drain-up machine (option parts). refrigerant pipe will be only upper drain pipe arrangement.

 

 

Electnical box

[ FRONT VIEW ]

 

1

4

ceiling

 

2

5

to

 

93

 

8

 

 

3

 

Celling

 

 

1

Gap

239

 

160

 

38 140

 

192

236

 

42

 

6~7

 

38

 

 

45

 

 

 

 

 

86

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

138

 

 

When electrical

 

171

box is pulled

 

 

 

 

263

down

525

687

 

 

 

1235

70

Electrical box

1

 

 

 

 

 

 

 

 

 

229

 

 

 

2

Air outlet

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air intake

 

6

 

17

 

 

150

 

80

140

70

320

 

1240 (suspension bolt pitch)

87 16

 

 

 

 

 

 

 

 

217

 

 

 

 

 

 

270

 

96

 

207

 

 

 

 

 

81

 

 

 

 

 

 

 

 

 

 

 

 

 

1214

1310

680

254

1228

182 (3/8F liquid)

198 (5/8F gas)

245 (Drainage)

100VGM-PCFY

1 Drainage pipe connection (26mm I.D.)

5 Refrigerant-pipe connection (liquid pipe side/flared connection)

2 Drainage pipe connection (for the left arrangement)

6 Knock out hole for upper drain pipe arrangement

3 Knock out hole for left drain-piping arrangement

7 Knock out hole for left drain pipe arrangement

4 Refrigerant-pipe connection (gas pipe side/flared connection)

8 Knock out hole for wining arrangement

NOTES:

1. Use M10 or W3/8 screws for anchor bolt.

2. Please be sure when installing the drain-up machine (option parts). refrigerant pipe will be only upper drain pipe arrangement.

2

3

239

42

When electrical box is pulled down

Electrical box

 

[ FRONT VIEW ]

 

5

1

4

ceiling

 

8

Gapto

 

93

Celling

 

1

 

 

 

 

 

 

 

 

 

 

 

 

160

 

38 140

 

192

236

 

6~7

 

 

38

 

 

45

 

 

 

 

86

 

 

 

 

 

 

 

 

 

 

 

 

 

 

138

 

 

 

 

 

 

 

171

 

 

263

525

687

1545

70

Electrical box

1

 

 

 

 

 

 

 

 

Air outlet

229

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

Air intake

 

6

 

18

 

 

150

 

80

140

70

320

 

1547(suspension bolt pitch)

87

16

81 96

207

270

217

1524

 

 

182

1620

 

 

198

 

 

 

245

 

680

 

 

254

1535

125VGM-PCFY

(3/8F liquid)

(3/4F gas)

(Drainage)

11